WB7-3 Observations Regarding
Window Testing and Failures
Roger G. MorseMorse Zehnter Associates
Rensselaer Technology Park
165 Jordan Road
Troy, NY 12180
![Page 2: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/2.jpg)
Window Testing
• Architect identifies a sampling of windows to be tested. – Representative sampling of each window type on the job
• Windows Leak Tested– Independent testing agency
– ASTM E1105 or AAMA 502
• Windows Leak
• Window sub-contractor tunes up windows
• Windows retested and pass
• Windows and their installation are accepted once the sample windows meet requirements of the test.
![Page 3: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/3.jpg)
Leak Test
• ASTM E1105 or AAMA 502
• Pressure differential across window
– Interior negative or
– Exterior positive
• Spray water to form a continuous film of
water on surface
– Does not attempt to mimic kinetic energy of
wind blown rain
![Page 4: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/4.jpg)
From ASTM
E1105
![Page 5: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/5.jpg)
Installer Tune-up
• Sealants at butt (mitered) joints in gaskets in corners,
• Cam locks, shimmed or adjusted to apply more pressure to gaskets
– “dollar bill” test
• Sealant at fixed joints between aluminum extrusions
– Corners of frames and sashes
– Fasteners
![Page 6: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/6.jpg)
End Result
• All windows are adjusted during “Tune Up”
• Testing of exemplar windows is a proper
test of the window system
• Windows don’t leak when tester and
contractor leave site
![Page 7: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/7.jpg)
Problems with Testing
• May not include doors
• Testing normally performed after interior
finishes in place
– Hides wall leaks
– May hide leaks within frame perimeter
![Page 8: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/8.jpg)
Problems with End Result
• Great that windows are tested – how
about the rest of the wall
• Windows may not leak at time of test but
how about several years later
• Windstorms
![Page 9: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/9.jpg)
Then Time Happens
• Sealants harden, shrink and crack
• Gaskets shrink and harden
– End joints open up
– Gaskets relax so air and water pass through gasketed joints at an increasing rate over time
• Buildings settle differentially twisting assemblies
• Users damage windows
• Fixed joints aren’t really fixed
![Page 10: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/10.jpg)
![Page 11: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/11.jpg)
![Page 12: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/12.jpg)
![Page 13: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/13.jpg)
![Page 14: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/14.jpg)
![Page 15: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/15.jpg)
Then Wind Happens
• Wind pressures during wind driven rain
exceed those in leak test
• Pressures during a hurricane event
drastically exceed test pressures
• Window must have some sort of pressure
relieve feature to prevent water passage
– Pressure balanced seals
– Drainage subsills
![Page 16: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/16.jpg)
Wind Creates Pressure Differentials
![Page 17: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/17.jpg)
Wind Speed Increases with Height
![Page 18: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/18.jpg)
Stack Effect – Warm Climate
![Page 19: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/19.jpg)
Stack Effect – Cold Climate
![Page 20: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/20.jpg)
Combined Effect –
HVAC, Stack and Wind
![Page 21: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/21.jpg)
![Page 22: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/22.jpg)
Pressure Differentials
Pressure Differential
PSF Inches Water
Test Pressure 9 1.73
Wind Pressure - High 86 17
Wind Pressure - Low 56 11
![Page 23: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/23.jpg)
![Page 24: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/24.jpg)
Paradigm Shift
• Good Old Days – Stupid & Simple
– Huge water storage, inorganic materials, simple materials and assemblies
• Now – Smart & Sophisticated
– High tech materials
– Complex assemblies
– High performing
– Sustainable
– Water sensitive
![Page 25: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/25.jpg)
Good Old Day
![Page 26: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/26.jpg)
Now
![Page 27: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/27.jpg)
Current State of the Construction
Industry
• Sophisticated High tech materials and systems
• Rapid product development
• Increasing specialization
– Manufacturers
– Contractors
• Increase in magnitude of natural forces affecting
materials and assemblies
– Insulation
– Membranes
![Page 28: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/28.jpg)
Case Study - Florida
• Windows in Florida
• Hurricanes
• General Guidance
– ASTM E2112 – Standard Practice for Installation of Exterior Windows Doors and Skylights
• Specific Regional Guidance
– Fenestration Manufacturers Association Standards
![Page 29: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/29.jpg)
![Page 30: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/30.jpg)
CSI Sections
• Division 03
– Concrete,
• Division 04
– Brick
– Stone
– Concrete Block
• Division 06
– Wood framing
• Division 07
– Flashing
– Sealants
• Division 08
– Windows
• Division 09
– Painting
![Page 31: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/31.jpg)
Manufacturers
• Window
• Flashing
• Sealants
• Brick
• Precast sill
• Concrete block
• Mortar
• Wood blocking
• Fasteners
• Metal furring
• Gypsum drywall
• Paint
![Page 32: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/32.jpg)
Contractors
• Window
• Masonry
• Carpentry
• Drywall
• Painting
• Caulking
![Page 33: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/33.jpg)
FMA Installation CommitteeFMA/AAMA 100 Flanged Wood Frame
FMA/AAMA 200 Frontal Flanged Surface Barrier
CMU
FMA/AAMA 250 Non-Frontal
Flange (wood)
Surface Barrier
CMU
FMA/AAMA 300 Sliding Glass
Door
Wood Frame
FMA/AAMA 400 Sliding Glass
Door
Surface Barrier
CMU
![Page 34: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/34.jpg)
Fenestration Manufacturer’s
Association
• Drainable sill pan
• Recommended section for a precast sill
that provides drainage
• Use of liquid applied sealants to form
perimeter flashing continuous with sill pan
![Page 35: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/35.jpg)
Strength of Approach
• Establishes draining subsill as a standard
part of window assembly
• Attempts to consolidate critical tasks with
one entity
• Written set of instructions
![Page 36: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/36.jpg)
Starting to Appear in Guide
Specifications
• Palm Beach County Schools
– In window section
• Broward County Schools
– Not yet
• Regional – not in national guide specs
![Page 37: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/37.jpg)
Contractors Involved in Window
Installation
• Mason sub-contractor
– Install precast sill
– prepare the masonry
opening
• Waterproofing sub-
contractor
– Install the sill pan and
perimeter coatings
• Carpentry sub-contractor
– install wood bucks
• Window sub-contractor
– install the window
• Stucco sub-contractor
– stucco over the sill and on
jambs and head
• Painter
– sealant between stucco
and window
– paint
• Drywall sub-contractor
– interior finishes
![Page 38: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/38.jpg)
Specification Sections Involved
• Masonry
• Waterproofing
• Window
• Stucco
• Painting
![Page 39: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/39.jpg)
Next Step
• New window specification section
– consolidates all of the work required by the
standard in a single specification section.
• Include in major guide specifications
providers
– NIBS Construction Criteria Base
– Arcom (AIA) MasterSpec®,
– CSI Spectext®.
![Page 40: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/40.jpg)
Proposed ASTM E 1105 Changes
• Add Low Pressure Water Test (LPWT)
• Intended to jibe better with end user
expectations of the test
![Page 41: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/41.jpg)
Proposed ASTM E 1105 Changes
• Low Pressure Water Test (LPWT)
– less than 75 pascals (1.57 lbf/ft2)
– No visible water through window
• High Pressure Water Test (HPWT)
– Current definition
– Water may be visible inside window (except
collector sills) - but not past it
• Water penetration through perimeter frame
![Page 42: WB7-3 Observations Regarding Window Testing and Failures€¦ · • Windows Leak Tested –Independent testing agency –ASTM E1105 or AAMA 502 • Windows Leak • Window sub-contractor](https://reader034.vdocument.in/reader034/viewer/2022042710/5f67612e7d2eef5e8b419829/html5/thumbnails/42.jpg)
WB7-3 Observations Regarding
Window Testing and Failures
Roger G. MorseMorse Zehnter Associates
Rensselaer Technology Park
165 Jordan Road
Troy, NY 12180