winding resis doc

Upload: jon-ford

Post on 10-Apr-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Winding Resis Doc

    1/6

    THE ART AND SCIENCE OF MEASURING

    THE WINDING RESISTANCE OF

    POWER TRANSFORMERS

    Oleh W.Iw ansiw , P.EngTechnical Consultant - Eltel Industries

    This a r t ic le descr ibes many of the

    techniques and problems tha t may be

    encoun tered wh en m easuring resistance in

    the presence of inductance, especially as

    app lied to measuring the wind ing resistance

    of Power Transformers.

    1. RESISTANCE MEASUREMENTS:

    Resistance of a cond uctor can be determined

    by d ividing the voltage across the condu ctor

    by the current flow ing throu gh it. This

    technique is employed wh en measuring

    many resistance samples including the

    windings of transformers to be discusses

    here. It shou ld be pointed ou t that such

    resistance measurement assumes steady

    state cond itions where the current throughthe sample remains steady and so does the

    voltage drop across it. This mu st be true

    through out the measurement period. Most

    professional knowledgeable in the field of

    electrical measurements will recognize that

    if inductance or capacitance is associated

    wi th the res i s tance to be measured, a

    t rans i en t wi l l be gene ra t ed on the

    app lication of voltage/ current to the test

    samp le. Accura t e measur ement s o f

    resistance will not be possible in R/ L/ Ccircuits un til the transient is allowed to d ie

    down and steady state conditions prevail.

    Most electrical engineers w ill recognize that

    the windings of most electrical power

    equipm ent such as m otors, generators and

    transformers have sizeable inductance

    assoc ia ted wi th the res i s tance of the

    wind ings. When measuring the wind ingsof such equipment, special techniques and

    precautions need to be emp loyed if accurate

    measurem ents are to result.

    2. MEASURING RESISTANCE

    ASSOCIATED WITH INDUCTANCE:

    Electrical laws and principles tell us that

    when induc t ance and re s i s t ance a re

    associated in a circuit, a transient will occur

    up on the app lication of power and that the

    time constant of this transient will be equa lto L/ R seconds, where L is the indu ctance

    in Henries and R is the Resistance in Ohm s.

    To make measurements in such a circuit, a

    t ime constant of several (5 to 9) t ime

    constants w ill be required to settle the circuit

    be fore meaningfu l measurement s o f

    resistance can be undertaken. The number

    of time constants required w ill depend on

    the accuracy desired . 5 time constan t will

    provide an accuracy of 1% and 9 t ime

    constants w ill provide an accuracy of 0.1%,approximately.

    1

    TWRM-10 ATWRM-25

  • 8/8/2019 Winding Resis Doc

    2/6

    transformers, being relatively large, this

    transient typ ically controls the time required

    to complete a measurement on a del ta

    connected transformer.

    It shou ld be p ointed out that this transient

    will occur regardless of which winding is

    tested (primary or secondary) and regardless

    of the measuring connection (phase-to-

    ph ase-to-neutral). The time constan t of the

    transient within the delta is pr opor tional to

    the ratio of the inductance to resistance

    within the delta circuit. This time constant

    increases with the increase in the KVA

    rating of the transformer as w ell as with the

    efficiency of the transformer.

    5. SAFETY CONSIDERATIONS:

    Most p rofessional in the electric pow er field

    will recognise that there is a danger when

    testing inductive equipment using Direct

    Current. The dan ger is due to the energy

    that is stored in the ind uctance (E=1/ 2I.I.L).

    This is the energy that mu st be app lied to

    the specimen u pon initiation of the test. The

    same energy must be dissipated in a safe

    manner upon completion of the test andbefore opening of the current circuit. Shou ld

    the current circuit be interrup ted d uring the

    test, the store energy will be dissipated in a

    High Voltage arc. Such an arc may dam age

    the test specimen, the test equipment or

    cause injury or death to personnel. The safe

    d issipa tion of the energy cannot be stressed

    enough. Safe ways of disposing of the stored

    energy include, the shorting of the test

    specimen (inductance) before d isconnection,

    the use of sui table surge or t rans ientprotectors, or by u sing electronic techniques.

    Shunt reactors due to their linearity store

    more energy than t ransformers and are

    therefore more d angerous.

    6. DISCUSSION OF PROBLEMS:

    6.1 INDUCTA NCE WITH RESISTA NCE

    The ind uctance typ ically associated w ith the

    measurement of winding resistance of

    pow er equipment to be measured causes atransient up on initiation. This transient

    The error in resistance measurements und er

    un stable or transient cond ition is all due to

    the ind uctance which will have a voltage

    developed across it equal to V=L.di/ dt,

    where L is the inductance in Henries and

    di/ dt i t the rate of change of current inamp eres per second . In order to make an

    error-free measurement, the inductance

    must be eliminated from the circuit or the

    current mu st remain p erfectly steady.

    3. TRANSFORMERS:

    It should be p ointed out that the indu ctive

    effects are m ore serious w ith large p ieces of

    equipm ent as large pieces of equipm ent will

    have a larger L/ R time constant. The above

    considerations assumed relatively linear

    inductors, such as are associated with

    moto rs , genera to rs or reac tors . An

    addi t iona l compl ica t ion occurs when

    measur ing the winding re s i s t ance of

    transformers. The core of the transformer

    comprises of a closed m agnetic circuit an d

    therefore the winding exhibits a very large

    ind u ctance. The core mu st be fully or

    partially saturated in order to reduce the

    high inductance and allow the current to

    flow.

    After the current is established one must still

    wa it several time constan ts before read ings

    can be taken. This time constant depends

    on the ratio of the residual inductance of

    the winding and the res i s tance of the

    measuring circuit.

    4. DELTA CONNECTED

    TRANSFORMERS:

    Del ta connected t ransformers present

    spec i a l p rob lems when the i r winding

    resistance is to be measu re. This problem is

    due to the transient current that will be

    established within the delta connection

    du ring the initial transient (start-up) period.

    As this current is coupled by transformer

    ac t ion t o a l l t he windings on the

    transformer, it mu st be allowed to d ie down

    before accura t e measurement can be

    accom pl ished . This t ran s ient i s anadditional complication when testing delta

    2

  • 8/8/2019 Winding Resis Doc

    3/6

    6.3 DELTA CONNECTIONS:

    Transformers wi th de l ta connected

    wind ings encoun ter an ad ditional transient

    and causes a delay du e to the L/ R time

    constant within the delta circuit. The testperson has li t t le control over this t ime

    constant except to t ry and modi fy the

    inductance by selecting a higher or lower

    tes t curren t . IT MUST NO T be

    autom atically assumed that a higher current

    will reduce the ind uctance. In fact when

    testing the low voltage wind ings of a large

    transformer, the inductance of the winding

    will increase with an increase in current, the

    current in such situations m ust be r educed

    or i nc reased pas t t he knee po in t t oeffect ively red u ce the ind u ctance. In

    numerous t e s t l abora tor i e s , t he de l t a

    connection is opened by m eans of a test link

    to fac i l i t a te the winding res i s tance

    measurement.

    7. PRACTICAL SUGGESTIONS AND

    SOLUTIONS:

    7. 1 M E A S UR I N G M OT OR S A N D

    GENERATORS:

    The measurement of motor and generator

    winding should present little difficulty to the

    test person. Although the ind uctance of

    such equipment can be substantial, it can

    readily dampened by incorporating resistance

    in the test circuit to reduce the time constant

    of the start-up transient. Unless currents in

    the order of 50 to 200 amperes are used the

    energy stored in the circuit is modes and odes

    not present a dangerous condition when

    terminating the test.

    7.2 USING DIGITAL MULTI-METERS OR

    OHM-METERS:

    A var iety of commercial digital multi-meters

    or ohm -meters all using a constan t cur rent

    source upto 1 amp will work well when

    used on small power t ransformers and

    motor/ generators. When the size of the test

    spec imen increases and the L/ R ra t io

    increases, the constant current sources

    within these instruments become unstable

    and the i ns t rument read ing becomesun stable. Instrum ents that use passive

    may have a time constant of 1 to 100 secs.

    A delay of 5 to 10 time constants may be

    required before a stable reading is obtained.

    This t ime constant may be effect ively

    redu ced by suitable test equipment. This testequipm ent wou ld provide additional circuit

    resistance, thereby reducing the L/ R ratio

    i.e. Time Constant.

    6.2 CORE SATURATION:

    The measurement of transformer winding

    resistance has an additional complication

    that of saturating the core to allow the

    curren t to flow in the wind ing. The typ ical

    time requ ired to saturate the core depend s

    on the voltage rating of the transformer

    wind ing be ing t es t ed . Thus t he t e s t

    equipment must apply vol t seconds

    equiva lent to the ra ted vol tage of the

    wind ing before any ap preciable cur rent w ill

    be established. The volt-second s can be

    calculated by integrating the area under on

    half cycle of the voltage and dividing this

    value by 2. Thus, a wind ing rated at 100KV

    at 50 Hz will be rated at approx 450 volt-

    second while a 100KV, 60 Hz w inding w ill

    have a ra t ing of 375 vol t -seconds ,

    app roximately. The 50 Hz wind ing will

    need the ap plication of 6 volts for 75 second s

    before the cur rent is establ ished . The

    satura tion will occur m uch faster if a higher

    voltage is app lied. Thus only 15 second s

    will be required if a voltage of 30 volts is

    applied.

    I t must be pointed out tha t the above

    calcula t ions assume no res idual f lux

    (residual m agnetism) in the core of the test

    t ransformer. As the residu al f lux in atransformer may be as high as 75% of the

    saturation flux density, the actual time for

    the current flow may be 0.25 to 1.7 times

    the calculated value.

    To reduce the time required to saturate the

    core of a high voltage wind ing, a large test

    voltage is ind icated. The use of a high test

    voltage will autom atically provide a higher

    resistance in the test circuit that red uces the

    L/ R time constant. At the same time, the

    use of a higher voltage increases the VArating and comp lexity of the pow er supp ly.

    3

  • 8/8/2019 Winding Resis Doc

    4/6

    circuitry (resistors) for controlling the test

    current will work properly on all sizes of

    equipment from smallest to the largest.

    These passive cur rent sou rces waste a lot

    of pow er in resistors wh ich convert vo ltage

    to current to stabi les the measurementcircuit.

    7.3 KELVIN A ND THOM PSON BRIDGES:

    The traditional method of measuring low

    resistance values has been the Kelvin or

    Thomp son bridges. These bridges continue

    to be used to d ate to measure the wind ing

    resistance of pow er equipment. When u sed

    to measure low resistance values, these

    bridges would be equipped with a battery

    and an adjustable resistor to provide thebridge with excitation curren t. The exact

    value or stabi l i ty of the current is not

    important when making measurements on

    resistances using a brid ge circuit.

    However, when measuring the value of

    resistances associated w ith inductance, the

    STABILITY of current is of great

    importance. If the curren t is not stable, the

    opera tor wi l l de termine a f ic t i t ious

    resistance. This resistance will be stable overa considerably long period of t ime and

    provide the operator w ith a false imp ression

    that he has mad e an accurate measurement.

    I t i s t he re fore ve ry impor t an t t o use

    electronic current stabilizers for the test

    current in addition to the usual current

    setting resistor.

    An e.g. of a typical fictitious resistance

    measu remen t is as follows:

    Assume a 12V battery source and a 1 ohmcurrent setting resistor that provides a test

    curren t of 12 amp eres. The battery voltage

    will fall continuously under the load of 12

    amperes and for our example we wi l l

    assum e a fall of 0.010 volt/ min (this is a

    good battery !). This mean s that the test

    curren t will also fall by 0.001 amperes/ min .

    This type of reduction in test current of

    battery voltage would not be noticeable, as

    the battery would fall only to 11.400 volts

    f rom 12.000 vol t s a f te r one hour of ope ra t i on . This cont inu ous cur ren t

    reduction would allow the bridge to be

    properly balanced and remain in balance

    for a long time. The reading of the bridge,

    however, would NOT BE CORRECT and

    the error would d epend on the magnitude

    of inductance associated with the sample(winding) being m easured.

    Assuming that the 11kv winding of a 10

    MVA t rans former i s be ing measured

    (winding res i s tance 30 mi l l i ohms,

    inductance about 5 Henries) the error in

    resistance measurement under the above

    conditions would be - 0.08 milli ohms or

    0.25%. It shou ld be noted that the reading

    will ALWAYS be lower under a falling

    voltage battery cond ition an d that the errorbecomes larger for a low-loss transformer

    (lower resistance and higher inductance)

    Calculations:

    R*I = 0.030 ohms * 12 amperes = 0.360 volts

    L*di/ d t = 5 H enries * 0.0005 a/ s = 0.0025

    volts

    Error = 0.0025/ 0.36 = 0.0069 or 0.69%

    7.4 VOLT-METER AM METER METHOD:

    Many find it more convenient to u se a shun t

    and two milli voltmeters to measure the

    resistance of a wind ing. By using quality

    digi ta l vol tmeters , one can make

    measur ement s ove r a wid e range of

    resistance provided that a suitable current

    sour ce and shu nt are available. As this

    method is very similar to the Kelvin bridge,

    all the advantages, disadvan tages and errors

    that w ere discussed in section 7.3 are equally

    appl icable here inc luding the fa l se

    reading examp les.

    7.5 THERM A L EMFs:

    As typical measurements discussed here

    involve the m easurem ents of DC millivolts,

    it is important to take precautions against

    the introd uction of therm al EMFs. This

    means that ALL connection to be made are

    copper-to-copper. Quality instrumen ts for

    this application will have copper binding

    posts rather than the usual plated brass

    term inals. Of extreme imp ortance is the

    connection of the leads to the test specimen.

    4

  • 8/8/2019 Winding Resis Doc

    5/6

    As these are typically made using clips,

    ON E MUST use SOLID COPPER clips. Very

    large errors can be introduced by using

    copper plated steel clips, especially du ring

    heat run s i tua t ions where the bushing

    terminals are hot.

    7.6 SELECTION OF TEST CURRENT:

    The statements by many in the industry is

    that the more current you app ly, the faster

    the reading will stabiles. Although th is

    may be true of many cases, this is NOT true

    in all cases. For best resu lts, the test curren t

    should be selected according to requirements

    of the test specimen. Thus, when m easuring

    t ransformer winding res i s tance , i t i s

    desirable to use a cur rent that is larger thanthe excitation curren t for that winding . This

    will tend to saturate the core and reduce

    the settling time for the measurement. The

    selected current sh ould be less than 10% of

    the ra ted current for tha t winding, as

    excessive current will be heating up the

    winding and caus ing i t s res i s tance to

    increase. A curren t of 10% will cause only

    1% of the normal heating of the winding.

    Caution shou ld be exercised w hen selecting

    the test current as some manufacturers claimthat excessive DC excitation of the core

    prod uces un des i rable s t resses . These

    stresses are similar to the stresses when a

    transformer is energized, saturates, and

    draws in-rush current.

    Therefore it may be desirable to limit the test

    current to 2-4 times the excitation current

    for the w inding be ing tes ted. As the

    excitation currents for larger transformers

    are typically less than 1% of rated, one

    should consider test currents in the rangeof 2-4% rated. This range would increase

    for med ium and small pow er transformers

    which draw a l a rge r pe rcen tage of

    excitation current.

    7.7 TIME REQUIRED FOR A

    MEASUREMENT:

    There are some individuals in the indu stry

    wh o are asking for a time of only 30 seconds

    to obtain a proper reading. Although this

    is readily possible for small or even m edium

    size transformers, this is very difficult to

    obtain for large pow er transform ers. The

    cost for equipment for accomplishing this

    on large power transformer is rather large

    and those who are asking for i t are not

    willing to p ay the p rice.

    Considering the measurement of winding

    resistance after a heat ru n is one of the most

    dem and ing app lication. The items that

    requ ire time are as follows:

    a) Shu tdow n of heat run .

    b) Disconnection of heat run leads.

    c) Connection of TWRM-10 leads.

    d) Satur ation of transform er and

    stabilisation of resistance reading .

    AN SI C-57 specification allow 4 minu tes of

    t ime be tween shut -down and the f i rs t

    resistance read ing. This time is reasonable

    for medium size transformers bu t becomes

    un reasonable for the large transformers

    being m anufactured tod ay. The test peop le

    are pressed for time so much that they design

    and procure high current short ing and

    unshort ing equipment for high current

    wind ings, as these typically take the longestto connect or d isconnect.

    Anyway, allowing half of the allowable time

    for tear ing down the connect ions and

    connecting the Ohm Meter, the remaining

    2 minutes i s typica l ly suff ic ient for

    saturating even the largest transformers and

    obtaining a reading with a TWRM-5.

    The exception to the 2 minute time would

    be delta connected transformers. As was

    explained in section 6.3 there is a transient

    circulating current set up within the delta

    and this current m ust be allowed to decay

    before accurate resistance readings can be

    taken . The time constan t of this circu it

    depend s on transformer characteristics and

    is relatively ind ependen t of test conditions.

    I t i s thi s prec ise reason tha t some

    manufacturers of large pow er transformers

    are prov iding a delta link wh ich can open

    the del ta circui t to avoid the t ransient

    condition within the delta for resistance

    measurement.

    5

  • 8/8/2019 Winding Resis Doc

    6/6

    8. TWRM-10

    The Eltel TWRM-10 is a second generation

    ins t rument des igned espec ia l ly for

    measur ing the winding re s i s t ance of

    transform ers, inductors and other electrical

    equipm ent. The TWRM-10 uses cur rentelectronic technology to p rovide a regulated

    outpu t cur rent of up to 10A in a smaller size

    and low er weight than the TWRM-5. The

    TWRM-10 provides, many of the features

    asked by the users of TWRM-5.

    Some of its salient features are :

    Test currents o f 10, 1, 0.1, and 0,01 Amperes

    Resistance ranges of 1.9999 milli ohms to

    1999.9 ohms

    Resolution of 0.1 micro ohms

    Two measuring inputs

    Provides a safe shu t-dow n system

    Provides protec t ion aga ins t induct ive

    kickback

    With the additional resolution, the TWRM-10

    is ideal for measuring winding resistance during

    heat run in factory tests. Without add itional

    weight the TWRM-10 is as portable as its

    predecessor the TWRM-5.

    8.1 TAP CHANGER APPLICATION:

    The des ign fea tures of the TWRM-10

    ATWRM-25 mak es the ins t ru men t

    especially useful in checking the proper

    operation of on-load tap changers on p ower

    transform ers. The protection circuit of the

    TWRM-10/ ATWRM-25 autom at ica l ly

    shuts down the instrument if the circuit is

    interrupted even for a few microseconds.

    This features is used for checking the proper,

    make-before-break, operation of the tap

    changer. The following procedu re is used :

    a) Connect the wind ing equipp ed with

    the on-load tap changer contacts to the

    TWRM-10 for m easurem ent.

    b) Energise the instrum ent and obtain a

    reading.

    c) Op erate the tap chan ger over its full

    range, up and down, while watching the

    indication of the instrument.

    d) If the instrum ent continues to operate

    after the up-d own cycle of the tap changer,

    the tap changer op eration is prop er.

    e ) The ins t rumen t wi l l shu t dow n

    immediately when a contact of the tap

    changer is operated incorrectly i.e. causes a

    break-before-make operation.

    9. ATWRM-25

    The Eltel ATWRM-25 is a high current,

    d ig i t a l d i r ec t r ead ing Au tomat ic

    Transformer Winding Resistance Meter. It

    is designed to m easure the DC resistance of

    circuits associated with large Inductances.

    It is specifically designed to measure the

    resistances of highly inductive transformer

    windings very quickly and accurately. The

    operat ion of the ins t rument i s micro-

    processor controlled and is fully au tomatic.

    The ATWRM-25 test set can measure the

    wind ing resistance of any transformer- small

    or very large, distribution or power, single

    or Three Phase , s tar , de l ta or z ig-zag

    connected. There are four independent

    measuring channels which can be used to

    simultaneously measure the DC resistance

    of upto four wind ings at the same time.

    SCROLL 10-10-2004

    OTHER PRODUCTS

    G Manual & Automatic

    Transformer Ratio Meters.

    G Digital Micro Ohm Meters.

    with built in 100Amp source.

    G Manual & Automatic Transformer Winding

    Resistance & On Load Tap Changer Test sets.

    G Automatic CT/PT Test sets & Systems

    G Automatic & Semi Automatic

    HV Capacitance & Tan Delta Test sets,

    10 kV Oil Test Cell.

    G

    Manual & Automatic Tan Delta & ResistivityTest sets for Transformer Oil, Solid Test Cell.

    G Portable LV Manual & AutomaticCapacitance

    and Tan Delta Test sets.

    ELTEL INDUSTRIES311 EMBASSY CENTRE, CRESCENT ROAD,

    BANGALORE-560 001, INDIA

    TEL : 91-80-22255467, 22205686, 22284253, 22284298

    FAX : 91-80-22252733

    E-mail: [email protected]

    Website: http//www.eltelindustries.com

    Works : Plot No. 39, KIADB Industrial Area, Veerapura,

    Doddaballapur, Bangalore 561 203, INDIA

    TEL : 91-80-7630350, 7630366, 7630367, 7630368 FAX : 91-80-7630351

    CHENNAI: 044-24312849/24339075 T KOLKATA: 033-24765536/ 24752394MUMBAI: 022-25383960/25398358 T NEW DELHI: 011-29810252/29815746

    (SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE)

    6