winding resis doc
TRANSCRIPT
-
8/8/2019 Winding Resis Doc
1/6
THE ART AND SCIENCE OF MEASURING
THE WINDING RESISTANCE OF
POWER TRANSFORMERS
Oleh W.Iw ansiw , P.EngTechnical Consultant - Eltel Industries
This a r t ic le descr ibes many of the
techniques and problems tha t may be
encoun tered wh en m easuring resistance in
the presence of inductance, especially as
app lied to measuring the wind ing resistance
of Power Transformers.
1. RESISTANCE MEASUREMENTS:
Resistance of a cond uctor can be determined
by d ividing the voltage across the condu ctor
by the current flow ing throu gh it. This
technique is employed wh en measuring
many resistance samples including the
windings of transformers to be discusses
here. It shou ld be pointed ou t that such
resistance measurement assumes steady
state cond itions where the current throughthe sample remains steady and so does the
voltage drop across it. This mu st be true
through out the measurement period. Most
professional knowledgeable in the field of
electrical measurements will recognize that
if inductance or capacitance is associated
wi th the res i s tance to be measured, a
t rans i en t wi l l be gene ra t ed on the
app lication of voltage/ current to the test
samp le. Accura t e measur ement s o f
resistance will not be possible in R/ L/ Ccircuits un til the transient is allowed to d ie
down and steady state conditions prevail.
Most electrical engineers w ill recognize that
the windings of most electrical power
equipm ent such as m otors, generators and
transformers have sizeable inductance
assoc ia ted wi th the res i s tance of the
wind ings. When measuring the wind ingsof such equipment, special techniques and
precautions need to be emp loyed if accurate
measurem ents are to result.
2. MEASURING RESISTANCE
ASSOCIATED WITH INDUCTANCE:
Electrical laws and principles tell us that
when induc t ance and re s i s t ance a re
associated in a circuit, a transient will occur
up on the app lication of power and that the
time constant of this transient will be equa lto L/ R seconds, where L is the indu ctance
in Henries and R is the Resistance in Ohm s.
To make measurements in such a circuit, a
t ime constant of several (5 to 9) t ime
constants w ill be required to settle the circuit
be fore meaningfu l measurement s o f
resistance can be undertaken. The number
of time constants required w ill depend on
the accuracy desired . 5 time constan t will
provide an accuracy of 1% and 9 t ime
constants w ill provide an accuracy of 0.1%,approximately.
1
TWRM-10 ATWRM-25
-
8/8/2019 Winding Resis Doc
2/6
transformers, being relatively large, this
transient typ ically controls the time required
to complete a measurement on a del ta
connected transformer.
It shou ld be p ointed out that this transient
will occur regardless of which winding is
tested (primary or secondary) and regardless
of the measuring connection (phase-to-
ph ase-to-neutral). The time constan t of the
transient within the delta is pr opor tional to
the ratio of the inductance to resistance
within the delta circuit. This time constant
increases with the increase in the KVA
rating of the transformer as w ell as with the
efficiency of the transformer.
5. SAFETY CONSIDERATIONS:
Most p rofessional in the electric pow er field
will recognise that there is a danger when
testing inductive equipment using Direct
Current. The dan ger is due to the energy
that is stored in the ind uctance (E=1/ 2I.I.L).
This is the energy that mu st be app lied to
the specimen u pon initiation of the test. The
same energy must be dissipated in a safe
manner upon completion of the test andbefore opening of the current circuit. Shou ld
the current circuit be interrup ted d uring the
test, the store energy will be dissipated in a
High Voltage arc. Such an arc may dam age
the test specimen, the test equipment or
cause injury or death to personnel. The safe
d issipa tion of the energy cannot be stressed
enough. Safe ways of disposing of the stored
energy include, the shorting of the test
specimen (inductance) before d isconnection,
the use of sui table surge or t rans ientprotectors, or by u sing electronic techniques.
Shunt reactors due to their linearity store
more energy than t ransformers and are
therefore more d angerous.
6. DISCUSSION OF PROBLEMS:
6.1 INDUCTA NCE WITH RESISTA NCE
The ind uctance typ ically associated w ith the
measurement of winding resistance of
pow er equipment to be measured causes atransient up on initiation. This transient
The error in resistance measurements und er
un stable or transient cond ition is all due to
the ind uctance which will have a voltage
developed across it equal to V=L.di/ dt,
where L is the inductance in Henries and
di/ dt i t the rate of change of current inamp eres per second . In order to make an
error-free measurement, the inductance
must be eliminated from the circuit or the
current mu st remain p erfectly steady.
3. TRANSFORMERS:
It should be p ointed out that the indu ctive
effects are m ore serious w ith large p ieces of
equipm ent as large pieces of equipm ent will
have a larger L/ R time constant. The above
considerations assumed relatively linear
inductors, such as are associated with
moto rs , genera to rs or reac tors . An
addi t iona l compl ica t ion occurs when
measur ing the winding re s i s t ance of
transformers. The core of the transformer
comprises of a closed m agnetic circuit an d
therefore the winding exhibits a very large
ind u ctance. The core mu st be fully or
partially saturated in order to reduce the
high inductance and allow the current to
flow.
After the current is established one must still
wa it several time constan ts before read ings
can be taken. This time constant depends
on the ratio of the residual inductance of
the winding and the res i s tance of the
measuring circuit.
4. DELTA CONNECTED
TRANSFORMERS:
Del ta connected t ransformers present
spec i a l p rob lems when the i r winding
resistance is to be measu re. This problem is
due to the transient current that will be
established within the delta connection
du ring the initial transient (start-up) period.
As this current is coupled by transformer
ac t ion t o a l l t he windings on the
transformer, it mu st be allowed to d ie down
before accura t e measurement can be
accom pl ished . This t ran s ient i s anadditional complication when testing delta
2
-
8/8/2019 Winding Resis Doc
3/6
6.3 DELTA CONNECTIONS:
Transformers wi th de l ta connected
wind ings encoun ter an ad ditional transient
and causes a delay du e to the L/ R time
constant within the delta circuit. The testperson has li t t le control over this t ime
constant except to t ry and modi fy the
inductance by selecting a higher or lower
tes t curren t . IT MUST NO T be
autom atically assumed that a higher current
will reduce the ind uctance. In fact when
testing the low voltage wind ings of a large
transformer, the inductance of the winding
will increase with an increase in current, the
current in such situations m ust be r educed
or i nc reased pas t t he knee po in t t oeffect ively red u ce the ind u ctance. In
numerous t e s t l abora tor i e s , t he de l t a
connection is opened by m eans of a test link
to fac i l i t a te the winding res i s tance
measurement.
7. PRACTICAL SUGGESTIONS AND
SOLUTIONS:
7. 1 M E A S UR I N G M OT OR S A N D
GENERATORS:
The measurement of motor and generator
winding should present little difficulty to the
test person. Although the ind uctance of
such equipment can be substantial, it can
readily dampened by incorporating resistance
in the test circuit to reduce the time constant
of the start-up transient. Unless currents in
the order of 50 to 200 amperes are used the
energy stored in the circuit is modes and odes
not present a dangerous condition when
terminating the test.
7.2 USING DIGITAL MULTI-METERS OR
OHM-METERS:
A var iety of commercial digital multi-meters
or ohm -meters all using a constan t cur rent
source upto 1 amp will work well when
used on small power t ransformers and
motor/ generators. When the size of the test
spec imen increases and the L/ R ra t io
increases, the constant current sources
within these instruments become unstable
and the i ns t rument read ing becomesun stable. Instrum ents that use passive
may have a time constant of 1 to 100 secs.
A delay of 5 to 10 time constants may be
required before a stable reading is obtained.
This t ime constant may be effect ively
redu ced by suitable test equipment. This testequipm ent wou ld provide additional circuit
resistance, thereby reducing the L/ R ratio
i.e. Time Constant.
6.2 CORE SATURATION:
The measurement of transformer winding
resistance has an additional complication
that of saturating the core to allow the
curren t to flow in the wind ing. The typ ical
time requ ired to saturate the core depend s
on the voltage rating of the transformer
wind ing be ing t es t ed . Thus t he t e s t
equipment must apply vol t seconds
equiva lent to the ra ted vol tage of the
wind ing before any ap preciable cur rent w ill
be established. The volt-second s can be
calculated by integrating the area under on
half cycle of the voltage and dividing this
value by 2. Thus, a wind ing rated at 100KV
at 50 Hz will be rated at approx 450 volt-
second while a 100KV, 60 Hz w inding w ill
have a ra t ing of 375 vol t -seconds ,
app roximately. The 50 Hz wind ing will
need the ap plication of 6 volts for 75 second s
before the cur rent is establ ished . The
satura tion will occur m uch faster if a higher
voltage is app lied. Thus only 15 second s
will be required if a voltage of 30 volts is
applied.
I t must be pointed out tha t the above
calcula t ions assume no res idual f lux
(residual m agnetism) in the core of the test
t ransformer. As the residu al f lux in atransformer may be as high as 75% of the
saturation flux density, the actual time for
the current flow may be 0.25 to 1.7 times
the calculated value.
To reduce the time required to saturate the
core of a high voltage wind ing, a large test
voltage is ind icated. The use of a high test
voltage will autom atically provide a higher
resistance in the test circuit that red uces the
L/ R time constant. At the same time, the
use of a higher voltage increases the VArating and comp lexity of the pow er supp ly.
3
-
8/8/2019 Winding Resis Doc
4/6
circuitry (resistors) for controlling the test
current will work properly on all sizes of
equipment from smallest to the largest.
These passive cur rent sou rces waste a lot
of pow er in resistors wh ich convert vo ltage
to current to stabi les the measurementcircuit.
7.3 KELVIN A ND THOM PSON BRIDGES:
The traditional method of measuring low
resistance values has been the Kelvin or
Thomp son bridges. These bridges continue
to be used to d ate to measure the wind ing
resistance of pow er equipment. When u sed
to measure low resistance values, these
bridges would be equipped with a battery
and an adjustable resistor to provide thebridge with excitation curren t. The exact
value or stabi l i ty of the current is not
important when making measurements on
resistances using a brid ge circuit.
However, when measuring the value of
resistances associated w ith inductance, the
STABILITY of current is of great
importance. If the curren t is not stable, the
opera tor wi l l de termine a f ic t i t ious
resistance. This resistance will be stable overa considerably long period of t ime and
provide the operator w ith a false imp ression
that he has mad e an accurate measurement.
I t i s t he re fore ve ry impor t an t t o use
electronic current stabilizers for the test
current in addition to the usual current
setting resistor.
An e.g. of a typical fictitious resistance
measu remen t is as follows:
Assume a 12V battery source and a 1 ohmcurrent setting resistor that provides a test
curren t of 12 amp eres. The battery voltage
will fall continuously under the load of 12
amperes and for our example we wi l l
assum e a fall of 0.010 volt/ min (this is a
good battery !). This mean s that the test
curren t will also fall by 0.001 amperes/ min .
This type of reduction in test current of
battery voltage would not be noticeable, as
the battery would fall only to 11.400 volts
f rom 12.000 vol t s a f te r one hour of ope ra t i on . This cont inu ous cur ren t
reduction would allow the bridge to be
properly balanced and remain in balance
for a long time. The reading of the bridge,
however, would NOT BE CORRECT and
the error would d epend on the magnitude
of inductance associated with the sample(winding) being m easured.
Assuming that the 11kv winding of a 10
MVA t rans former i s be ing measured
(winding res i s tance 30 mi l l i ohms,
inductance about 5 Henries) the error in
resistance measurement under the above
conditions would be - 0.08 milli ohms or
0.25%. It shou ld be noted that the reading
will ALWAYS be lower under a falling
voltage battery cond ition an d that the errorbecomes larger for a low-loss transformer
(lower resistance and higher inductance)
Calculations:
R*I = 0.030 ohms * 12 amperes = 0.360 volts
L*di/ d t = 5 H enries * 0.0005 a/ s = 0.0025
volts
Error = 0.0025/ 0.36 = 0.0069 or 0.69%
7.4 VOLT-METER AM METER METHOD:
Many find it more convenient to u se a shun t
and two milli voltmeters to measure the
resistance of a wind ing. By using quality
digi ta l vol tmeters , one can make
measur ement s ove r a wid e range of
resistance provided that a suitable current
sour ce and shu nt are available. As this
method is very similar to the Kelvin bridge,
all the advantages, disadvan tages and errors
that w ere discussed in section 7.3 are equally
appl icable here inc luding the fa l se
reading examp les.
7.5 THERM A L EMFs:
As typical measurements discussed here
involve the m easurem ents of DC millivolts,
it is important to take precautions against
the introd uction of therm al EMFs. This
means that ALL connection to be made are
copper-to-copper. Quality instrumen ts for
this application will have copper binding
posts rather than the usual plated brass
term inals. Of extreme imp ortance is the
connection of the leads to the test specimen.
4
-
8/8/2019 Winding Resis Doc
5/6
As these are typically made using clips,
ON E MUST use SOLID COPPER clips. Very
large errors can be introduced by using
copper plated steel clips, especially du ring
heat run s i tua t ions where the bushing
terminals are hot.
7.6 SELECTION OF TEST CURRENT:
The statements by many in the industry is
that the more current you app ly, the faster
the reading will stabiles. Although th is
may be true of many cases, this is NOT true
in all cases. For best resu lts, the test curren t
should be selected according to requirements
of the test specimen. Thus, when m easuring
t ransformer winding res i s tance , i t i s
desirable to use a cur rent that is larger thanthe excitation curren t for that winding . This
will tend to saturate the core and reduce
the settling time for the measurement. The
selected current sh ould be less than 10% of
the ra ted current for tha t winding, as
excessive current will be heating up the
winding and caus ing i t s res i s tance to
increase. A curren t of 10% will cause only
1% of the normal heating of the winding.
Caution shou ld be exercised w hen selecting
the test current as some manufacturers claimthat excessive DC excitation of the core
prod uces un des i rable s t resses . These
stresses are similar to the stresses when a
transformer is energized, saturates, and
draws in-rush current.
Therefore it may be desirable to limit the test
current to 2-4 times the excitation current
for the w inding be ing tes ted. As the
excitation currents for larger transformers
are typically less than 1% of rated, one
should consider test currents in the rangeof 2-4% rated. This range would increase
for med ium and small pow er transformers
which draw a l a rge r pe rcen tage of
excitation current.
7.7 TIME REQUIRED FOR A
MEASUREMENT:
There are some individuals in the indu stry
wh o are asking for a time of only 30 seconds
to obtain a proper reading. Although this
is readily possible for small or even m edium
size transformers, this is very difficult to
obtain for large pow er transform ers. The
cost for equipment for accomplishing this
on large power transformer is rather large
and those who are asking for i t are not
willing to p ay the p rice.
Considering the measurement of winding
resistance after a heat ru n is one of the most
dem and ing app lication. The items that
requ ire time are as follows:
a) Shu tdow n of heat run .
b) Disconnection of heat run leads.
c) Connection of TWRM-10 leads.
d) Satur ation of transform er and
stabilisation of resistance reading .
AN SI C-57 specification allow 4 minu tes of
t ime be tween shut -down and the f i rs t
resistance read ing. This time is reasonable
for medium size transformers bu t becomes
un reasonable for the large transformers
being m anufactured tod ay. The test peop le
are pressed for time so much that they design
and procure high current short ing and
unshort ing equipment for high current
wind ings, as these typically take the longestto connect or d isconnect.
Anyway, allowing half of the allowable time
for tear ing down the connect ions and
connecting the Ohm Meter, the remaining
2 minutes i s typica l ly suff ic ient for
saturating even the largest transformers and
obtaining a reading with a TWRM-5.
The exception to the 2 minute time would
be delta connected transformers. As was
explained in section 6.3 there is a transient
circulating current set up within the delta
and this current m ust be allowed to decay
before accurate resistance readings can be
taken . The time constan t of this circu it
depend s on transformer characteristics and
is relatively ind ependen t of test conditions.
I t i s thi s prec ise reason tha t some
manufacturers of large pow er transformers
are prov iding a delta link wh ich can open
the del ta circui t to avoid the t ransient
condition within the delta for resistance
measurement.
5
-
8/8/2019 Winding Resis Doc
6/6
8. TWRM-10
The Eltel TWRM-10 is a second generation
ins t rument des igned espec ia l ly for
measur ing the winding re s i s t ance of
transform ers, inductors and other electrical
equipm ent. The TWRM-10 uses cur rentelectronic technology to p rovide a regulated
outpu t cur rent of up to 10A in a smaller size
and low er weight than the TWRM-5. The
TWRM-10 provides, many of the features
asked by the users of TWRM-5.
Some of its salient features are :
Test currents o f 10, 1, 0.1, and 0,01 Amperes
Resistance ranges of 1.9999 milli ohms to
1999.9 ohms
Resolution of 0.1 micro ohms
Two measuring inputs
Provides a safe shu t-dow n system
Provides protec t ion aga ins t induct ive
kickback
With the additional resolution, the TWRM-10
is ideal for measuring winding resistance during
heat run in factory tests. Without add itional
weight the TWRM-10 is as portable as its
predecessor the TWRM-5.
8.1 TAP CHANGER APPLICATION:
The des ign fea tures of the TWRM-10
ATWRM-25 mak es the ins t ru men t
especially useful in checking the proper
operation of on-load tap changers on p ower
transform ers. The protection circuit of the
TWRM-10/ ATWRM-25 autom at ica l ly
shuts down the instrument if the circuit is
interrupted even for a few microseconds.
This features is used for checking the proper,
make-before-break, operation of the tap
changer. The following procedu re is used :
a) Connect the wind ing equipp ed with
the on-load tap changer contacts to the
TWRM-10 for m easurem ent.
b) Energise the instrum ent and obtain a
reading.
c) Op erate the tap chan ger over its full
range, up and down, while watching the
indication of the instrument.
d) If the instrum ent continues to operate
after the up-d own cycle of the tap changer,
the tap changer op eration is prop er.
e ) The ins t rumen t wi l l shu t dow n
immediately when a contact of the tap
changer is operated incorrectly i.e. causes a
break-before-make operation.
9. ATWRM-25
The Eltel ATWRM-25 is a high current,
d ig i t a l d i r ec t r ead ing Au tomat ic
Transformer Winding Resistance Meter. It
is designed to m easure the DC resistance of
circuits associated with large Inductances.
It is specifically designed to measure the
resistances of highly inductive transformer
windings very quickly and accurately. The
operat ion of the ins t rument i s micro-
processor controlled and is fully au tomatic.
The ATWRM-25 test set can measure the
wind ing resistance of any transformer- small
or very large, distribution or power, single
or Three Phase , s tar , de l ta or z ig-zag
connected. There are four independent
measuring channels which can be used to
simultaneously measure the DC resistance
of upto four wind ings at the same time.
SCROLL 10-10-2004
OTHER PRODUCTS
G Manual & Automatic
Transformer Ratio Meters.
G Digital Micro Ohm Meters.
with built in 100Amp source.
G Manual & Automatic Transformer Winding
Resistance & On Load Tap Changer Test sets.
G Automatic CT/PT Test sets & Systems
G Automatic & Semi Automatic
HV Capacitance & Tan Delta Test sets,
10 kV Oil Test Cell.
G
Manual & Automatic Tan Delta & ResistivityTest sets for Transformer Oil, Solid Test Cell.
G Portable LV Manual & AutomaticCapacitance
and Tan Delta Test sets.
ELTEL INDUSTRIES311 EMBASSY CENTRE, CRESCENT ROAD,
BANGALORE-560 001, INDIA
TEL : 91-80-22255467, 22205686, 22284253, 22284298
FAX : 91-80-22252733
E-mail: [email protected]
Website: http//www.eltelindustries.com
Works : Plot No. 39, KIADB Industrial Area, Veerapura,
Doddaballapur, Bangalore 561 203, INDIA
TEL : 91-80-7630350, 7630366, 7630367, 7630368 FAX : 91-80-7630351
CHENNAI: 044-24312849/24339075 T KOLKATA: 033-24765536/ 24752394MUMBAI: 022-25383960/25398358 T NEW DELHI: 011-29810252/29815746
(SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE)
6