Updated January 2018 1 WATER / WASTEWATER Basis The standards set forth herein are intended to provide a basis for design and construction. Applicable Federal, State, County and local laws and regulations should be considered concurrently with this text. These standards complement the Palm Beach Park of Commerce Association Inc. Uniform Service Policy on Water, Wastewater and Fire Protection. In the case of conflict between these standards and the Uniform Service Policy, the requirements of the Uniform Service Policy shall prevail. Both these Design Standards and the Uniform Service Policy are subject to change without notice. It is the Engineer of Record’s responsibility to assure that all protocols, procedures and submittals meet the requirements of the Design Standards and Uniform Service Policy in effect at the time of making submittal or implementing a protocol or procedure. Preparation and Approval of Project Documents It shall be the responsibility of the Owner's engineer to obtain record information for existing water and wastewater infrastructure and prepare plans in accordance with the minimum standards shown herein. Record information shall be field verified prior to design and confirmed prior to construction. All construction plans shall be approved by the PBPOC Land Development Review Board (LDRB), acting on behalf of the POA. The approval shall be valid for one year. This approval does not relieve the Owner of the responsibility of meeting the POA’s minimum design and construction standards shown herein or the requirements of the PBPOC Uniform Service Policy. No changes shall be made on approved plans without specific written POA concurrence. Revisions which directly or indirectly impact water and/or wastewater design (e.g., changes in property use in whole or part, adding or deleting plumbing fixtures in buildings, site plan changes, etc.) void the plan approval. Revised plans are required for review and approval, subject to the prevailing PBPOC Uniform Service Policy and Design Standards as well as new plan review fees. No construction shall start prior to a pre-construction conference to be held at a location designated by the POA. Utility Easement/Utility Location Guidelines The location and size of utility easements shall be determined using the following guidelines: (a) The Palm Beach County Health Department’s requirements for design, construction, clearance and separation of water, wastewater and other facilities shall be strictly observed in addition to those outlined in these Standards. (b) Water and wastewater mains shall be located a minimum of ten (10) feet horizontal from other public utilities or privately owned mains when installed parallel, unless specifically approved by POA. A minimum of ten (10) feet of horizontal separation is also required from structures, buildings, walls, and fences, unless specifically approved by the POA in writing. Phone lines shall cross the POA’s water/wastewater facilities with a minimum of twelve (12) inch vertical clearance. Gas mains and electric power cables shall cross the POA’s water/ wastewater facilities with a minimum of eighteen (18) inch vertical clearance. (c) Structures and landscaping should be placed no closer than ten (10) feet to a water/wastewater pipe or facility. The POA may consent, on a case by case basis, to the location of trees closer than ten (10) feet to water/wastewater facilities if an approved root barrier system is installed a minimum distance of five (5) feet from the water/wastewater facilities by the Owner’s landscaping contractor.

Upload: others

Post on 22-Oct-2019

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Updated January 2018

1

WATER / WASTEWATER

Basis The standards set forth herein are intended to provide a basis for design and construction. Applicable Federal, State, County and local laws and regulations should be considered concurrently with this text. These standards complement the Palm Beach Park of Commerce Association Inc. Uniform Service Policy on Water, Wastewater and Fire Protection. In the case of conflict between these standards and the Uniform Service Policy, the requirements of the Uniform Service Policy shall prevail. Both these Design Standards and the Uniform Service Policy are subject to change without notice. It is the Engineer of Record’s responsibility to assure that all protocols, procedures and submittals meet the requirements of the Design Standards and Uniform Service Policy in effect at the time of making submittal or implementing a protocol or procedure.

Preparation and Approval of Project Documents It shall be the responsibility of the Owner's engineer to obtain record information for existing water and wastewater infrastructure and prepare plans in accordance with the minimum standards shown herein. Record information shall be field verified prior to design and confirmed prior to construction. All construction plans shall be approved by the PBPOC Land Development Review Board (LDRB), acting on behalf of the POA. The approval shall be valid for one year. This approval does not relieve the Owner of the responsibility of meeting the POA’s minimum design and construction standards shown herein or the requirements of the PBPOC Uniform Service Policy. No changes shall be made on approved plans without specific written POA concurrence. Revisions which directly or indirectly impact water and/or wastewater design (e.g., changes in property use in whole or part, adding or deleting plumbing fixtures in buildings, site plan changes, etc.) void the plan approval. Revised plans are required for review and approval, subject to the prevailing PBPOC Uniform Service Policy and Design Standards as well as new plan review fees. No construction shall start prior to a pre-construction conference to be held at a location designated by the POA.

Utility Easement/Utility Location Guidelines The location and size of utility easements shall be determined using the following guidelines:

(a) The Palm Beach County Health Department’s requirements for design, construction, clearance and separation of water, wastewater and other facilities shall be strictly observed in addition to those outlined in these Standards.

(b) Water and wastewater mains shall be located a minimum of ten (10) feet horizontal from other

public utilities or privately owned mains when installed parallel, unless specifically approved by POA. A minimum of ten (10) feet of horizontal separation is also required from structures, buildings, walls, and fences, unless specifically approved by the POA in writing. Phone lines shall cross the POA’s water/wastewater facilities with a minimum of twelve (12) inch vertical clearance. Gas mains and electric power cables shall cross the POA’s water/ wastewater facilities with a minimum of eighteen (18) inch vertical clearance.

(c) Structures and landscaping should be placed no closer than ten (10) feet to a water/wastewater

pipe or facility. The POA may consent, on a case by case basis, to the location of trees closer than ten (10) feet to water/wastewater facilities if an approved root barrier system is installed a minimum distance of five (5) feet from the water/wastewater facilities by the Owner’s landscaping contractor.

Page 2: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Updated January 2018

2

Approved Materials and Equipment The materials and equipment set forth in Section III.I, Section IV.J and Exhibit “D” of the Seacoast Utility Authority (SUA) “Minimum Construction Standards and Specifications for Water Distribution Systems, Sewer Collection Systems, Reclaimed Water Systems,” latest revision (hereafter, the “Specifications”) are approved for use within the PBPOC POA potable water and wastewater systems. Any party constructing improvements to the PBPOC POA potable water and wastewater systems or which will become part of the PBPOC POA potable water and wastewater systems following construction shall utilize materials and equipment set forth in the Specifications. The POA may consent, on a case by case basis and upon written request with supporting documentation, to deviations from the materials and equipment required by the Specifications. Any references in the Specifications to the authorities and/or responsibilities of the “Authority” or the “Authority’s” personnel, representatives or agents shall be interpreted to mean the PBPOC POA or its designated agent. Any references in the List to the authorities and/or responsibilities of the “Developer” or the “Developer’s” personnel, representatives or agents shall be interpreted to mean the Owner or its designated agent.

Exceptions 1. Section III.I.1.a – The PBPOC Property Owners Association Public Water System (POAPWS)

shall allow the use of SDR-18 (minimum) restrained joint polyvinyl chloride (PVC) pipe for sizes up to and including 12 inch for pressure pipe. The pipe shall conform to AWWA C-900 and NSF-61 and have a minimum 235 psi pressure rating.

2. Section III.I.1.a – The PBPOC POAPWS shall allow the use of high density polyethylene (HDPE) piping for pressure pipe installed via directional drill/bore method. The pipe shall be fusible HDPE, PE 4710, DR 11 minimum conforming to AWWA C-906 and NSF-61 and in minimum 40-foot standard lengths.

3. Section III.I.1.c – The use of thrust blocks is not allowed. 4. Section III.I.2.a – The minimum size for single services shall be ¾”. 5. Section III.I.2.b – This section is removed in its entirety. 6. Section IV.J.5.a – The PBPOC POAPWS shall allow the use of SDR-18 (minimum) restrained

joint polyvinyl chloride (PVC) pipe for sizes up to and including 12 inch for pressure pipe in all areas. The pipe shall conform to AWWA C-900 and NSF-61 and have a minimum 235 psi pressure rating.

7. Section IV.J.5.a – The PBPOC POAPWS shall allow the use of high density polyethylene (HDPE) piping for pressure pipe installed via directional drill/bore method. The pipe shall be fusible HDPE, PE 4710, DR 11 minimum conforming to AWWA C-906 and NSF-61 and in minimum 40-foot standard lengths.

8. Section IV.J.5.c – The use of thrust blocks is not allowed. 9. Exhibit “D” – All references to reclaimed water main(s) and reclaimed main(s) are not

applicable. 10. Exhibit “D,” Section A.1 – Sub-item “c” is added as follows: Push-on Joint PVC pipe, AWWA

C-900, SDR-18 min., 235 psi min., NSF-61: 1. JM Manufacturing Company* 2. Diamond Plastic Corporation* 3. CertainTeed* 4. North American Pipe Corp.; NAPCO* 5, IPEX, Inc.** 6. National Pipe and Plastics** 7. Sanderson Pipe** [*No pipe deflection at the joint allowed. **Up to two (2) degrees deflection at pipe joint allowed.]

11. Exhibit “D,” Section A.1 – Sub-item “d” is added as follows: Restrained Joint PVC pipe, AWWA C-900, SDR-18 min., NSF-61. D1. Non-metallic Modular Joint Restraint Design 1. CertainTeed Certalok D2. Belle Integrated Metallic Ring Restraint Design 1. JMM Eagle Lok

12. Exhibit “D,” Section A.1 – Sub-item “e” is added as follows: HDPE pipe (Fusible HDPE, PE 4710, AWWA C-906); minimum 40 feet standard lengths, DR 11 minimum, 3” and larger 1. CP Chem 2. JM Manufacturing Company 3. IPEX, Inc. 4. Polypipe by Dura-Line 5. KWH Pipe by Uponor Infra Ltd.

Page 3: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Updated January 2018

3

13. Exhibit “D,” Section A.2 – Sub-item “d” is added as follows: Push-on Joint PVC pipe, AWWA C-900, SDR-18 min., 235 psi min., NSF-61: 1. JM Manufacturing Company* 2. Diamond Plastic Corporation* 3. CertainTeed* 4. North American Pipe Corp.; NAPCO 5, IPEX, Inc.** 6. National Pipe and Plastics 7. Sanderson Pipe** [*No pipe deflection at the joint allowed. **Up to two (2) degrees deflection at pipe joint allowed.]

14. Exhibit “D,” Section A.2 – Sub-item “e” is added as follows: Restrained Joint PVC pipe, AWWA C-900, SDR-18 min., NSF-61. D1. Non-metallic Modular Joint Restraint Design 1. CertainTeed Certalok D2. Belle Integrated Metallic Ring Restraint Design 1. JMM Eagle Lok

15. Exhibit “D,” Section A.2 – Sub-item “f” is added as follows: HDPE pipe (Fusible HDPE, PE 4710, AWWA C-906); minimum 40 feet standard lengths, DR 11 minimum, 3” and larger 1. CP Chem 2. JM Manufacturing Company 3. IPEX, Inc. 4. Polypipe by Dura-Line 5. KWH Pipe by Uponor Infra Ltd.

16. Exhibit “D,” Section B.5.a.1 – This section shall be amended to include PVC mains. 17. Exhibit “D,” Section II.A.1 – This section shall be amended to include ¾”.

Potable Water and Wastewater System Design and Construction Standards Any party constructing improvements to the PBPOC POA potable water and/or wastewater systems or which will become part of the PBPOC POA potable water and/or wastewater systems following construction, shall comply with the SUA “Minimum Construction Standards and Specifications for Water Distribution Systems, Sewer Collection Systems, Reclaimed Water Systems,” (hereafter, the “Standards”), as appropriate and as set forth in the SUA Service Policy, latest revision. Any references in the Standards to the authorities and/or responsibilities of the “Authority” or the “Authority’s” personnel, representatives or agents shall be interpreted to mean the PBPOC POA or its designated agent. Any references in the List to the authorities and/or responsibilities of the “Developer” or the “Developer’s” personnel, representatives or agents shall be interpreted to mean the Owner or its designated agent. Notwithstanding anything to the contrary herein, the LDRB may authorize deviations from the Standards if, in the opinion of the LDRB, said deviations are necessary to protect the health, safety, or welfare of the public or to avoid an undue financial and/or maintenance burden on the PBPOC POA.

Exceptions

Section I – General 1. This section shall be replaced in its entirety by the corresponding prevailing PBPOC Uniform

Service Policy and Design Standards requirements. Section II – Design/Construction Plan Requirements

1. This section shall be replaced in its entirety by the corresponding prevailing PBPOC Uniform Service Policy and Design Standards requirements.

Section III - Water Distribution System 1. The requirements of this Section shall apply to the PBPOC POAPWS’ non-transient, non-

community water system. 2. All references to residential or multi-family dwelling requirements are not applicable and shall be

removed from this Section. 3. Section A.5 shall be revised to read “Approved backflow prevention devices are required on each

and every water service connection in accordance with specifications shown in Exhibit “I” in this manual. Backflow devices shall be installed on the outlet side of the water meter; no tees or other branch fittings are allowed between the water meter and backflow device. In the absence of special circumstances, which would cause a great degree for cross connections, the general backflow device required is as follows: (a) Potable water connection – reduced pressure zone device; (b) Dedicated process water connection – double check valve device; (c) Dedicated fire

Page 4: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Updated January 2018

4

line – Double detector check valve device; (d) Temporary water – reduced pressure zone device.” 4. The last sentence of Section A.6 shall be stricken. 5. The first sentence of Section A.7.b shall be stricken. 6. The first sentence of Section A.7.c shall be revised to read “In commercial areas when…” 7. The first sentence of Section B shall be revised to read “Hydraulic designs shall be based on the

prevailing minimum guaranteed water system pressure at the closest point of connection between the PBPOC POAPWS’ water system and the Palm Beach County Water Utility Department’s water system.”

8. Section C.3 shall be revised to read “Any pavement cut shall be replaced in accordance with the requirements of Northern Palm Beach County Improvement District’s (NPBCID) Pavement Replacement Detail as provided in their Engineering Standards Manual, latest revision.”

9. The last sentence of Section C.6 shall be stricken. 10. Section E.2 shall be revised to read “…procedure outlined in ANSI/AWWA C-600 Latest

Revision. Record drawings in accordance with the prevailing PBPOC Uniform Service Policy and Design Standards must be accepted prior…”

11. The last two sentences of Section H.3 shall be stricken. 12. Section I shall be amended described in the Water/Wastewater Approved Materials and

Equipment section of these Design Standards. 13. Section J.2 shall be revised to read “Each fire hydrant shall be capable of delivering a flow as

prescribed by Palm Beach County Fire Rescue with a residual pressure…” 14. Section L.3 shall be revised to read “The PBPOC POA shall furnish and have installed all

meters.” 15. Section L.4 shall be revised to read “The Developer/Customer shall be responsible for providing

and resetting the meter box, if required, after the...” 16. Section M shall be amended to add the following language at the end of the section: “Backflow

prevention devices will not be owned or maintained by the POAPWS. The initial required testing and certification of backflow prevention devices shall be scheduled with the POA prior to the installation of meter(s) and shall be the financial responsibility of the Owner or the Owner’s utility contractor. Required subsequent annual testing and certification of backflow devices will be handled by the POAPWS; however, any required repairs are the responsibility of the Owner.

17. Section N.2 shall be removed in its entirety.

Section IV – Sanitary Sewer System 1. All references to residential or multi-family dwelling requirements are not applicable and shall be

removed from this Section. 2. The last sentence of Section A.1shall be revised to read “Special allowance may be made for

sewage from industrial facilities and other large projects.” 3. Section A.3 shall be revised to read “Industrial wastes from any source shall not be connected…” 4. The last sentence of Section B.11.e shall be amended to add PVC force mains and fitting as

acceptable materials. 5. Section D.9 shall be revised to read “…inverted crown roadways or parking lots), the PBPOC

POAPWS may require watertight inserts…” 6. Sections E.12.h through m shall be removed in their entirety. 7. Section F.3 shall be revised to read “Any pavement cut shall be replaced in accordance with the

requirements of Northern Palm Beach County Improvement District’s (NPBCID) Pavement Replacement Detail as provided in their Engineering Standards Manual, latest revision.”

8. The last sentence of Section F.7 shall be stricken. 9. Section F.13 shall be revised to read “All joints and conflicts in the force main…” 10. Section G shall be removed in its entirety. 11. Section H.2.a shall be removed in its entirety. 12. Section I.9 shall be revised to read “The minimum size pipe for service laterals shall be 6 inch;

however, the POA may allow smaller service laterals on a case by case basis with the concurrence of the Palm beach County Health Department.”

Page 5: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Updated January 2018

5

13. Section I.10 shall be revised to read “Sewer Tie-in connections “Flexible rubber type connectors are not permitted.”

14. Section J shall be amended described in the Water/Wastewater Approved Materials and Equipment section of these Design Standards.

Section V – Reclaimed Water System 1. This Section shall be removed in its entirety.

Exhibits 1. Exhibit “A” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 2. Exhibit “B” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 3. Exhibit “C” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 4. Exhibit “D” – This exhibit shall be amended described in the Water/Wastewater Approved

Materials and Equipment section of these Design Standards. 5. Exhibit “E” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 6. Exhibit “F” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 7. Exhibit “G” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 8. Exhibit “H” – This exhibit shall be replaced in its entirety by the corresponding prevailing

PBPOC Uniform Service Policy and Design Standards requirements. 9. Exhibit “I” – This exhibit shall be replaced in its entirety by Exhibit C (latest revision) of the

PBPOC Uniform Service Policy. The standard details depicted in Exhibit C will be made available to the Engineer of Record for use on the design, permit, construction and record drawings. No modifications to the standard details will be allowed without specific written request from the Engineer of Record and written authorization of the PBPOC POAPWS.

a. The “Pavement Replacement Detail,” Dr. No. N-006 from the NPBCID Engineering Standards Manual, latest revision shall be added to Exhibit C as Drawing No. 5.

b. The “Subaqueous Crossing – Directional Bore” detail, Dr. No. N-008A from the NPBCID Engineering Standards Manual, latest revision shall be added to Exhibit C as Drawing No. 11A.

Project Representatives and Authority of Project Representatives Project Representatives acting on behalf of the POA may examine all construction and materials and may also examine preparation, fabrication or manufacture of components, materials and supplies. The Project Representative is not authorized to revoke, alter or waive any requirements of the approved plans or these specifications unless approved by the POA. The Project Representative is authorized to call to the attention of the Owner's Engineer or Contractor any failure of work or materials to conform to the plans or specifications. The Project Representative shall have the authority to reject materials or suspend the work until questions of issue can be referred to and decided upon by the POA or its designated agent. The Project Representative shall also have the authority to suspend the work when questions of safety or potential liability to the Park arise or unsafe conditions that may affect the work present. The Project Representative shall in no case act as foreman or perform other duties for the Project Engineer and/or Contractor nor interfere with the management of the work. The advice which the Project Representative may give shall in no way be construed as binding to the POA or releasing the Owner, his Engineer or Contractor from performing according to the intent of the plans, specifications and the POA’s Minimum Design and Construction Standards.

Page 6: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Updated January 2018

6

Required inspections will be scheduled for regular working hours only, except when service interruptions are involved. Work will not be scheduled for weekends or holidays unless approved in advance by the POA. The POA shall be provided with at least three (3) full working days’ notice for scheduled (required) inspections, and a minimum of seven (7) days’ notice is required for construction with service interruptions. If requested by the Owner’s Engineer or Contractor or under emergency conditions, the POA may be able to accommodate requests for inspections with notice given in a shorter time frame. These requests and/or conditions will be evaluated on a case by case basis. Project Representative(s) will make routine passes to examine such items as piping restraint, material on site and clearances between conflicting lines. Scheduled inspections are required for jack and bores and pipe slippage through same, directional drills/bores, filling and flushing of potable water mains, pressure testing, flow testing of hydrants, application of coatings to manholes and wet wells, setting of wet wells, installation of lift station grounding rods, installation of base elbow anchors, prior to pouring any concrete, field welding/fusion of HDPE pipe and fittings, lift station start-ups, and tie-ins and/or modifications to POA facilities. Density test results shall be submitted to the POA prior to pressure testing. The contractor shall keep a copy of the current approved plans on the project site at all times. Approved work schedules are required prior to the beginning of construction for main shutdowns or for modifications to operating pipe systems. It shall be the Owner's Engineer's responsibility to schedule inspections, and their qualified representative shall be present at all scheduled inspections. A scheduled inspection will be canceled if said representative is not present. The Engineer’s representative shall be present during the entire length of the inspection. The Owner's Engineer shall ensure that pre-test pressure tests are conducted to minimize inspection failures. The Owner's Engineer shall prepare accurate record drawings and same shall be submitted to the POA for review and approval before a pressure test is scheduled. In any case, record drawings must be submitted and approved prior to request of a conditional final/final inspection or service being provided to any phase of a project. All POA-authorized representatives shall be permitted to enter upon any property without prior notification for the purposes of examination, observation, measurement, sampling, testing, review and/or photocopying of records, or investigation as maybe necessary for enforcement of the permit or ordinance. Entry shall be made during daylight or operating hours unless abnormal or emergency circumstances require otherwise. Official Reporting For all Permitting Applications, Testing Reports/Results and Laboratory Results that require the inclusion of information pertaining to the POAPWS, the following information is to be used: Public Water System (PWS) Name: Palm Beach Park of Commerce Association, Inc. PWS I.D. 4504516 PWS Address: 15132 Park of Commerce Blvd., Suite 101 City: Jupiter PWS Phone# (561) 625-8027 Any permitting applications, test reports/results and/or lab results that contain erroneous information regarding the POAPWS, including reference to the Palm Beach County Water Utility Department or Seacoast Utility Authority as the PWS, will not be signed until all documentation reflects the correct PWS information.

Page 7: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Symbols

C-1

AutoCAD SHX Text
6"GM
AutoCAD SHX Text
RIM
AutoCAD SHX Text
INV
AutoCAD SHX Text
6"STM
AutoCAD SHX Text
6"GM
AutoCAD SHX Text
6"STM
AutoCAD SHX Text
RIM
AutoCAD SHX Text
INV
AutoCAD SHX Text
STORM SEWER ELEVATIONS
AutoCAD SHX Text
GUY WIRE & ANCHOR
AutoCAD SHX Text
BACKFLOW PREVENTER
AutoCAD SHX Text
GAS MAIN
AutoCAD SHX Text
STORM SEWER
AutoCAD SHX Text
POWER POLE
AutoCAD SHX Text
LIGHT POLE
AutoCAD SHX Text
ASSEMBLY
AutoCAD SHX Text
6"WM
AutoCAD SHX Text
RIM
AutoCAD SHX Text
INV
AutoCAD SHX Text
6"FM
AutoCAD SHX Text
6"SAN
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
6"WM
AutoCAD SHX Text
6"FM
AutoCAD SHX Text
6"SAN
AutoCAD SHX Text
RIM
AutoCAD SHX Text
INV
AutoCAD SHX Text
PROPOSED
AutoCAD SHX Text
SINGLE WATER SERVICE
AutoCAD SHX Text
SPRINKLER HEAD (IRR)
AutoCAD SHX Text
SINGLE SANITARY SERVICE
AutoCAD SHX Text
FIRE HYDRANT
AutoCAD SHX Text
WATER MAIN
AutoCAD SHX Text
SAMPLE POINT
AutoCAD SHX Text
WITH METER
AutoCAD SHX Text
SANITARY SEWER
AutoCAD SHX Text
ELEVATIONS
AutoCAD SHX Text
FORCE MAIN
AutoCAD SHX Text
MANHOLE
AutoCAD SHX Text
SANITARY SEWER
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
REDUCER
AutoCAD SHX Text
BEND
AutoCAD SHX Text
TEE
AutoCAD SHX Text
VALVE
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 8: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Water, Reclaimed Water and Sewer Separation StatementWater and Sewer Separation Statement

C-2

AutoCAD SHX Text
1. STORM SEWER, GRAVITY WASTEWATER AND FORCE MAINS CROSSING UNDER POTABLE WATER MAINS SHALL BE LAID TO PROVIDE A MINIMUM VERTICAL DISTANCE OF TWELVE (12) INCHES BETWEEN THE OUTSIDE OF THE WATER MAIN AND THE CROWN OF THE LOWER PIPE. WHERE THIS MINIMUM SEPARATION CANNOT BE MAINTAINED BETWEEN GRAVITY SEWER OR STORM SEWER, THE CROSSING SHALL BE ARRANGED SO THAT THE STORM/GRAVITY SEWER PIPE JOINTS AND POTABLE WATER MAIN JOINTS ARE EQUIDISTANT FROM THE POINT OF CROSSING WITH NO LESS THAN SIX (6) FEET BETWEEN ANY TWO JOINTS, BOTH PIPES SHALL BE D.I.P., AND THE MINIMUM VERTICAL SEPARATION SHALL BE SIX (6) INCHES. WHERE THERE IS NO ALTERNATIVE TO STORM/WASTEWATER/FORCE MAIN MAINS CROSSING OVER A POTABLE WATER MAIN, THE CRITERIA FOR MINIMUM TWELVE (12) INCH VERTICAL SEPARATION BETWEEN LINES AND JOINT ARRANGEMENT, AS STATED ABOVE, SHALL BE REQUIRED, AND BOTH PIPES SHALL BE D.I.P. IRRESPECTIVE OF SEPARATION, IN ALL OF THE ABOVE CASES D.I.P. IS NOT REQUIRED FOR STORM SEWER PIPE. 2. FORCE MAINS CROSSING STORM SEWER SHALL BE LAID TO PROVIDE A MINIMUM VERTICAL DISTANCE OF TWELVE (12) INCHES BETWEEN THE OUTSIDE OF THE FORCE MAIN AND THE OUTSIDE OF THE STORM SEWER. 3. AT THE UTILITY CROSSING DESCRIBED IN ITEMS 1 AND 2 ABOVE, ONE FULL LENGTH OF DUCTILE IRON WATER MAIN PIPE SHALL BE CENTERED SO THE WATER MAIN JOINTS WILL BE AS FAR AS POSSIBLE FROM THE OTHER PIPELINE JOINTS. WHERE THIS IS NOT POSSIBLE, JOINTS SHALL BE AT LEAST THREE (3) FEET FROM STORM SEWERS AND SIX (6) FEET FROM GRAVITY SEWER MAINS AND FORCE MAINS. 4. SEWER SERVICE LATERALS SHALL CROSS UNDER WATER MAINS WITH A MINIMUM VERTICAL SEPARATION OF TWELVE (12) INCHES. IF 12" VERTICAL SEPARATION CANNOT BE MAINTAINED, THEN THE WATER MAIN SHALL BE D.I.P. AND THE SEWER SERVICE LATERAL SHALL BE C-900 SDR 18 OR BETTER AND THE MINIMUM SEPARATION SHALL BE SIX (6) INCHES. WHEN IT IS NOT POSSIBLE FOR THE WATER MAIN TO CROSS OVER THE SEWER SERVICE LATERAL A MINIMUM VERTICAL SEPARATION OF AT LEAST TWELVE (12) INCHES MUST BE MAINTAINED, THE WATER MAIN SHALL BE D.I.P. AND THE SEWER LATERAL SHALL BE C-900 SDR 18 OR BETTER. 5. MAINTAIN MINIMUM TEN (10) FEET HORIZONTAL DISTANCE BETWEEN POTABLE WATER MAIN OR FORCE MAIN, STORM SEWER OR GRAVITY SEWER MAIN OR ON SITE SEWAGE DISPOSAL SYSTEMS. ADDITIONAL SEPARATION MAY BE REQUIRED AS DETERMINED BY THE LDRB.
AutoCAD SHX Text
STANDARD WATER AND SEWER SEPARATION STATEMENT
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 9: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Tapping and Main Clearing ProcedureTapping and Main Clearing Procedure

C-3

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. THIS METHOD SHALL BE COMPLIED WITH WHEN CONNECTING TO AN EXISTING WATER MAIN, (ONE THAT HAS ALREADY BEEN BACTERIOLOGICALLY CLEARED OR IS IN USE) WHETHER BY TEE AND VALVE OR BY CONTINUATION OF A PLUGGED STUB OUT WITH AN EXISTING GATE VALVE. 2. THESE REQUIREMENTS ARE BASED ON PALM BEACH COUNTY HEALTH DEPARTMENT REQUIREMENTS. 3. WHEN A TAPPING TEE AND VALVE IS INSTALLED, A PRESSURE/LEAKAGE TEST SHALL BE PERFORMED ON THE ASSEMBLY IN THE PRESENCE OF AN AUTHORIZED POAPWS REPRESENTATIVE PRIOR TO PERFORMING THE ACTUAL TAP. 4. ALL TAPS ON PIPE SIX (6) INCH IN DIAMETER AND LARGER SHALL BE INSTALLED AT THE CENTER/MIDDLE OF A LENGTH OF PIPE. 5. DOUBLE VALVING PERMITS PHYSICAL CONNECTION TO AN EXISTING WATER MAIN WHEN USED IN CONJUNCTION WITH A BYPASS LINE. 6. A 2" BYPASS LINE (MAXIMUM) SHALL BE INSTALLED AS SHOWN BELOW PRIOR TO CANNON FLUSHING. 7. THE 2" TEE SHALL BE USED FOR FEEDING CHLORINE SOLUTION AND FOR ATMOSPHERIC VENT DURING PRESSURE/LEAKAGE TESTS. 8. UNDER NO CIRCUMSTANCES SHALL VALVES BE OPERATED WITHOUT AN AUTHORIZED POAPWS REPRESENTATIVE PRESENT. 9. ALL WATER MAINS SHALL BE FILLED WITH WATER UTILIZING JUMPER METER AND THEN BE THOROUGHLY CANNON FLUSHED IN ACCORDANCE WITH PBPOC POA SPECIFICATIONS PRIOR TO PRESSURE/LEAKAGE TESTING. THE PROCEDURE SHALL BE DONE ONLY IN THE PRESENCE OF AN AUTHORIZED POAPWS REPRESENTATIVE. 10. FOLLOWING INITIAL CANNON FLUSHING, ALL WATER FOR PRESSURE/LEAKAGE TESTING AND BACTERIOLOGICAL CLEARANCES MUST BE DRAWN FROM THE BYPASS LINE WITH METER AND REDUCED PRESSURE BACKFLOW PREVENTER IN PLACE. THE WATER METER SHALL BE PROVIDED BY THE PBPOC POA. ALL WATER USED FOR CONSTRUCTION PURPOSES SHALL BE IN ACCORDANCE WITH THE PBPOC POA UNIFORM SERVICE POLICY. METER, BALL VALVE, REDUCED PRESSURE BACKFLOW PREVENTER AND TEE SHALL INSTALLED AT LEAST 18" ABOVE EXISTING GRADE, SUPPORTED, AND PROTECTED FROM DAMAGE. ANY DAMAGE SHALL BE APPLICANT'S RESPONSIBILITY AND SHALL BE CHARGED ACCORDINGLY. 11. EXCEPT DURING CANNON FLUSHING VALVES SHALL NOT BE OPENED UNTIL AFTER AN APPROVED PRESSURE/ LEAKAGE TEST, BACTERIOLOGICAL CLEARANCE, CERTIFICATION BY THE ENGINEER OF RECORD, RELEASE FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT AND APPROVAL BY POAPWS. 12. DISINFECTION AND BACTERIOLOGICAL CLEARANCES SHALL COMPLY WITH CURRENT AWWA PROCEDURES, PALM BEACH COUNTY HEALTH DEPARTMENT, AND FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION REQUIREMENTS.
AutoCAD SHX Text
EXISTING MAIN
AutoCAD SHX Text
2" REDUCED PRESSURE BACKFLOW PREVENTER
AutoCAD SHX Text
2" DOUBLE STRAP TAPPING SADDLE
AutoCAD SHX Text
2" CORP. STOP WITH AWWA THREADS
AutoCAD SHX Text
PROPOSED MAIN
AutoCAD SHX Text
DOUBLE VALVE (MIN. 3'-0" SEPARATION)
AutoCAD SHX Text
2" TEE
AutoCAD SHX Text
2" POLYETHYLENE TUBE C.T.S.
AutoCAD SHX Text
2" WATER METER (SEE NOTE 10)
AutoCAD SHX Text
2" BALL VALVE WITH LOCKING WINGS
AutoCAD SHX Text
2" CORP. STOP WITH AWWA THREADS
AutoCAD SHX Text
(MALE x FEMALE)
AutoCAD SHX Text
2" DOUBLE STRAP TAPPING SADDLE
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 10: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Standard Trenching ProcedureStandard Trenching Procedure

C-4

AutoCAD SHX Text
EXCAVATION SIDE SLOPE SHORING, ETC. SHALL CONFORM TO O.S.H.A. STANDARDS. COMPACT TRENCH BACKFILL TO 100% OF MAXIMUM DENSITY IN ACCORDANCE WITH AASHTO T-180. DENSITY TESTS SHALL BE TAKEN AT 12" LIFTS EVERY 100' IN PUBLIC RIGHT-OF-WAY AND 200' IN EASEMENTS
AutoCAD SHX Text
4"
AutoCAD SHX Text
ALTERNATE FOR MACHINE
AutoCAD SHX Text
AND GRAVEL BACKFILL
AutoCAD SHX Text
MINIMUM SAND, STONE
AutoCAD SHX Text
EXCAVATION AND OVER EXCAVATION
AutoCAD SHX Text
LIMIT FOR
AutoCAD SHX Text
EXISTING GROUND
AutoCAD SHX Text
4"
AutoCAD SHX Text
INVERT
AutoCAD SHX Text
EXCAVATION
AutoCAD SHX Text
MACHINE
AutoCAD SHX Text
PIPE O.D. + 24"
AutoCAD SHX Text
12"
AutoCAD SHX Text
12"
AutoCAD SHX Text
RECEIVE PIPE BELL AND BARREL
AutoCAD SHX Text
LOWER QUADRANT TO BE SHAPED TO
AutoCAD SHX Text
BACKFILL OVER PIPE
AutoCAD SHX Text
FOR PLACEMENT OF
AutoCAD SHX Text
MATERIAL IN 6" LIFTS
AutoCAD SHX Text
HAND PLACED SELECT
AutoCAD SHX Text
PROPOSED PIPELINE
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
SEE SPECIFICATION
AutoCAD SHX Text
(PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS)
AutoCAD SHX Text
CONTRACTOR SHALL AT ALL TIMES COMPLY WITH THE REQUIREMENTS OF THE FLORIDA TRENCH SAFETY ACT.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 11: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Pipe Restraint TablePipe Restraint Table

C-6

AutoCAD SHX Text
PUSH ON JOINT PIPE RESTRAINT REQUIREMENTS AT FITTINGS, VALVES AND DEAD ENDS
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. ALL BURIED PRESSURE MAINS SHALL INCLUDE A RESTRAINED JOINT SYSTEM. THE CONTRACTOR SHALL USE A DUCTILE IRON RESTRAINING SYSTEM AS MANUFACTURED BY EBAA IRON, INC. (MEGALUG) OR APPROVED EQUAL FOR ALL MECHANICAL JOINT FITTINGS AND LOCKING GASKETS FOR PUSH-ON JOINT PIPE. 2. RESTRAINING LENGTHS SHOWN ARE THE MINIMUM LENGTH REQUIRED BASED ON A TEST PRESSURE OF 150 P.S.I.G. WITH A MINIMUM COVER OF 30". 3. IF LENGTH BETWEEN MECHANICAL JOINT FITTINGS AND/OR VALVES IS LESS THAN THE MINIMUM LENGTHS SHOWN IN THIS TABLE, THE CONTRACTOR SHALL RESTRAIN THE ENTIRE LENGTH.
AutoCAD SHX Text
90° BEND
AutoCAD SHX Text
54'
AutoCAD SHX Text
8"
AutoCAD SHX Text
20"
AutoCAD SHX Text
24"
AutoCAD SHX Text
30"
AutoCAD SHX Text
48"
AutoCAD SHX Text
42"
AutoCAD SHX Text
54"
AutoCAD SHX Text
36"
AutoCAD SHX Text
12"
AutoCAD SHX Text
14"
AutoCAD SHX Text
16"
AutoCAD SHX Text
18"
AutoCAD SHX Text
10"
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
108'
AutoCAD SHX Text
90'
AutoCAD SHX Text
54'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
6"
AutoCAD SHX Text
4"
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
270'
AutoCAD SHX Text
270'
AutoCAD SHX Text
270'
AutoCAD SHX Text
154'
AutoCAD SHX Text
154'
AutoCAD SHX Text
154'
AutoCAD SHX Text
180'
AutoCAD SHX Text
270'
AutoCAD SHX Text
172'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
VALVE
AutoCAD SHX Text
36'
AutoCAD SHX Text
36'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
MINIMUM LENGTH OF PUSH ON JOINT PIPE WITH SPECIAL RESTRAINING GASKETS
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
36'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
108'
AutoCAD SHX Text
90'
AutoCAD SHX Text
54'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
36'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
90'
AutoCAD SHX Text
54'
AutoCAD SHX Text
36'
AutoCAD SHX Text
36'
AutoCAD SHX Text
11¼° BEND
AutoCAD SHX Text
22½° BEND
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
45° BEND
AutoCAD SHX Text
36'
AutoCAD SHX Text
36'
AutoCAD SHX Text
REDUCER
AutoCAD SHX Text
54'
AutoCAD SHX Text
54'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
154'
AutoCAD SHX Text
154'
AutoCAD SHX Text
172'
AutoCAD SHX Text
180'
AutoCAD SHX Text
270'
AutoCAD SHX Text
270'
AutoCAD SHX Text
154'
AutoCAD SHX Text
270'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
270'
AutoCAD SHX Text
DEAD END
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
154'
AutoCAD SHX Text
154'
AutoCAD SHX Text
172'
AutoCAD SHX Text
180'
AutoCAD SHX Text
270'
AutoCAD SHX Text
270'
AutoCAD SHX Text
154'
AutoCAD SHX Text
270'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
108'
AutoCAD SHX Text
270'
AutoCAD SHX Text
TEE
AutoCAD SHX Text
72'
AutoCAD SHX Text
72'
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 12: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Steel Casing Installation

C-7

AutoCAD SHX Text
OF CEMENT NON-SHRINK GROUT
AutoCAD SHX Text
SEAL ENDS WITH A MINIMUM OF 18"
AutoCAD SHX Text
NOMINAL
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
R/W LINE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
R/W LINE
AutoCAD SHX Text
48"
AutoCAD SHX Text
4"
AutoCAD SHX Text
6"
AutoCAD SHX Text
42"
AutoCAD SHX Text
8"
AutoCAD SHX Text
36"
AutoCAD SHX Text
10"
AutoCAD SHX Text
30"
AutoCAD SHX Text
12"
AutoCAD SHX Text
24"
AutoCAD SHX Text
14"
AutoCAD SHX Text
20"
AutoCAD SHX Text
18"
AutoCAD SHX Text
16"
AutoCAD SHX Text
72"
AutoCAD SHX Text
12"
AutoCAD SHX Text
16"
AutoCAD SHX Text
60"
AutoCAD SHX Text
18"
AutoCAD SHX Text
54"
AutoCAD SHX Text
20"
AutoCAD SHX Text
48"
AutoCAD SHX Text
24"
AutoCAD SHX Text
42"
AutoCAD SHX Text
24"
AutoCAD SHX Text
36"
AutoCAD SHX Text
30"
AutoCAD SHX Text
30"
AutoCAD SHX Text
.500
AutoCAD SHX Text
.375
AutoCAD SHX Text
.500
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.375
AutoCAD SHX Text
.500
AutoCAD SHX Text
.500
AutoCAD SHX Text
.500
AutoCAD SHX Text
CASING SIZE AS REQUIRED
AutoCAD SHX Text
(SEE "PIPE CASING SPACERS" DETAIL)
AutoCAD SHX Text
ROCK BASE
AutoCAD SHX Text
30" MINIMUM OR AS NPBCID AND THE ENGINEER
AutoCAD SHX Text
THICKNESS
AutoCAD SHX Text
SCHEDULE
AutoCAD SHX Text
PIPELINE CASING SPACER
AutoCAD SHX Text
OF RECORD MAY DIRECT
AutoCAD SHX Text
ROADWAY OR WATER BODY
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
CASING
AutoCAD SHX Text
PAVING
AutoCAD SHX Text
JOINT TYPE AS SPECIFIED
AutoCAD SHX Text
DUCTILE IRON PIPE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
(PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS)
AutoCAD SHX Text
FAST GRIP OR FIELD LOK GASKET
AutoCAD SHX Text
RESTRAINED MECHINICAL JOINT
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 13: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Pipe Casing Spacers

C-8

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. CARRIER PIPE FOR 4" THROUGH 24" DIAMETER PIPE WITHIN CASING SHALL BE RESTRAINT GASKET. 2. RESTRAINED MECHANICAL JOINTS SHALL BE USED FOR PIPE 30" DIAMETER AND ABOVE AND SHALL HAVE FACTORY WELDED RETAINING RINGS. AMERICAN RESTRAINED JOINT PIPE OR APPROVED EQUAL MAY BE USED. 3. FOR PIPE DIAMETERS 4" THROUGH 12" INSTALL STAINLESS STEEL PIPE CASING SPACERS 5' OR LESS FROM EACH END OF PIPE BUT NOT MORE THAN 10' APART (2 PER PIPE). FOR PIPE DIAMETERS 14" AND LARGER INSTALL STAINLESS STEEL PIPE CASING SPACERS 5' OR LESS FROM EACH END OF PIPE AND ONE CENTERED ON PIPE (3 PER PIPE)(CASCADE MFG. CO. OR APPROVED EQUAL). 4. PIPE CASING SPACERS SHALL BE CENTER POSITIONED. 5. ALTERNATE METHODS OF PIPE SUPPORT WITHIN THE CASING MUST BE APPROVED BY POAPWS PRIOR TO INSTALLATION.
AutoCAD SHX Text
PIPE JOINT AND STEEL CASING
AutoCAD SHX Text
1" MINIMUM CLEARANCE BETWEEN
AutoCAD SHX Text
SHEET OF A 0.090" THICKNESS, OVERLAPS AT EDGES
AutoCAD SHX Text
THICKNESS. SHELL SHALL BE LINED WITH RIBBED PVC
AutoCAD SHX Text
OF 304 STAINLESS STEEL OF A MINIMUM 14-GAUGE
AutoCAD SHX Text
SPACERS SHALL BE BOLT ON STYLE, TWO PIECE SHELL
AutoCAD SHX Text
STEEL CASING
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 14: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Typical Underground Valve Installation

C-10

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. CONCRETE COLLAR MAY NOT BE REQUIRED IN PAVED AREAS IF PAVEMENT SURFACE IS FINISHED PRIOR TO FINAL INSPECTION AND VALVE BOX LID IS AT FINISHED GRADE. 2. WHEN VALVE IS DEEPER THAN 48" AN EXTENSION WILL BE REQUIRED TO BRING OPERATING NUT TO 24" OF FINISHED GRADE. 3. TWO OF THE FOLLOWING FORMS OF RESTRAINT SHALL BE USED WHEN PIPE IS GREATER THAN 12". A) APPROVED MECHANICAL JOINT RESTRAINT (i.e. MEGALUG) B) TIE RODS AND NUTS EQUAL IN DIA. TO TEE BOLTS AND NUTS, COATED WITH KOP-COAT 300-M OR APPROVED EQUAL.
AutoCAD SHX Text
TOP OF PAVEMENT
AutoCAD SHX Text
WHEN USED ON FORCE MAIN
AutoCAD SHX Text
USED ON WATER MAIN, "SEWER"
AutoCAD SHX Text
"WATER" TO BE CAST IN COVER WHEN
AutoCAD SHX Text
APPROVED VALVE
AutoCAD SHX Text
TRAFFIC LOADS TO VALVE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
5 1/4" CAST IRON ADJUSTABLE
AutoCAD SHX Text
VALVE BOX (SCREW TYPE)
AutoCAD SHX Text
VALVE BOX SHALL NOT TRANSMIT
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
4 x 4 WIRE MESH
AutoCAD SHX Text
8"
AutoCAD SHX Text
24"
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
48" MAXIMUM
AutoCAD SHX Text
8" THICK MINIMUM
AutoCAD SHX Text
CONCRETE COLLAR
AutoCAD SHX Text
24"
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 15: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Subaqueous Crossing - Direct Bury

C-11

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. DIRECT BURY ALLOWED ONLY IF DIRECTIONAL BORE METHOD IS NOT FEASIBLE. 2. VALVES TO BE TIED BACK TO NEAREST FITTING ONE EACH SIDE PER POAPWS STANDARDS. ALL TIE RODS AND BOTS SHALL BE COATED WITH KOPPERS 300-M OR APPROVED EQUAL. 3. VALVE EXTENSIONS AND BOXES SHOULD NOT BE LOCATED IN THE MAINTENANCE EASEMENT WITHOUT NPBCID APPROVAL. 4. MEGALUG RESTRAINTS REQUIRED. (TYPICAL) 5. FLOW THROUGH CANAL SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. 6. FLOW DIVERSION WILL NOT BE PERMITTED DURING WET SEASON. 7. IN SOME CASES AIR RELIEF VALVES MAY BE REQUIRED.
AutoCAD SHX Text
APPROVED VALVE
AutoCAD SHX Text
5' - 0" MIN.
AutoCAD SHX Text
COVER
AutoCAD SHX Text
TIE BACK ALL FITTINGS
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
CROSSING
AutoCAD SHX Text
C.I. VALVE
AutoCAD SHX Text
BOX
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
CROSSING
AutoCAD SHX Text
CONCRETE COLLAR
AutoCAD SHX Text
SUBAQUEOUS MAIN CROSSING WARNING SIGN
AutoCAD SHX Text
DESIGN SECTION
AutoCAD SHX Text
WATERWAY
AutoCAD SHX Text
E.M.S. MARKER
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
AND VALVES
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 16: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Canal CrossingCanal Crossing

C-12

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. ALL EXPOSED PIPE SHALL BE DUCTILE IRON WITH FLANGED FITTINGS. RETAINER GLANDS AND UNIFLANGE TYPE FITTINGS ARE NOT TO BE SUBSTITUTED FOR FLANGED FITTINGS. 2. SPAN LENGTHS AS REQUIRED BY PERMITTING AGENCY. 3. FAN GUARDS ARE REQUIRED. SEE "TYPICAL FAN GUARD" DETAIL. 4. PIPE SHALL BE CRADLED ON NEOPRENE, 1/2" THICK MINIMUM. 5. TIE-DOWN STRAPS SHALL FIT PROPERLY AND SECURE PIPE IN CRADLE. 6. PIPE CRADLE IN CAP SHALL CONTACT 1/2 CIRCUMFERENCE OF PIPE. 7. SHOW ULTIMATE CANAL SECTION AND RELEVANT ELEVATIONS AND DISTANCES ON PLANS. 8. PIPE SHALL BE RESTRAINED FOR A MINIMUM DISTANCE OF 60' FROM EACH BOTTOM DEFLECTION. SEE "PIPE RESTRAINT TABLE" DETAIL FOR ADDITIONAL RESTRAINT DISTANCES FOR PIPE 12" AND LARGER. 9. TWO OF THE FOLLOWING FORMS OF RESTRAINT SHALL BE USED ON ALL BELOW GRADE FITTINGS. A) APPROVED MECHANICAL JOINT RESTRAINT. (i.e. MEGALUG) B) TIE ROD AND NUTS EQUAL IN DIA. TO TEE BOLTS AND NUTS, COATED WITH KOP-COAT 300-M OR APPROVED EQUAL. 10. STAINLESS STEEL (316) REQUIRED FOR ALL STRAPS, SADDLES, FLANGE BOLTS, AND OTHER HARDWARE FOR INSTALLATIONS OVER BRACKISH OR MARINE WATERS (ANTI-GALL COMPOUND TO BE USED WHEN ASSEMBLING STAINLESS STEEL NUTS AND BOLTS.) 11. PILES SHALL BE SET A MINIMUM OF 10' INTO FIRM SOIL. LENGTH OF SPAN WILL DETERMINE NUMBER OF PILES REQUIRED. 12. AERIAL CROSSING TO BE FIELD COATED PER SPECIFICATIONS. COLOR SHALL BE PER SPECIFICATIONS. 13. ENGINEER SHALL BE REQUIRED TO DESIGN AND PROVIDE A DETAILED DRAWING OF PROPOSED PILE AND PILE CAP. THE DESIGN AND INSTALLATION SHALL MEET MANUFACTURERS RECOMMENDATION.
AutoCAD SHX Text
VALVE INSTALLATION" DETAIL
AutoCAD SHX Text
SEE "TYPICAL UNDERGROUND
AutoCAD SHX Text
FAN GUARD
AutoCAD SHX Text
(SEE NOTE 3)
AutoCAD SHX Text
F.D.O.T. GRADE (ACTUAL SIZE TO BE DETERMINED BY E.O.R.
AutoCAD SHX Text
MINIMUM 10" x 10" PRESTRESSED CONCRETE PILES
AutoCAD SHX Text
D.H.W.
AutoCAD SHX Text
4'-0"
AutoCAD SHX Text
SADDLE AND CORPORATION STOP
AutoCAD SHX Text
WITH DOUBLE STRAP TAPPING
AutoCAD SHX Text
AUTOMATIC AIR RELEASE VALVE
AutoCAD SHX Text
30"
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 17: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Typical Fan Guard

C-13

AutoCAD SHX Text
FLAT BAR
AutoCAD SHX Text
5/8" x 1 1/2"
AutoCAD SHX Text
5/8" x 2" FLAT BAR
AutoCAD SHX Text
5/8" DIA. x 8" LONG
AutoCAD SHX Text
EMBEDDED FASTENER
AutoCAD SHX Text
(STAINLESS STEEL)
AutoCAD SHX Text
5' - 6"
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. FAN GUARDS SHALL BE PLACED AT EACH END OF CANAL CROSSING. 2. FAN GUARD AND ALL MOUNTING BRACKETS TO BE HOT DIP GALVANIZED AFTER FABRICATION AND MOUNTING HARDWARE TO BE STAINLESS STEEL. 3. 1/2" THICK NEOPRENE PAD TO INSULATE PIPE FROM CONTACT WITH ALL MOUNTING HARDWARE, FAN GUARD HARDWARE, AND CONCRETE SURFACES.
AutoCAD SHX Text
BETWEEN CONC. CAP AND PIPE
AutoCAD SHX Text
1/2" THICK NEOPRENE PAD
AutoCAD SHX Text
5/8" x 2" FLAT BAR
AutoCAD SHX Text
5/8" DIA.
AutoCAD SHX Text
1/2" x 2" FLAT BAR
AutoCAD SHX Text
10' - 0"
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 18: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Pressure Pipe Deflection

C-14

AutoCAD SHX Text
SEE NOTE #1
AutoCAD SHX Text
SEE NOTE #1
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. FOR VERTICAL SEPARATION SEE "WATER AND SEWER SEPARATION STATEMENT" DETAIL. 2. ONE OF THE FOLLOWING FORMS OF RESTRAINT SHALL BE USED FROM FITTING TO FITTING FOR PIPE SIZES UP TO AND INCLUDING 12", FOR PIPE SIZES GREATER THAN 12" BOTH FORMS OF RESTRAINT SHALL BE USED. A) APPROVED MECHANICAL JOINT RESTRAINT. ( i.e. MEGALUG) B) TIE RODS AND NUTS EQUAL IN DIA. TO TEE BOLTS AND NUTS, COATED WITH KOP-COAT 300-M OR APPROVED EQUAL. 3. THE DEFLECTION TYPE CROSSING IS PREFERRED, BUT IN INSTANCES WHERE THE FITTING TYPE DEFLECTION IS USED, 22 1/2° BENDS ARE PREFERRED. 4. DO NOT EXCEED 75% OF MANUFACTURERS RECOMMENDED MAXIMUM JOINT DEFLECTION. 5. PIPE SHALL BE RESTRAINED FOR A MINIMUM DISTANCE OF 60' FROM EACH TOP DEFLECTION. SEE "PIPE RESTRAINT TABLE" DETAIL FOR ADDITIONAL RESTRAINT DISTANCES FOR PIPE GREATER THAN 12".
AutoCAD SHX Text
%%UDEFLECTION TYPE
AutoCAD SHX Text
PIPE AT POINT OF CROSSING
AutoCAD SHX Text
CENTER A FULL LENGTH OF
AutoCAD SHX Text
NO JOINTS BETWEEN FITTINGS
AutoCAD SHX Text
10'-0"
AutoCAD SHX Text
SEE NOTE 4
AutoCAD SHX Text
10'-0"
AutoCAD SHX Text
%%UFITTING TYPE
AutoCAD SHX Text
PRESSURE PIPE
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
MIN. COVER
AutoCAD SHX Text
SLOPE UP TO
AutoCAD SHX Text
CONFLICT PIPE
AutoCAD SHX Text
SEE NOTE 5
AutoCAD SHX Text
CONFLICT PIPE
AutoCAD SHX Text
30" MIN
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 19: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Installation ProtocolInstallation Protocol

C-15

AutoCAD SHX Text
INSTALLATION PROTOCOL 1. All pipe is to be laid in a clean dry trench. 2. All muck and unsuitable materials encountered in trench bottom shall be removed and replaced with compacted granular material to 100% of maximum density per AASHTO T-180. Proctor and density test results shall be submitted to EOR with a copy to PBPOC POA. 3. All backfill shall be placed in 12 inch lifts and compacted by mechanical means to 98% of maximum density per AASHTO T-180 or as otherwise required by the permitting agency. 4. Utilities crossing road right-of-way shall be installed prior to road construction and backfilled and compacted within right-of-way limits in strict accordance with the directions of the EOR and requirements of all agencies of jurisdiction. 5. Embedment materials below pipe shall conform to Unified Soil Classification System (U.S.C.S.) Soil Classification Class I or II as noted in ASTM D2321. 6. All lines under construction shall be plugged with a wing plug, and all pressure pipes are to be plugged with a mechanical plug or cap at the end of the working day to prevent ground water and potential contaminants from entering completed lines and lines under construction. 7. Above ground piping, including but not limited to, aerial crossings, lift station piping, fire lines, meter/backflow prevention device assemblies, etc. shall be flanged and be coated in the following manner: Blast clean and remove all paint and any loose material in accordance with NADF 500-3. Blasting Cleaning shall be performed using non-silcia media. Paint all exterior ferrous metal surfaces. The manufacturer's recommendations for surface preparation, priming, recoating, etc. shall be strictly followed. Do not paint or coat any nameplates, brass or stainless steel surfaces. Contractor shall use the following paint system or approved equal. TNEMEC a. Primer: TNEMEC-MODIFIED POLYAMIDOAMINE EPOXY #135 (3.0 to 5.0 mils DFT) aluminum color b. Intermediate Coat: TNEMEC-MODIFIED POLYAMIDOAMINE EPOXY (3.0 to 5.0 mils DFT) off white color c. Finish Coat: Series 1074 Endura-Shield, DFT. The finished coat of paint shall be green in color for sanitary sewer and blue for potable water appurtenances. 8. All flanged pipe shall be caulked between each flange and threads with Sika 1 A urethane caulk. 9. All tie rods, bolts, nuts, etc. installed underground must be Cor Ten and shall be painted with Koppers 300-M or an approved equal. Brass and stainless steel hardware is exempt from this requirement. 10. Coatings and linings damaged due mishandling or otherwise, must be replaced. Coating and linings damaged due to field cutting shall be repaired in strict accordance with the manufacturer's recommendations. This includes, but is not limited to, cement mortar and polyethylene pipe linings, Protecto 401, galvanized coatings, PVC fence coatings and other paint type coatings. Specific approval must be obtained from POAPWS prior to performing coating and lining repairs. The POAPWS will require inspections of all repairs. 11. All stainless steel nuts, bolts and hardware referenced in these standards, shall be SS 316 grade and shall be so stamped by the manufacturer to verify alloy. The use of any other stainless steel alloy will require specific approval by the POAPWS. In general, stainless steel nuts, bolts and hardware are required in and around lift stations and for facilities installed over or under brackish or marine waters. This requirement applies to flange bolts and nuts on flanged piping, mounting brackets, all thread rod, anchor bolts, washers, clamps and other miscellaneous hardware. Anti-galling compound anti-seize lubricant shall be applied to the threads of all stainless steel bolts prior to installation. Anti-seize lubricant shall be graphite 50 anti-seize by Loctite Corporation, 1000 anti-seize paste by Dow Corning, 3M Lube and anti-seize by 3M. 12. All rubber and synthetic elastomeric components of products that come in contact with potable water shall be manufactured with chloramine resistant elastomers and shall bear NSF approval. 13. All main, including fittings, shall be easily identifiable as to their contents and shall be color coded or marked using the universal color code of blue for water and green for sewer. Pipe striped during manufacturing of the pipe shall have continuous stripes that run parallel to the axis of the pipe, that are located at no greater than 90-degree intervals around the pipe, and that will remain intact during and after installation of the pipe. If tape is used to stripe pipe during installation of the pipe, the tape shall be applied in a continuous line that runs parallel to the axis of the pipe and that is located along the top of the pipe; for pipes with an internal diameter of 24 inches or greater, tape shall be applied in continuous lines along each side of the pipe as well as along the top of the pipe.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 20: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Valve ExtensionValve Extension

C-16

AutoCAD SHX Text
ALUMINUM OPERATING NUT
AutoCAD SHX Text
JOINT WELD
AutoCAD SHX Text
ROD - 1 " DIAMETER X " 12" DIAMETER X " 12" THICK ONE PIECE ALUMINUM
AutoCAD SHX Text
3 "116"
AutoCAD SHX Text
3 "116"
AutoCAD SHX Text
WELDED JOINT
AutoCAD SHX Text
WELDED JOINT
AutoCAD SHX Text
BOTTOM VIEW
AutoCAD SHX Text
TOP VIEW
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
1 "1516"
AutoCAD SHX Text
2'
AutoCAD SHX Text
2"
AutoCAD SHX Text
6"
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
2"
AutoCAD SHX Text
WELDED JOINT
AutoCAD SHX Text
GUIDE PLATE - 5" DIAMETER X " 14" ALUMINUM TO FIT INSIDE VALVE BOX RISER
AutoCAD SHX Text
VALVE BOX RISER
AutoCAD SHX Text
WELDED JOINT
AutoCAD SHX Text
INSIDE DIMENSION WILL BE 2 " TO 316" TO GO OVER AWWA BRASS WRENCH NUT. MAKE TOP PLATE OF 3 " X "316" X "12"
AutoCAD SHX Text
SIDE VIEW
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. EXTENSIONS ARE REQUIRED FOR VALVES EXTENDING FOR MORE THAN 4 FEET BELOW FINISHED GRADE. 2. ALL MATERIALS SHALL BE 6061 T-6 ALUMINUM.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 21: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Fence Detail

C-17

AutoCAD SHX Text
TOP RAIL 1 5/8" O.D.
AutoCAD SHX Text
GSP SCHD. 40
AutoCAD SHX Text
2 1/2" O.D. GSP
AutoCAD SHX Text
SCHD. 40 SPACED
AutoCAD SHX Text
AT 10'-0" MAX.
AutoCAD SHX Text
7 GA. AL. COATED
AutoCAD SHX Text
SPR. COIL TENSION
AutoCAD SHX Text
WIRE
AutoCAD SHX Text
CONCRETE FTG.
AutoCAD SHX Text
DIAGONAL
AutoCAD SHX Text
BRACE W/
AutoCAD SHX Text
TURNBUCKLE
AutoCAD SHX Text
STRETCHER
AutoCAD SHX Text
BAR
AutoCAD SHX Text
HORIZONTAL
AutoCAD SHX Text
BRACE
AutoCAD SHX Text
9 GA. VINYL
AutoCAD SHX Text
COATED STEEL
AutoCAD SHX Text
FABRIC
AutoCAD SHX Text
3" O.P. GST. SCHD.
AutoCAD SHX Text
40 AT CORNER
AutoCAD SHX Text
8'-0"
AutoCAD SHX Text
3'-6"
AutoCAD SHX Text
18"
AutoCAD SHX Text
6"
AutoCAD SHX Text
18"
AutoCAD SHX Text
8'-0"
AutoCAD SHX Text
%%ULINE POST
AutoCAD SHX Text
%%UCORNER POST
AutoCAD SHX Text
18"
AutoCAD SHX Text
6"
AutoCAD SHX Text
3'-6"
AutoCAD SHX Text
WATERPROOF CAP
AutoCAD SHX Text
HINGE (2)
AutoCAD SHX Text
4" O.D. GSP SCHD.
AutoCAD SHX Text
40 AT GATE OPENING
AutoCAD SHX Text
HORIZONTAL BRACE
AutoCAD SHX Text
DIAGONAL BRACE W/
AutoCAD SHX Text
TURNBUCKLE
AutoCAD SHX Text
CONCRETE FTG.
AutoCAD SHX Text
HOR,
AutoCAD SHX Text
BRACE
AutoCAD SHX Text
VERT.
AutoCAD SHX Text
BRACE
AutoCAD SHX Text
GATE RAIL & POSTS 1 5/8"
AutoCAD SHX Text
O.D. GSP SCHD. 40
AutoCAD SHX Text
STRETCHER BAR
AutoCAD SHX Text
%%UGATE
AutoCAD SHX Text
%%UGATE POST
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
1.
AutoCAD SHX Text
2.
AutoCAD SHX Text
3.
AutoCAD SHX Text
GATE TO BE SIZED PER REQUIREMENTS
AutoCAD SHX Text
VINYL COATED STEEL WOVEN WIRE FABRIC TO BE STRETCHED TAUT W/
AutoCAD SHX Text
STRETCHER BARS AND STRAPS AND FASTENED TOP & BOTTOM AND AT LINE
AutoCAD SHX Text
POSTS WITH GALV. PIG RING TIES.
AutoCAD SHX Text
GATE TO BE SECURED OPEN WITH GATE STOP SET IN CONCRETE.
AutoCAD SHX Text
ALL RAILS, POSTS AND HARDWARE TO BE BLACK VINYL COATED.
AutoCAD SHX Text
4.
AutoCAD SHX Text
5.
AutoCAD SHX Text
WHERE POSTS COME IN CONTACT WITH CONCRETE THEY SHALL BE COATED WITH KOPPERS 300M OR APPROVED EQUAL.
AutoCAD SHX Text
3/8" DIAGONAL BRACE ROD W/ TURNBUCKLE
AutoCAD SHX Text
GATES SHALL HAVE WELDED STEEL JOINTS COATED WITH ZINC BASED PAINT
AutoCAD SHX Text
GA. CALL-OUTS ARE FOR WIRE BEFORE VINYL COATING.
AutoCAD SHX Text
6.
AutoCAD SHX Text
FABRIC SHALL BE CONNECTED TO GATE FRAME EVERY 15" MAX.
AutoCAD SHX Text
VERTICAL BLACK PVC FENCE SLATS REQUIRED.
AutoCAD SHX Text
7.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 22: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Sample Point - In LineSample Point - In Line

C-20

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. WHERE POSSIBLE, SERVICE TAPS OR FIRE HYDRANTS (SEE "SAMPLE POINT - FIRE HYDRANT" DETAIL) SHALL BE USED AS SAMPLING POINTS.
AutoCAD SHX Text
DOUBLE STRAP TAPPING SADDLE - AWWA
AutoCAD SHX Text
THREADS. NO DIRECT TAPS SHALL BE PERMITTED.
AutoCAD SHX Text
WATER MAIN
AutoCAD SHX Text
3/4" LOCKING BALL VALVE
AutoCAD SHX Text
NATURAL GROUND
AutoCAD SHX Text
DISCHARGING ANY WATER ON THE GROUND
AutoCAD SHX Text
CORPORATION STOP - AFTER SAMPLING IS
AutoCAD SHX Text
COMPLETE, TURN CORPORATION STOP OFF,
AutoCAD SHX Text
THE EXCAVATED HOLE FOR THIS
AutoCAD SHX Text
INSTALLATION SHALL BE BACKFILLED
AutoCAD SHX Text
TO NATURAL GRADE PRIOR TO
AutoCAD SHX Text
REMOVE TUBING, AND PLUG SADDLE
AutoCAD SHX Text
WITH BRASS PLUG
AutoCAD SHX Text
3/4" COPPER TUBING TYPE "K" OR
AutoCAD SHX Text
POLYETHYLENE TUBING
AutoCAD SHX Text
24" MIN.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 23: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Sample Point - Fire Hydrant

C-21

AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
3/4" LOCKING
AutoCAD SHX Text
2 1/2" x 3/4" HYDRANT ADAPTER
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
18"
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
AS SPECIFIED
AutoCAD SHX Text
FIRE HYDRANT
AutoCAD SHX Text
2'-0" MIN.
AutoCAD SHX Text
OR COPPER
AutoCAD SHX Text
3/4" PVC SCH 40
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 24: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Flushing Hydrant

C-22

AutoCAD SHX Text
CONCRETE COLLAR (SEE "TYPICAL UNDER-
AutoCAD SHX Text
GROUND VALVE INSTALLATION" DETAIL)
AutoCAD SHX Text
VALVE BOX
AutoCAD SHX Text
CAST IRON
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
MECHANICAL JOINT RESTRAINTS
AutoCAD SHX Text
PLAIN END REDUCER
AutoCAD SHX Text
PLAIN END BY
AutoCAD SHX Text
2 1/2" NOZZLE TO FACE STREET
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
MUELLER 2 " POST AND FLUSH TYPE FIRE 12" POST AND FLUSH TYPE FIRE HYDRANT AS MANUFACTURED BY MUELLER CO.
AutoCAD SHX Text
4" M.J. SHOE
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 25: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Temporary Blow Off

C-23

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. TRAFFIC BEARING METER BOXES WILL BE REQUIRED IN ALL PAVED AREAS AND AREAS WHICH MAY BE PAVED IN THE FUTURE. 2. TUBING SHALL BE CONTINUOUS FROM CORPORATION STOP TO CURB STOP, NO FITTINGS SHALL BE PERMITTED. 3. PREVIOUS JOINTS SHALL BE RESTRAINED IN ACCORDANCE WITH "PIPE RESTRAINT TABLE" DETAIL.
AutoCAD SHX Text
STANDARD DOUBLE STRAP
AutoCAD SHX Text
TAPPING SADDLE WITH
AutoCAD SHX Text
AWWA THREADS AND 2"
AutoCAD SHX Text
CORPORATION STOP
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
48" MAX.
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
METER BOX
AutoCAD SHX Text
MEGALUG
AutoCAD SHX Text
M.J. SOLID PLUG
AutoCAD SHX Text
2" CORP. STOP
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
%%UPLAN VIEW
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
2" BRASS PLUG
AutoCAD SHX Text
VALVE AND BOX
AutoCAD SHX Text
STANDARD 1" CDR
AutoCAD SHX Text
METER BOX BY CONTRACTOR
AutoCAD SHX Text
STOP 4" BELOW GRADE
AutoCAD SHX Text
2" POLYETHYLENE TUBING C.T.S.
AutoCAD SHX Text
2" LOCKING CURB
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 26: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Cannon Flushing Procedure

C-24

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. UPON COMPLETION OF THE PIPE INSTALLATION FOR ANY SECTION, THE MAINS SHALL BE CANNON FLUSHED TO REMOVE DIRT AND ANY OTHER FOREIGN MATTER BY ACHIEVING A MINIMUM VELOCITY OF 2.5 FEET PER SECOND IN THE PIPE. TEMPORARY FITTINGS, PIPE, ETC. MAY BE NEEDED TO FACILITATE CANNON FLUSHING. 2. INSTALL A 45° BEND AND ASSOCIATED PIPING AS SHOWN TO DIRECT THE FLUSHING WATER AWAY FROM THE IMMEDIATE WORK AREA, EXERCISE DUE CARE TO ENSURE THAT THE WATER USED IN FLUSHING DOES NOT CAUSE A NUISANCE OR CAUSE PROPERTY DAMAGE. 3. BENDS AND PIPING SHALL BE THE SAME SIZE AS THE LINE TO BE FLUSHED. 4. PRIOR TO THE ACTUAL LINE FLUSHING OPERATION, THE CONTRACTOR SHALL PROPERLY NOTIFY PBPOC POA OF SUCH INTENDED WATER USE. 5. NO EXISTING VALVES SHALL BE TURNED ON OR OFF, EXCEPT BY AUTHORIZED POAPWS PERSONNEL. 6. FLUSHING SHALL NOT BE ACCOMPLISHED WITHOUT THE ACTUAL PRESENCE OF A POAPWS REPRESENTATIVE. 7. AFTER THE LINE UNDER CONSTRUCTION HAS BEEN SUCCESSFULLY FLUSHED THE CONTRACTOR SHALL REMOVE THE TEMPORARY PIPING ARRANGEMENT AND PROCEED WITH THE REMAINING CONSTRUCTION AS SPECIFIED. 8. THERE ARE SPECIAL REQUIREMENTS FOR CLEANING AND FLUSHING PIPE LARGER THAN 12".
AutoCAD SHX Text
PIPE AND VALVE
AutoCAD SHX Text
UNDER CONSTRUCTION
AutoCAD SHX Text
AND 45%%D BEND
AutoCAD SHX Text
TEMPORARY FLUSH PIPE
AutoCAD SHX Text
TEMPORARY BACKFILL
AutoCAD SHX Text
3' MIN.
AutoCAD SHX Text
6' MAX.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 27: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Typical Fire Hydrant InstallationTypical Fire Hydrant Installation

C-25

AutoCAD SHX Text
INSTALL A SECOND VALVE AS SHOWN
AutoCAD SHX Text
WHEN DISTANCE EXCEEDS 20'-0"
AutoCAD SHX Text
4 1/2" PUMPER NOZZLE FACING ACCESS
AutoCAD SHX Text
R/W AND TWO 2 1/2" HOSE NOZZLES
AutoCAD SHX Text
CONCRETE COLLAR (SEE "TYPICAL UNDER-
AutoCAD SHX Text
GROUND VALVE INSTALLATION" DETAIL)
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. DRAINS OR WEEP HOLES ON HYDRANT BARREL SHALL BE PLUGGED. 2. FIRE HYDRANT SHALL BE INSTALLED PLUMB AND TRUE. 3. REFER TO SHOP SPECIFICATION LIST FOR ACCEPTABLE FIRE HYDRANTS. 4. TWO OF THE FOLLOWING FORMS OF RESTRAINT SHALL BE USED WHEN PIPE IS GREATER THAN 12". A) APPROVED MECHANICAL JOINT RESTRAINT (i.e. MEGALUG) B) TIE RODS AND NUTS EQUAL IN DIA. TO TEE BOLTS AND NUTS, COATED WITH KOP-COAT 300-M OR APPROVED EQUAL.
AutoCAD SHX Text
CAST IRON
AutoCAD SHX Text
VALVE BOX
AutoCAD SHX Text
FINISH GROUND OR
AutoCAD SHX Text
PAVEMENT SURFACE
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
6" D.I.
AutoCAD SHX Text
M.J. PIPE
AutoCAD SHX Text
NON-RISING STEM
AutoCAD SHX Text
6" GATE VALVE
AutoCAD SHX Text
18" SPOOL PIECE
AutoCAD SHX Text
MECHANICAL JOINT TEE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
18" MIN
AutoCAD SHX Text
24" MAX
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
48" MAX.
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
MEASURED FLANGE TO FLANGE
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 28: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

·

Water Service Installation - Angle Meter Stop

C-27

AutoCAD SHX Text
MAGNETIC MARKER
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. CASINGS SHALL BE REQUIRED FOR ALL LONG SIDE SERVICES. 2. SUCCESSIVE TAPS INTO THE WATER MAIN SHALL BE SPACED A MINIMUM OF 18" OFFSET AND AT 90° FROM THE CENTERLINE AS SHOWN ON DETAIL "A". 3. WHERE NO SIDEWALK EXISTS, METER BOXES SHALL BE SET TO CONFORM TO FINISH GRADE. 4. COPPER TUBING SHALL BE TYPE "K" WITH COMPRESSION FITTINGS. 5. POLYETHYLENE TUBING SHALL BE SDR 9, COPPER TUBE SIZE. 8. TAPPING SADDLES AND CORPORATION STOPS SHALL HAVE AWWA INLET THREADS. 9. SERVICE CASING SHALL NOT BE INSTALLED BY WATER JETTING UNDER ROADWAY. 10. GALVANIZED SCHEDULE 40 CASING REQUIRED FOR ANY INSTALLATION REQUIRING A JACK AND BORE, SCHEDULE 40 PVC MAY BE USED FOR AN OPEN CUT INSTALLATION WITH THE APPROVAL OF PBPOC LDRB, CASING SHOULD EXTEND TEN (10) FEET BEYOND EDGE OF PAVEMENT AND SIZED AS FOLLOWS: 1 1/2" SERVICE USE 3" CASING
AutoCAD SHX Text
CASING WITH GROUT
AutoCAD SHX Text
SEAL BOTH ENDS OF
AutoCAD SHX Text
36" MAXIMUM
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
30" MIN. COVER
AutoCAD SHX Text
OR EXISTING COVER
AutoCAD SHX Text
10'
AutoCAD SHX Text
AND TUBING (MINIMUM SIZE)
AutoCAD SHX Text
1-1/2" CORPORATION STOP
AutoCAD SHX Text
DOUBLE STRAP TAPPING SADDLE
AutoCAD SHX Text
(NO DIRECT TAPS PERMITTED)
AutoCAD SHX Text
SEE NOTE NO. 9
AutoCAD SHX Text
10'
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
EDGE OF PAVEMENT
AutoCAD SHX Text
METER PURCHASE THROUGH PBPOC POA
AutoCAD SHX Text
FORD UVB 43-42W-65 NL BALL
AutoCAD SHX Text
VALVE BRANCH ASSEMBLY
AutoCAD SHX Text
PAVEMENT
AutoCAD SHX Text
12"
AutoCAD SHX Text
10"
AutoCAD SHX Text
%%UDETAIL "A"
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
1'%%P
AutoCAD SHX Text
PACK JOINT 90°
AutoCAD SHX Text
METER BOX PROVIDED BY OWNER OR CONTRACTOR
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 29: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Typical Water ServiceTypical Water Service

C-28

AutoCAD SHX Text
DOUBLE STRAP TAPPING
AutoCAD SHX Text
THREADS (TYPICAL)
AutoCAD SHX Text
SADDLE WITH AWWA
AutoCAD SHX Text
BRASS COMPRESSION
AutoCAD SHX Text
%%UQUAD SERVICE
AutoCAD SHX Text
1 1/2" SERVICE
AutoCAD SHX Text
15" MIN.
AutoCAD SHX Text
18"%%P
AutoCAD SHX Text
1" LINE (TYPICAL)
AutoCAD SHX Text
"Y" BRANCH
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
METER PURCHASE THROUGH PBPOC POA (TYPICAL)
AutoCAD SHX Text
METER BOX BY OWNER OR CONTRACTOR
AutoCAD SHX Text
%%UDOUBLE SERVICE
AutoCAD SHX Text
BALL VALVE BRANCH
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
(FORD Y44-264 NL)
AutoCAD SHX Text
FORD UVB43-42W-65
AutoCAD SHX Text
(TYPICAL ALL SERVICES)
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
3/4" SERVICE LINE (MIN)
AutoCAD SHX Text
%%USINGLE SERVICE
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. REQUIRED LOCATION OF METER AND METER BOX MAY VARY DEPENDENT UPON SITE CONDITIONS. 2. AUTHORIZED SERVICE LINE MATERIAL: A) TYPE "K" COPPER TUBING WITH COMPRESSION FITTINGS. B) POLYETHYLENE TUBING SDR 9, COPPER TUBE SIZE. 3. METER CURB STOP SHALL BE 1" MINIMUM. 4. 1" METER CURB STOPS WITH 3/4" VALVES SHALL NOT BE PERMITTED. 5. MULTIPLE SERVICE/METER INSTALLATIONS OF MORE THAN 4 METERS PER SERVICE AND SERVICE LINES LARGER THAN 2" IN DIAMETER SHALL BE HANDLED ON AN INDIVIDUAL BASIS. 6. METER CURB STOPS 1 1/2" AND 2" IN SIZE SHALL BE PROVIDED WITH BOTH A LOCKING CAP AND METER FLANGE. 7. NO FITTINGS BETWEEN CORP STOP AND METER CURB STOP ALLOWED WHEN USING POLYETHYLENE TUBING.
AutoCAD SHX Text
METER CURB STOP
AutoCAD SHX Text
PROPERTY
AutoCAD SHX Text
12"
AutoCAD SHX Text
LINE
AutoCAD SHX Text
1 1/2" SERVICE (MIN)
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 30: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Typical Water Service Installation

C-29

AutoCAD SHX Text
MAGNETIC MARKER
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. CASINGS SHALL BE REQUIRED FOR ALL LONG SIDE SERVICES. 2. SUCCESSIVE TAPS INTO THE WATER MAIN SHALL BE SPACED A MINIMUM OF 18" OFFSET AND AT 90° FROM THE CENTERLINE AS SHOWN ON DETAIL "A". 3. WHERE NO SIDEWALK EXISTS, METER BOXES SHALL BE SET TO CONFORM TO FINISH GRADE. 4. COPPER TUBING SHALL BE TYPE "K" WITH COMPRESSION FITTINGS. 5. POLYETHYLENE TUBING SHALL BE SDR 9, COPPER TUBE SIZE. 6. ROTATE THE CORPORATION STOP SO THAT THE OPERATING NUT IS ACTUATED FROM THE VERTICAL POSITION RATHER THAN THE HORIZONTAL. 7. BOTH COPPER AND POLYETHYLENE TUBING SERVICE LINES SHALL BE CONTINUOUS FROM CORPORATION STOP TO CURB STOP WITH NO FITTINGS IN BETWEEN. 8. TAPPING SADDLES AND CORPORATION STOPS SHALL HAVE AWWA INLET THREADS. 9. SERVICE CASING SHALL NOT BE INSTALLED BY WATER JETTING UNDER ROADWAY. 10. GALVANIZED SCHEDULE 40 CASING REQUIRED FOR ANY INSTALLATION REQUIRING A JACK AND BORE , SCHEDULE 40 PVC MAY BE USED FOR AN OPEN CUT INSTALLATION WITH THE APPROVAL OF PBPOC LDRB, CASING SHOULD EXTEND TEN (10) FEET BEYOND EDGE OF PAVEMENT AND SIZED AS FOLLOWS: A.) 1" SERVICE USE 2" CASING B.) 1 1/2" SERVICE USE 3" CASING C.) 2" SERVICE USE 4" CASING
AutoCAD SHX Text
CASING WITH GROUT
AutoCAD SHX Text
SEAL BOTH ENDS OF
AutoCAD SHX Text
PROPERTY LINE
AutoCAD SHX Text
36" MAXIMUM
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
30" MIN. COVER
AutoCAD SHX Text
OR EXISTING COVER
AutoCAD SHX Text
10'
AutoCAD SHX Text
AND TUBING (MINIMUM SIZE)
AutoCAD SHX Text
1" CORPORATION STOP
AutoCAD SHX Text
DOUBLE STRAP TAPPING SADDLE
AutoCAD SHX Text
(NO DIRECT TAPS PERMITTED)
AutoCAD SHX Text
SEE NOTE NO. 9
AutoCAD SHX Text
10'
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
EDGE OF PAVEMENT
AutoCAD SHX Text
METER BOX PROVIDED BY OWNER OR CONTRACTOR
AutoCAD SHX Text
1" CURB STOP (MIN.) WITH LOCKING
AutoCAD SHX Text
WINGS AND DRILLED METER NUT
AutoCAD SHX Text
PAVEMENT
AutoCAD SHX Text
12"
AutoCAD SHX Text
8"
AutoCAD SHX Text
%%UDETAIL "A"
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
METER PURCHASE THROUGH PBPOC POA
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 31: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Water Service Tap Under Pavement

C-30

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. SUCCESSIVE TAPS INTO THE WATER MAIN SHALL BE SPACED A MINIMUM OF 18" OFFSET AND AT 90° FROM THE CENTERLINE AS SHOWN ON DETAIL "A". 2. COPPER TUBING SHALL BE TYPE "K" WITH COMPRESSION FITTINGS. 3. POLYETHYLENE TUBING SHALL BE SDR 9, COPPER TUBE SIZE. 4. BOTH COPPER AND POLYETHYLENE TUBING SERVICE LINES SHALL BE CONTINUOUS FROM CURB STOP TO ANGLE METER STOP WITH NO FITTINGS IN BETWEEN. 5. TAPPING SADDLES TO HAVE AWWA THREADS. 6. CORPORATION STOP AT THE MAIN TO HAVE MALE AWWA THREADS ON ONE SIDE AND BE COMPRESSION ON THE OTHER SIDE. 7. VALVE BOX SHALL BE 5 1/4" CAST IRON SCREW TYPE ADJUSTABLE. 8. CONCRETE COLLAR VALVE BOX SUPPORT TO BE PLACED ON COMPACTED SOIL TO SUPPORT VALVE BOX SO THAT A MINIMUM OF 4 INCHES EXISTS BETWEEN THE BOTTOM OF THE CONCRETE COLLAR AND THE TOP OF THE WATER MAIN.
AutoCAD SHX Text
3" PVC SCH 40 SLEEVE
AutoCAD SHX Text
4" PVC SCH 40 SLEEVE
AutoCAD SHX Text
"WATER" CAST IN COVER (SEE NOTE 7)
AutoCAD SHX Text
ADJUSTABLE CAST IRON VALVE BOX WITH
AutoCAD SHX Text
%%UDETAIL "A"
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
"TYPICAL WATER SERVICE" DETAIL
AutoCAD SHX Text
SADDLE (NO DIRECT TAPS
AutoCAD SHX Text
DOUBLE STRAP TAPPING
AutoCAD SHX Text
CORP STOP AND TUBING
AutoCAD SHX Text
CONCRETE COLLAR VALVE BOX SUPPORT
AutoCAD SHX Text
STATIONARY ROD WITH GUIDE
AutoCAD SHX Text
VIA STAINLESS STEEL COTTER PIN
AutoCAD SHX Text
RING, SECURED TO CURB STOP
AutoCAD SHX Text
(SEE NOTE 6)
AutoCAD SHX Text
24"x 24"x 4" THK. WITH WIRE MESH
AutoCAD SHX Text
(SEE NOTE 8)
AutoCAD SHX Text
FOR METER DETAILS SEE
AutoCAD SHX Text
PERMITTED)
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
4" MIN.
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
48" MAX.
AutoCAD SHX Text
EXTEND 6" TO 12" BELOW PAVING
AutoCAD SHX Text
MUELLER STATIONARY ROD TO
AutoCAD SHX Text
PAVEMENT
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 32: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Protective Enclosures for Above Ground Devices

C-31

AutoCAD SHX Text
ON LOCATION)
AutoCAD SHX Text
QUIRED DEPENDING
AutoCAD SHX Text
SIZE MAY BE RE-
AutoCAD SHX Text
CONCRETE(LARGER
AutoCAD SHX Text
PIPE FILLED WITH
AutoCAD SHX Text
SCH 40 GALV.STEEL
AutoCAD SHX Text
MIN. 4" D.I.P. OR
AutoCAD SHX Text
SET PIPE IN
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
PROTECTIVE PIPE STANCHIONS
AutoCAD SHX Text
%%UOPTION "A"
AutoCAD SHX Text
SEE APPROPRIATE VALVING
AutoCAD SHX Text
ARRANGEMENT TO PROPERLY
AutoCAD SHX Text
QUANTITY OF STANCHIONS AND
AutoCAD SHX Text
SPACING (D") BETWEEN THEM
AutoCAD SHX Text
SHALL BE DETERMINED ON AN
AutoCAD SHX Text
INDIVIDUAL PROJECT BASIS
AutoCAD SHX Text
GRADE
AutoCAD SHX Text
SIZE METER PIT
AutoCAD SHX Text
3'-0"
AutoCAD SHX Text
2'-0"
AutoCAD SHX Text
D"
AutoCAD SHX Text
3 - #5 REBAR
AutoCAD SHX Text
SEE APPROPRIATE VAL-
AutoCAD SHX Text
VING ARRANGEMENT TO
AutoCAD SHX Text
PROPERLY SIZE METER
AutoCAD SHX Text
PIT AND LOCATION OF
AutoCAD SHX Text
METER WALL OPENING
AutoCAD SHX Text
ON ABOVE GROUND IN-
AutoCAD SHX Text
STALLATIONS.
AutoCAD SHX Text
TOP OF WALL TO HAVE CONTINUOUS
AutoCAD SHX Text
U-BLOCK WITH ONE #5 REBAR
AutoCAD SHX Text
AND FILLED WITH CONCRETE
AutoCAD SHX Text
%%UOPTION "B"
AutoCAD SHX Text
SCREENING WALL
AutoCAD SHX Text
BACK FOOTER TO BE A MINIMUM OF 12" FROM
AutoCAD SHX Text
PIPE ASSEMBLY AND SIDE WALLS TO BE A
AutoCAD SHX Text
MINIMUM OF 36" FROM PIPE ASSEMBLY
AutoCAD SHX Text
8"
AutoCAD SHX Text
%%USECTION "A-A"
AutoCAD SHX Text
10"
AutoCAD SHX Text
8"
AutoCAD SHX Text
*
AutoCAD SHX Text
D"
AutoCAD SHX Text
8"
AutoCAD SHX Text
30"
AutoCAD SHX Text
*
AutoCAD SHX Text
1/2" - 3/4" ROCK
AutoCAD SHX Text
MINIMUM 8" THICK
AutoCAD SHX Text
CONCRETE BLOCKS WITH #5 REBAR AT CORNERS
AutoCAD SHX Text
AND ON 2'-0" CENTERS, FILL VOIDS WITH
AutoCAD SHX Text
2500 P.S.I. CONCRETE
AutoCAD SHX Text
D"
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2016
AutoCAD SHX Text
Revision 1
Page 33: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Pipe SupportPipe Support

C-32

AutoCAD SHX Text
12.0"
AutoCAD SHX Text
NOTE: ALL MATERIAL SHALL BE 316 STAINLESS STEEL
AutoCAD SHX Text
18"
AutoCAD SHX Text
16"
AutoCAD SHX Text
14"
AutoCAD SHX Text
12"
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
10"
AutoCAD SHX Text
8"
AutoCAD SHX Text
6"
AutoCAD SHX Text
4"
AutoCAD SHX Text
3"
AutoCAD SHX Text
1 1/2"
AutoCAD SHX Text
1 1/2"
AutoCAD SHX Text
1 1/4"
AutoCAD SHX Text
1 1/4"
AutoCAD SHX Text
1 1/4"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1 1/4"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1/2" x 3"
AutoCAD SHX Text
1/2" x 3"
AutoCAD SHX Text
3/8" x 3"
AutoCAD SHX Text
3/8" x 3"
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
1 1/4"
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
1"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
A
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
3/8" x 3"
AutoCAD SHX Text
1/4" x 2"
AutoCAD SHX Text
1/4" x 2"
AutoCAD SHX Text
1/4" x 2"
AutoCAD SHX Text
1/4" x 2"
AutoCAD SHX Text
SADDLE
AutoCAD SHX Text
A
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
6" x 6"
AutoCAD SHX Text
6" x 6"
AutoCAD SHX Text
6" x 6"
AutoCAD SHX Text
6" x 6"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
1' - 0"
AutoCAD SHX Text
PLATE
AutoCAD SHX Text
SUPPORT PIPE
AutoCAD SHX Text
6" x 6"
AutoCAD SHX Text
4" x 4"
AutoCAD SHX Text
4" x 4"
AutoCAD SHX Text
4" x 4"
AutoCAD SHX Text
PLATE
AutoCAD SHX Text
4" x 4"
AutoCAD SHX Text
SADDLE
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 34: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

3" and Larger Meter and Backflow AssemblyMeter and Backflow Assembly (3" and Larger)

C-33

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. MECHANICAL JOINT FITTINGS SHALL BE REQUIRED UNDERGROUND AND FLANGED FITTINGS FOR ABOVE GROUND USE, NO UNIFLANGES PERMITTED. 2. PAINT THE ABOVE GROUND ASSEMBLY IN ACCORDANCE WITH STANDARDS AND SPECIFICATIONS, AFTER MANUFACTURERS RECOMMENDED SURFACE PREP IS COMPLETED. DO NOT PAINT OVER NAME/SERIAL PLATE, STAINLESS STEEL OR BRASS FITTINGS. 3. WHEN PROTECTIVE PIPE STANCHIONS OR A SCREEN WALL IS REQUIRED, SEE "PROTECTIVE ENCLOSURES FOR ABOVE GROUND DEVICES" DETAIL. 4. APPROVED REDUCED PRESSURE BACKFLOW PREVENTER WITH SILICONE RUBBER SEAL RINGS OR DISKS: A.) APOLLO MODEL RPL 4A, 4" TO 12" B.) AMES MODEL 4000 SSSR, 4" TO 10" C.) AMES MODEL 4000 SSI, 4" TO 10" 5. APPROVED DOUBLE CHECK VALVE ASSEMBLIES WITH SILICONE RUBBER SEAL RINGS OR DISKS. A.) AMES 2000 SS 6. 3" METER REQUIRES 4" BACKFLOW ASSEMBLY AND PIPING. 7. ALL TEST PORTS SHALL BE PLUGGED WITH BRASS PLUGS.
AutoCAD SHX Text
DOUBLE CHECK VALVE ASSEMBLY(SEE NOTE 5)
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
FROM
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
4" MIN. SIZE
AutoCAD SHX Text
18" MAX.
AutoCAD SHX Text
FULL FACED NEOPRENE GASKETS
AutoCAD SHX Text
SHALL BE REQUIRED ON ALL
AutoCAD SHX Text
FLANGES
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW PREVENTION DEVICE
AutoCAD SHX Text
(3/4" TAP WITH LOCKING
AutoCAD SHX Text
NON-RISING STEM GATE
AutoCAD SHX Text
VALVE WITH HAND WHEEL
AutoCAD SHX Text
OPERATOR (TYPICAL)
AutoCAD SHX Text
(TO BE SIZED BY ENGINEER
AutoCAD SHX Text
____" EMERGENCY BYPASS
AutoCAD SHX Text
OF RECORD)(4" MIN. SIZE)
AutoCAD SHX Text
TEST PORT
AutoCAD SHX Text
BALL VALVE)(TYPICAL)
AutoCAD SHX Text
(SEE NOTE 4)
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
TO
AutoCAD SHX Text
(SEE "PIPE SUPPORT" DETAIL)
AutoCAD SHX Text
PIPE SUPPORTS REQUIRED
AutoCAD SHX Text
THIS DRAWING DEPICTS A GENERAL ASSEMBLY ONLY. THE ENGINEER OF RECORD SHALL COORDINATE THE SPECIFIC ASSEMBLY'S REQUIREMENTS WITH POAPWS.
AutoCAD SHX Text
COMPOUND WATER METER (TO BE PROVIDED BY PBPOC POA)
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 35: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Above Ground FirelineAbove Ground Fireline

C-34

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. MECHANICAL JOINT FITTINGS SHALL BE REQUIRED UNDERGROUND AND FLANGED FITTINGS FOR ABOVE GROUND USE, NO UNIFLANGES PERMITTED. 2. PAINT THE ABOVE GROUND ASSEMBLY, INCLUDING ENTIRE LENGTH OF TIE RODS, IN ACCORDANCE WITH STANDARDS AND SPECIFICATIONS, AFTER MANUFACTURERS RECOMMENDED SURFACE PREP IS COMPLETED. DO NOT PAINT OVER NAME/SERIAL PLATE, STAINLESS STEEL OR BRASS FITTINGS. 3. WHEN PROTECTIVE PIPE STANCHIONS OR A SCREEN WALL IS REQUIRED, SEE "PROTECTIVE ENCLOSURES FOR ABOVE GROUND DEVICES" DETAIL. 4. APPROVED DOUBLE CHECK DETECTOR VALVE ASSEMBLIES WITH SILICONE RUBBER SEAL RINGS OR DISKS: A.) AMES MODEL 3000 SSI B.) AMES MODEL 3000 SSR C.) WATTS MODEL 774 DCDA SERIES 994 D.) APOLLO MODEL DCDA LF4A 5. SPECIAL FIRE PROTECTION SYSTEMS USING INTERNAL PUMPS, TANKS, ETC. SHALL BE REQUIRED TO USE AN APPROVED REDUCED PRESSURE BACKFLOW PREVENTION ASSEMBLY. 6. ALL TEST PORTS SHALL BE PLUGGED WITH BRASS PLUGS. 7. TWO OF THE FOLLOWING FORMS OF RESTRAINT SHALL BE USED WHEN PIPE IS GREATER THAN 12". A) APPROVED MECHANICAL JOINT RESTRAINT (i.e. MEGALUG) B) TIE RODS AND NUTS EQUAL IN DIA. TO TEE BOLTS AND NUTS, COATED WITH KOP-COAT 300-M OR APPROVED EQUAL.
AutoCAD SHX Text
BY-PASS CHECK VALVES SHALL CONFORM
AutoCAD SHX Text
TO POAPWS STANDARDS
AutoCAD SHX Text
5/8" SENSUS METER
AutoCAD SHX Text
(PURCHASE FROM PBPOC POA)
AutoCAD SHX Text
FULL FACED NEOPRENE GASKETS
AutoCAD SHX Text
SHALL BE REQUIRED ON ALL
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
FLANGES
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
18" MAX.
AutoCAD SHX Text
DOUBLE CHECK DETECTOR VALVE ASSEMBLY
AutoCAD SHX Text
(SEE NOTE 4)
AutoCAD SHX Text
O.S.& Y. GATE VALVE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
POST INDICATOR VALVE
AutoCAD SHX Text
WHERE SPECIFIED
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 36: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Fireline with 1" to 2" Domestic SupplyFireline with 1" to 2" Domestic Supply

C-35

AutoCAD SHX Text
CORPORATION
AutoCAD SHX Text
STOP
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. MECHANICAL JOINT FITTINGS SHALL BE REQUIRED UNDERGROUND AND FLANGED FITTINGS FOR ABOVE GROUND USE, NO UNIFLANGES PERMITTED. 2. PAINT THE ABOVE GROUND ASSEMBLY, INCLUDING ENTIRE LENGTH OF TIE RODS, IN ACCORDANCE WITH STANDARDS AND SPECIFICATIONS, AFTER MANUFACTURERS RECOMMENDED SURFACE PREP IS COMPLETED. DO NOT PAINT OVER NAME/SERIAL PLATE, STAINLESS STEEL OR BRASS FITTINGS. 3. WHEN PROTECTIVE PIPE STANCHIONS OR SCREEN WALL IS REQUIRED, SEE "PROTECTIVE ENCLOSURES FOR ABOVE GROUND DEVICES" DETAIL. 4. APPROVED DOUBLE CHECK DETECTOR VALVE ASSEMBLIES WITH SILICONE RUBBER SEAL RINGS OR DISKS: A.) AMES MODEL 3000 SSI B.) AMES MODEL 3000 SSR C.) WATTS MODEL 774 DCDA SERIES 994 D.) APOLLO MODEL DCDA LF4A 4" - 12" 5. TYPE "K" COPPER TUBING (SOFT DRAWN) OR POLYETHYLENE TUBING SDR 9 COPPER TUBING SIZE. (UNDERGROUND USE ONLY) IF DISTANCE BETWEEN METER AND RISER IS LESS THAN 6 FEET ONLY COPPER TUBING SHALL BE PERMITTED. 6. TWO OF THE FOLLOWING FORMS OF RESTRAINT SHALL BE USED WHEN PIPE IS GREATER THAN 12". A) APPROVED MECHANICAL JOINT RESTRAINT (i.e. MEGALUG) B) TIE RODS AND NUTS EQUAL IN DIA. TO TEE BOLTS AND NUTS, COATED WITH KOP-COAT 300-M OR APPROVED EQUAL.
AutoCAD SHX Text
METER (PURCHASE FROM PBPOC POA)
AutoCAD SHX Text
FULL FACED NEOPRENE GASKETS
AutoCAD SHX Text
SHALL BE REQUIRED ON ALL
AutoCAD SHX Text
FIRE LINE
AutoCAD SHX Text
FLANGES
AutoCAD SHX Text
DOUBLE STRAP
AutoCAD SHX Text
TAPPING SADDLE
AutoCAD SHX Text
SEE NOTE 6
AutoCAD SHX Text
DOMESTIC WATER LINE
AutoCAD SHX Text
INSTALL BRASS PLUG
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
DOUBLE CHECK DETECTOR VALVE
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
CURB STOP
AutoCAD SHX Text
3' (TYP)
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
18" MAX.
AutoCAD SHX Text
5/8" SENSUS METER
AutoCAD SHX Text
(PURCHASE FROM PBPOC POA)
AutoCAD SHX Text
12"
AutoCAD SHX Text
O.S.& Y. GATE VALVE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
(SEE NOTE 4)
AutoCAD SHX Text
FOR DOMESTIC SUPPLY BACKFLOW DEVICE REQUIREMENTS SEE "WATER METER AND BACKFLOW DEVICE 34" TO 2".
AutoCAD SHX Text
TEST PORT
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 37: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Water Meter and Backflow Device - 3/4" to 2"Water Meter and Backflow Device 3/4" to 2"

C-36

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. TYPE "K" COPPER TUBING (SOFT DRAWN) OR POLYETHYLENE TUBING SDR 9 COPPER TUBE SIZE. 2. IF THIS DISTANCE IS LESS THAN 6 FEET ONLY COPPER TUBING SHALL BE PERMITTED. 3. BOTH RISERS SHALL BE TYPE "K" COPPER TUBING (HARD DRAWN) WITH COPPER/BRASS SOLDER FITTINGS AND ADAPTERS. ONLY LEAD FREE SOLDER AND FLUX SHALL BE PERMITTED. 4. 1 1/2" AND 2" METER STOPS SHALL BE EQUIPPED WITH LOCKING CAPS AND METER FLANGES. 5. APPROVED BACKFLOW PREVENTION DEVICES WITH SILICONE RUBBER SEAL RINGS OR DISKS: A.) WATTS MODEL LF919 3/4" TO 2" B.) AMES MODEL LF400B 3/4" TO 2" C.) WILKINS 975 XL2 3/4" TO 2" D.) APOLLO MODEL RPLF 4A 3/4" TO 2" APOLLO MODEL RPLF 4A 3/4" TO 2" 3/4" TO 2" 6. WHEN THE DEVICE IS INSTALLED PARALLEL TO A BUILDING WALL THERE SHALL BE A MINIMUM OF 2' BETWEEN THE EDGE OF THE DEVICE AND THE BUILDING WALL. 7. BACKFLOW PREVENTION DEVICE SHALL BE EQUIPPED WITH BALL VALVES. 8. BACKFLOW PREVENTION DEVICE SHALL BE SUPPORTED AT BOTH RISERS WITH A MINIMUM OF 2 - 1 " STAINLESS STEEL 58" STAINLESS STEEL UNISTRUTS. RISERS TO BE SECURED TO UNISTRUT WITH 304 STAINLESS STEEL MOUNTING HARDWARE AND " NEOPRENE 14" NEOPRENE INSULATORS BETWEEN ALL DISSIMILAR METALS. 9. BACKFLOW DEVICES SHALL BE A MINIMUM OF 3' FROM BACK OF CURB.
AutoCAD SHX Text
FOR ABOVE GROUND DEVICES" DETAIL)
AutoCAD SHX Text
THE FIELD (SEE "PROTECTIVE ENCLOSURES
AutoCAD SHX Text
EXACT LOCATION TO BE DETERMINED IN
AutoCAD SHX Text
30" TAIL PIECE INSTALLED TO
AutoCAD SHX Text
WITHIN 3" OF CURB STOP
AutoCAD SHX Text
CURB STOP
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
8"
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW PREVENTION
AutoCAD SHX Text
DEVICE AND BALL VALVES BY CONTRACTOR
AutoCAD SHX Text
2'
AutoCAD SHX Text
%%UDETAIL "A"
AutoCAD SHX Text
(SEE NOTE 6)
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
SEE NOTE 3
AutoCAD SHX Text
SEE NOTE 2
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
UNION (TYP.)
AutoCAD SHX Text
SEE NOTE 8
AutoCAD SHX Text
(SEE NOTE 5)
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
BUILDING WALL
AutoCAD SHX Text
TEST COCK
AutoCAD SHX Text
MINIMUM 24" COPPER TAIL PIECE
AutoCAD SHX Text
12"
AutoCAD SHX Text
2"MAX
AutoCAD SHX Text
SS UNISTRUT
AutoCAD SHX Text
3'MIN
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 38: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Water Meter and Dual Backflow Device - 3/4" - 2"Water Meter and Dual Backflow Device 3/4" to 2"

C-37

AutoCAD SHX Text
WITHIN 3" OF CURB STOP
AutoCAD SHX Text
30" TAIL PIECE INSTALLED TO
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW PREVENTION DEVICE AND BALL VALVES BY CONTRACTOR (SEE NOTE 5)
AutoCAD SHX Text
THE FIELD (SEE "PROTECTIVE ENCLOSURES
AutoCAD SHX Text
FOR ABOVE GROUND DEVICES" DETAIL)
AutoCAD SHX Text
EXACT LOCATION TO BE DETERMINED IN
AutoCAD SHX Text
CURB STOP
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
8"
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
BALL VALVE (TYP)
AutoCAD SHX Text
UNION (TYPICAL)
AutoCAD SHX Text
SEE NOTE 3
AutoCAD SHX Text
SEE NOTE 2
AutoCAD SHX Text
12"
AutoCAD SHX Text
SEE NOTE 8
AutoCAD SHX Text
18"
AutoCAD SHX Text
TEST COCK (TYP)
AutoCAD SHX Text
MINIMUM 24" COPPER TAIL PIECE
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. TYPE "K" COPPER TUBING (SOFT DRAWN) OR POLYETHYLENE TUBING SDR 9 COPPER TUBE SIZE. 2. IF THIS DISTANCE IS LESS THAN 6 FEET ONLY COPPER TUBING SHALL BE PERMITTED. 3. BOTH RISERS SHALL BE TYPE "K" COPPER TUBING (HARD DRAWN) WITH COPPER/BRASS SOLDER FITTINGS AND ADAPTERS. ONLY LEAD FREE SOLDER AND FLUX SHALL BE PERMITTED. 4. 1 1/2" AND 2" METER STOPS SHALL BE EQUIPPED WITH LOCKING CAPS AND METER FLANGES. 5. APPROVED BACKFLOW PREVENTION DEVICES WITH SILICONE RUBBER SEAL RINGS OR DISKS: A.) WATTS MODEL LF919 3/4" TO 2" B.) AMES MODEL LF400B 3/4" TO 2" C.) WILKINS 975 XL2 3/4" TO 2" D.) APOLLO MODEL RPLF 4A 3/4" TO 2" APOLLO MODEL RPLF 4A 3/4" TO 2" 3/4" TO 2" 6. WHEN THE DEVICE IS INSTALLED PARALLEL TO A BUILDING WALL THERE SHALL BE A MINIMUM OF 2' BETWEEN THE EDGE OF THE DEVICE AND THE BUILDING WALL. 7. BACKFLOW PREVENTION DEVICE SHALL BE EQUIPPED WITH BALL VALVES. 8. BACKFLOW PREVENTION DEVICE SHALL BE SUPPORTED AT BOTH RISERS WITH A MINIMUM OF 4 - 1 " STAINLESS STEEL 58" STAINLESS STEEL UNISTRUTS. RISERS TO BE SECURED TO UNISTRUT WITH 304 STAINLESS STEEL MOUNTING HARDWARE AND " NEOPRENE 14" NEOPRENE INSULATORS BETWEEN ALL DISSIMILAR METALS. 9. BACKFLOW DEVICES SHALL BE A MINIMUM OF 3' FROM BACK OF CURB.
AutoCAD SHX Text
2"MAX
AutoCAD SHX Text
SS UNISTRUT
AutoCAD SHX Text
3'MIN
AutoCAD SHX Text
SS UNISTRUTS (TYP)
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 39: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Backflow Preventer Assembly

C-38

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. TYPE "K" COPPER TUBING (SOFT DRAWN). 2. BOTH RISERS SHALL BE TYPE "K" COPPER TUBING (HARD DRAWN) WITH COPPER/BRASS SOLDER FITTINGS AND ADAPTERS. ONLY LEAD FREE SOLDER AND FLUX SHALL BE PERMITTED. 3. APPROVED BACKFLOW PREVENTION DEVICES WITH SILICONE RUBBER SEAL RINGS OR DISKS: A.) WATTS MODEL LF919 3/4" TO 2" B.) AMES MODEL LF400B 3/4" TO 2" C.) WILKINS 975 XL2 3/4" TO 2" D.) APOLLO MODEL RPLF 4A 4. BACKFLOW PREVENTION DEVICE SHALL BE EQUIPPED WITH BALL VALVES. 5. FOR PLACEMENT OF BACKFLOW ASSEMBLY WITHIN FENCED AREA SEE "TYPICAL LIFT STATION SITE PLAN" DETAIL. 6. BACKFLOW PREVENTION DEVICE SHALL BE SUPPORTED AT BOTH RISERS WITH ALUMINUM ANGLE AS SHOWN ABOVE. RISERS TO BE SECURED TO ANGLE WITH TYPE 304 SST MOUNTING HARDWARE AND NEOPRENE INSULATORS BETWEEN ALL DISSIMILAR METALS.
AutoCAD SHX Text
STAINLESS STEEL U-BOLT
AutoCAD SHX Text
SECURE TO PIPE SUPPORT WITH
AutoCAD SHX Text
WRAP PIPE WITH 1/4" NEOPRENE AND
AutoCAD SHX Text
BY CONTRACTOR (SEE NOTE 3)
AutoCAD SHX Text
PREVENTION DEVICE AND BALL VALVES
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW
AutoCAD SHX Text
TO METER LOCATED IN GREEN
AutoCAD SHX Text
AREA OUTSIDE FENCED AREA
AutoCAD SHX Text
TEST COCK (TYPICAL)
AutoCAD SHX Text
BALL VALVE WITH
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
PVC SLEEVE THROUGH CONCRETE
AutoCAD SHX Text
SEE NOTE 2
AutoCAD SHX Text
12"
AutoCAD SHX Text
3' - 0"
AutoCAD SHX Text
HOSE CONNECTION
AutoCAD SHX Text
2"x 2"x 1/4" ALUMINUM ANGLE
AutoCAD SHX Text
6"x 3"x 3/8" THICK ALUMINUM PLATE
AutoCAD SHX Text
3/8" STAINLESS STEEL WEDGE TYPE CONC. ANCHOR (2 REQUIRED)
AutoCAD SHX Text
3" MIN.
AutoCAD SHX Text
3/16
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 40: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Private Auxiliary Water Supply Backflow DevicePrivate Auxiliary Water Supply Backflow Device

C-39

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. TYPE "K" COPPER TUBING (SOFT DRAWN) OR POLYETHYLENE TUBING SDR 9 COPPER TUBE SIZE. 2. BOTH RISERS SHALL BE TYPE "K" COPPER TUBING (HARD DRAWN) WITH COPPER/BRASS SOLDER FITTINGS AND ADAPTERS. ONLY LEAD FREE SOLDER AND FLUX SHALL BE PERMITTED. 3. BACKFLOW PREVENTION DEVICES SHALL BE USC APPROVED WITH SILICONE RUBBER SEAL RINGS OR DISKS: 4. BACKFLOW PREVENTION DEVICE SHALL BE SUPPORTED AT BOTH RISERS WITH STAINLESS STEEL UNISTRUT. RISERS TO BE SECURED TO UNISTRUT WITH 304 STAINLESS STEEL MOUNTING HARDWARE AND " NEOPRENE INSULATORS BETWEEN ALL 14" NEOPRENE INSULATORS BETWEEN ALL DISSIMILAR METALS. 5. BACKFLOW DEVICES SHALL BE A MINIMUM OF 3' FROM BACK OF CURB AND SIDEWALKS
AutoCAD SHX Text
30" TAIL PIECE INSTALLED TO
AutoCAD SHX Text
WITHIN 3" OF CURB STOP
AutoCAD SHX Text
CURB STOP
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
8"
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
SEE NOTE 2
AutoCAD SHX Text
30"
AutoCAD SHX Text
SEE NOTE 4
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
TEST COCK
AutoCAD SHX Text
MINIMUM 24" COPPER TAIL PIECE
AutoCAD SHX Text
12" MIN
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW PREVENTION DEVICE
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 41: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Manual Air Release Valve (Underground Water Main)Manual Air Release Valve (Underground Water Main)

C-40

AutoCAD SHX Text
SEE "MANHOLE FRAME AND COVER-30" OPENING" DETAIL
AutoCAD SHX Text
24" DIA. OPENING
AutoCAD SHX Text
FILLED WITH 3/4" ROCK
AutoCAD SHX Text
3/4" ROCK BASE 12" DEEP
AutoCAD SHX Text
3/4" ROCK BASE 12" DEEP
AutoCAD SHX Text
TAPPING SADDLE
AutoCAD SHX Text
BRASS DOUBLE STRAP
AutoCAD SHX Text
STOP WITH AWWA THREADS
AutoCAD SHX Text
LOCKING 1" CORPORATION
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
PRECAST CONCRETE
AutoCAD SHX Text
CONCENTRIC MANHOLE SECTION
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
PROOF GROUT
AutoCAD SHX Text
NON-SHRINKING WATER-
AutoCAD SHX Text
SEAL WATER TIGHT WITH
AutoCAD SHX Text
4" ALL AROUND OPENING
AutoCAD SHX Text
21"
AutoCAD SHX Text
ADJUST WITH COURSE(S) OF BRICK AND
AutoCAD SHX Text
(MAX. 5 COURSES OF BRICK - 18")
AutoCAD SHX Text
(MIN. 2 COURSES OF BRICK - 6")
AutoCAD SHX Text
MORTAR TO BRING TO GRADE
AutoCAD SHX Text
EACH WAY (TYPICAL)
AutoCAD SHX Text
#4 REBAR AT 12" O.C.
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
8"
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
48" MAXIMUM
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
1" BRASS PLUG
AutoCAD SHX Text
STANDARD PRECAST SECTION (4'-0" DIA.)
AutoCAD SHX Text
BASE SLAB
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 42: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Automatic Air Release Valve (Underground Water Main)Automatic Air Release Valve (Underground Water Main)

C-41

AutoCAD SHX Text
SEE "MANHOLE FRAME AND COVER-30" OPENING" DETAIL
AutoCAD SHX Text
24" DIA. OPENING
AutoCAD SHX Text
FILLED WITH 3/4" ROCK
AutoCAD SHX Text
3/4" ROCK BASE 12" DEEP
AutoCAD SHX Text
3/4" ROCK BASE 12" DEEP
AutoCAD SHX Text
TAPPING SADDLE
AutoCAD SHX Text
BRASS DOUBLE STRAP
AutoCAD SHX Text
STOP WITH AWWA THREADS
AutoCAD SHX Text
LOCKING 1" CORPORATION
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
PRECAST CONCRETE
AutoCAD SHX Text
CONCENTRIC MANHOLE SECTION
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
PROOF GROUT
AutoCAD SHX Text
NON-SHRINKING WATER-
AutoCAD SHX Text
SEAL WATER TIGHT WITH
AutoCAD SHX Text
4" ALL AROUND OPENING
AutoCAD SHX Text
21"
AutoCAD SHX Text
ADJUST WITH COURSE(S) OF BRICK AND
AutoCAD SHX Text
(MAX. 5 COURSES OF BRICK - 18")
AutoCAD SHX Text
(MIN. 2 COURSES OF BRICK - 6")
AutoCAD SHX Text
MORTAR TO BRING TO GRADE
AutoCAD SHX Text
EACH WAY (TYPICAL)
AutoCAD SHX Text
#4 REBAR AT 12" O.C.
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
8"
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
48" MAXIMUM
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
1" CHECK VALVE
AutoCAD SHX Text
STEEL FITTINGS
AutoCAD SHX Text
BRONZE OR STAINLESS
AutoCAD SHX Text
APPROVED AIR RELEASE VALVE
AutoCAD SHX Text
THREADED PVC SCH 80 OR
AutoCAD SHX Text
BRASS FITTING
AutoCAD SHX Text
BASE SLAB
AutoCAD SHX Text
STANDARD PRECAST SECTION (4'-0" DIA.)
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 43: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Tracer Wire Access BoxTracer Wire Access Box

C-42

AutoCAD SHX Text
TOP OF PAVEMENT
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
4 x 4 WIRE MESH
AutoCAD SHX Text
8"
AutoCAD SHX Text
24"
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
48" MAXIMUM
AutoCAD SHX Text
8" THICK MINIMUM
AutoCAD SHX Text
CONCRETE COLLAR
AutoCAD SHX Text
24"
AutoCAD SHX Text
VALCO ADJUSTABLE CAST IRON TRACER WIRE ACCESS BOX, MODEL # TWABADJ18 OR APPROVED EQUAL, WITH STAINLESS STEEL TERMINAL CONNECTORS
AutoCAD SHX Text
AWG #6 STRANDED COPPER TRACER WIRE SECURED TO PIPE WITH CABLE TIES EVERY 10 FEET
AutoCAD SHX Text
"WATER" TO BE CAST IN COVER WHEN USED ON WATER MAIN, "SEWER" WHEN USED ON FORCE MAIN
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. REQUIRED FOR HDD OR AS DIRECTED BY POAPWS.
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 44: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Manhole Frame and Cover (30" Opening)

C-50

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. IN GREEN AREAS OR ANY AREA DEEMED TO HAVE QUESTIONABLE DRAINAGE, A WATER TIGHT MANHOLE INSERT SUCH AS "SEWER GUARD" OR APPROVED EQUAL WILL BE REQUIRED. 2. APPROVED MANHOLES (DOUBLE COVER TYPE): A) U.S. FOUNDRY MODEL No. 230-AB-M B) VULCAN FOUNDRY MODEL No. VM-101 3. CONCRETE COLLAR IS REQUIRED ONLY WHEN MANHOLE IS OUT OF PAVEMENT.
AutoCAD SHX Text
"WATER" TO BE CAST IN COVER WHEN USED ON WATER MAIN
AutoCAD SHX Text
AIR RELEASE VALVE STRUCTURE, "SANITARY SEWER" WHEN USED
AutoCAD SHX Text
ON SANITARY SEWER COLLECTION STRUCTURE OR FORCE MAIN
AutoCAD SHX Text
AIR RELEASE VALVE STRUCTURE
AutoCAD SHX Text
SEWER
AutoCAD SHX Text
SANITARY
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
5' x 5' x 8" CONCRETE
AutoCAD SHX Text
COLLAR WITH 4" x 4"
AutoCAD SHX Text
WIRE MESH REINFORCING
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 45: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Flow Patterns for Invert Channels

C-51

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. INVERT CHANNELS TO BE CONSTRUCTED FOR SMOOTH FLOW WITH NO OBSTRUCTIONS. 2. SPILLWAYS SHALL BE CONSTRUCTED BETWEEN PIPES WITH DIFFERENT INVERT ELEVATIONS PROVIDING FOR SMOOTH FLOWS. 3. CHANNELS FOR FUTURE CONSTRUCTIONS (STUBS) SHALL BE CONSTRUCTED, FILLED WITH SAND, AND COVERED WITH 1" OF MORTAR. 4. SLOPE MANHOLE ITSELF WITH A 1:2 SLOPE FROM MANHOLE WALL TO CHANNEL. 5. INVERT SHALL BE A MINIMUM OF 1/2 THE DIAMETER OF THE LARGEST PIPE OR 4" DEEP.
AutoCAD SHX Text
%%USECTION "A-A"
AutoCAD SHX Text
"A"
AutoCAD SHX Text
"A"
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 46: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Standard Precast ManholeStandard Precast Manhole

C-52

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. MANHOLES SHALL CONFORM TO A.S.T.M. C478.(MIN.) 2. WALL REINFORCEMENTS A.S.T.M. DESIGNATION A185-64.(LATEST REVISION)(MIN.) 3. IF TWO CAGES OF WIRE MESH ARE USED, ONE SHALL BE POSITIONED 3" FROM THE INSIDE SURFACE AND ONE 3" FROM THE OUTSIDE SURFACE. IF A SINGLE CAGE OR REBAR IS USED, IT SHALL BE CENTERED WITHIN WALL THICKNESS. NO EXPOSED STEEL SHALL BE PERMITTED. 4. LIFT HOLES THROUGH PRECAST STRUCTURE ARE PERMITTED. 5. A MINIMUM OF SEVEN DAYS CURE TIME IS REQUIRED PRIOR TO DELIVERY. 6. ALL PIPE HOLES SHALL BE PRECAST OR CORE DRILLED. OVERSIZED HOLES WILL BE REJECTED. 7. ANY VISIBLE REINFORCING WIRE, STEEL OR HONEYCOMBS SHALL BE CAUSE FOR REJECTION. 8. SEE TECHNICAL SPECIFICATIONS FOR BEDDING REQUIREMENTS. 9. "RAM-NEK" OR APPROVED EQUAL AT ALL RISER JOINTS (1/2" THICK WITH WIDTH AT LEAST 1/2 THE WALL THICKNESS) WITH GROUT ON INSIDE AND OUTSIDE. 10. ALL OPENINGS SHALL BE SEALED USING ONLY TYPE II PORTLAND CEMENT/SAND MORTOR AND POTABLE WATER FOR MUD WORK ON JOINTS, LIFTING HOLES, INVERTS, ETC. WHEN AN ACCELERATOR IS NECESSARY, "ANTI HYDRO" IS THE ONLY PRODUCT APPROVED. 11. BRICK MASONRY CONSTRUCTION TO BE STUCCOED WITH 3/4" TYPE II CEMENT INSIDE AND OUTSIDE, AND INSIDE TO BE COATED WITH TWO COATS OF KOPPERS 300 OR APPROVED EQUAL. 12. A FLOW CHANNEL SHALL BE CONSTRUCTED INSIDE MANHOLE TO DIRECT INFLUENT INTO FLOW STREAM, AND COATED WITH TWO COATS OF KOPPERS 300 OR APPROVED EQUAL 13. INTERIOR OF ALL SANITARY MANHOLES SHALL HAVE AGRU SURE GRIP CONCRETE PROTECTIVE LINER INSTALLED AT THE TIME OF MANUFACTURING. SEE "AGRU SURE GRIP LINER DETAILS" DRAWING FOR ADDITIONAL AGRU SURE GRIP REQUIREMENTS.
AutoCAD SHX Text
SPEC. 20 OR #4 REBAR 12" O.C.
AutoCAD SHX Text
NO. 4 WIRE 3" x 6" MESH A.S.T.M.
AutoCAD SHX Text
0.20 SQ.FT./LF. EACH WAY, EITHER
AutoCAD SHX Text
WALL STEEL SHALL BE EQUAL TO
AutoCAD SHX Text
(MAX. 5 COURSES OF BRICK - 18")
AutoCAD SHX Text
(MIN. 2 COURSES OF BRICK - 6")
AutoCAD SHX Text
TYPE II PORTLAND CEMENT TO BRING TO GRADE
AutoCAD SHX Text
ADJUST WITH COURSE(S) OF BRICK AND
AutoCAD SHX Text
EACH WAY
AutoCAD SHX Text
SECTION (KEYED TO LOWER WALL)
AutoCAD SHX Text
PRECAST REINFORCED CONCRETE
AutoCAD SHX Text
COVERED WITH TYPE II PORTLAND CEMENT
AutoCAD SHX Text
BRICK RUBBLE BEDDED AND
AutoCAD SHX Text
TYPE II CEMENT 4000 P.S.I.
AutoCAD SHX Text
8"
AutoCAD SHX Text
COVER-30" OPENING" DETAIL
AutoCAD SHX Text
SEE "MANHOLE FRAME AND
AutoCAD SHX Text
#4 REBAR 12" ON CENTER EACH WAY
AutoCAD SHX Text
8"
AutoCAD SHX Text
18"
AutoCAD SHX Text
POUR
AutoCAD SHX Text
MONOLITHIC
AutoCAD SHX Text
6"
AutoCAD SHX Text
4'-0" MINIMUM
AutoCAD SHX Text
SLOPE: 3/4"/FT.
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
ALL AROUND WITH
AutoCAD SHX Text
PIPE O.D. PLUS 4"
AutoCAD SHX Text
KEYWAY
AutoCAD SHX Text
PRECAST CONCRETE
AutoCAD SHX Text
NO JOINT WITHIN 5' OF MANHOLE
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 47: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Precast Manhole - Drop Connection Type A

C-53

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. CONCRETE ENCASEMENT FOR DROP CONNECTION TO BE FIELD POURED. 2. DROP CONNECTIONS SHALL BE REQUIRED WHENEVER AN INFLUENT SEWER IS LOCATED TWO (2) FEET OR MORE ABOVE THE MAIN INVERT CHANNEL. 3. A FLOW CHANNEL SHALL BE CONSTRUCTED INSIDE MANHOLE TO DIRECT INFLUENT INTO FLOW STREAM. 4. WHEN PVC IS USED IN SANITARY SEWER LINES, SOLVENT TYPE JOINT PVC FITTINGS MAY BE UTILIZED IN THE DROP ASSEMBLY ONLY. 5. MINIMUM PIPE SIZE FOR DROP IS 8". 6. SEE "STANDARD PRECAST MANHOLE" DETAIL FOR ADDITIONAL REQUIREMENTS.
AutoCAD SHX Text
#3 STIRUPS 12" O.C.
AutoCAD SHX Text
DOWELS ALLOWED)
AutoCAD SHX Text
TO BENCH POUR (NO
AutoCAD SHX Text
#4 REBAR 12" ON CENTER
AutoCAD SHX Text
RADIUS ELBOW
AutoCAD SHX Text
STANDARD LONG
AutoCAD SHX Text
PER SHELF AND INTEGRAL
AutoCAD SHX Text
#4 REBAR, MINUMUM OF 4
AutoCAD SHX Text
STANDARD "T" BRANCH
AutoCAD SHX Text
CONFORMING TO POAPWS SPECIFICATIONS
AutoCAD SHX Text
TYPICAL PRECAST MANHOLE
AutoCAD SHX Text
4'-0" MINIMUM
AutoCAD SHX Text
EACH WAY
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
16"
AutoCAD SHX Text
6"
AutoCAD SHX Text
8"
AutoCAD SHX Text
6"
AutoCAD SHX Text
NO JOINT WITHIN 5' OF MANHOLE
AutoCAD SHX Text
BRICK RUBBLE BEDDED AND
AutoCAD SHX Text
COVERED WITH TYPE II PORTLAND CEMENT
AutoCAD SHX Text
POURED CONCRETE
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 48: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Precast Manhole - Drop Connection Type B

C-54

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. INSIDE DROP TO BE USED WHEN DROP IS GREATER THAN 6 INCHES AND LESS THAN 24 INCHES. 2. A FLOW CHANNEL SHALL BE CONSTRUCTED INSIDE MANHOLE TO DIRECT INFLUENT INTO FLOW STREAM. 3. CONSTRUCTION OF DROP SHALL PROVIDE AN OVERSIZED SLAB TO EXTEND UNDER THE DROP CONNECTION. 4. MINIMUM PIPE SIZE FOR DROP IS 8". 5. SEE "STANDARD PRECAST MANHOLE" DETAIL FOR ADDITIONAL REQUIREMENTS.
AutoCAD SHX Text
CONFORMING TO POAPWS SPECIFICATIONS
AutoCAD SHX Text
TYPICAL PRECAST MANHOLE
AutoCAD SHX Text
8"
AutoCAD SHX Text
#4 REBAR 12" O.C. EACH WAY
AutoCAD SHX Text
4'-0" MINIMUM
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
1'-0"
AutoCAD SHX Text
POURED CONCRETE
AutoCAD SHX Text
#4 REBAR, MINIMUM OF 4
AutoCAD SHX Text
PER SHELF AND INTEGRAL
AutoCAD SHX Text
DOWELS ALLOWED)
AutoCAD SHX Text
TO BENCH POUR (NO
AutoCAD SHX Text
8"
AutoCAD SHX Text
6"
AutoCAD SHX Text
6"
AutoCAD SHX Text
COVERED WITH TYPE II PORTLAND CEMENT
AutoCAD SHX Text
BRICK RUBBLE BEDDED AND
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 49: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Sewer Service Connection (Wye Branch)

C-55

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. THE END OF EACH SERVICE CONNECTION SHALL BE MARKED WITH A 2" x 2" TREATED WOOD STAKE AND AN E.M.S. SANITARY SEWER MARKER. 2. EACH SERVICE CONNECTION SHALL BE PLUGGED WATERTIGHT WITH AN APPROVED CAP OR PLUG. 3. FOR PVC INSTALLATIONS, CONNECT TO EXISTING "BELL END" AND CONNECT OPPOSITE END WITH PVC TO PVC KNOCK ON SLEEVE. 4. SOLIDLY TAMP BACKFILL AT LEAST ONE FOOT ABOVE TOP OF PIPE. SERVICES UNDER PAVED AREAS SHALL BE BACKFILLED TO THE SAME SPECIFICATIONS AS SHOWN ON "PAVEMENT REPLACEMENT" DETAIL. 5. CONTRACTOR SHALL MARK ON A CLEAN SET OF PLANS THE FINAL STATIONING OR DISTANCE AND DIRECTION FROM MANHOLE TO EACH SERVICE LATERAL AND GIVE TO ENGINEER FOR RECORD DRAWING PURPOSES. 6. ANY DEVIATION FROM THESE METHODS MUST BE APPROVED BY POAPWS. 7. THE USE OF UNNECESSARY FITTINGS ON THE CUSTOMERS LINE TO REDUCE EXCAVATION EFFORTS WILL BE CAUSE FOR REJECTION. 8. THE USE OF 90° SWEEPS ON THE CUSTOMERS LINE IN LIEU OF 45° BENDS WILL REQUIRE AN ADDITIONAL CLEAN OUT AS SHOWN ON "SANITARY SERVICE CLEAN OUT DETAIL". THE CLEAN OUT SHALL BE ON THE HOUSE SIDE OF THE TOP SWEEP WITHIN 2' OF THE SWEEP.
AutoCAD SHX Text
6" x 4" WYE BRANCH
AutoCAD SHX Text
(SEE "SANITARY SERVICE CLEAN OUT" DETAIL)
AutoCAD SHX Text
(TYPICAL SINGLE AND DOUBLE SERVICE)
AutoCAD SHX Text
CLEAN OUT WITH CONCRETE COLLAR
AutoCAD SHX Text
SLOPE = 1.0%%%
AutoCAD SHX Text
DISTANCE VARIES
AutoCAD SHX Text
PROPERTY LINE
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
PROPERTY LINE
AutoCAD SHX Text
12"
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
48" MAX
AutoCAD SHX Text
DEPTH VARIES
AutoCAD SHX Text
30" MIN
AutoCAD SHX Text
6"
AutoCAD SHX Text
45%%D BEND
AutoCAD SHX Text
SANITARY MAIN
AutoCAD SHX Text
45%%d MAX.
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
45%%D BEND
AutoCAD SHX Text
WYE
AutoCAD SHX Text
2 - 45° (NO 90° OR SWEEPS)
AutoCAD SHX Text
MAGNETIC MARKER-OMNI #75027 OR 3M 1404-1265 (TYPICAL)
AutoCAD SHX Text
RISER PIPE SHALL BE ONE PIECE FROM CLEAN OUT ADAPTER TO 45°
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 50: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

C-900 Sewer Service Transition

C-56

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) WHERE NO WATER MAIN EXISTS AND SANITARY MAIN IS SDR 26 PVC, LATERAL FROM MAIN TO CLEAN OUT SHALL BE SDR PVC. SEWER SERVICE LATERALS SHALL CROSS UNDER WATER MAINS WITH A MINIMUM VERTICAL SEPARATION OF TWELVE (12) INCHES. IF 12" VERTICAL SEPARATION CANNOT BE MAINTAINED, THEN THE WATER MAIN SHALL BE D.I.P. AND THE SEWER SERVICE LATERAL SHALL BE C-900 SDR 18 OR BETTER AND THE MINIMUM SEPARATION SHALL BE SIX (6) INCHES. WHEN IT IS NOT POSSIBLE FOR THE WATER MAIN TO CROSS OVER THE SEWER SERVICE LATERAL A MINIMUM VERTICAL SEPARATION OF AT LEAST TWELVE (12) INCHES MUST BE MAINTAINED, THE WATER MAIN SHALL BE D.I.P. AND THE SEWER LATERAL SHALL BE C-900 SDR 18 OR BETTER.
AutoCAD SHX Text
C-900
AutoCAD SHX Text
DISTANCE VARIES
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
48" MAX
AutoCAD SHX Text
DEPTH VARIES
AutoCAD SHX Text
30" MIN
AutoCAD SHX Text
MAGNETIC MARKER
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
WATER MAIN
AutoCAD SHX Text
C-900
AutoCAD SHX Text
DISTANCE VARIES
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
48" MAX
AutoCAD SHX Text
DEPTH VARIES
AutoCAD SHX Text
30" MIN
AutoCAD SHX Text
MAGNETIC MARKER
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
2 - 45° (NO 90° OR SWEEPS)
AutoCAD SHX Text
DISTANCE VARIES
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
48" MAX
AutoCAD SHX Text
DEPTH VARIES
AutoCAD SHX Text
30" MIN
AutoCAD SHX Text
MAGNETIC MARKER
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
SOIL
AutoCAD SHX Text
SDR 26
AutoCAD SHX Text
C-900
AutoCAD SHX Text
C-900 PVC SANITARY SEWER MAIN
AutoCAD SHX Text
C-900 BY SDR 26 TRANSITION COUPLING
AutoCAD SHX Text
C-900
AutoCAD SHX Text
C-900 BY SDR 26 TRANSITION COUPLING
AutoCAD SHX Text
C-900 PVC SANITARY SEWER MAIN
AutoCAD SHX Text
SDR 26 PVC SANITARY SEWER MAIN
AutoCAD SHX Text
WATER MAIN
AutoCAD SHX Text
C-900 BY SDR 26 TRANSITION COUPLING
AutoCAD SHX Text
C-900 BY SDR 26 TRANSITION COUPLING
AutoCAD SHX Text
SDR 26
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 51: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Sanitary Service Clean Out

C-57

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. U.S. FOUNDRY NO. 7621 REVERSIBLE HANDHOLE RING AND COVER OR APPROVED EQUAL SHALL BE USED, COVER TO BE CAST WITH "S" IN THE CENTER. 2. CLEAN OUT REQUIRED ON ALL SERVICES AT PROPERTY LINE OR EASEMENT LINE WHERE APPLICABLE. 3. STANDARD WYE SHALL BE USED AT CLEAN OUT.
AutoCAD SHX Text
CLEAN OUT IN VEHICULAR OR
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
30" MIN
AutoCAD SHX Text
48" MAX
AutoCAD SHX Text
8" x 24" x 24"
AutoCAD SHX Text
CONCRETE COLLAR
AutoCAD SHX Text
WITH 4" x 4" WIRE
AutoCAD SHX Text
MESH REINFORCEMENT
AutoCAD SHX Text
PAVEMENT
AutoCAD SHX Text
%%USECTION "A-A"
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
A
AutoCAD SHX Text
S
AutoCAD SHX Text
8" x 24" x 24"
AutoCAD SHX Text
CONCRETE COLLAR
AutoCAD SHX Text
ROCK BASE
AutoCAD SHX Text
A
AutoCAD SHX Text
PEDESTRIAN TRAFFIC AREA
AutoCAD SHX Text
CLEAN OUT IN GREEN AREA
AutoCAD SHX Text
%%USECTION "A-A"
AutoCAD SHX Text
PVC WITH 2" x " SQUARE 716" SQUARE SQUARE RECESSED NUT
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 52: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Air Release Valve (Underground Force Main)

C-58

AutoCAD SHX Text
PRECAST CONCRETE
AutoCAD SHX Text
CONCENTRIC MANHOLE SECTION
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
4" ALL AROUND OPENING
AutoCAD SHX Text
SEAL WATER TIGHT WITH
AutoCAD SHX Text
NON-SHRINKING WATER-
AutoCAD SHX Text
PROOF GROUT
AutoCAD SHX Text
ADJUST WITH COURSE(S) OF BRICK AND
AutoCAD SHX Text
MORTAR TO BRING TO GRADE
AutoCAD SHX Text
(MIN. 2 COURSES OF BRICK - 6")
AutoCAD SHX Text
(MAX. 5 COURSES OF BRICK - 18")
AutoCAD SHX Text
MALE NPT OUTLET THREADS
AutoCAD SHX Text
AWWA INLET THREADS AND
AutoCAD SHX Text
2" CORPORATION STOP WITH
AutoCAD SHX Text
FILLED WITH 3/4" ROCK
AutoCAD SHX Text
THREADED BRASS FITTING
AutoCAD SHX Text
APPROVED AIR RELEASE VALVE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
3/4" ROCK BASE 12" DEEP
AutoCAD SHX Text
3/4" ROCK BASE 12" DEEP
AutoCAD SHX Text
BRASS DOUBLE STRAP
AutoCAD SHX Text
TAPPING SADDLE
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
21"
AutoCAD SHX Text
24" DIA. OPENING
AutoCAD SHX Text
#4 REBAR AT 12" O.C.
AutoCAD SHX Text
EACH WAY (TYPICAL)
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
8"
AutoCAD SHX Text
48" MAXIMUM
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
STANDARD PRECAST SECTION (4'-0" DIA.)
AutoCAD SHX Text
INTERIOR TO BE COATED WITH TWO COATS OF COAL TAR EPOXY
AutoCAD SHX Text
BASE SLAB
AutoCAD SHX Text
SEE "MANHOLE FRAME AND COVER-30" OPENING" DETAIL
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 53: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Grease TrapGrease Trap

C-59

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. SHOP DRAWINGS FOR PRECAST TANKS SHALL BEAR THE FOLLOWING STATEMENT:"THIS CONCRETE STRUCTURE MEETS OR EXCEEDS ALL THE REQUIREMENTS FOR GREASE INTERCEPTORS/SEPTIC TANKS AS IN THE FLORIDA ADMINISTRATIVE CODE, CHAPTER 10D-6 AND 64E-6, AND SUA "SPECIFICATIONS AND STANDARDS". THE SHOP DRAWINGS (3 COPIES MINIMUM) SHALL THEN BE SIGNED AND SEALED BY THE ENGINEER OF RECORD AND FORWARDED TO SUA FOR APPROVAL. 2. LID TYPES: A) 4" REGULAR LID B) 8" TRAFFIC BEARING LID 3. ALL PIPING SHALL BE SOLVENT WELD PIPE. 4. ALL TANKS IN TRAFFIC AREA SHALL BE H2O WHEEL LOAD BEARING. 5. INSPECTION OF TANK REQUIRED BY SUA PRIOR TO PLACEMENT. 6. INSPECTION OF TANK REQUIRED BY SUA AFTER TANK IS PIPED. 7. TANKS IN SERIES SHALL HAVE BAFFLE IN LAST TANK ONLY.
AutoCAD SHX Text
(MAX. 5 COURSES OF BRICK - 18")
AutoCAD SHX Text
ADJUST WITH COURSE(S) OF BRICK AND
AutoCAD SHX Text
OPENING
AutoCAD SHX Text
INLET
AutoCAD SHX Text
(MIN. 2 COURSES OF BRICK - 6")
AutoCAD SHX Text
MORTAR TO BRING TO GRADE
AutoCAD SHX Text
WITH TYPE II PORTLAND
AutoCAD SHX Text
AROUND BOOT INSIDE & OUT
AutoCAD SHX Text
RUBBER BOOT (FILL OPENING
AutoCAD SHX Text
OUTLET OPENING WITH
AutoCAD SHX Text
"SANITARY SERVICE CLEAN
AutoCAD SHX Text
CONCRETE COLLAR (SEE
AutoCAD SHX Text
(TYPICAL BOTH INFLUENT AND
AutoCAD SHX Text
BRING CLEAN OUT TO GRADE
AutoCAD SHX Text
4" CONCRETE BAFFLE
AutoCAD SHX Text
WATER LEVEL
AutoCAD SHX Text
LID (SEE NOTE 2)
AutoCAD SHX Text
22"
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
8"
AutoCAD SHX Text
INTERCEPTOR" TO BE CAST IN COVER
AutoCAD SHX Text
WORDS "GREASE TRAP" OR "GREASE
AutoCAD SHX Text
RING AND COVER (HEAVY DUTY)
AutoCAD SHX Text
BRICK MASONRY(TYPICAL)
AutoCAD SHX Text
SUBMIT SHOP DRAWINGS
AutoCAD SHX Text
OUT" DETAIL)
AutoCAD SHX Text
EFFLUENT LINES)
AutoCAD SHX Text
12"
AutoCAD SHX Text
60% OF TOTAL WIDTH
AutoCAD SHX Text
8" HOLE
AutoCAD SHX Text
2 WAY CLEAN OUT
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
INSIDE AND OUT WITH
AutoCAD SHX Text
LID TO BE GROUTED
AutoCAD SHX Text
TYPE II PORTLAND
AutoCAD SHX Text
CEMENT/SAND MORTAR
AutoCAD SHX Text
CEMENT/SAND MORTAR
AutoCAD SHX Text
6"
AutoCAD SHX Text
6"
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 54: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Oil SeperatorOil Seperator

C-60

AutoCAD SHX Text
TYPE II PORTLAND
AutoCAD SHX Text
LID TO BE GROUTED
AutoCAD SHX Text
INSIDE AND OUT WITH
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
2 WAY CLEAN OUT
AutoCAD SHX Text
8" HOLE
AutoCAD SHX Text
60% OF TOTAL WIDTH
AutoCAD SHX Text
24"
AutoCAD SHX Text
EFFLUENT LINES)
AutoCAD SHX Text
OUT" DETAIL)
AutoCAD SHX Text
SUBMIT SHOP DRAWINGS
AutoCAD SHX Text
BRICK MASONRY(TYPICAL)
AutoCAD SHX Text
RING AND COVER (HEAVY DUTY)
AutoCAD SHX Text
WORDS "OIL SEPARATOR" OR "OIL
AutoCAD SHX Text
INTERCEPTOR" TO BE CAST IN COVER
AutoCAD SHX Text
12"
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
22"
AutoCAD SHX Text
LID (SEE NOTE 2)
AutoCAD SHX Text
WATER LEVEL
AutoCAD SHX Text
4" CONCRETE BAFFLE
AutoCAD SHX Text
BRING CLEAN OUT TO GRADE
AutoCAD SHX Text
(TYPICAL BOTH INFLUENT AND
AutoCAD SHX Text
CONCRETE COLLAR (SEE
AutoCAD SHX Text
"SANITARY SERVICE CLEAN
AutoCAD SHX Text
OUTLET OPENING WITH
AutoCAD SHX Text
RUBBER BOOT (FILL OPENING
AutoCAD SHX Text
AROUND BOOT INSIDE & OUT
AutoCAD SHX Text
WITH TYPE II PORTLAND
AutoCAD SHX Text
MORTAR TO BRING TO GRADE
AutoCAD SHX Text
(MIN. 2 COURSES OF BRICK - 6")
AutoCAD SHX Text
INLET
AutoCAD SHX Text
OPENING
AutoCAD SHX Text
ADJUST WITH COURSE(S) OF BRICK AND
AutoCAD SHX Text
(MAX. 5 COURSES OF BRICK - 18")
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. SHOP DRAWINGS FOR PRECAST TANKS SHALL BEAR THE FOLLOWING STATEMENT:"THIS CONCRETE STRUCTURE MEETS OR EXCEEDS ALL THE REQUIREMENTS FOR GREASE INTERCEPTORS/SEPTIC TANKS AS IN THE FLORIDA ADMINISTRATIVE CODE, CHAPTER 10D-6 AND 64E-6, AND SUA "SPECIFICATIONS AND STANDARDS". THE SHOP DRAWINGS (3 COPIES MINIMUM) SHALL THEN BE SIGNED AND SEALED BY THE ENGINEER OF RECORD AND FORWARDED TO SUA FOR APPROVAL. 2. LID TYPES: A) 4" REGULAR LID B) 8" TRAFFIC BEARING LID 3. INTERIOR PIPING SHALL BE SOLVENT WELD PVC PIPE. 4. ALL TANKS IN TRAFFIC AREA SHALL BE H2O WHEEL LOAD BEARING. 5. INSPECTION OF TANK REQUIRED BY SUA PRIOR TO PLACEMENT. 6. INSPECTION OF TANK REQUIRED BY SUA AFTER TANK IS PIPED.
AutoCAD SHX Text
CEMENT/SAND MORTAR
AutoCAD SHX Text
CEMENT/SAND MORTAR
AutoCAD SHX Text
6"
AutoCAD SHX Text
6"
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 55: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

CORBEL DETAIL

BOOT CONNECTION DETAIL

JOINT DETAIL

Agru Sure Grip Liner Details

C-61

AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
MIN. 2" CAST-IN AGRU TURN BACK WITH POLYSTER BACK LINING EXPOSED AND STUB EMBEDED IN STRUCTURE
AutoCAD SHX Text
2" MIN. CHIMNEY RISE IN CORBEL
AutoCAD SHX Text
EXTRUSION WELD
AutoCAD SHX Text
2" WIDE PP-R CAP STRIP WELDED TOP AND BOTTOM
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
RAMNEK; MEETS OR EXCEEDS ALL REQUIREMENTS OF ASTM C-990 U.S. FEDERAL SPECS. S-S-210A, TYPE A AASHTD M-19875 I, TYPE B
AutoCAD SHX Text
1 1/4" BUTYL EVERGRIP 990 STRIPS OR EQUAL
AutoCAD SHX Text
PROTECTIVE PAPER WRAPPER MUST BE REMOVED BEFORE CLOSING JOINT
AutoCAD SHX Text
9" WIDE ASTM-C877 TYPE II EXTERION JOINT WRAP REQUIRED
AutoCAD SHX Text
GROUT EXTERIOR
AutoCAD SHX Text
POSITION BOOT TO LAP THE END OF THE SLEEVE
AutoCAD SHX Text
"TURN BACK" JOINT METHOD DESIGN
AutoCAD SHX Text
AGRU SURE GRIP LINER
AutoCAD SHX Text
MANHOLE ADAPTER
AutoCAD SHX Text
P-201 ADEKA ULTRA SEAL
AutoCAD SHX Text
ALL FITTINGS HOT AIR ROD WELDED
AutoCAD SHX Text
3mm POLYSTER BACKED PP-R WRAP EPOXIED TO PIPE PRIOR TO INSTALL
AutoCAD SHX Text
3mm PP-R FLANGE WELDED TO WALL LINER AND PIPE WRAP
AutoCAD SHX Text
3M WEATHERBAN SEALANT (#5354) TO BE APPLIED BEFORE CONCRETE FILLET IS CONSTRUCTED
AutoCAD SHX Text
1 1/4" BUTYL EVERGRIP 990 STRIPS OR EQUAL
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
9" WIDE ASTM-C877 TYPE II EXTERION JOINT WRAP REQUIRED
AutoCAD SHX Text
GROUT EXTERIOR
AutoCAD SHX Text
RAMNEK; MEETS OR EXCEEDS ALL REQUIREMENTS OF ASTM C-990 U.S. FEDERAL SPECS. S-S-210A, TYPE A AASHTD M-19875 I, TYPE B
AutoCAD SHX Text
POSITION BOOT TO LAP THE END OF THE SLEEVE
AutoCAD SHX Text
3M WEATHERBAN SEALANT (#5354) TO BE APPLIED BEFORE CONCRETE FILLET IS CONSTRUCTED
AutoCAD SHX Text
"TURN BACK" JOINT METHOD DESIGN
AutoCAD SHX Text
"AGRU SURE-GRIP" HDPE LINER TO PENETRATE 2" INTO BASE SLAB WITH P-201 ADEKA ULTRA SEAL
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
30"
AutoCAD SHX Text
EXTRUSION WELD
AutoCAD SHX Text
P.E. TURN BACK WITH EXTRUSION WELDED TO AGRU AND EPOXIED TO EXPOSED CONCRETE
AutoCAD SHX Text
P.E. SLEVE CAST-IN
AutoCAD SHX Text
POSITION BOOT TYPE PRESS SEAL PSX DRIVE TO LAP THE MIDDLE OF THE SLEEVE
AutoCAD SHX Text
EXTRUSION WELD
AutoCAD SHX Text
AGRU-LINER (TYPICAL)
AutoCAD SHX Text
ADEKA P-201
AutoCAD SHX Text
9" WIDE ASTM-C877 TYPE II EXTERION JOINT WRAP
AutoCAD SHX Text
1 " BUTYL EVERGRIP 990 14" BUTYL EVERGRIP 990 STRIPS OR EQUAL
AutoCAD SHX Text
P.E. TURN BACK WITH EXTRUSION WELDED TO AGRU AND EPOXIED TO EXPOSED CONCRETE
AutoCAD SHX Text
GROUT EXTERIOR
AutoCAD SHX Text
RAMNEK: MEET OR EXCEEDS ALL REQUIREMENTS OF ASTM. C-900 US FEDERAL SPECS S-S-210A, TYPE A AASHTD M-19875I, TYPE B
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 56: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Detail

C-63

AutoCAD SHX Text
EXPANSION JOINT (TYP. 4 SIDES)
AutoCAD SHX Text
#4 REBAR - 6" O.C. EACH WAY
AutoCAD SHX Text
GROUT WATERTIGHT CONTINUOUS AROUND
AutoCAD SHX Text
ALL JOINTS SHALL BE SEALED WATERTIGHT
AutoCAD SHX Text
WITH RAM-NEK OR AN APPROVED EQUAL
AutoCAD SHX Text
#8 REBAR AT 10" O.C. EACH WAY
AutoCAD SHX Text
AND SIZED PER PUMP MANUFACTURER, ALL
AutoCAD SHX Text
TIGHT, WITH NON-CORROSIVE LOCKING BAR
AutoCAD SHX Text
1/4" ALUMINUM PLATE HATCH COVER, AIR-
AutoCAD SHX Text
GUIDE BARS TO BE
AutoCAD SHX Text
STAINLESS STEEL LIFTING CABLE WITH
AutoCAD SHX Text
STAINLESS STEEL RINGS (HELD BY HOOK)
AutoCAD SHX Text
BOTTOM ELEV.=
AutoCAD SHX Text
TYPE II CONCRETE FILLET
AutoCAD SHX Text
FORCE MAINS, ETC.
AutoCAD SHX Text
ORIENTATION OF INFLUENT PIPES,
AutoCAD SHX Text
NOTE: SEE PLOT PLAN FOR PROPER
AutoCAD SHX Text
SMOOTH FORMED
AutoCAD SHX Text
BASE PLATE
AutoCAD SHX Text
DIA.
AutoCAD SHX Text
%%USECTION THRU LIFT STATION
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
D.I.P.
AutoCAD SHX Text
H.W. ALARM EL.=
AutoCAD SHX Text
LAG PUMP NO. 2 "ON" EL.=
AutoCAD SHX Text
LEAD PUMP NO. 1 "ON" EL.=
AutoCAD SHX Text
PUMPS "OFF" EL.=
AutoCAD SHX Text
2" GROUT
AutoCAD SHX Text
PRECAST WET WELL
AutoCAD SHX Text
PUMP MOUNTING HARDWARE
AutoCAD SHX Text
SUPPLIED BY PUMP MFGR.
AutoCAD SHX Text
316 SST SCH 40
AutoCAD SHX Text
(TYPE 316 STAINLESS STEEL)
AutoCAD SHX Text
FLANGE CONNECTION
AutoCAD SHX Text
316 STAINLESS STEEL
AutoCAD SHX Text
(SCH 80 PVC OR BRASS)
AutoCAD SHX Text
D.I. CHECK VALVE WITH OUTSIDE
AutoCAD SHX Text
LEVER AND WEIGHT (TYPICAL)
AutoCAD SHX Text
D.I. 90° BEND
AutoCAD SHX Text
(ROTATED 45%%d)
AutoCAD SHX Text
D.I. PLUG VALVE (TYPICAL)
AutoCAD SHX Text
D.I. TEE WITH SUPPORT
AutoCAD SHX Text
WITH THE EMERGENCY PUMP OUT PORT
AutoCAD SHX Text
BE LOCATED SO AS NOT TO CONFLICT
AutoCAD SHX Text
NOTE: THE ELECTRICAL CONTROL PANEL SHALL
AutoCAD SHX Text
HARDWARE
AutoCAD SHX Text
FINISH GRADE EL.=
AutoCAD SHX Text
2" BRASS NIPPLE AND 2" CURB STOP
AutoCAD SHX Text
D.I. 45%%d BEND AND
AutoCAD SHX Text
D.I. CROSS (ROTATED 45%%d)
AutoCAD SHX Text
4" D.I. VENT PIPE WITH SCREENED
AutoCAD SHX Text
OPENING (20/20 MESH)
AutoCAD SHX Text
STAINLESS STEEL PIPE SUPPORTS AT EACH
AutoCAD SHX Text
ELBOW WITH #4 REBAR (AS REQUIRED)
AutoCAD SHX Text
"SEWER" TO BE
AutoCAD SHX Text
CAST IN COVER
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
VENT INTO WET WELL
AutoCAD SHX Text
BLIND FLANGE TAPPED 2"
AutoCAD SHX Text
(2" BRASS CHECK VALVE TO BE USED
AutoCAD SHX Text
WHEN FORCE MAIN IS OPEN ENDED)
AutoCAD SHX Text
D.I. PLUG VALVE
AutoCAD SHX Text
CAST IRON
AutoCAD SHX Text
VALVE BOX
AutoCAD SHX Text
COLLAR
AutoCAD SHX Text
D.I. CROSS
AutoCAD SHX Text
FORCE MAIN AIR RELEASE VALVE PER
AutoCAD SHX Text
STANDARDS AND SPECIFICATIONS
AutoCAD SHX Text
TO BE STAINLESS STEEL
AutoCAD SHX Text
ALL FLANGE BOLTS AND NUTS
AutoCAD SHX Text
D.I.P.
AutoCAD SHX Text
%%UPLAN VIEW
AutoCAD SHX Text
18"
AutoCAD SHX Text
1/2" TAP W/PETCOCK & PRESSURE GAUGE
AutoCAD SHX Text
0 - p.s.i. (3" O.D. FACE MIN.) AND
AutoCAD SHX Text
NEEDLE STOP COCK (GLYCERIN FILLED)
AutoCAD SHX Text
316 STAINLESS STEEL FLOAT HANGER
AutoCAD SHX Text
WET WELL, INSIDE AND OUTSIDE
AutoCAD SHX Text
CONDUIT TO CONTROL PANEL
AutoCAD SHX Text
100 YR. STORM EL.=
AutoCAD SHX Text
HARDWARE TO BE 316 SST
AutoCAD SHX Text
INFLUENT SEWER
AutoCAD SHX Text
INVERT ELEV.=
AutoCAD SHX Text
INFLUENT SEWER
AutoCAD SHX Text
FEMALE CAM-LOCK WITH MALE PLUG (3" OR 6" ONLY) PUMPOUT TO BE LOCATED ON OPPOSITE SIDE WHEN LIFT STATION IS EQUIPED WITH BIO-CUBE
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
BASE TO BE CONCENTRIC WITH WETWELL AND MINIMUM 14" THICK
AutoCAD SHX Text
15" MIN.
AutoCAD SHX Text
THICKNESS
AutoCAD SHX Text
WALL
AutoCAD SHX Text
PADLOCK BAR
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 57: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Control Panel (Single Door)

C-64a

AutoCAD SHX Text
RED LIGHT "HIGH WATER ALARM"
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
WETWELL SLAB
AutoCAD SHX Text
POURED CONCRETE BASE 1'-6" DIA x 3'-0" (TYP.)
AutoCAD SHX Text
%%UFRONT VIEW
AutoCAD SHX Text
3" DIA. ANODYZED ALUMINUM PIPE SUPPORT, 6061 T6, SCH 40 TO BE FILLED WITH CLEAN SAND AND CAPPED. THE PORTION OF PIPE SUPPORTS COVERED BY CONCRETE SHALL BE COATED WITH BITUMASTIC PAINT (8 MIL THICK)
AutoCAD SHX Text
2" SCH 80 U.V. RESISTANT P.V.C. CONDUITS BETWEEN PANEL J-BOX AND WETWELL, ONE PER PUMP AND ONE FOR FLOATS. WIRES SHALL BE CONTINUOUS, NO SPLICES.
AutoCAD SHX Text
20' (MIN.) LONG COPPER CLAD GROUND ROD SHALL BE LOCATED OUTSIDE CONCRETE SLAB.
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
1 5/8" x 1 5/8" UNI-STRUT SUPPORT STRAP, 12 GAUGE, STAINLESS STEEL AND RIGID CONDUIT CLAMP #B2015-SS4 (TYP)
AutoCAD SHX Text
GENERATOR RECEPTACLE
AutoCAD SHX Text
4" CONCRETE SLAB
AutoCAD SHX Text
TO F.P.&L. POWER SOURCE, CONDUIT AS PER F.P.& L. REQUIREMENTS
AutoCAD SHX Text
TO ANTENNA
AutoCAD SHX Text
1"TYP.
AutoCAD SHX Text
2" PVC SCHEDULE 80 WYE WITH 2" PVC INSECT AND RODENT SINGLE VENT SCREEN KIT PVS-IRS2 (TYP.)
AutoCAD SHX Text
MOUNT METER AND CAN, HEIGHT AS PER CODE AND F.P.& L. STANDARDS AND A MINIMUM OF 3.5' FROM FENCE
AutoCAD SHX Text
CIRCUIT BREAKER IN CIRCUIT BREAKER ENCLOSURE, SQUARE D PART #J250SS, SERVICE ENTRANCE RATED, BETWEEN F.P.& L. METER AND CONTROL PANEL WITH NEMA 4X STAINLESS STEEL ENCLOSURE (SEE NOTE 7)
AutoCAD SHX Text
%%USECTION "A-A"
AutoCAD SHX Text
APPROVED PRESSURE TYPE BRONZE CONNECTOR CLAMP
AutoCAD SHX Text
#4 CU GROUND WIRE
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1.ALL CONDUIT SIZES INCLUDING F.P.& L. SHALL BE SIZED FOR TWICE THE ALL CONDUIT SIZES INCLUDING F.P.& L. SHALL BE SIZED FOR TWICE THE INSTALLED H.P. AMPACITY UNLESS OTHERWISE INDICATED. 2.ALL CONDUCTORS SHALL BE COPPER. ALL CONDUCTORS SHALL BE COPPER. 3.ALL CONDUIT OPENINGS IN J-BOX AND CONTROL PANEL SHALL BE SEALED ALL CONDUIT OPENINGS IN J-BOX AND CONTROL PANEL SHALL BE SEALED AIR TIGHT. 4.CONDUITS BETWEEN CONTROL PANEL AND ISOLATION PANEL SHALL HAVE CONDUITS BETWEEN CONTROL PANEL AND ISOLATION PANEL SHALL HAVE SEALING HUBS, APPLETON ES150-100 OR EQUIVALENT, AT THE ISOLATION PANEL. 5.CONTROL PANEL AND ANTENNA GROUND RODS TO BE UL LISTED COPPER CONTROL PANEL AND ANTENNA GROUND RODS TO BE UL LISTED COPPER CLAD STEEL " THICK, 34" THICK, 6.ALL PVC CONDUIT TO BE SCH 80 UV RESISTANT. ALL PVC CONDUIT TO BE SCH 80 UV RESISTANT. 7.FOR LIFTSTATIONS UP TO 150 AMP: FOR LIFTSTATIONS UP TO 150 AMP: (a.) H()L36###(C) - MOLDED CASE CIRCUIT BREAKER, 3 POLE, 600 VAC FRAME, ### = CURRENT RATING (15-150 AMP) (b.) PDC3HD2 - POWER DISTRIBUTION CONNECTOR FOR H FRAME BREAKER (3 14-2AWG Cu) (c.) S37449 - H FRAME LONG LUG SHIELD FOR LIFTSTATIONS OVER 150 AMP: (a.) J()L36###(C) - MOLDED CASE CIRCUIT BREAKER, 3 POLE, 600 VAC FRAME, ### = CURRENT RATING (150-250 AMP) (b.) PDC3JD20 - POWER DISTRIBUTION CONNECTOR FOR J FRAME BREAKER (2 14-1AWG AND 1 3-2/0 Cu) (c.) S37450 - J FRAME LONG LUG SHIELD
AutoCAD SHX Text
36" MIN.
AutoCAD SHX Text
TO BE DETERMINED IN THE FIELD
AutoCAD SHX Text
TO GROUND ROD
AutoCAD SHX Text
ISOLATION PANEL (J-BOX) SEE DWG.64B,64C
AutoCAD SHX Text
6" CONDUIT
AutoCAD SHX Text
6" CONDUIT
AutoCAD SHX Text
Pencell Plastic PE-6 HD
AutoCAD SHX Text
Pencell Plastic PE-6 HD
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 58: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Duplex Lift Station Control Panel J-Box

C-64b

AutoCAD SHX Text
A-16H2006SS6LP,
AutoCAD SHX Text
HOFFMAN ENCLOSURE, NEMA 4X
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
16"
AutoCAD SHX Text
U.L. 508
AutoCAD SHX Text
20"
AutoCAD SHX Text
SUBPLATE
AutoCAD SHX Text
P1
AutoCAD SHX Text
P2
AutoCAD SHX Text
TO WET WELL
AutoCAD SHX Text
INSTALLATION
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. SHOWN FOR GENERAL ARRANGEMENT PROVIDE EQUIPMENT AS INDICATED PER NUMBER OF PUMPS. 2. JUNCTION BOX SHALL BE PROVIDED BY THE SAME MANUFACTURER AS THE CONTROL PANEL AND SHALL BE U.L. 508 LISTED. 3. ALL CONTROL CABLES SHALL HAVE A SERVICE LOOP WITHIN J BOX AND CONTROL PANEL. 4. JUNCTION BOX ENCLOSURE SHALL BE NEMA 4X AND MINIMUM 16"H x 20"W x 6"D.
AutoCAD SHX Text
ALUMINUM ISOLATION BARRIER WITH SS HARDWARE
AutoCAD SHX Text
SQUARE D "LBC" COPPER POWER DISTRIBUTION BLOCK 3 - POLE (9080LBC362101 OR APPROVED EQUAL)
AutoCAD SHX Text
WITH SUBPLATE OR APPROVED EQUAL
AutoCAD SHX Text
FROM CONTROL PANEL
AutoCAD SHX Text
2" PVC SCHEDULE 80 WYE WITH 2" PVC INSECT AND RODENT SINGLE VENT SCREEN KIT PVS-IRS2 (TYP.)
AutoCAD SHX Text
TOP OF FITTING WITHIN 4" TO 6" OF BOTTOM OF BOX.
AutoCAD SHX Text
SQUARE D TERMINAL BLOCK ASSEMBLY 600V, 30 AMP #22-#10 AWG (QTY AS REQUIRED)
AutoCAD SHX Text
MECHANICAL GROUND CONNECTOR SINGLE CONDUCTOR, 1 HOLE MOUNT, 14AWG - 2/0 STR THOMAS & BETTS MODEL ADR21
AutoCAD SHX Text
MECHANICAL GROUND CONNECTOR MINIMUM TWO CONDUCTOR, 1 HOLE MOUNT, 14AWG - 2/0 STR THOMAS & BETTS MODEL ADR21-21
AutoCAD SHX Text
HIGH
AutoCAD SHX Text
FLOAT TERMINAL BLOCK LAYOUT
AutoCAD SHX Text
LAG
AutoCAD SHX Text
LEAD
AutoCAD SHX Text
OFF
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 59: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Triplex Lift Station Control Panel J-Box

C-64c

AutoCAD SHX Text
A20H2408SS6LP,
AutoCAD SHX Text
HOFFMAN ENCLOSURE, NEMA 4X
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
20"
AutoCAD SHX Text
U.L. 508
AutoCAD SHX Text
24"
AutoCAD SHX Text
SUBPLATE
AutoCAD SHX Text
P1
AutoCAD SHX Text
P2
AutoCAD SHX Text
P3
AutoCAD SHX Text
TO WET WELL
AutoCAD SHX Text
INSTALLATION
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. SHOWN FOR GENERAL ARRANGEMENT PROVIDE EQUIPMENT AS INDICATED PER NUMBER OF PUMPS. 2. JUNCTION BOX SHALL BE PROVIDED BY THE SAME MANUFACTURER AS THE CONTROL PANEL AND SHALL BE U.L. 508 LISTED. 3. ALL CONTROL CABLES SHALL HAVE A SERVICE LOOP WITHIN J BOX AND CONTROL PANEL. 4. JUNCTION BOX ENCLOSURE SHALL BE NEMA 4X 20"H x 24"W x 8"D.
AutoCAD SHX Text
ALUMINUM ISOLATION BARRIER WITH SS HARDWARE
AutoCAD SHX Text
SQUARE D "LBC" COPPER POWER DISTRIBUTION BLOCK 3 - POLE (9080LBC362101 OR APPROVED EQUAL)
AutoCAD SHX Text
SQUARE D TERMINAL BLOCK ASSEMBLY 600V, 30 AMP #22-#10 AWG (QTY AS REQUIRED)
AutoCAD SHX Text
WITH SUBPLATE OR APPROVED EQUAL
AutoCAD SHX Text
MECHANICAL GROUND CONNECTOR SINGLE CONDUCTOR, 1 HOLE MOUNT, 14AWG - 2/0 STR THOMAS & BETTS MODEL ADR21
AutoCAD SHX Text
FROM CONTROL PANEL
AutoCAD SHX Text
2" PVC SCHEDULE 80 WYE WITH 2" PVC INSECT AND RODENT SINGLE VENT SCREEN KIT PVS-IRS2 (TYP.)
AutoCAD SHX Text
TOP OF FITTING WITHIN 4" TO 6" OF BOTTOM OF BOX.
AutoCAD SHX Text
MECHANICAL GROUND CONNECTOR MINIMUM TWO CONDUCTOR, 1 HOLE MOUNT, 14AWG - 2/0 STR THOMAS & BETTS MODEL ADR21-21
AutoCAD SHX Text
HIGH
AutoCAD SHX Text
FLOAT TERMINAL BLOCK LAYOUT
AutoCAD SHX Text
LAG
AutoCAD SHX Text
LEAD
AutoCAD SHX Text
OFF
AutoCAD SHX Text
LAG2
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 60: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Control Panel Schematic - Duplex - 230V/3PHLift Station Control Panel Schematic - Duplex - 230V/3PH

C-65a

AutoCAD SHX Text
MB1
AutoCAD SHX Text
MB2
AutoCAD SHX Text
TERMINAL
AutoCAD SHX Text
TERMINAL
AutoCAD SHX Text
4
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
23
AutoCAD SHX Text
24
AutoCAD SHX Text
32
AutoCAD SHX Text
8
AutoCAD SHX Text
28
AutoCAD SHX Text
P2
AutoCAD SHX Text
STRIP
AutoCAD SHX Text
8
AutoCAD SHX Text
7
AutoCAD SHX Text
5
AutoCAD SHX Text
11
AutoCAD SHX Text
9
AutoCAD SHX Text
U
AutoCAD SHX Text
C
AutoCAD SHX Text
12
AutoCAD SHX Text
17
AutoCAD SHX Text
15
AutoCAD SHX Text
16
AutoCAD SHX Text
14
AutoCAD SHX Text
22
AutoCAD SHX Text
24
AutoCAD SHX Text
18
AutoCAD SHX Text
T
AutoCAD SHX Text
DFS
AutoCAD SHX Text
17
AutoCAD SHX Text
23
AutoCAD SHX Text
18
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
STRIP
AutoCAD SHX Text
P1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
5
AutoCAD SHX Text
6
AutoCAD SHX Text
7
AutoCAD SHX Text
37
AutoCAD SHX Text
36
AutoCAD SHX Text
1
AutoCAD SHX Text
10
AutoCAD SHX Text
21
AutoCAD SHX Text
22
AutoCAD SHX Text
19
AutoCAD SHX Text
20
AutoCAD SHX Text
29
AutoCAD SHX Text
1A
AutoCAD SHX Text
F3
AutoCAD SHX Text
31
AutoCAD SHX Text
12VDC
AutoCAD SHX Text
(BACKUP)
AutoCAD SHX Text
BATTERY
AutoCAD SHX Text
9
AutoCAD SHX Text
-
AutoCAD SHX Text
+
AutoCAD SHX Text
F1
AutoCAD SHX Text
F2
AutoCAD SHX Text
1A
AutoCAD SHX Text
1A
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
RECEPTACLE
AutoCAD SHX Text
PM
AutoCAD SHX Text
3O
AutoCAD SHX Text
60Hz
AutoCAD SHX Text
230V
AutoCAD SHX Text
3
AutoCAD SHX Text
TFS001
AutoCAD SHX Text
MCB
AutoCAD SHX Text
10A
AutoCAD SHX Text
4
AutoCAD SHX Text
1
AutoCAD SHX Text
1 AMP
AutoCAD SHX Text
FB1
AutoCAD SHX Text
CB
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
GR
AutoCAD SHX Text
ECB
AutoCAD SHX Text
4
AutoCAD SHX Text
2
AutoCAD SHX Text
5
AutoCAD SHX Text
PDB
AutoCAD SHX Text
(3)
AutoCAD SHX Text
(1)
AutoCAD SHX Text
MS2A
AutoCAD SHX Text
MS1A
AutoCAD SHX Text
26
AutoCAD SHX Text
25
AutoCAD SHX Text
MB2
AutoCAD SHX Text
MB1
AutoCAD SHX Text
27
AutoCAD SHX Text
13
AutoCAD SHX Text
MS2
AutoCAD SHX Text
C
AutoCAD SHX Text
11
AutoCAD SHX Text
12
AutoCAD SHX Text
MS1
AutoCAD SHX Text
C
AutoCAD SHX Text
A1
AutoCAD SHX Text
FL
AutoCAD SHX Text
(3)
AutoCAD SHX Text
(1)
AutoCAD SHX Text
(5)
AutoCAD SHX Text
FS2
AutoCAD SHX Text
FS1
AutoCAD SHX Text
FS3
AutoCAD SHX Text
OL
AutoCAD SHX Text
(7)
AutoCAD SHX Text
9
AutoCAD SHX Text
PM
AutoCAD SHX Text
TB1
AutoCAD SHX Text
FS4
AutoCAD SHX Text
8
AutoCAD SHX Text
18
AutoCAD SHX Text
LAG
AutoCAD SHX Text
LEAD
AutoCAD SHX Text
OFF
AutoCAD SHX Text
(4)
AutoCAD SHX Text
(2)
AutoCAD SHX Text
(6)
AutoCAD SHX Text
27
AutoCAD SHX Text
TTS
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
(8)
AutoCAD SHX Text
(4)
AutoCAD SHX Text
OL
AutoCAD SHX Text
14
AutoCAD SHX Text
A2
AutoCAD SHX Text
17
AutoCAD SHX Text
TTS
AutoCAD SHX Text
(2)
AutoCAD SHX Text
AL
AutoCAD SHX Text
A3
AutoCAD SHX Text
3
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
SHIPPED AS PART
AutoCAD SHX Text
120V NEUTRAL
AutoCAD SHX Text
120VAC SURGE
AutoCAD SHX Text
SUPPRESSOR
AutoCAD SHX Text
DRB
AutoCAD SHX Text
15A
AutoCAD SHX Text
2
AutoCAD SHX Text
MS2
AutoCAD SHX Text
OL
AutoCAD SHX Text
MS1
AutoCAD SHX Text
OL
AutoCAD SHX Text
PUMP 1
AutoCAD SHX Text
PUMP 2
AutoCAD SHX Text
GFDR
AutoCAD SHX Text
LA
AutoCAD SHX Text
3
AutoCAD SHX Text
SA
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
NOTE 1 - MS1A AND MS2A ARE AUXILIARY RUN CONTACTS.
AutoCAD SHX Text
(ISOLATED)
AutoCAD SHX Text
CCB
AutoCAD SHX Text
15A
AutoCAD SHX Text
RED (LABEL "POS")
AutoCAD SHX Text
BLACK (LABEL "NEG")
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 61: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Control Panel Deadfront LayoutLift Station Control Panel Dead Front Layout

C-65b

AutoCAD SHX Text
GFDR
AutoCAD SHX Text
TCU/ANTENNA CONNECTION
AutoCAD SHX Text
TCU
AutoCAD SHX Text
POLYPHASER
AutoCAD SHX Text
RF PIG TAIL
AutoCAD SHX Text
ANTENNA
AutoCAD SHX Text
TO
AutoCAD SHX Text
ANTENNA COAX
AutoCAD SHX Text
GND
AutoCAD SHX Text
(NOT TO SCALE)
AutoCAD SHX Text
SUBPANEL LAYOUT
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
6"
AutoCAD SHX Text
TB1
AutoCAD SHX Text
PM
AutoCAD SHX Text
FB1
AutoCAD SHX Text
TTS
AutoCAD SHX Text
BATTERY
AutoCAD SHX Text
12VDC
AutoCAD SHX Text
TFS
AutoCAD SHX Text
CTRL.
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
TELE.
AutoCAD SHX Text
ALARM STRIP
AutoCAD SHX Text
DRB
AutoCAD SHX Text
OL
AutoCAD SHX Text
MS1
AutoCAD SHX Text
OL
AutoCAD SHX Text
GND
AutoCAD SHX Text
MB2
AutoCAD SHX Text
MS2
AutoCAD SHX Text
MB1
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CCB
AutoCAD SHX Text
MECHANICALLY
AutoCAD SHX Text
ECB
AutoCAD SHX Text
INTERLOCKED
AutoCAD SHX Text
MCB
AutoCAD SHX Text
C
AutoCAD SHX Text
U
AutoCAD SHX Text
T
AutoCAD SHX Text
RESET
AutoCAD SHX Text
OL
AutoCAD SHX Text
RESET
AutoCAD SHX Text
OL
AutoCAD SHX Text
MCB
AutoCAD SHX Text
DRB
AutoCAD SHX Text
MB1
AutoCAD SHX Text
CCB
AutoCAD SHX Text
MB2
AutoCAD SHX Text
ECB
AutoCAD SHX Text
INTERLOCKED
AutoCAD SHX Text
MECHANICALLY
AutoCAD SHX Text
GR
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1. TELEMETRY CONTROL UNIT SUPPLIED WITH PANEL. (ANTENNA SUPPLIED BY OTHERS) 2. MINIMUM ENCLOSURE 42x30x10. 3. LEAVE MINIMUM 6" SPACE AT BOTTOM OF ENCLOSURE. 4. U.L. LABEL, SERVICE ENTRANCE RATED. 5. CONTROL WIRE TO BE AWG 14 MINIMUM. 6. LAMINATED SCHEMATIC TO BE 11X17. 7. PROVIDE ADEQUATE SPACE FOR 12V DC BATTERY REPLACEMENT. 8. OUTER DOOR REMOVED TO SHOW DEAD FRONT LAYOUT. 9. NEMA TYPE 12M 316 S.S. ENCLOSURE WITH CONTINUOUS HINGE. 10. INCLUDES 3 PT. LATCH. (NOT SHOWN) AND DOOR STOPS ON OUTER DOOR AND DEAD FRONT. 11. ALL HARDWARE TYPE 316 S.S. 12. TYPICAL, ACTUAL LAYOUT MAY VARY WITH HORSEPOWER. 13. MOUNT RECEPTACLE IN GANG BOX TO PREVENT EXPOSURE OF LIVE CONDUCTORS AND CONTACTS. 14. 480/120 TRANSFORMER ONLY REQUIRED IN CONTROL PANELS WITH 480VAC SERVICE.
AutoCAD SHX Text
DRB
AutoCAD SHX Text
CCB
AutoCAD SHX Text
FB
AutoCAD SHX Text
FS
AutoCAD SHX Text
GR
AutoCAD SHX Text
MB
AutoCAD SHX Text
MCB
AutoCAD SHX Text
OL
AutoCAD SHX Text
MS
AutoCAD SHX Text
TCU
AutoCAD SHX Text
GFDR
AutoCAD SHX Text
TTS
AutoCAD SHX Text
TB
AutoCAD SHX Text
F
AutoCAD SHX Text
FL
AutoCAD SHX Text
AL
AutoCAD SHX Text
-MOTOR STARTER
AutoCAD SHX Text
-TELEMETRY CONTROL UNIT
AutoCAD SHX Text
-THERMAL TERMINAL STRIP
AutoCAD SHX Text
-OVERLOAD
AutoCAD SHX Text
-TERMINAL BLOCK
AutoCAD SHX Text
-GENERATOR RECEPTACLE
AutoCAD SHX Text
-DUPLEX RECEPTACLE BREAKER
AutoCAD SHX Text
-GROUND FAULT DUPLEX RECEPTACLE
AutoCAD SHX Text
-CONTROL CIRCUIT BREAKER
AutoCAD SHX Text
-MAIN CIRCUIT BREAKER
AutoCAD SHX Text
-FUSE
AutoCAD SHX Text
-FLASHER
AutoCAD SHX Text
-FUSE BLOCK
AutoCAD SHX Text
-MOTOR BREAKER
AutoCAD SHX Text
-FLOAT SWITCH
AutoCAD SHX Text
-ALARM LIGHT
AutoCAD SHX Text
ECB
AutoCAD SHX Text
-EMERGENCY CIRCUIT BREAKER
AutoCAD SHX Text
120
AutoCAD SHX Text
480
AutoCAD SHX Text
XFR
AutoCAD SHX Text
XFR
AutoCAD SHX Text
-TRANSFORMER(480V LIFTSTATION ONLY)
AutoCAD SHX Text
SEE NOTE 14
AutoCAD SHX Text
PDB
AutoCAD SHX Text
MIN
AutoCAD SHX Text
PDB
AutoCAD SHX Text
-POWER DISTRIBUTION BLOCK
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 62: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Control Panel Schematic - Duplex - 480V/3PH

C-65c

AutoCAD SHX Text
ANTENNA COAX
AutoCAD SHX Text
5
AutoCAD SHX Text
TERMINAL
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
STRIP
AutoCAD SHX Text
P2
AutoCAD SHX Text
7
AutoCAD SHX Text
8
AutoCAD SHX Text
29
AutoCAD SHX Text
28
AutoCAD SHX Text
24
AutoCAD SHX Text
23
AutoCAD SHX Text
22
AutoCAD SHX Text
21
AutoCAD SHX Text
TERMINAL
AutoCAD SHX Text
T
AutoCAD SHX Text
18
AutoCAD SHX Text
U
AutoCAD SHX Text
9
AutoCAD SHX Text
11
AutoCAD SHX Text
16
AutoCAD SHX Text
15
AutoCAD SHX Text
14
AutoCAD SHX Text
17
AutoCAD SHX Text
C
AutoCAD SHX Text
24
AutoCAD SHX Text
22
AutoCAD SHX Text
23
AutoCAD SHX Text
18
AutoCAD SHX Text
19
AutoCAD SHX Text
20
AutoCAD SHX Text
10
AutoCAD SHX Text
9
AutoCAD SHX Text
F3
AutoCAD SHX Text
1A
AutoCAD SHX Text
1A
AutoCAD SHX Text
F2
AutoCAD SHX Text
17
AutoCAD SHX Text
DFS
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
32
AutoCAD SHX Text
31
AutoCAD SHX Text
P1
AutoCAD SHX Text
STRIP
AutoCAD SHX Text
7
AutoCAD SHX Text
5
AutoCAD SHX Text
6
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
1
AutoCAD SHX Text
8
AutoCAD SHX Text
1A
AutoCAD SHX Text
F1
AutoCAD SHX Text
(4)
AutoCAD SHX Text
(2)
AutoCAD SHX Text
9
AutoCAD SHX Text
8
AutoCAD SHX Text
MS1A
AutoCAD SHX Text
26
AutoCAD SHX Text
MS2A
AutoCAD SHX Text
25
AutoCAD SHX Text
MB1
AutoCAD SHX Text
MB2
AutoCAD SHX Text
(3)
AutoCAD SHX Text
(1)
AutoCAD SHX Text
PM
AutoCAD SHX Text
FS1
AutoCAD SHX Text
FS2
AutoCAD SHX Text
27
AutoCAD SHX Text
OFF
AutoCAD SHX Text
LEAD
AutoCAD SHX Text
AL
AutoCAD SHX Text
(8)
AutoCAD SHX Text
(6)
AutoCAD SHX Text
R1
AutoCAD SHX Text
C
AutoCAD SHX Text
R2
AutoCAD SHX Text
C
AutoCAD SHX Text
13
AutoCAD SHX Text
12
AutoCAD SHX Text
TB1
AutoCAD SHX Text
(7)
AutoCAD SHX Text
(5)
AutoCAD SHX Text
FS3
AutoCAD SHX Text
FS4
AutoCAD SHX Text
DPDT
AutoCAD SHX Text
DPDT
AutoCAD SHX Text
11
AutoCAD SHX Text
A1
AutoCAD SHX Text
(BACKUP)
AutoCAD SHX Text
FL
AutoCAD SHX Text
A2
AutoCAD SHX Text
12VDC
AutoCAD SHX Text
BATTERY
AutoCAD SHX Text
-
AutoCAD SHX Text
+
AutoCAD SHX Text
14
AutoCAD SHX Text
LAG
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
27
AutoCAD SHX Text
POLYPHASER
AutoCAD SHX Text
RF PIG TAIL
AutoCAD SHX Text
TCU/ANTENNA CONNECTION
AutoCAD SHX Text
A3
AutoCAD SHX Text
3
AutoCAD SHX Text
DRB
AutoCAD SHX Text
15A
AutoCAD SHX Text
FB1
AutoCAD SHX Text
1AMP
AutoCAD SHX Text
4A
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
RECEPTACLE
AutoCAD SHX Text
10A
AutoCAD SHX Text
CB
AutoCAD SHX Text
4
AutoCAD SHX Text
6
AutoCAD SHX Text
UNPROTECTED
AutoCAD SHX Text
PROTECTED
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
DFS
AutoCAD SHX Text
5
AutoCAD SHX Text
2
AutoCAD SHX Text
15A
AutoCAD SHX Text
CCB
AutoCAD SHX Text
GR
AutoCAD SHX Text
ECB
AutoCAD SHX Text
1
AutoCAD SHX Text
20A
AutoCAD SHX Text
PM
AutoCAD SHX Text
3O
AutoCAD SHX Text
60Hz
AutoCAD SHX Text
480V
AutoCAD SHX Text
MCB
AutoCAD SHX Text
C
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
PDB
AutoCAD SHX Text
C
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
SHIPPED AS PART
AutoCAD SHX Text
120V NEUTRAL
AutoCAD SHX Text
SUPPRESSOR
AutoCAD SHX Text
120VAC SURGE
AutoCAD SHX Text
2
AutoCAD SHX Text
GFDR
AutoCAD SHX Text
FB2
AutoCAD SHX Text
10A
AutoCAD SHX Text
10A
AutoCAD SHX Text
1A
AutoCAD SHX Text
120V
AutoCAD SHX Text
480V
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
2KVA
AutoCAD SHX Text
LA
AutoCAD SHX Text
PUMP 2
AutoCAD SHX Text
3
AutoCAD SHX Text
SA
AutoCAD SHX Text
MS1
AutoCAD SHX Text
MS2
AutoCAD SHX Text
MB2
AutoCAD SHX Text
MB1
AutoCAD SHX Text
OL
AutoCAD SHX Text
OL
AutoCAD SHX Text
PUMP 1
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
R2
AutoCAD SHX Text
1
AutoCAD SHX Text
R1
AutoCAD SHX Text
1
AutoCAD SHX Text
MS1
AutoCAD SHX Text
MS2
AutoCAD SHX Text
16
AutoCAD SHX Text
C
AutoCAD SHX Text
15
AutoCAD SHX Text
ANTENNA
AutoCAD SHX Text
TO
AutoCAD SHX Text
(2)
AutoCAD SHX Text
(4)
AutoCAD SHX Text
OL
AutoCAD SHX Text
30
AutoCAD SHX Text
OL
AutoCAD SHX Text
29
AutoCAD SHX Text
TTS
AutoCAD SHX Text
(3)
AutoCAD SHX Text
TTS
AutoCAD SHX Text
(1)
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
TCU
AutoCAD SHX Text
TO
AutoCAD SHX Text
(ISOLATED)
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text
NOTE 1 - MS1A AND MS2A ARE AUXILIARY RUN CONTACTS.
AutoCAD SHX Text
RED (LABEL "POS")
AutoCAD SHX Text
BLACK (LABEL "NEG")
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 63: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Diaphragm Seal, Pressure Gauge and Transducer Installation Detail

C-65d

AutoCAD SHX Text
AIR RELEASE VALVE
AutoCAD SHX Text
2" RED VALVE SERIES 42 DIAPHRAGM SEAL 316 STAINLESS STEEL WITH BUNA-N SLEEVE AND ETHYLENE GLYCOL FILL
AutoCAD SHX Text
2" CURB STOP VALVE
AutoCAD SHX Text
1/4" BALL VALVE
AutoCAD SHX Text
0-100 PSI GAUGE
AutoCAD SHX Text
2"TO DISCHARGE PIPING
AutoCAD SHX Text
0-100 PSI PRESSURE TRANSDUCER (4-20mA LOOP POWERED)
AutoCAD SHX Text
SHUNT ANALOG - ANALOG 1 + ANALOG 2 + TGND GND RXD_232 TXD_232 ISO+24V ISOGND
AutoCAD SHX Text
24 23 22 21 20 19 18 17 16 15
AutoCAD SHX Text
CONNECTOR P2
AutoCAD SHX Text
TCU
AutoCAD SHX Text
X X X
AutoCAD SHX Text
LINE 1 LINE 2 SHIELD (GND)
AutoCAD SHX Text
1A FAST ACTING
AutoCAD SHX Text
+ - GROUND
AutoCAD SHX Text
TRANSDUCER
AutoCAD SHX Text
NOTES: 1.4-20mA INTERFACE SHOWN. REMOVE JUMPER FROM P2-24 TO P2-23 FOR 0-5V INTERFACE. 4-20mA INTERFACE SHOWN. REMOVE JUMPER FROM P2-24 TO P2-23 FOR 0-5V INTERFACE. 2.SURGE ARRESTOR RECOMMENDED. SURGE ARRESTOR RECOMMENDED. 3.ANALOG IS BOUNDED INTERNALLY TO ISOGND. ANALOG IS BOUNDED INTERNALLY TO ISOGND. 4.THE ANALOG SHIELD WIRE MUST ONLY BE GROUNDED AT ONE END. THE ANALOG SHIELD WIRE MUST ONLY BE GROUNDED AT ONE END. 5.INSTALL AS DIRECTED BY POAPWS.INSTALL AS DIRECTED BY POAPWS.
AutoCAD SHX Text
NOTE 1.
AutoCAD SHX Text
NOTE 2.
AutoCAD SHX Text
316 SS SCHEDULE 40 THREADED TUBING & FITTINGS
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 64: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Lift Station Control Panel Material List

C-66

AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
MOTOR BREAKER
AutoCAD SHX Text
MB
AutoCAD SHX Text
TELEMETRY CONTROL UNIT
AutoCAD SHX Text
TERMINAL BOARD
AutoCAD SHX Text
SURGE ARRESTOR
AutoCAD SHX Text
PHASE MONITOR
AutoCAD SHX Text
MOTOR STARTER
AutoCAD SHX Text
TCU
AutoCAD SHX Text
TB
AutoCAD SHX Text
SA
AutoCAD SHX Text
PM
AutoCAD SHX Text
M
AutoCAD SHX Text
OL
AutoCAD SHX Text
MCB
AutoCAD SHX Text
OVERLOADS
AutoCAD SHX Text
MAIN BREAKER
AutoCAD SHX Text
DATA FLOW SYSTEMS
AutoCAD SHX Text
MARATHON
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
DIVERSIFIED
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
GENERATOR RECEPTACLE 200 AMP
AutoCAD SHX Text
LIGHTNING ARRESTOR
AutoCAD SHX Text
GENERATOR RECEPTACLE 100 AMP
AutoCAD SHX Text
EMERGENCY BREAKER
AutoCAD SHX Text
RECEPTACLE BREAKER
AutoCAD SHX Text
DUPLEX RECEPTACLE (GFI)
AutoCAD SHX Text
CONTROL TRANSFORMER
AutoCAD SHX Text
CONTROL BREAKER
AutoCAD SHX Text
NOMENCLATURE
AutoCAD SHX Text
F1 - F3
AutoCAD SHX Text
FB 2
AutoCAD SHX Text
FB 1
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
GR 2
AutoCAD SHX Text
FB 2
AutoCAD SHX Text
FS
AutoCAD SHX Text
LA
AutoCAD SHX Text
GR 1
AutoCAD SHX Text
ECB
AutoCAD SHX Text
DRB
AutoCAD SHX Text
DR
AutoCAD SHX Text
CT1
AutoCAD SHX Text
CCB
AutoCAD SHX Text
AL
AutoCAD SHX Text
FLOAT SWITCH
AutoCAD SHX Text
480/120V
AutoCAD SHX Text
ALARM LIGHT
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
FUSE X2
AutoCAD SHX Text
FUSE X3
AutoCAD SHX Text
APPLETON
AutoCAD SHX Text
BUSSMAN-MDL
AutoCAD SHX Text
ANCHOR SCIENTIFIC
AutoCAD SHX Text
BUSSMAN-KTK
AutoCAD SHX Text
BUSSMAN-KTK
AutoCAD SHX Text
BUSSMAN-KTK
AutoCAD SHX Text
OR HEAVY DUTY
AutoCAD SHX Text
SQUARD D
AutoCAD SHX Text
DELTA
AutoCAD SHX Text
APPLETON
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
HUBBELL
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
FEDERAL SIGNAL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
THERMAL MAGNETIC MOLDED CASE WITH AUX CONTACT
AutoCAD SHX Text
MELTING ALLOY WITH SO-4 AUX CONTACT
AutoCAD SHX Text
THERMAL MAGNETIC MOLDED CASE
AutoCAD SHX Text
200 SERIES
AutoCAD SHX Text
SDSA3650
AutoCAD SHX Text
SLA-XXX-ALE
AutoCAD SHX Text
8536 SERIES
AutoCAD SHX Text
AR20034RS
AutoCAD SHX Text
1 AMP WITH 250V FUSE BLOCK
AutoCAD SHX Text
ROTO-FLOAT
AutoCAD SHX Text
20 AMP WITH 250V FUSE BLOCK
AutoCAD SHX Text
10 AMP WITH 600V FUSE BLOCKS
AutoCAD SHX Text
1 AMP WITH 600V FUSE BLOCKS
AutoCAD SHX Text
LA303 (250V) OR LA603 (480V)
AutoCAD SHX Text
THERMAL MAGNETIC MOLDED CASE
AutoCAD SHX Text
ADR1034RS W/SPRING DOOR
AutoCAD SHX Text
PART NUMBER
AutoCAD SHX Text
FAL 12015
AutoCAD SHX Text
GFTR15SNAPWNA
AutoCAD SHX Text
2000 VA
AutoCAD SHX Text
FAL 12###
AutoCAD SHX Text
LP3P-120R
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
GROUND LUG-2 CONDUCTOR
AutoCAD SHX Text
GL
AutoCAD SHX Text
THOMAS & BETTS
AutoCAD SHX Text
ADR 21-21
AutoCAD SHX Text
GROUND LUG-SINGLE CONDUCTOR
AutoCAD SHX Text
GL
AutoCAD SHX Text
THOMAS & BETTS
AutoCAD SHX Text
ADR 21
AutoCAD SHX Text
TCV SNAP-IN KIT
AutoCAD SHX Text
TCV
AutoCAD SHX Text
DATA FLOW SYSTEMS
AutoCAD SHX Text
DFS-00392-008-09
AutoCAD SHX Text
POLYPHASER
AutoCAD SHX Text
PP
AutoCAD SHX Text
DATA FLOW SYSTEMS
AutoCAD SHX Text
DFS-00392-008-01
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
RC SNUBBER
AutoCAD SHX Text
RC
AutoCAD SHX Text
DATA FLOW SYSTEMS
AutoCAD SHX Text
DFS-007-C084
AutoCAD SHX Text
ANGLE ADAPTER
AutoCAD SHX Text
GR1A
AutoCAD SHX Text
APPLETON
AutoCAD SHX Text
AJA100
AutoCAD SHX Text
(X)
AutoCAD SHX Text
ANGLE ADAPTER
AutoCAD SHX Text
GR2A
AutoCAD SHX Text
APPLETON
AutoCAD SHX Text
AJA200
AutoCAD SHX Text
(X)
AutoCAD SHX Text
NOTE: EQUIVALENT MAY BE USED EXCEPT WHERE MARKED BY (X)
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 65: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Telementry Antenna General Requirements

C-67

AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1.ANTENNA HEIGHT SHALL CONFORM TO F.C.C. AND TELEMETRY MANUFACTURERS REQUIREMENTS AND SPECIFICATIONS. ANTENNA HEIGHT SHALL CONFORM TO F.C.C. AND TELEMETRY MANUFACTURERS REQUIREMENTS AND SPECIFICATIONS. 2.TELEMETRY ANTENNA AND RELATED EQUIPMENT AS MANUFACTURED BY DATA FLOW SYSTEMS, INC. SHALL BE COMPATIBLE TELEMETRY ANTENNA AND RELATED EQUIPMENT AS MANUFACTURED BY DATA FLOW SYSTEMS, INC. SHALL BE COMPATIBLE WITH EXISTING SEACOAST UTILITIES AUTHORITY TELEMETRY SYSTEM. 3.GROUND WIRE SHALL BE CONTINOUS FROM FIRST GROUND ROD TO SERVICE DISCONNECT, TO CONTROL PANEL, TO GROUND WIRE SHALL BE CONTINOUS FROM FIRST GROUND ROD TO SERVICE DISCONNECT, TO CONTROL PANEL, TO ANTENNA BASE, TO SECOND GROUND ROD 6' TO 8' FROM FIRST GROUND ROD. 4.ANTENNA SHALL BE INSTALLED TO WITHSTAND 150 MPH WINDS.ANTENNA SHALL BE INSTALLED TO WITHSTAND 150 MPH WINDS.
AutoCAD SHX Text
1" UV RESISTANT P.V.C. CONDUIT
AutoCAD SHX Text
TO CONTROL PANEL
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
12"
AutoCAD SHX Text
YAGI ANTENNA
AutoCAD SHX Text
ANTENNA, CONTROL PANEL AND GROUNDING RODS
AutoCAD SHX Text
GROUND WIRE SHALL BE CONTINOUS BETWEEN
AutoCAD SHX Text
CABLE GLAND TO BE 3" BELOW THE BOTTOM OF THE CONTROL PANEL
AutoCAD SHX Text
ROLL COAXIAL CABLE INTO AN APROXIMATE 9" DIAMETER LOOP AT TOP OF MAST
AutoCAD SHX Text
48"
AutoCAD SHX Text
30"
AutoCAD SHX Text
6"CONDUIT
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 66: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Typical Lift Station Site Plan

C-68

AutoCAD SHX Text
COORDINATE THE SPECIFIC SITE PLAN REQUIREMENTS WITH THE PBPOC POA AND LDRB
AutoCAD SHX Text
THIS DRAWING DEPICTS A GENERAL SITE PLAN ONLY. THE ENGINEER OF RECORD SHALL
AutoCAD SHX Text
STANDARD FDOT "NO PARKING"
AutoCAD SHX Text
SIGN ATTACHED TO 6' GATES
AutoCAD SHX Text
1'-0"
AutoCAD SHX Text
ENTRANCE ROAD PER
AutoCAD SHX Text
ASPHALT/CONCRETE
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
25' - 0"
AutoCAD SHX Text
25' - 0"
AutoCAD SHX Text
NOTES: (PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS) 1.COLLECTOR MANHOLE SHALL NOT BE PLACED IN TRAVEL LANE OR AREAS THAT WOULD LIMIT ACCESS. COLLECTOR MANHOLE SHALL NOT BE PLACED IN TRAVEL LANE OR AREAS THAT WOULD LIMIT ACCESS. 2.GROUND COVER WITHIN FENCED AREA SHALL BE 6" THICK CONCRETE (4000psi) WITH A 12" x 12" FOOTER AND 6" x 6" GROUND COVER WITHIN FENCED AREA SHALL BE 6" THICK CONCRETE (4000psi) WITH A 12" x 12" FOOTER AND 6" x 6" WIRE MESH AND BE SLOPED IN SUCH A WAY TO PROMOTE RUNOFF AND PREVENT PUDDLING. 3.LANDSCAPING SHALL BE A MINIMUM OF 2' FROM FENCE. TREE, TREE PLACEMENT AND LANDSCAPING SHALL CONFORM TO LANDSCAPING SHALL BE A MINIMUM OF 2' FROM FENCE. TREE, TREE PLACEMENT AND LANDSCAPING SHALL CONFORM TO PBPOC POA SET BACK REQUIREMENTS AND BE APPROVED BY THE LDRB. 4.FENCE SHALL BE INSTALLED PER DETAIL 17.FENCE SHALL BE INSTALLED PER DETAIL 17.
AutoCAD SHX Text
12" x 12" FOOTER
AutoCAD SHX Text
1" WATER SERVICE WITH BACKFLOW PREVENTOR, SEE "LIFT STATION BACKFLOW PREVENTOR ASSEMBLY" DETAIL
AutoCAD SHX Text
SEPERATE CONCRETE POUR
AutoCAD SHX Text
FDOT SPECIFICATIONS
AutoCAD SHX Text
BOX HINGE ONLY FOR EACH 6' GATE
AutoCAD SHX Text
ISOLATION PANEL
AutoCAD SHX Text
SERVICE DISCONNECT
AutoCAD SHX Text
F&L METER
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
18" MIN
AutoCAD SHX Text
TELEMENTRY ANTENNA
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1
Page 67: WATER / WASTEWATER Basis - pbpoc.orgpbpoc.org/data/documents/PBPOC_Water-Wastewaste_Standards-01-25-2018.pdf · Potable Water and Wastewater System Design and Construction Standards

Wet Well Section Retainer Strap

C-69

AutoCAD SHX Text
30.00"
AutoCAD SHX Text
2.00"
AutoCAD SHX Text
2.00"
AutoCAD SHX Text
3.00"
AutoCAD SHX Text
(TYP)(4 PLACES)
AutoCAD SHX Text
3/4" DIA. HOLE
AutoCAD SHX Text
1/2" THICK STEEL PLATE
AutoCAD SHX Text
2.00"
AutoCAD SHX Text
1.00"
AutoCAD SHX Text
2.00"
AutoCAD SHX Text
PLEASE REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
AutoCAD SHX Text
CONSTRUCTION STANDARDS AND DETAILS
AutoCAD SHX Text
PALM BEACH PARK OF COMMERCE ASSOCIATION, Inc.
AutoCAD SHX Text
DATE APPROVED:
AutoCAD SHX Text
DRAWING No.
AutoCAD SHX Text
January 26, 2018
AutoCAD SHX Text
Revision 1