www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 Product information VAV-Compact KNX A pressure sensor, digital VAV controller and damper actuator all in one, providing a compact solution with a communications capability for pressure-independent VAV and CAV systems in the comfort zone • Communication via KNX (S mode) • Conversion of sensor signals • Service socket for operating devices Brief description Application The VAV-Compact has PI control characteristics and is used for pressure-independent control of VAV units in the comfort zone. Pressure measurement The integrated D3 differential pressure sensor is also suitable for very small volumetric flows. The maintenance-free sensor technology enables versatile applications in the comfort zone: in residential construction, offices, hospitals, hotels, cruise ships, etc.. Actuator 2 different actuator variants (5 or 10 Nm) are available for different VAV unit structures. Control function Volumetric flow (VAV-CAV) or Open-Loop (for integration in an external VAV control loop). VAV – variable volumetric flow Demand-dependant setting of volumetric flows min max on a modulating reference variable via KNX, e.g. room temperature / CO2 controller, DDC or Bus system, for energy-saving air conditioning in individual rooms or zones. DCV – Demand Controlled Ventilation In higher-level KNX system, for example with integrated optimiser function. Type of action The actuator is fitted with an integrated interface for KNX (S mode), it receives the digital positioning signal from the KNX system and returns the current status. Converter for sensors Connection option for a sensor (active sensor or switching contact). In this way, the analogue sensor signal can be easily digitised and passed along to KNX. Parameterisation The factory settings cover the most common applications. As desired, individual parameters can be adapted for specific systems or servicing with a service tool (e.g. ZTH EU). Communication parameters The VAV Compact is equipped with an integrated interface for KNX (S MODE). The VAV controller can be connected with all KNX devices that have corresponding data points available. Operating and service devices Service tool ZTH, PC-Tool service socket: locally pluggable or via PP connection. Electrical connection The connection is made with the integrated connection cable. Sales, mounting and setting VAV-Compact will be mounted by the VAV unit manufacturer (OEM), the application will be set and calibrated accordingly. The VAV-Compact is sold exclusively via the OEM channel for this reason. Type overview KNX versions Type Torque Power consumption Rating Weight LMV-D3-KNX 5 Nm 2 W 4 VA (max. 8 A @ 5 ms) Approx. 500 g NMV-D3-KNX 10 Nm 3 W 5 VA (max. 8 A @ 5 ms) Approx. 700 g Other versions The VAV-Compact is also available with a built-in interface for direct integration in MP-Bus systems, Modbus and LONWORKS®. See www.belimo.eu for more information and documentation. LMV-D3-KNX NMV-D3-KNX

Upload: truongminh

Post on 19-Mar-2018

225 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1

Product information VAV-Compact KNX

A pressure sensor, digital VAV controller and damper actuator all in one, providing a compact solution with a communications capability for pressure-independent VAV and CAV systems in the comfort zone• Communication via KNX (S mode)• Conversion of sensor signals• Service socket for operating devices

Brief description

Application The VAV-Compact has PI control characteristics and is used for pressure-independent control of VAV units in the comfort zone.

Pressure measurement The integrated D3 differential pressure sensor is also suitable for very small volumetric flows. The maintenance-free sensor technology enables versatile applications in the comfort zone: in residential construction, offices, hospitals, hotels, cruise ships, etc..

Actuator 2 different actuator variants (5 or 10 Nm) are available for different VAV unit structures.

Control function Volumetric flow (VAV-CAV) or Open-Loop (for integration in an external VAV control loop).

VAV – variable volumetric flow Demand-dependant setting of volumetric flows min … max on a modulating reference variable via KNX, e.g. room temperature / CO2 controller, DDC or Bus system, for energy-saving air conditioning in individual rooms or zones.

DCV – Demand Controlled Ventilation In higher-level KNX system, for example with integrated optimiser function.

Type of action The actuator is fitted with an integrated interface for KNX (S mode), it receives the digital positioning signal from the KNX system and returns the current status.

Converter for sensors Connection option for a sensor (active sensor or switching contact). In this way, the analogue sensor signal can be easily digitised and passed along to KNX.

Parameterisation The factory settings cover the most common applications. As desired, individual parameters can be adapted for specific systems or servicing with a service tool (e.g. ZTH EU).

Communication parameters The VAV Compact is equipped with an integrated interface for KNX (S MODE). The VAV controller can be connected with all KNX devices that have corresponding data points available.

Operating and service devices Service tool ZTH, PC-Tool service socket: locally pluggable or via PP connection.

Electrical connection The connection is made with the integrated connection cable.

Sales, mounting and setting VAV-Compact will be mounted by the VAV unit manufacturer (OEM), the application will be set and calibrated accordingly. The VAV-Compact is sold exclusively via the OEM channel for this reason.

Type overview KNX versions

Type Torque Power consumption Rating Weight

LMV-D3-KNX 5 Nm 2 W 4 VA (max. 8 A @ 5 ms) Approx. 500 gNMV-D3-KNX 10 Nm 3 W 5 VA (max. 8 A @ 5 ms) Approx. 700 g

Other versions The VAV-Compact is also available with a built-in interface for direct integration in MP-Bus systems, Modbus and LONWORKS®. See www.belimo.eu for more information and documentation.

LMV-D3-KNX NMV-D3-KNX

Page 2: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

2 VAV-Compact KNX • en-gb • 2017-08 • Changes reserved www.belimo.eu

Electrical installation

Notes– Supply via safety isolating transformer!– Signal assignment KNX: D+ = KNX+ (pink > red) D– = KNX– (grey > black)– The connection to the KNX line should take place

via WAGO connection terminals 222/221.

!

No. Designation Wire colour Function1

– T

blackAC/DC 24 V supply

2 ~ + red

35 MFT orange PP connection6 D+ pink > red

KNX7 D– grey > black

Safety notes

!• The device must not be used outside the specified field of application, especially

not in aircraft or in any other airborne means of transport.• Outdoor applications: possible only in the absence of direct effects on the actuator from

(sea)water, snow, ice, sunlight and aggressive gases and when it is guaranteed that the ambient conditions do not deviate at any time from the limit values specified in the datasheet.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied with during installation.

• The device may only be opened at the manufacturer's site. It does not contain any parts that can be replaced or repaired by the user.

• Cables must not be removed from the device.• When calculating the torque required, the specifications supplied by the damper

manufacturers (cross-section, construction, place of installation), and the ventilation conditions must be observed.

• The device contains electrical and electronic components and is not allowed to be disposed of as household refuse. All locally valid regulations and requirements must be observed.

See separate documentation for description of functions and applications

Page 3: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 3

Technical Data

Electrical data Nominal voltage AC/DC 24 V, 50/60 HzOperating range AC 19.2 ... 28.8V / DC 21.6 ... 28.8VPerformance data See Overview of types (page 1)Connecting Cable, 6 x 0,75 mm2, preassembled

VAV controllers Control function VAV/CAV and Open-Loopnom 1) OEM specific nominal volumetric flow setting, suitable for VAV unitΔp @ nom 1) 38 … 500 Pamax 20 … 100 % of nom, adjustablemid >min … <max, adjustable min 0 … 100 % of nom, adjustable (<max)

Sensor integration input 0 … 32 V, input impedance 100 kΩSensor Active Sensor (0 … 10 V)

Switching contact (0 / 1) switching capacity 16 mA @ 24 V

Local override control Override CLOSED / max / OPEN, AC 24 V supply required

Data for KNX Medium KNX TPNumber of nodes Max. 64 per line segment,

reduce number of nodes with connection cable with short linesOperating mode S modeVoltage consumption of KNX-Bus Max. 5 mAPlanning and commissioning tool ETS4 or higherParameterisation with service tool ZTH EUSensor integration Active sensor (0 … 10 V)

Switching contact (0 / 1) (switching capacity 16 mA @ 24 V)

Operation and servicing Service tool ZTH, PC-Tool Local plug / Remote via PP connectionLED Supply , status and communication displayPush-button Addressing, angle of rotation adaptation and test function

Actuator Rotary/linear version Brushless, non-blocking actuator with power-save modeDirection of rotation 1) ccw / cwAngle of rotation 95°, adjustable mechanical or electronic limitingGear disengagement Push-button self-resetting without functional impairmentPosition indication Mechanical or accessible (Tool, Bus-Master)Spindle holder Spindle clamp for round and square shafts

Volumetric flow measurement

Differential pressure sensor Belimo D3 sensor, dynamic measurement principle

cMeasurement range, operating range –20 … 500 Pa, 0 … 500 PaOverload capability ±3000 PaAltitude compensation Adaptation to system altitude (adjustable between 0 … 3000 m above sea level)Installation position Any, no reset necessaryMaterials in contact with medium Glass, epoxy resin, PA, TPEMeasuring air conditions Comfort zone 0 … 50°C / 5 … 95% rH, non-condensing

Safety Protection class IEC/EN III Safety extra-low voltageDegree of protection IEC / EN IP54EMC CE according to 2014/30/EUCertification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14Rated current voltageSupply / control

0.8 kV

Control pollution degree 3Ambient temperature -30...50°CNon-operating temperature -40...80°CAmbient humidity range 95% r.h., non-condensingMaintenance Maintenance-free. Depending on the application, the differential pressure sensor

(measuring cross, disc, …) of the VAV unit is checked occasionally and cleaned if required.

1) Setting by VAV manufacturer (OEM)

Page 4: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

4 VAV-Compact KNX • en-gb • 2017-08 • Changes reserved www.belimo.eu

KNX Group Objects

Name Type Flags Data point type Values rangeK L S Ü A ID DPT_Name Format Unit

Setpoint E K – S – – 5.001 _Scaling 1 Byte % [0...100]Resolution 0.4%

Override control E K – S – – 20.* _Enum 1 Byte – 0 = no override1 = Open2 = Closed3 = Min4 = Mid5 = Max

Reset E K – S – – 1.015 _Reset 1 Bit – 0 = no action1 = reset

Adaptation E K – S – – 1.001 _Switch 1 Bit – 0 = no action1 = adapt

Test run E K – S – – 1.001 _Switch 1 Bit – 0 = no action1 = Test run

Min E/A K L S – – 5.001 _Scaling 1 Byte % [0...100]Resolution 0.4%

Max E/A K L S – – 5.001 _Scaling 1 Byte % [0...100]Resolution 0.4%

Relative position A K L – Ü – 5.001 _Scaling 1 Byte % [0...100]Resolution 0.4%

Absolute position A K L – Ü – 8.0117.011

_Rotation_Angle_Length_mm

2 Byte °mm

[–32‘768...32‘768][0...65‘535]

Relative volumetric flow A K L – Ü – 5.001 _Scaling 1 Byte % [0...100]Resolution 0.4%

Absolute volumetric flow A K L – Ü – 14.077 _Value_Volume_Flux 4 Byte m3/s 1.0 x 10–10 m3/sNominal volumetric flow A K L – Ü – 14.077 _Value_Volume_Flux 4 Byte m3/s 1.0 x 10–10 m3/sFault status A K L – Ü – 1.002 _Bool 1 Bit – 0 = no error

1 = errorOverride control active A K L – Ü – 1.002 _Bool 1 Bit – 0 = not active

1 = activeGear disengagement active A K L – Ü – 1.002 _Bool 1 Bit – 0 = engaged

1 = disengagedService information A K L – Ü – 22.* _Bitset16 2 Byte – Bit 0 (1)

cBit 1 (2)Bit 2 (4)Bit 3 (8)Bit 4 (16)Bit 5 (32)Bit 6 (64)Bit 7 (128)Bit 8 (256)Bit 9 (512)

Utilisation too highActuation path increasedMechanical overload– (Not used)– (Not used)– (Not used)– (Not used)– (Not used)Internal activityBus monitoring triggered

Sensor value– relative humidity– air quality– voltage mV– voltage scaled– Voltage scaled %– Switching contact

A K L – Ü –9.0079.0089.020

7.*5.0011.001

_Value_Humidity_Value_AirQuality_Value_Voltage

–_Scaling_Switch

2 Byte2 Byte2 Byte2 Byte1 Byte

% rHppmmV–%–

[0...670‘760][0...670‘760][–670‘760...670‘760][0...65‘535][0...100]0/1

Page 5: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 5

KNX Group Objects (Continued)

Setpoint Specification of set volume or actuator position in % between the parameterised Min and Max limits.The operating mode is set by the manufacturer of the volumetric flow unit.

Override control Overriding the setpoint with defined compulsions.As data point type, 1 Byte (without algebraic sign) is recommended (DPT 20.*)

Reset Resetting the saved service messages(see KNX group object Service information).

Adaptation Perform the adaption. The first-time adaption is performed by the manufacturer of the volumetric flow unit.An active adaption is signalled in Bit 8 of Service information.

Test run Performance of a test run that checks the entire operating range.An active test run is signalled in Bit 8 of Service information. After completion, detected faults (mechanical overload, actuation path exceeded) are signalled in Service Information.

Min Minimum Limit (volumetric flow or position) in % of the nominal volumetric flow Vnom

Caution: Changing the setting may result in malfunctions.

Max Maximum Limit (volumetric flow or position) in % of the nominal volumetric flow Vnom

Caution: Changing the setting may result in malfunctions.

Relative position Current actuator position in %

Absolute position Absolute position/strokeThe data point type is to be selected depending on the type of movement:[°] DPT 8.011[mm] DPT 7.011

Relative volumetric flow Relative volumetric flow in % of the nominal volumetric flow Vnom

Absolute volumetric flow Absolute volumetric flow in m3/s

Nominal volumetric flow Nominal volumetric flow in m3/sThe nominal volumetric flow is determined by the manufacturer of the volumetric flow unit.

Fault status Collective fault based on Bit 0 … Bit 7 of Service information

Override control active Signalling of an active override control (OPEN/CLOSED)The device can be commanded via the KNX group object Override control or via the forced switching at the input Y/3. Only the override controls OPEN and CLOSED are signalled.

Gear disengagement active Signalling an active gear disengagement

Service information Detailed information regarding instrument statusAs data point type, Bitset 16-Bit is recommended (DPT 22.*)Status informationBit 0: Motor operation in relation to operating period too highBit 1: Actuation path increased, e.g. defined end position exceededBit 2: Mechanical overload, i.e. defined end position not reachedBit 3 … 7: not used with this instrument typeBit 8: Internal activity (Synchronisation, Adaption, Test run, …)Bit 9: Bus monitoring triggeredBit 0 … Bit 7 are saved by the device and can be reset with the KNX group object Reset. As an alternative, they can be read as total fault status.

Sensor value The representation of the sensor value is dependent on the parameterization.See section "KNX parameters – Sensor"

Page 6: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

6 VAV-Compact KNX • en-gb • 2017-08 • Changes reserved www.belimo.eu

KNX parameters – General

System altitude [m] The specification of the system altitude increases the precision of the volumetric flow control.Values range: 0 … 3000 mFactory setting: 500 m

Setpoint with bus fail A setpoint can be defined for cases of communication interruption.Values range: None (last setpoint) Open Closed MidFactory setting: None (last setpoint)The monitoring of the communication takes place for the KNX group objects Setpoint and Override control. If none of the objects is written within the parameterised monitoring time, the bus fail position is set an signalled in the Service information (Bit 9).

Bus monitoring time [min] Monitoring time for the detection of a communication interruption.Values range: 1 … 120 minFactory setting: –

Difference value for sending the actual values [%]

Actual values (position, volumetric flow) are transferred at the time of a value change insofar as these change by the parameterised difference value. If the relative value changes by the difference value, not only the relative actual value but also the absolute actual value are transferred.Values range: 0 … 100%Factory setting: 5%The transfer is deactivated with 0% in the event of a value change.

Repetition time [s] Repetition time for all position, volume and sensor actual values. Status objects are not transferred except with a change.Values range: 0 … 3600 sFactory setting: 0 = no periodic transmission

KNX parameters – Sensor

Sensor type The input Y/3 can be used to connect a sensor. The sensor value is digitised and made available as KNX communication object. Values range: No sensor Active sensor (0 … 32 V) Switching contact (0 / 1) Humidity sensor (0-10 V corresponds to 0 – 100%) Air quality sensor CO2 (0-10 V corresponds to 0 – 2000 ppm)Factory setting: No sensorA switching to Y/3 is treated as local override switching in the absence of sensor parameterization.

Difference value for sending the sensor value The sensor value is transferred at the time of a value change insofar as this changes by the parameterised difference value.Values range: 0 … 65,535Factory setting: 1The transfer is deactivated with 0 in the event of a value change. Without value change, the sensor value is sent because of the repetition time.

Output(for sensor type "Active sensor")

Only for "Active sensor" sensor typeValues range: Sensor value mV (DPT 9.020) Sensor value scaled (DPT 7.xxx) Sensor value scaled % (DPT 5.001)Factory setting: –For "Sensor value mV", the measured voltage is made available without processing. In the case of the scaled sensor values, a linear transformation can be defined with two points.

Polarity(for sensor type "Switching contact")

The polarity can be defined for the sensor type "Switching contact".Values range: Normal InvertedFactory setting: –

Page 7: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 7

Work procedures

Product database The product database for the import in ETS4 or higher is available at the Belimo website www.belimo.eu (Download Centre)

Setting physical address The programming of the physical address takes place by ETS and the programming button on the device. If the programming button is not accessible or accessible only with difficulty, then the address can be set using a point-to-point connection: "Overwrite physical address: 15.15.255"As a third possibility, the physical address can be programmed on the basis of the KNX series number (e.g. with Move’n’Group). The KNX series number is place on the device in two versions. One sticker can be removed for adhesion on the commissioning journal, for example.

Firmware upgrade The KNX firmware of the device is updated automatically with the programming of the application program insofar as the product database has a more recent version. The first programming procedure takes somewhat longer in such cases (>1 min).

Resetting to KNX factory settings If necessary, the device can be reset manually to the KNX factory settings (physical address, group address, KNX parameters).For the reset, the programming button on the device must be pressed down for at least 5 s during start-up.

Connection without sensor

1 2

+

~

T

3 5 6 7

KNX

MFT D –D+

KNX signal assignment:D+ = KNX+ (pink > red)D – = KNX – (grey > black)The connection to the KNX line should take place via WAGO connection terminals 222/221.

Connection with switching contact, e.g. ∆p-monitor Connection of active sensors, e.g. 0...10 V @ 0...50°C

1 2

+

~

T

3 5 6 7

KNX

∆p

MFT D –D+

Switching contact requirements: The switching contact must be able to switch a current of 16 mA at 24V accurately.

1 2

+

~

T

3 5 6 7

KNX

MFT D –D+Possible voltage range:0 ... 32 V (resolution 30 mV)

Local override controlIf no sensor is integrated, then connection 3 (Y) is available for the protective circuit of a local override control.Options: CLOSED – max – OPENNote: Functions only with AC 24V supply!

1 2 3 5

~T

Y

a b c d

KNX

MFT D –D+

6 7a Damper CLOSEDb Maxc Damper OPENd Bus mode

Electrical installation

Page 8: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

8 VAV-Compact KNX • en-gb • 2017-08 • Changes reserved www.belimo.eu

Control functions - VAV / CAV

VAV-operating volumetric flow – Setting and control Open-Loop (separate external VAV-Control)

0%

nom

max

100%

20%

0%

0% 100%

min

<max

KNX reference signal

Ran

ge

min

Ran

ge

max

100%

0%0 100%20 40 60 80 KNX reference signal

Control damper Y

Page 9: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 9

Setting and Tool function

Designation Adjustment values, limits, explanations Units Tools 5) RemarksZTH EU PC-Tool

System specific dataPosition 16 characters e.g.: Office 4 6.OG ZL Text r r/wDesignation 16 Characters: Unit designation, etc. Text r r/wAddress (MP) PP r/w r/w for KNX applications: PPmax 20…100 % [nom] m3/h / l/s / cfm r/w r/w >/= minmid min…max m3/h / l/s / cfm r/w r/wmin 0…100 % [nom] m3/h / l/s / cfm r/w r/w </= maxSystem altitude 0…3000 Meter r/w r/w Adaptation of Δp-Sensor

to system altitude (above sea level) Controller settingsController function Volumetric flow / open loop - r/wMode 0…10 / 2…10 Volt - r/w for KNX applications: 2…10CAV function 2) CLOSED/min/max; Shut-off level

CLOSED 0.1 VCLOSED/min/max; Shut-off level CLOSED 0.5 Vmin/mid/max; (NMV-D2M comp.)

- r/w not relevant for KNX applications

Positioning signal Y Start value: 0.6 … 30; Stop value: 2.6 … 32 Volt r r/w not relevant for KNX applicationsFeedback U Volume / damper position / Δp - r/w Defining feedback signalFeedback U Start value: 0.0 … 8.0; Stop value: 2.0 … 10 Volt - r/wResponse when switched on(Power-On) 4)

No action / Adaption / Synchronisation - r/w

Synchronisation behaviour Y=0 %Y=100 %

- r/w Synchronisation to damper position 0 or 100 %

Bus fail position Last set point / Damper CLOSEDmin / max / Damper OPEN

- r/w

Unit specific settings *) Write function only available for VAV manufacturernom 0 … 60‘000 m3/h m3/h / l/s / cfm r r/(w*) Unit specific adjustment valueΔp@nom 38 … 450 Pa Pa r r/(w*) Unit specific adjustment valueLabel print function - w Incl. customer logoOther settings Direction of rotation (for Y = 100%)

cw/ccw r/w 1) r/w

Range of rotation Adapted 3) / programmed 30 … 95 ° - r/wTorque 100 / 75 / 50 / 25 % r/w % of nominal torqueOperating dataSetpoint / actual valueDamper position

m3/h / l/s / cfmPa / %

r r Trend display with print function and data storage on HD

Simulation Damper CLOSED / OPENmin / mid / max / motor stop

w w

Running times Operating time, running timeRatio

h%

- r

Alarm messages Setting range enlarged, mech. overload, Stop&Go ratio too high

- r/w

Series number Device ID. r r incl. date of manufactureType Type designation r rVersion display Firmware, Config table ID r rConfiguration dataPrint, create PDF - YesSave to file - YesLog data / book Activity log c- Yes incl. complete setting data

Explanations 1) Access only on operating level 22) CAV setting for MP/MF type3) within the mechanical limit.4) The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out an adaption, which is when the operating

range and position feedback adjust themselves to the mechanical setting range. The actuator then moves into the required position in order to ensure the volumetric flow defined by the positioning signal.

5) See www.belimo.eu for function and version history.

Page 10: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

10 VAV-Compact KNX • en-gb • 2017-08 • Changes reserved www.belimo.eu

ZTH / PC-Tool - local service connection The settings and diagnostics of the VAV-Compact can be performed easily and rapidly with the Belimo PC-Tool or with the ZTH-EU service tool. When using the PC-Tool, the ZTH EU serves as an interface converter.

BELIMOPC-Tool

USB

MP

USB � �i esc OK

ZTH EU

RJ12ZK1-GEN

AC 24 VDC 24 V

1 2

+

~

T

3 5 6 7

MFT D –D+

ZTH EU(or ZIP-USB-MP)

Download PC-Tool (MFT-P) from www.belimo.eu

ZTH / PC-Tool - remote connection The VAV-Compact can communicate with the service tools via the PP connection (wire 5). The connection can be made in operating mode in the junction box or the control cabinet terminals. When using the PC-Tool, the ZTH EU serves as an interface converter.

AC 24 VDC 24 V

1 2

+

~

T

3 5 6 7

MFT D –D+

BELIMOPC-Tool

USB

MP

USB � �i esc OK

ZTH EU

RJ11ZK2-GEN

GND

PPwhite = GND green = PP

ZTH EU (or ZIP-USB-MP)

blue, do not connect

Download PC-Tool (MFT-P) from www.belimo.eu

Display and operation

AdaptionPower

Status

3

1

2

4

1 Push-button and LED display greenOff:On:Press button:

No power supply or malfunctionIn operationTriggers angle of rotation adaptation

2 Push-button and LED display yellowOff:On:

Flashing:Press button:

The actuator is readyAdaption or synchronising process activeor actuator in programming mode (KNX)Connection test (KNX) activeIn operation (>1 s): Switch programming mode On and Off (KNX)When starting (>5 s): Reset to factory setting (KNX)

3 Gear disengagement buttonPress button:Release button:

Gear disengaged, motor stops, manual override possibleGear engaged, synchronisation starts, followed by standard mode

4 Service plugFor connecting parameterisation and service tools

Page 11: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

VAV-Compact KNX Volumetric flow compact control device for KNX

www.belimo.eu VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 11

VAV-Compact / VAV-Universal Description

VAV-Compact: version with integrated MP-Bus, LONWORKS® and Modbus interfaceVAV-Universal: VAV pressure controller, ∆p sensors, actuator(spring-return, fast runner, etc.)see www.belimo.eu for more information and documentation

Electrical accessories Description Type

Connection cable 5 m, to ZTH / ZIP-USB-MP (RJ12) with service plug ZK1-GENConnection cable 5 m, to ZTH / ZIP-USB-MP (RJ11) with free wire ends ZK2-GEN

Tools Description Type

Service Tool, for MF/MP/Modbus/LonWorks® actuators and VAV controllers ZTH EUBelimo PC-Tool, software for adjustments and diagnostics MFT-P

Accessories

Dimensions [mm]

Dimensional drawings LMV-D3-KNX Dimensional drawings NMV-D3-KNX

116

61

11622

66

41

12125

80

41

124

62

Further documentation

• Tool connections

Page 12: w.belimouA b.prmubA sns, · PDF file  VAV-Compact KNX • en-gb • 2017-08 • Changes reserved 1 w.belimouA b.prmubA sns,dbpgrimotaV A pressure sensor, digital VAV controller

12 VAV-Compact KNX • en-gb • 2017-08 • Changes reserved www.belimo.eu

VAV-Compact KNX VAV-Compact Model overview / feature comparison

-MF -MP -KNX LON -KNX

Field of application: Supply and exhaust air in the comfort zone and sensor-compatible media

X X X X X

AC/DC 24 V supply X X X X X

Integrated Δp sensor, dynamic D3, measuring range:

–20 … 500 Pa

–20 … 500 Pa

–20 … 500 Pa

–20 … 500 Pa

–20 … 500 Pa

Actuator variants: – Rotary actuator 5 / 10 Nm 5 / 10 / 20 Nm 5 / 10 / 20* Nm 5 / 10 / 20* Nm 5 / 10 / 20* Nm– Linear actuator – 150 / 200 / 300 mm 150* / 200* / 300* mm 150* / 200* / 300* mm 150* / 200* / 300* mm

VAV function min … max X X X X X

CAV stages min / mid / max X X – – –

Open Loop (external V control) X X X X X

DCV (Optimiser function) – DDC MP PartnersBelimo fan optimiser Yes, programmable Yes, programmable Yes, programmable

Analogue control 0/2 ... 10 V 0/2 ... 10 V – – –

With bus control – X X X X

Bus specification – Belimo MP bus KNXS mode

LONWORKS

FTT-10AModbus RTU

RS485

Direct integration DDC MP Partners – X – – –

Integration via Gateway – – – –– BACnet X– KNX X– LONWORKS X– Modbus RTU X

Number of bus devices – 8 per strand 64 per line segment 64 per bus segment 32 per strand

Sensor integration –– passive (resistance) X – – –– active (0…10 V) X X X X– Switching contact X X X X

Optional control function – – – Temperature / CO2 –

Local forced (override) – CLOSED / max / OPEN

CLOSED / max / OPEN

CLOSED / max / OPEN

CLOSED / max / OPEN

Aids – MP-Bus TesterMP Monitor

ETSProduct database – –

Integration tools – PC-Tool ETS LNS Tool + Plug-in …

cTypeList function (Retrofit, OEM) – X (–) (–) (–)

Tool connection (U – PP/MP) PP PP/MP PP PP PP

Service socket ZTH / PC-Tool X X X X X

cNFC interface – X – – –

Assistant App – X – – –

Service tool ZTH EU X X X X X

PC-Tool X X X X X– Parameter– Save data– Trend, Logbook– Label Print

* on request