z = v/i does not make a distance relay

21
Z = V/I Does Not Make a Distance Relay J. Roberts, A. Guzman, and E. O. Schweitzer, III Schweitzer Engineering Laboratories, Inc. Presented at the 48th Annual Georgia Tech Protective Relaying Conference Atlanta, Georgia May 4–6, 1994 Previously presented at the 47th Annual Conference for Protective Relay Engineers, March 1994 Originally presented at the 20th Annual Western Protective Relay Conference, October 1993

Upload: phunganh

Post on 31-Dec-2016

265 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Z = V/I Does Not Make a Distance Relay

Z = V/I Does Not Make a Distance Relay

J. Roberts, A. Guzman, and E. O. Schweitzer, III Schweitzer Engineering Laboratories, Inc.

Presented at the 48th Annual Georgia Tech Protective Relaying Conference

Atlanta, Georgia May 4–6, 1994

Previously presented at the 47th Annual Conference for Protective Relay Engineers, March 1994

Originally presented at the 20th Annual Western Protective Relay Conference, October 1993

Page 2: Z = V/I Does Not Make a Distance Relay

z = v II DOES NOT MAKE A DIST ANCE RELA y

INTRODUCTION

Distance relays can provide effective transmission line protection. Their characteristics haveusually been created from comparators and various combinations of voltages and currents.

The mho characteristic, for example, is a popular design because it can be made from a singlecomparator, has well-defined reach, is inherently directional, and can be made to tolerate faultresistance quite well without serious overreaching errors due to load .

Quadrilateral characteristics traditionally require four comparators; e.g., one for each side of

the characteristic.

Because of the variety of fault types possible on a three-phase circuit, distance relays must beavailable to respond to the voltages and currents associated with six different fault loops.

The number of relay elements required for complete schemes is usually quite large. Forexample, a four-zone phase and ground mho distance relay requires 24 comparators.Quadrilateral characteristics require even more.

One approach to making a distance relay with a computer is to calculate the apparentimpedance Z = V 11, and then check if that impedance is inside some geometric shape, like a

circle or box. The hope is that one impedance calculation (per loop) might be useful for all

zones.

Although relays have been made using this approach, their performance suffers under manypractical conditions of load flow and fault resistance.

This paper examines the z = V II approach, and shows the degradations due to load flow andfault resistance. It shows us that calculating Z = V II and testing Z against a circle passing

through the origin is equivalent to a self-polarized mho element --generally a poor performer

for distance protection.

This paper shows some much better methods used in numerical relays, and emphasizes thatthese methods have their roots in better polarization methods.

z = v II AS A DIST ANCE MEASUREMENT

Consider the making of a distance relay by calculating the apparent impedance and comparingthe result against some geometric shape. In this paper, we refer to this approach as theZ = VII method. This method is appealing in that it only requires one impedance calculationper fault loop. Multiple zones (or geometric shapes) only require more geometric tests of theresult. These apparent impedance equations are listed in Table I.

1

Page 3: Z = V/I Does Not Make a Distance Relay

Table I: Z = VII Apparent Impedance Equations

Fault Loop Equations

First look at the AG element performance for an AG fault on the radially configured systemin Figure I. The A<p voltage at Bus S is:

Equation 1v = m.Z .(1 + k O .I \ + R .1tL A R1 F F

where:

v = A<t> voltage measured at Bus S

m = per-unit distance to the fault from Bus S

ZlL = positive-sequence line impedance

IA = A<t> current measured at Bus S

kO = (ZoL -ZlL)/(3.Z1J (ZoL = zero-sequence line impedance)

IR = residual current measured at Bus S

RF = fault resistance

IF = total current flowing through RF

ELcS

0-

21R =2152 OR = 2 os

215 = Z1L .(0,1)Z 05 = 3 ' Z 15PTR = 3500:1CTR = 320'1m = 0,85kV = 400

Z1L =10+j.110!2pri.= 0.91 + j 10.06 Q sec

Z OL = 3. Z 1L

Figure 1: System Single Line Diagram

2

Page 4: Z = V/I Does Not Make a Distance Relay

Convert Equation 1 into an impedance measurement by dividing every term by I, where

I = (IA + kO.IJ. This yields:

Equation 2vZ = -= m.Z1LI

z includes the line impedance to the fault plus RF"(IF/I}" For the radial system, L If = L I

and Z accurately measures the reactance to the fault. Figure 2 shows the resistance andreactance impedance measured by the relay for an AG fault at m = 0.85, with ~ = 4.60

secondary (or 500 primary given PTR/CTR = 3500/320}. Because Rf"(IF/I} is all real,

Im(V/I) = m" I X1L I, regardless the magnitude of RF.

AG Apparent Impedance Method Correctly Measures Reactance to Faultfor a Radial Line

Figure 2:

This suggests that we can define a zone of ground distance protection with two reactance and

resistance thresholds; i.e., the geometric test is a rectangle.

Thus, the first major problem to note is the Z = V II approach is not inherently directional for

ground faults.

3

Convert Equation 1 into an impedance measurement by dividing every term by I, where

I = (IA + kO.IJ, This yields:

Z = ~ = m .Z + R .~ Equation 2I lL F I

Z includes the line impedance to the fault plus RF.(IF/I). For the radial system, L IF = L I

and Z accurately measures the reactance to the fault, Figure 2 shows the resistance andreactance impedance measured by the relay for an AG fault at m = 0.85, with ~ = 4.60

secondary (or 500 primary given PTR/CTR = 3500/320), Because RF.(IF/I) is all real,

Im(V/I) = m. I X1L I, regardless the magnitude of RF,

Jm(+)

RF'(-1fj

E

Re (+ )

Figure 2: AG Apparent Impedance Method Correctly Measures Reactance to Fault

for a Radial Line

This suggests that we can define a zone of ground distance protection with two reactance and

resistance thresholds; i,e., the geometric test is a rectangle.

Figure 3 shows how these threshold checks enclose AG faults up to m = 0.85 with ~ less

than 9.20 secondary .Reactance Threshold 2 and Resistance Threshold 2 define the desiredreactance and resistance reach thresholds respectively. Reactance Threshold 1 and Resistance

Threshold 1 restrict the zone definition to mostly the first quadrant in the impedance plane.Their small negative settings accommodate slight measurement errors near either axis (Im[V /1]or Re[V/I]). These later thresholds must be replaced with a separate directional element to

insure directional security ,

Thus, the first major problem to note is the Z = V /1 approach is not inherently directional for

ground faults.

Page 5: Z = V/I Does Not Make a Distance Relay

(~)Im

RESIST ANCE

THRESHOLD 1RESISTANCE

: r THRESHOLO2

;1

!

I

I

I

r--\-- ,

J

,

, J

!

"

'1

"

'1

"

'1

I

\

10

m=1

~ ~

.~~~~~~-

00 REACTANCE'-- THRESHOLD 2

(8596 .Z1U

",~~,~~~~,~~~~,~,,~,.

:~::::.~..7:..0:J~::::::~:::::::::~::::--:'

u

Q)

If)

~'"-'

w

u

z

<3::1-U

<3::w(1:

N...

~~~~J

::~~::~

:-:7 :::;::]

:::~::~:

...

~

""""""""" " "05 "" """"".""" m -" ."

4..~

i';-;

,',',l' ,

! ~ ~ ~ :

.1::~(v

Ret;:;:;:;:;:;.;.;.

t~~~~~~:~i

~ ~ ~ :[ : [ : [ : ~ ~ ~ : [ : [~ [ ~ ~ :[ : [ : ~ ~ ~: ~ :[ ~ ~ : ~ :j

J

: : : : : : : : : : : : : :: : : : : : : : : : : : : : : : : : : : : : : :j

'J

";r t "J...:.:. :.. J2 j :4 S [) , B gJ 1D

;~ ~. ~~~:~ ~ ~ ~ ~:~. ~~~~:~~~~~~ ~ ~ ~~~~~~~~~~ ~~:~:~ t \

REACTANCE'--

THRESHOLO1RESIST ANCE [.0. sec "

Figure 3:

Load Flow and Fault Resistance Effects on Z

What effect does load flow and RF have on the Z = V II measurement? Consider the faulted

system in Figure 1 again, except now close the switch near Bus R and assume load flowsfrom Bus S to Bus R with O = 30°,

Figure 4a shows the relay at Bus S overreaches in that Im(V II) measures a reactance less than

the line reactance to the fault. This is because IF and I are not in phase {Figure 4b) and RF

appears as a complex impedance.

This overreach becomes more pronounced with increasing RF and 0.

4

Im (+)RESIST ANCE I RESISTANCE

THRESHOLD 1 ~ : : r THRESHOLD 2, :I

m=1 ,I;I

9---[':':':':':':':'. ~:':':':':' :,:,~:,:,:,:,:,:,:,:,:,:':':':':':':':':':':':':':,:,:,:,:,:,:,:,~:,:,r-- ---

i L~"

~ l~""

t""C1C Re (-Y-Jt

RESISTANCE [.0. sec.] '-- REACTANCE

THRESHOLD 1

Figure 3: AG Apparent Impedance Compared to Reactance and ResistanceThresholds (Radial Case)

Load Flow and Fault Resistance Effects on Z

What effect does load flow and RF have on the Z = V II measurement? Consider the faultedsystem in Figure 1 again, except now close the switch near Bus R and assume load flowsfrom Bus S to Bus R with 0 = 30°,

Figure 4a shows the relay at Bus S overreaches in that Im(V II) measures a reactance less thanthe line reactance to the fault. This is because IF and I are not in phase (Figure 4b) and RF

appears as a complex impedance.

This overreach becomes more pronounced with increasing RF and 0,

4

Page 6: Z = V/I Does Not Make a Distance Relay

fu (l"

II

'F.RF

'.R L

b. Voltage and Current Phasorsa Impedance Plane

Figure 4: AG Apparent Impedance Overreach with R.. and Load Flow Out (0 = 300)

Figure 5 illustrates under- and overreaching of the Z = V II approach for different ~ andload flow conditions. The relay reach is set to r.ZlL' where r = 0.85. The Z = VII

approach underreaches for incoming load (IF leads I), and overreaches for load out (IF lags I).

Im(V/I)

20/

m=O.850=.60 .

/

v

(1)In

0:

LJ.Juz<1:f-u<I:LJ.Jcx:

I/

/

~

10 k 6=0.

: 1 5=+30.;:! 5=+60 .

Re(V/I)G6+ -+ LOAD OUT6- -+ LOAD IN

-5-5 0 2010

RESIST ANCE [Q sec.]

5

/

(V~mlT)

IF-R F

,

'.R -.L

Re(+)

a Impedance Plane b. Voltage and Current Phasors

Figure 4: AG Apparent Impedance Overreach with R.. and Load Flow Out (0 = 300)

Figure 5 illustrates under- and overreaching of the Z = V II approach for different ~ andload flow conditions. The relay reach is set to r.ZlL' where r = 0.85. The Z = VII

approach underreaches for incoming load (IF leads I), and overreaches for load out (IF lags I).

Im(V/I)20

m::0,85

v(1)tn

0:LJ.J 10u 0 .z =<1:f-u« -'~ N 8::+60 .

a Re(V/I)

8+ -+ LOAD OUT8- -+ LOAD IN

-5-so 10 20

RESIST ANCE [..\2 sec.]

FAUL T RESIST ANCE LEGEND'

x RF=O..\2 .RF::10..\2 .RF::25..Q ~ RF::50..Q PRI.

Figure 5: AG Apparent Impedance Method Performance Depends on RF and 0

5

Page 7: Z = V/I Does Not Make a Distance Relay

Per-unit AG Apparent Impedance Calculation ~ Illustrates the Amount ofUnder- and Overreach with Fault Resistance and Load Flow

Figure 6:

The overreaching problem can be minimized by restricting the reactive reach. For a zone 1ground distance element, this means reducing the amount of instantaneous protective cover-age. We could also restrict the resistive coverage to avoid the overreach which occurs forline-end faults. However, this penalizes the fault resistance coverage for all fault locations.

IMPROVED QUADRILA TERAL CHARACTERISTIC

There are much better ways to estimate the reactance to the fault, and the fault resistance,than to use R + j.X = VII.

These better methods depend on proper selection of polarizing quantities

Reactance Element

Reference 1 describes one means of obtaining an improved reactance characteristic using thesine-phase comparator. This comparator measures the angle, e, between the operating (Sop)and polarizing (SPOJ signals. The torque of this comparator is defined by Im(Sop.SPOL *);where * indicates the complex conjugate. For 00 ~ e ~ 180°, the characteristic is a

6

To better illustrate the under- and overreaching of this reactance measurement. compareX = Im(Z)lIm(r.Z1J to unity for the same system conditions shown in Figure 5. The resultsare shown in Figure 6 where the ideal X is unity .

5.0m=O.85

w Rf=50.Q PRIMARYu .,z ' .<! ./ ",I-z ! '.u O .1 \<!- 1 ,w 1-'a:<! \1- 5' :\z u \w-J ~ "a: .11: 6 -Rf=25.Q \, CO.J: --.<<! u --'. w

, " CI: t1-<! ,- ' 0=

~ ~ F3!:=.1P-~ ~---~'.,. ~, ,

a: 1.0 ;,;: SET REACHw Rf-O.Q -.""'- :1:

~0. ---:0.:::-.=::-.=-.:-.:-.:-.:-.=::::=. ~~0=

0 ~O

-60 O 60.LOAD IN I LOAD OUT -

Figure 6: Per-unit AG Apparent Impedance Calculation ~ Illustrates the Amount ofUnder- and Overreach with Fault Resistance and Load Flow

The overreaching problem can be minimized by restricting the reactive reach. For a zone 1ground distance element. this means reducing the amount of instantaneous protective cover-age. We could also restrict the resistive coverage to avoid the overreach which occurs forline-end faults. However. this penalizes the fault resistance coverage for all fault locations.

IMPROVED QUADRILA TERAL CHARACTERISTIC

There are much better ways to estimate the reactance to the fault, and the fault resistance,than to use R + j.X = VII.

These better methods depend on proper selection of polarizing quantities.

Reactance Element

Reference 1 describes one means of obtaining an improved reactance characteristic using thesine-phase comparator. This comparator measures the angle, e, between the operating (Sop)and polarizing (SpQJ signals. The torque of this comparator is defined by Im(Sop.SPOL *);where * indicates the complex conjugate. For 00 ~ e ~ 180°, the characteristic is a

6

Page 8: Z = V/I Does Not Make a Distance Relay

The reactance element comparator has the following input signals:

SPOL = IpSop = oV

where:

oV = (r.ZlL.I -V), line-drop compensated voltage

r = per-unit reachZlL = positive-sequence line impedance

I = IA + kO. IRV = A<1> measured voltageIp = polarizing current

Figure 4 shows that the faulted phase current is not always in-phase with the total faultcurrent, IF. Thus, phase current makes a poor choice for the polarizing reference signal,Negative-sequence or residual currents are much better choices.

Equation 3 illustrates why IR is an appropriate polarizing choice. In this equation, the residualcurrent measured at Bus S is expressed in terms of the total fault current, 4. For systemswhere the L Zos = L ZOL = L ZOR (homogeneous systems), the L IR equals the L IF regard-

less of the load condition or fault resistance magnitude.

Equation 3I =R

By selecting Ip = IR, the reactance element measurement is insensitive to load flow condi-

tions. Equation 4 defines the reach of a residual current (IR) polarized reactance element of

reach r for a boundary fault condition.

Equation 4

In Equation 4, r is equal to the reach setting r for a fault on the boundary of a zone. For

faults internal to a zone, r < r .

To show the improved performance of the IR polarized reactance element for different RF and

load flow conditions, compare the per unit reach result of Equation 4 to unity; where per-unitreach, r' = r/r. These results are shown in Figure 7.

From the figure, notice this reactance element does not have the under-and overreachingproblems we saw earlier with the Z = V II method.

7

straight line, and the torque is positive. The angles e = 00 and e = 180° define the

boundary line in the impedance plane.

The reactance element comparator has the following input signals:

SOP = oV SPOL = Ip

where:

oV = (r.ZlL .1 -V), line-drop compensated voltager = per-unit reach

ZlL = positive-sequence line impedanceI = IA + kO.IR

V = A<1> measured voltageIp = polarizing current

Figure 4 shows that the faulted phase current is not always in-phase with the total faultcurrent, IF. Thus, phase current makes a poor choice for the polarizing reference signal.Negative-sequence or residual currents are much better choices.

Equation 3 illustrates why IR is an appropriate polarizing choice. In this equation, the residualcurrent measured at Bus S is expressed in terms of the total fault current, 4. For systemswhere the L Z05 = L ZOL = L ZOR (homogeneous systems), the L IR equals the L IF regard-

less of the load condition or fault resistance magnitude.

[(l-m).Z +Z]I = OL OR. I Equation 3

R Z +Z +Z F05 OL OR

By selecting Ip = IR, the reactance element measurement is insensitive to load flow condi-tions. Equation 4 defines the reach of a residual current (IR) polarized reactance element ofreach r for a boundary fault condition.

Im(V.IR .)! = .Equation 4Im(I.ZlL.IR )

In Equation 4, r is equal to the reach setting r for a fault on the boundary of a zone. Forfaults internal to a zone, r < r .

To show the improved performance of the IR polarized reactance element for different RF andload flow conditions, compare the per unit reach result of Equation 4 to unity; where per-unitreach, r' = rlr. These results are shown in Figure 7.

From the figure, notice this reactance element does not have the under-and overreachingproblems we saw earlier with the Z = V II method.

7

Page 9: Z = V/I Does Not Make a Distance Relay

5.DI I I I I I I I

m=O85U.Juz<1-U<U.J0:OU.JN5:<-J

~

-0:1-z=>

d:U.J0.

~

~

\ SAME LINE FOR Rf:O, 10, 25, AND 50.Q PRIMARY

\

::I:u«wc:c:wOz=>

SET REACH::I:u«w

I I I , I I I c:~ -c:

-60 O 60 w>

-LOAD IN I LOAD OUT --0

1,lI -\1

Per-unit Improved Reactance Reach Calculation (r') Shows IR PolarizationNot Affected by O and Fault Resistance in Homogeneous Systems

Figure 7:

Resistive Elements

The job of a resistive element is to limit the resistive coverage for a quadrilateral zone ofprotection. Some resistive elements measure the line resistance plus RF. Reference 1describes a resistance element which limits its measurement to RF alone. Reference 1 also

shows the derivation of the following equation for RF:

The greatest advantage of this fault resistance element is that its measurement is not appreci-ably affected by load flow conditions. This allows setting the resistive boundary (or thres-hold) greater than the minimum load impedance. The resulting quadrilateral characteristic andits response to different load flow and RF conditions for an AG fault at m = 0.85 is shown in

Figure 8.

8

z

Q1-<1:-'=>u..J<1:u

J:u<1:LU0:

Page 10: Z = V/I Does Not Make a Distance Relay

LUUZ~f-u~LUcr

OLUN

cr:~-'

~

CX

RF CALC

Figure 8: Improved Quadrilateral Characteristic Performance Does Not Depend on O

MHO CHARACTERISTIC

The typical means of obtaining a mho characteristic is to use the cosine-phase comparator .

This comparator measures the phase angle, e, between the operating and polarizing signals.For -90 o ~ e ~ 90 0, the characteristic is circular .The angle e = -90 ° and e = + 90 °

defines the boundary of the characteristic in the impedance plane.

The mho characteristic comparator has two inputs: operating (Sop) and polarizing (SPOL):

Sop = oV SPOL = Vp

where:

oV = (r.ZlL .1 -V), line-drop compensated voltager = per-unit reach

ZlL = positive-sequence line impedanceI = IA + kO.IR

V = A<t> measured voltageVp = polarizing voltage

9

uQ)(/1

9f--I=>(/)LUa:

Z

Qf-<!-I=>U-I~U

Page 11: Z = V/I Does Not Make a Distance Relay

Reference 1 describes the torque expression for this cosine-phase comparator, labeled P, as:

Equation 5p = Re(SOp.SPOL *) = Re[(r.ZlL.I -V).Vp*]

All points where p = O define the boundary of a mho characteristic of reach r.Z1Lo

Self-Polarized Mho Characteristic

Earlier we checked the Z = V II result against a rectangular characteristic. Let's now test Z

against a self-polarized mho characteristic to see how it performs.

For a self-polarized mho characteristic, Vp = V. To determine the boundary characteristic of

this element, set p = 0, substitute V for Vp in Equation 5, and solve for z:

Equation 6Re[(r.ZtL.I -V).V*] = ORe(r.ZtL.I.V*) -I V I 2 = 0

where eL = positive-sequence line angle

ev = angle of V

el = angle of I

Let r.Z1L = I r.Z1L I L eL

I v 12r.ZlL

=Re {1.1 L eL.v*)

I r.Z1L=

and <I> = (ev -el )Next, let Z = I Z I L <1> = VII

Equation 7I Z I = I r.ZlL I .COS(eL- <1»

When I/> = eL, I Z I = I r.Z1L I. Equation 7 describes a mho circle passing through the

origin and r.Z1L on the impedance plane (Figure 9). Equation 7 also shows the self-polarizedmho distance element is equivalent to testing Z = V II against a circular characteristic in the

impedance plane.

10

Page 12: Z = V/I Does Not Make a Distance Relay

~

n(V/IJ

20

Re(V/I)0

.5

Figure 9: Self-polarized Mho Characteristic with Reach r.Z1L

Figure 10 shows the Z = VII AG apparent impedance values tested against the self-polarizedmho characteristic for different load flow and fault resistance conditions. With load flow andfault resistance, this relay has severe underreaching problems and slight overreachingproblems. As compared with the rectangular characteristic, the overreaching problem is

reduced because there is less resistive coverage.

-so 10 20

RESISTANCE [.Q sec.]

FAUL T RESISTANCE LEGEND:

X RF=O.Q .RF=10.Q .RF=25.Q ~ RF=50.Q PRI.

Figure 10: Self-Polarized Mlo Performance Depends on ~ and O

11

~"'

9. 10wuz<1-U<wa:

Page 13: Z = V/I Does Not Make a Distance Relay

Re (v.v.)r =Re (IoZlLoV.)

To determine if the fault is inside or outside the characteristic, compare the r calculationagainst r (same process as for the reactance element). The per-unit self-polarized mhoelement reach result, r', in Figure 11 shows the amount of under- and overreach for variousRF and load flow conditions for the system shown in Figure 1. The source impedance ratio(SIR) for this example equals 0.1 (SIR = Z1S/(r.Z1J).

SO, ~.:~!2-P-~~ARY' , , , m=~8S I

OI~OUJNcr<1:-.J

~u.-'UJU)f-

~ciUJ0..

-,

rRf=25.Q

---,Rf=10.Q ---'---

:--~--~---: : ~~

Rf=O.Q I

:I:u<w

I tSET REACH

~ ~a:w>0

1.

, I I I I I I I 60O 8

-60 -". I LOADOUr -

~ LOAO IN

Per-unit Self-polarized Mho Reach Result Illustrates the Amount of Under-and Overreach (for SIR = 0.1)

Figure 11:

Positive-seouence Memorv Polarized Mho Characteristic

The biggest disadvantage of using V for the polarizing signal is the lack of security for zerovoltage faults. For these faults the polarizing signal has no definite phase angle.

The ideal polarizing signal should be available at all times, and not disappear with the fault.One thing we know is that if the system is energized prior to the fault, the prefault voltage isavailable. We must memorize this prefault voltage and use it for the polarizing signal.

Table 2 compares the self-polarized and phase-voltage memory-polarized cosine-phase-comparator results for an AG fault at m = 0. Notice the eov -evPRE is available (notindeterminate) and less than 90° for all cases. This shows memorized prefault voltage is

excellent polarization.

12

1-..J::.(I)UJcr:r:u«UJcr

Solving Equation 6 for the minimum reach required to just detect a fault, instead of Z, results

in the following expression:

Re (V.V.)r =-Re (I.Z1L.V.)

To determine if the fault is inside or outside the characteristic, compare the r calculationagainst r (same process as for the reactance element). The per-unit self-polarized mhoelement reach result, r', in Figure 11 shows the amount of under- and overreach for variousRF and load flow conditions for the system shown in Figure 1. The source impedance ratio(SIR) for this example equals 0.1 (SIR = ZIS/(r.Z1J).

5.0Rf=5O.Q PRIMARY m=O.BS

/ ~ O .,I ,/ '"~ I '.~ .,O I' .,w I., ,N 1- ,-I ,0= ...1 .,4: ~ ,-.J1n ,~ w ' ,, a: r Rf=25.Q '" :I:

u.I , u-' u <w 4: ---wIn w ---, 0:

t0: ~ a: ~!-=-:~~--- ', ---~

-' ::>c:i: 10 :-:--- SET REACHw -Rf=O.Q -

~a.. :I: u<~

0 ffi>

-60 8 60 o

~ LOAD IN I LOAD OUT -

Figure II: Per-unit Self-polarized Mho Reach Result Illustrates the Amount of Under-and Overreach (for SIR = 0.1)

Positive-seouence MemorY Polarized Mho Characteristic

The biggest disadvantage of using V for the polarizing signal is the lack of security for zerovoltage faults. For these faults the polarizing signal has no definite phase angle.

The ideal polarizing signal should be available at all times, and not disappear with the fault.One thing we know is that if the system is energized prior to the fault, the prefault voltage isavailable. We must memorize this prefault voltage and use it for the polarizing signal.

Table 2 compares the self-polarized and phase-voltage memory-polarized cosine-phase-comparator results for an AG fault at m = 0. Notice the eov -evPRE is available (notindeterminate) and less than 90° for all cases. This shows memorized prefault voltage is

excellent polarization.

12

Page 14: Z = V/I Does Not Make a Distance Relay

Table 2: Memory Polarization is Better than Self-Polarization for Close-in Faults

If we use memorized positive-sequence voltage (Vlmem) for Vp, the polarizing signal is

present even if the memory has expired for all fault types except three-phase faults .Anotherbenefit of V p = V 1 mem is the improved security during open-pole conditions in single-pole

tripping schemes .

To obtain the boundary equation for the positive-sequence memory-polarized mho characteris-tic, set Vp = Vlmem in Equation 5, and solve for the boundary condition. This yields:

Equation 8

Figure 12 shows the per-unit reach calculation (r') for different RF and load flow conditionsfor a SIR = 0.1. Notice there is not much difference between the performance of theV1mem and V polarized mho elements for AG faults at m = 0.85. This is due to the

relatively strong source behind the relay. What happens if we increase the SIR?

13

Page 15: Z = V/I Does Not Make a Distance Relay

5.0 I I I I I I I

Rf=50..Q PRIMARY m=0.85

,OI~OUJt:::!a:~--1O0.

~.->!=z=>

,a:UJ0.

Rf=25.Q.

:

~

----0,0

Rf=10.Q. 0-0'0

, :~;:;~::::::-~~:

Rf=O.Q.

:x:u..wc:c:wOz:) SET REACH

1.0

0 I I I I I I I Il

-60 8 60-LOAD IN I LOAD OUT -

Per-unit V1mem Polarized !\fi1o Reach Result Illustrates the Same Amountof Under- and Overreach as the Self-polarized !\fi1o (for SIR = 0.1)

Figure 12:

Figures 14 and 15 show the amount of underreach for the self- and positive-sequence memorypolarized relays for a AG fault at m = 0.85 on the system in Figure 13 (SIR = 1.2). From

these figures, you can see the V1mem relay performance is better than the self-polarized relaybecause its underreach is much less. This improvement increases with increasing SIR.

7777

z 1R = z 15Z OR = Z OS

z 1L = 2 + j ,22 .Q. pri.= 0.18 + j'2.01.Q. sec.

Z OL = 3 Z 1L

z 15 = Z 1LZ OS = 3 .Z 15PTR = 3500:1CTR = 320:1m = 0.85kV = 400

14

1--J~tnw0:

:I:u~UJ0:

5.0

o Rf=SO.Q PRIMARY m=O.BS

I ~ ,-,

0 -,UJN ,-1- ,a: --I'~ , ~ ,~ tn -,O w I -,-0. a: r Rf=2S.Q '"

~ :I: ' :1:u " u

, <w

.-UJ ---'-- 0: t> a: Rf=10.Q ffio

1- z, ::>:5 1.0 Rf=O.Q :::::::::-: :I: ~ SET REACH

, L>a: <w w0. 0:

0 ffi>-6U 15 60 o

-LOAD IN I LOAD OUT -

Figure 12: Per-unit V1mem Polarized Mlo Reach Result Illustrates the Same Amountof Under- and Overreach as the Self-polarized Mlo (for SIR = 0.1)

Figures 14 and 15 show the amount of underreach for the self- and positive-sequence memorypolarized relays for a AG fault at m = 0.85 on the system in Figure 13 (SIR = 1.2). From

these figures, you can see the V1mem relay performance is better than the self-polarized relaybecause its underreach is much less. This improvement increases with increasing SIR.

EL15 BUSS BUSR ELO

Z1S =Z1L Z1L =2+j-22.Qpri. Z1R =Z1SZOS =3.Z1s =0.18+j-2.01.Qsec. Zo~=ZosPTR =3500:1 ZOL=3Z1LCTR = 320:1m = 0.85kV = 400

Figure 13: System Single Line Diagram (SIR = 1.2)

14

Page 16: Z = V/I Does Not Make a Distance Relay

15.0 III j I I I

Rf=5D.Q PRIMARY m=085

~~QwNii:-t-'

~u:.-'wVJf-'-z=>ci:w0.

,- ,

nf 25 n 1"1= ~ ---

---

~~

1.0

0

Rf=10.Q.

Rf=O.Q.--1--- III I I I

-60 5 60

-LOAD IN I LOAD OUT

Self-Polarized Mlo Underreach Increases Dramatically with Increasing SIR(SIR shown = 1.2)

Figure 14:

r I I I I I I I15.0 m=0.85

~

L:

0wN

a:<I:-'

OQ.

E<11

E

>1-

Z:)

ci:wQ.

Rf=50.Q PRIMARY

,"'.

'.

~

Rf=25.Q. -'-.-

Rf=10.Q. Rf=O.Q

1--- I I I I I I

-60 O 60

04 LOAD IN I LOAD our -

SET REACH

i I>

0

1.0

0

Figure 15:

15

1--'::>tnUJc:

:tu<I:UJc:

10,0

r'

5.0

1-..1::>Inw0:Iu<w0:

10.0

r

5.0

15.DRf=5D.Q PRIMARY ~ m=085

/;/ -.'./ ,

0 ./. :,:I: , / ,.., 10.0 / ,..:. ,0 /w / ,N 1- ,-",! /a: :J r / ,-t (/) .,-' w'/ ,Oa: / ,I:i :I: ,u:. ,-' uw -t(/) ~ 5.01-z Rf=25n => , J:

a: ---uw a. --wt--a:

~f-=-1-0-~ -~1.0 SET REACH

D 5 I

-60 O 60 i ,

~ LOADIN I LOADOUT -~

Figure 14: Selr-Polarized M1o Underreach Increases Dramatically with Increasing SIR

(SIR shown = 1.2)

1S.0

m=0.85

~ 10.0L: Rf=50.Q PRIMARYo

~ 1- .~ a: -' r I.-.<f => -' If) O w a. ~ ." " Eu (j) <f

S 0 c E w ." -a:> 1 z Rf=25.Q -' :I:

:)" u1a: w

w ~a. Rf=10.Q w

§

1.0 SET REACH

Rf=0 :I:~u

-60 6 60 i

..LOAD IN I LOADOUT ---~

Figure 15: V1mem Polarized M1o Underreach is Less than Selr-polarized M1o withIncreasing SIR (SIR shown = 1.2)

15

Page 17: Z = V/I Does Not Make a Distance Relay

In Equation 8, V in the numerator could be zero for close-in faults. Therefore, we cannotrely on the sign of r to dependably indicate direction. Fortunately, the denominator ofEquation 8 defines a directional element. This directional element measures the angle ebetween the operating signal {I.Z1J and the polarizing signal (Vlmem). The angle e = -90°and e = 90 ° defines the zero torque threshold.

Label the denominator term for the AG mho distance element as MAGD. From Equation 8,

MAGD is defined as:

Equation 9MAGD = Re[I°ZlL"(Vlmem)*]

Figure 16 shows the inputs to this denominator for forward (16a) and reverse (16b) AGfaults. For simplicity of illustration, this example assumes O = 00, RF = 0, and a 90°

system angle.

90.

V1

270.

b. Reverse AG Faulta. Forward AG Fault

Figure 16: AG l\D1o Denominator Term Inputs for Forward and Reverse AG Faults

The sign of MAGD is positive for forward faults and negative for reverse faults. Because thesign changes with fault direction, we can use the denominator as a directional element.

CAN SUPERPOSITION IMPROVE THE Z = V II PERFORMANCE?

The z = v II method under- and overreaches for resistive ground faults with load because Iand IF are not in phase. Subtracting balanced prefault current (IAPRE) from the faulted phasecurrent (IJ results in a current (1') which is in phase with the total fault current, IF, assumingbalanced prefault load. This I' current is referred to as the superposition current. Let'sanalyze the approach of substituting I' for the faulted phase current in the AG equation shownin Table 1 and check its performance.

16

THE V1mem POLARIZED MHO DENOMINATOR TERM IS A

DIRECTIONAL ELEMENT

In Equation 8, V in the numerator could be zero for close-in faults. Therefore, we cannotrely on the sign of r to dependably indicate direction. Fortunately, the denominator ofEquation 8 defines a directional element. This directional element measures the angle ebetween the operating signal {I.Z1J and the polarizing signal (V1mem). The angle e = -90°and e = 90 ° defines the zero torque threshold.

Label the denominator term for the AG mho distance element as MAGD. From Equation 8,

MAGD is defined as:

MAGD = Re[l.Z1L .(V1mem)*] Equation 9

Figure 16 shows the inputs to this denominator for forward (16a) and reverse (16b) AGfaults. For simplicity of illustration, this example assumes O = 0°, RF = 0, and a 90°

system angle.

90. 90.

V1 V1mem Z1L .1 mem

Z1L .1

270 .270 .

a. Forward AG Fault b. Reverse AG Fault

Figure 16: AG Mho Denominator Term Inputs for Forward and Reverse AG Faults

The sign of MAGD is positive for forward faults and negative for reverse faults. Because thesign changes with fault direction, we can use the denominator as a directional element.

CAN SUPERPOSITION IMPROVE THE Z = V II PERFORMANCE?

The Z = V II method under- and overreaches for resistive ground faults with load because Iand IF are not in phase. Subtracting balanced prefault current {lAPRE) from the faulted phasecurrent {lJ results in a current {1') which is in phase with the total fault current, IF, assumingbalanced prefault load. This I' current is referred to as the superposition current. Let'sanalyze the approach of substituting I' for the faulted phase current in the AG equation shownin Table 1 and check its performance.

16

Page 18: Z = V/I Does Not Make a Distance Relay

x

Figure 17: Superposition Apparent Impedance Performance Depends on RF and O

Also notice the right-hand resistance threshold must be set almost ten times greater than theline resistance value to just detect an AG fault with zero fault resistance during heavyincoming load flow conditions (0 = -600). While it is desirable to detect these faults, thislarge resistance reach makes the relay susceptible to overreach for lower incoming loadconditions (eg. 0 = -30°) with fault resistance.

These last points, coupled with those noted earlier for the Z = V II calculation results,

emphasizes that an apparent impedance relay is not an acceptable alternative to properly

polarized distance elements.

17

Figure 17 shows the superposition current apparent impedance calculation (Z') results for AGfaults at m = 0.85 and various RF and load flow conditions. This modification of theapparent impedance relay has severe under- and overreaching tendencies. One differencebetween the distance measurement results shown in Figure 17 and those shown in Figure 10,is the load flow conditions which cause under- and overreach are exactly opposite. Thesuperposition apparent impedance relay underreaches for load out, and overreaches forincoming load flow, where the simple apparent impedance relay underreached for incoming

load and overreached for load out.

Im(Z ') ~ "

8=+30"

8=0 "

8=-30 "

Re(Z ')

8=-60 "

FAULT RESISTANCE LEGEND'

X RF=O.Q .RF=10.Q .RF=25.Q ~ RF=50.Q PR(,

Figure 17: Superposition Apparent Impedance Performance Depends on RF and O

Also notice the right-hand resistance threshold must be set almost ten times greater than theline resistance value to just detect an AG fault with zero fault resistance during heavyincoming load flow conditions (0 = -60°). While it is desirable to detect these faults, thislarge resistance reach makes the relay susceptible to overreach for lower incoming loadconditions (eg. 0 = -30°) with fault resistance.

These last points, coupled with those noted earlier for the Z = V II calculation results,

emphasizes that an apparent impedance relay is not an acceptable alternative to properlypolarized distance elements.

17

Page 19: Z = V/I Does Not Make a Distance Relay

One example where Z = VII can be useful is the detection of balanced conditions, such as

load. For example, we can define incoming (ZLOADIN) and outgoing (ZLOADoUT) loadregions with thresholds and check the V II calculation result against these thresholds. Theseregions define the Load-Encroachment Characteristics. If the calculated V II is inside either of

these regions, the load-encroachment logic blocks the phase distance elements from tripping.

A load condition, a three-phase mho (3P21) and relay load-encroachment characteristics areshown in Figure 18. For this heavy load-out condition, the 3P21 element is blocked from

operating because load also resides inside the LOADoUT load-encroachment characteristic.

35

I 3P21 TIME

DELAYED

ZLOAD OUT

ZLOAD IN

52A

I

vIJ)U1

9.WUZ«1-U«Wa:

-35

3535

RESIST ANCE [.Qsec

Z1s=(0.1).Z1L 6=60" ZR = 3. Z1L

z = VII Load-Encroachment Characteristic Prevents Phase Distance

Element from Operating Under Heavy Load ConditionsFigure 18:

SUMMARY

1. The apparent impedance calculation result (Z = V /1) compared with geometric character-

istics (box or circle) presents serious under- and overreaching problems when load flowand fault resistance are combined.

The z = VII method has the same performance deficiencies as self-polarized relays.2.

18

WHEN CAN WE USE V II CHARACTERISTICS?

One example where Z = VII can be useful is the detection of balanced conditions, such asload. For example, we can define incoming (ZLOADIN) and outgoing (ZLOADoUT) loadregions with thresholds and check the V II calculation result against these thresholds. Theseregions define the Load-Encroachment Characteristics. If the calculated VII is inside either ofthese regions, the load-encroachment logic blocks the phase distance elements from tripping.A load condition, a three-phase mho (3P21) and relay load-encroachment characteristics areshown in Figure 18. For this heavy load-out condition, the 3P21 element is blocked fromoperating because load also resides inside the LOADoUT load-encroachment characteristic.

Im(V/I)

35

T 3P21 TIMEDELAYED

u(1)~ ZLOAD OUT

~ LOAD.u~ Re(V/I) ZLOAD IN

1-U

~ L ZLOAD

OUT

! I52A-35 :

-35 35RESISTANCE [.Qsec.]

Z1S=(0.1).Z1L 6=60. ZR=3.Z1L

Figure 18: Z = VII Load-Encroachment Characteristic Prevents Phase DistanceElement from Operating Under Heavy Load Conditions

SUMMARY

1. The apparent impedance calculation result (Z = V II) compared with geometric character-

istics (box or circle) presents serious under- and overreaching problems when load flowand fault resistance are combined.

2. The Z = VII method has the same performance deficiencies as self-polarized relays.

18

Page 20: Z = V/I Does Not Make a Distance Relay

The z = v 1I approach is not improved by using superposition current.3

Writing the torque equation for a properly polarized relay characteristic, setting it equalto zero, and solving for the minimum reach required to just detect the fault yields a resultwhich we can test against scalar thresholds (Reference I). This method achieves the verydesirable result of offering one calculation (per fault loop) for all zones with theperformance of properly polarized relay elements.

4.

We present ground-fault-resistance elements which estimate the fault resistance. Thisestimate rejects the load-influenced positive-sequence current, can be used for multiplezones, and can be set greater than the minimum load impedance.

5

The z = v II calculation can be used to detect load conditions, as in the new load-

encroachment characteristic (Reference I).6.

In conclusion, the Z = V 1I calculations have some use in elements intended to measure load,

but perform poorly compared to properly polarized relay element calculations, as represented

by the equations given for r and RF"

REFERENCES

Edmund 0. Schweitzer III and Jeff Roberts, Distance Element Design, 19th AnnualWestern Protective Relay Conference, October 1992, Spokane, W A, USA.

1.

A. R. Van C. Warrington, Protective Relays: Their Theory and Practice, Chapman andHall, 1969, Volumes I and II. .2.

v. Cook, Analysis of Distance Protection, John Wiley and Sons Inc., 19853.

Paul M. Anderson, Analysis of Faulted Power Systems, The Iowa State University Press,

1983.4.

19

Page 21: Z = V/I Does Not Make a Distance Relay

BIOGRAPHIES

Edmund 0. Schweitzer. III is President of Schweitzer Engineering Laboratories, Inc.,Pullman, Washington, U.S.A., a company that designs and manufactures microprocessor-based protective relays for electric power systems. He is also an Adjunct Professor atWashington State University. He received his BSEE at Purdue University in 1968 and MSEEat Purdue University in 1971. He earned his PhD at Washington State University in 1977.He has authored or co-authored over 30 technical papers. He is a member of Eta Kappa Nu

and Tau Beta Pi.

Jeff B. Roberts received his BSEE from Washington State University in 1985. He worked forPacific Gas and Electric Company as a Relay Protection Engineer for over three years. InNovember, 1988 he joined Schweitzer Engineering Laboratories, Inc. as an ApplicationEngineer. He now serves as Application Engineering Manager. He has delivered papers atthe Western Protective Relay Conference, Texas A&M University, Georgia Tech and theSouthern African Conference on Power System Protection. He holds multiple patents and has

other patents pending.

Armando Guzman received a BSEE degree from University Autonomous of Guadalajara(UAG), Mexico, in 1979. He received a Fiber Optics Engineering Diploma from MonterreyAdvanced Studies Technological Institute (ITESM), Mexico, in 1990. He served as RegionalSupervisor of the Protection Department in the Western Transmission Region of FederalElectricity Commission (the electrical utility company of Mexico) for 13 years. He lecturedat the University Autonomous of Guadalajara in power system protection. Since 1993, he hasbeen with Schweitzer Engineering Laboratories, Inc., where he is currently an ApplicationEngineer. He has authored or co-authored several technical papers.

20

Copyright © SEL 1993, 1994All rights reserved.