chapter1 Date 3/17/98, page 1 EUROPEAN FIELDBUS STANDARD EN 50170 P R O C E S S M A N U F A C T U R I N G B U I L D I N G Workshop for PC based Controller

Upload: others

Post on 17-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 1

EUROPEANFIELDBUS STANDARD

EN 50170

P R O

C E S S

M A N U F A C T U R I N G

B U

I L

D I

N G

Workshop forPC based Controller

Page 2: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 2

PROFIBUS

ð Overview chapter 1ü PROFIBUS EN 50170ü PTOü Protocols FMS, DP, PAü wiring

ð DP-details chapter 2ü functionsü configuration toolü data baseü DP-V1 / PA

ð Siemens interface chapter 3

ð OPC chapter 4

Page 3: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 3

PROFIBUS

ð Why select a fieldbus system

ü independent of proprietary solution

ü vendor independent

ü cost savings

ü increase of productivity in terms of

û faster

û more flexible

û easy expandable

û customized

Page 4: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 4

PROFIBUS

ð What a fieldbus system needs to offer

ü deterministic (since parallel wiring will be replaced)

ü flexible

ü interoperable (multi vendor use)

ü cost effective (installation, startup, service)

ü reliable and safe

ü easy to use

ü solution for all your automation needs

ü openness and vendor independent

ð standardization

Page 5: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 5

CNCPC/VME

VME/PCPLC DCS

AreaController

Ethernet/TCP/IP TCP/IP/Ethernet

PROFIBUS-FMS

PROFIBUS-DP PROFIBUS-PA

Factory level

Bus CycleTime

< 1000 ms

Cell Level

Bus CycleTime

< 100 ms

Field Level

Bus Cycle-Time

< 10 ms

Page 6: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 6

EN 50170 Volume 2

Process Automation

PROFIBUS-PAIEC 1158-2

- Powering over the bus - Intrinsic safety

Factory Automation

PROFIBUS-DPRS 485 / FO

- Plug and play- Efficient and cost effective

Fast

General PurposeAutomation

PROFIBUS-FMSRS 485 / FO

- Large variety of applications- Multi-master communication

Universal Application Oriented

Page 7: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 7

PRODUCT variety

ð Today there are more than 1,100 products frommore than 250 different vendors available

or visit the Web - Site:http://www.profibus.com

on disk available from every user group world-wide

Get your free copy of the latest PROFIBUS product guide:

*Status: Q4/1997

Page 8: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 8

PRODUCT varietyDrives

AC Drives

DC Drives

Decentralized I/O

Binary I/O

Analog I/O

Regulators

Timer

Counter

Ident-Systems

Gateways

AS-Interface

Proprietary networks

Tools

Configuration

Bus Monitor

Engineering

Host Interfaces

VAX computers

VME computers

Network components

Repeaters

Fiber optics

Cables

Controllers

PLC/NC/RC

VME, PC

Workstation

Software Drivers

DOS/Windows/NT/95

RT-OS/OS9/VRTX

VxWorks/PSOS+

OS2, QNX

UNIX/VMS

Services

Development Support

Implementation Support

TrainingMMI

Operator Panels

Text DisplaysValves

Pneumatic Valves

Magnetic Valves

Instruments

Level

Flow

Pressure

Temperature

Page 9: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 9

Product profiles

ð PROFIBUS has defined profiles for the easyinterconnectivity of certain product ranges

ü NC/RC Profile (3.052)

ü Encoder Profile (3.062)

ü Variable-Speed Drive Profile (3.071)

ü Operator control and process monitoring profile (HMI)

F PC based controller could offer integrated basicPC based controller could offer integrated basicfunctionsfunctions

Page 10: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 10

EN 50170 - 2

ð The PROFIBUS Protocol is in Accordance with theISO/OSI Reference Model for Open Systems

PA-ProfilesFMS

DeviceProfiles

FMS

IEC 1158-2

User

Laye

r

(3)-(6)

Application(7)

Data Link(2)

Physical(1)

not used

PA

EN 50 170 PROFIBUS guidelines + profiles

DP

DP-Extensions

DP-Profiles

RS-485 / Fiber Optic

* Proposed amendment A2 to EN 50170 Volume 2 under vote until Q1 / 1998

DP Basic Functions

Fieldbus Data Link (FDL) IEC Interface*

Fieldbus MessageSpecification

Page 11: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 11

BUS access

ð The PROFIBUS Bus Access Method combinesMulti-Master and Master-Slave communications

PROFIBUS

Active Stations, Master Devices

Passive Stations(Slave Devices) are polled

PLCPC

Page 12: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 12

Bus access

ð the PROFIBUS Bus Access Protocol (Layer 2) isidentical for all three PROFIBUS variations

ð this enables transparent communication and easycombinations of FMS/DP/PA Network sections

ð Because FMS/DP are using the same PhysicalMedia (RS-485/FO) they can be combined on thesame cable

Active Stations, Master Devices

PROFIBUS

PLCPLC PC

Page 13: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 13

Bus access

ð Hybrid Bus Access Protocol

ü Token-Passing between MastersMaster - Slave Protocol between Master and Slaves

ð Master

ü active stations with the right to control the bus for alimited amount of time (Token - Hold - Time)

ð Slave

ü Slaves only respond on request of a Masterthey have no rights to control the bus

Page 14: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 14

Bus access

ü in Multi Master Networks the Token Passing proceduremust ensure that each master has enough time to fulfill it scommunication tasks

ü the user therefore configures the overall Target TokenRotation Time (TTR) taking into account thecommunication tasks of all masters

ü each Master calculates the available amount of time for it scommunication tasks at token receipt according to thefollowing rule:

TTH = Token Hold TimeTTR = Target Token Rotation TimeTRR = Real Token Rotation Time

TTH = TTR - TRR

Page 15: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 15

FMS, DP, PA

ð FMS stands for Fieldbus Messaging System

ü peer to peer communication

ð DP stands for Decentralized Pheripherie

ü fast data exchange

ð PA stands for Process Automation

ü intrinsically safe environment

Page 16: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 16

FMS/DP in common

FMSDeviceProfiles

IEC Interface*

FMS

User

Laye

r

(3)-(6)

Application(7)

Data Link(2)

Physical(1)

not used

EN 50 170 PROFIBUS guidelines + profiles

DP

DP-Profiles

RS-485 / Fiber Optic

Fieldbus data link (FDL)

DP Basic Functions

Fieldbus MessageSpecification

Page 17: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 17

FMS/DP in common

ð DP and FMS are based on Layer 1 and 2, that is

ü DP and FMS can be operated on the same bus

ü Message header and data length are identical

ü The bus physics are identical

ð One master can service several slaves

ð Several masters can participate on the bus

ð Baudrates from 9.6 kBd up to 12 M B d are possible

Page 18: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 18

FMS/DP in common

ð Data transmission can be between 1 and 244 bytes

ð 126 stations can be connected

ð System can consist of several segments

ð 32 stations (RS 485 drivers) per segment

ð Common components

ü Cabling, connectors, repeater, fibre optic

ð Savings in maintenance and spare parts inventory

Page 19: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 19

PA/DP in common

User

Laye

r

(3)-(6)

Application(7)

Data Link(2)

Physical(1)

EN 50 170 PROFIBUS guidelines + profiles

Specification (FMS)

PA-Profiles

IEC 1158-2

not used

PADP

DP-Extensions

Fieldbus Data Link (FDL)

DP-Profiles

RS-485 / Fiber Optic

FDL

DP Basic Functions

IEC Interface*

Page 20: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 20

PA/DP in common

ð DP and PA are based on the same protocoldefinition - DP/V1 (extended DP)

ü DP and PA can use the same master systems

ü Message header and data length are identical

ü Configuration tools are the same

ü Data transmission can be between 1 and 244 bytes

ü System can consist of several segments

ü 32 stations per segment

Page 21: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 21

PA/DP in common

PROFIBUS-PA

PROFIBUS-DP, up to 12 Mbit/s

PLC or PC with PROFIBUS

DP-Slave

DP/AS-ilink

Actuator/sensor interface

24 VDP/PA coupler,

DP/PA link

PA - 31.25 kBd

Page 22: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 22

FMS features

ð FMS is optimized for universal, object orientedcommunication of intelligent master devices at thecell level

ð FMS permits a subset of the MMS-Functions(Manufacturing Message Specification, ISO 9506)

ð A slave can be assigned to several masters

ü Several masters can write to the same slave

ð Communication connections can be temporary orpermanent

ð Communication is defined in a communicationrelation list

Page 23: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 23

FMS features

ð Main application areas are:

ü Transmission of large amounts of data e.g.programs, data blocks....

ü Integration of several decentralized process partsto one common process

ü Communication between intelligent stations

Page 24: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 24

FMS features

ð FMS access procedure

Slave 1 Slave 2 Slave 3 Slave x

Page 25: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 25

PA features

ð Based on the extended PROFIBUS-DP Protocol andIEC 1158-2 Transmission

ü Suitable to replace today's 4...20 mA Technology

ü Only two wires for data and power

ü Connects Instruments to the control system via a serialbus

ü Functional improvements, reliable serial digitaltransmission

ü Control, regulation and monitoring via a simple twisted paircable

ü A single engineering tool for all devices

Page 26: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 26

PA features

ü Interoperability and interchangeability due to thePROFIBUS-PA Profile

ü Maintenance and diagnosis information from theinstruments available

ü low power management, therefore suitable for EEx-Applications with Intrinsic Safety

ü Distance up to 1900m per segment, expandable up to 10km

ü 10 - 32 stations per segment, up to 125 stations

Page 27: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 27

PA features

Typical System Configuration with PROFIBUS-PA

PROFIBUS-DP RS 485 up to 12 MBit/s

Area Controller (PLC) Engineering or

B&B Tool

PROFIBUS-PA

IEC 1158-2 with 31,25 kBit/sI

ex

Segment-coupler/Link

Transmitter

H2

H1

+ ex

Page 28: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 28

DP features

ð same priority for data exchange

ð DP communication is permanent and cyclic

ð the transmitted data is specified during theconfiguration (optimized data exchange)

ð only one master can write outputs (safety aspect)

ð data can be read by any master

ð acyclic data via DP V1 functions

ð Alarm acknowledgement

ð fastest fieldbus system (up to 12 Mbaud)

ð up to 244 byte input and output data per station

Page 29: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 29

DP features

ð DP- access procedure

Slave 1 Slave 2 Slave 3 Slave x

Master - Token exchange

Page 30: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 30

Combination

CNCPC/VME

AreaController

Ethernet/TCP/IP TCP/IP/Ethernet

PROFIBUS-FMS

PROFIBUS-DP PROFIBUS-PA

one PC card handles the communication

Page 31: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 31

Combination

CNCPC/VME

AreaController

Ethernet/TCP/IP TCP/IP/Ethernet

PROFIBUS-FMS

PROFIBUS-DP PROFIBUS-PA

separate solution

Page 32: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 32

PROFIBUS wiring

ð PROFIBUS DP/FMS wiring can be done with:

ü twisted shielded pair copper cable

ü fiber optic components

ü infrared components

ð detailled installation guideline is availablePTO order no. 2.112

Page 33: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 33

PROFIBUS wiring

ð twisted shielded pair cable

ü line parameters are defined in EN 50170

ü standard cable available from Belden and Siemens

ü standard connectors available

Baudrate Max. Segment length Max. Expansion9.6 1000m / 3278feet 10,000m / 32786feet

19.2 1000m / 3278feet 10,000m / 32786feet93.75 1000m / 3278feet 10,000m / 32786feet187.5 1000m / 3278feet 10,000m / 32786feet500.0 400m / 1311feet 4,000m / 13114feet

1,500.0 200m / 655feet 2,000m / 6557feet3,000.0 100m / 327feet 1,000m / 3270feet6,000.0 100m / 327feet 1,000m / 3270feet

12,000.0 100m / 327feet 1,000m / 3270feetmax. expansion is done with 9 repeaters in a row

Page 34: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 34

PROFIBUS wiring

ð Special requirements for baudrates >1.5 MBaud

ü use of Baudrates greater than 1.5 MBaud requires specialconnectors. The connector or the device has to have builtin Inductors in order to run with higher baudrates (asstated in the PROFIBUS guidelines)

ü spur lines are not allowed when using baud rates greaterthan 1.5 MBaud

ü the maximum length between optical link components is:300m / 981feet

ü in some applications, several bus connectors are used atelectrically short distances, 12 Mbaud installations requirea minimum cable length between two stations of 1m/ 3feet

Page 35: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 35

PROFIBUS wiring

ð Cable shielding

ü use only cables with braided shields.

ü the shield density should be more than 80 %

ü always connect the cable shields at both ends

ü if a potential difference occurs between the groundingpoints, an equalization current can flow through a shieldconnected at both ends. In this case, install an additionalpotential equalization line

Page 36: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 36

PROFIBUS wiring

ð one prefered connector type - 9 pin Sub-D

ü connectors with integrated termination available

ü for use of higher baudrates Inductivity built in

ü easy plug and unplug without interrupting thecommunication to other devices

ü other connector types are possible, mandatory signals(A,B, Gnd, 5V) must be provided as well as a possibility fortermination

Page 37: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 37

PROFIBUS wiring

ð 9 pin sub D

Page 38: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 38

PROFIBUS wiring

ð fiber optic components

ü plastic and glass fiber optic is available

ü optical plugs and modules are available

ü distances up to 20 miles are possible

Cnoise immune

Cpotential difference independent

Clonger distances

Credundant operating is possible

Cline, ring and star configuration

Page 39: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 39

PROFIBUS wiring

ð infrared components

ü wireless linking of devices in close up ranges

ü communication with moving devices

ü communication with changing devices

ü noise immune

ü ground independent

Page 40: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 40

PROFIBUS wiring

ð PROFIBUS FMS / DP are based on RS 485

ü Termination is necessary

ü Expansion of network through segments

ü the two wire cable is usually color coded

!! recommendation:

use always the red wire for signal B (pin3 - TXD/RXD-positiv)

and the green wire for signal A (pin 8 - TXD/RXD-negativ)

ü the shield is connected to housing

Page 41: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 41

PROFIBUS wiring

ð Termination

ü each segment needs to be terminated at both ends

ü termination needs to be powered at all time

ü if possible use one termination at the master

ü power for termination or the termination itself needs to beprovided by the device

390 Ohm

A-Line (3)

B-Line (8)

220 Ohm

390 Ohm

GND(5)

VP(6)

Page 42: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 42

PROFIBUS wiring

ð Segment structure with termination

Repeater or last device

...

Master

Termination “on” (usually whenever only one cable is connectedto a device the termination needs to be “on”)

Page 43: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 43

PROFIBUS wiring

ð Segments are needed by

ü exceeding the length

ü exceeding 32 devices (incl. Repeater/OLM)

ð Segments can be used for

ü building branch segments

ü connecting up to 126 stations (Repeater/ OLM don’t count)

ð Rules

ü one segment has a maximum of 32 devices (incl. Repeater)

ü the first and the last segment can have 31 stations

ü segments between have 30 stations as a maximum

Page 44: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 44

PROFIBUS wiring

ð segment structure with termination

Connectsegments

...

RemoteRepeater

Link Segment(Segment withoutstations)

...Branch segments

...

Interface forfiber optic

Max. Number Repeater Cascading: 9 Termination “on”

Page 45: Workshop for PC based Controller - profibus.co.kr · Workshop for PC based Controller . chapter1 Date 3/17/98, page 2 PROFIBUS ... ü DP-V1 / PA ðSiemens interface chapter 3 ðOPC

chapter1Date 3/17/98, page 45

PROFIBUS wiring

Several interfaces enableredundant systems

Fiber optic segmentsenable redundant wiring

Two devices per measuring point

FOcoupler

FOcoupler

FOcoupler

FOcoupler

System redundancy Media redundancy

ð Redundancy Improves System Reliability