ZEROPHASECURRENTTRANSFORMER MODEL INSTRUCTION MANUAL T h e m o d e l w h i c h c a n b e c o m b i n e d w i t h t h i s Z C T E M i t s u b i s h i E l e c t r o n i c M u l t i - M e a s u r i n g I n s t r u m e n t : M E 1 1 0 N S F L E M i t s u b i s h i P r o g r a m m a b l e C o n t r o l l e r M E L S E C - Q E E n e r g y M e a s u r i n g U n i t I n s u l a t i o n M o n i t o r i n g M o d e l : E M U 4 - L G 1 - M B ƒ D o n t u s e t h i s Z C T i n s t a t e c o n n e c t e d b e s i d e s t h e m o d e l @ m e n t i o n e d a b o v e . I n s u l a t i o n M o n i t o r i n g M o d u l e : Q E 8 2 L G Read this manual carefully, and use this instrument properly. Read this manual thoroughly before using the equipment for proper handling. This manual should be retained for the future reference. Be sure that the manual is delivered to the end users. 1 Safety Precautions 1.1 Precautions concerning working environment and conditions Do not use the unit in any of the following places. Doing so may cause malfunctions or a reduction in service life. E Places where the ambient temperature exceeds the working temperature range(-20 to +50 ) Places where the daily average temperature exceeds 35 E Places where the humidity is 85%RH or more or where condensation occurs E Places with a lot of dust, corrosive gas, salt or oily smoke E Places with a lot of vibration or impacts E Places where the unit may be exposed to rain or drops of water, and direct sunlight E Places where the circuit with many harmonics. E Places with strong electromagnetic field or noise E Places where the out of the cabinet. E Place where the altitude exceeds 2000m 1.2 Precautions concerning preparations before using the equipment E Use the unit in the specified usage environment and conditions. E Don’t give this product vibration, a shock at the time of the transportation as much as possible. E Check the current ratings of the equipment. 1.3 Precautions concerning installation and connection For safety, the unit must be installed and connected by experts in electrical work. Danger E Perform installation, disassembly, the wiring work after intercepting a power supply by all means. There might be the damage of an electric shock or the product. Caution <Precautions concerning installation and connection> E Carry out the clamping of the crimp-type terminal lugs by prescribed torque (refer to figure 1). The excessive clamping becomes the ruination of a terminal and the screw. E After tightening, be sure to check that all screws have been tightened. Failure to tighten any screw can cause unit malfunctions, fires, and electric shocks. E Connect the wires carefully, checking the wiring diagram. Incorrect wiring can cause unit failures, fires, and electric shocks. E Use an electric wire of the size of penetrating this ZERO PHASE CURRENT TRANSFORMER (ZCT) for primary side cable, do not use a non-insulation electric wire or a metal for a primary cable E Lay the connection of the second terminal so that vibration / a shock does not depend on the terminal part directly. E Use an electric wire of the size of penetrating this ZCT for a primary side cable, do not use a non-insulation electric wire or a metal for a primary cable E Use the M4 screws crimp type terminals appropriate for for which is suitable for electric wire size (1.2-2.0mm 2 ). The use of the infelicity causes malfunction of the machinery, trouble, a damage by a fire, the fire by outbreak of the poor disconnection and contact. E Read the manual of measuring units which is used with this ZCT , and is used well, and follow it E To avoid the influence of external magnetic fields, the installation shall be at least 45cm away from large current bus bars with serveral 1000A. E Use this ZCT in cabinet certainly. E Arrange an electric wire so that the weight of the electric wire does not depend on ZCT. <To avoid getting shock> E As for the panel, it be assumed that it was given the following matters E It is necessary to attach a key to the cabinet. The structure that a power supply is intercepted automatically is necessary when opening a cabinet. E Degrees of protection (IP code) needs to higher than IP2X level. Caution <Precautions concerning usage> E Dust or rust on the split part can degrade the performance of the ZCT. Wipe the dirt from the surface with soft dry cloth. E Use this ZCT within the rated range stated here. Using the unit out of the rated range may cause not only malfunctions or unit failure, but also fires or burnout. E Do not open the secondary side of the ZCT while the primary current is running. When the secondary side of the ZCT is open, the primary current runs while the secondary current does not, which induces high voltage on the secondary side and increases the temperature. This may cause an insulation breakdown of the secondary winding and results in burnout. 1.4 Precautions concerning maintenance Caution E Protect the unit from a power failure. Failure to do so can cause unit failures, fires, or electric shocks. E Wipe off the surface dirt with tender cloth. Don’t let chemical cloths touch it for a long time, and do not wipe it with benzine or thinner. E Wipe off the separate surface on cores with tender cloth. Don’t use wet cloth. 1.5 Precautions concerning inspection Caution E Perform the care for ZCT at the time of a periodic inspection with the blackout. E When there is the loosen screws in a joint, fasten it again. 1.6 Precautions concerning storage When storing the ZCT, disconnect cables and wires, and put them in vinyl bags or the like. When storing the ZCT for a long time, avoid keeping it in the places shown below. Places where the ambient temperature is out of the range from -30 to +60 i Places where the daily average temperature exceeds 35 Places with a lot of vibration or impacts. Places where the humidity is 90%RH or more or where condensation occurs. Places where the unit is exposed directly to rain, water droplets. Places with a lot of dust, corrosive gas, salt or oily smoke. 1.7 Precautions concerning disposal Dispose this product appropriately in accordance with the national or community rule. mounting bracket can be recycled as iron. 2 Instllation 2.2 Installation points 1) U nscrew the short bar and take off the one side of the short bar. 2) L oosen a joining screw of ZCT in right and left side alternation equality and take off upper core. 3) Put a primary wire through lower core. 4) Install lower core in the setting position and tighten screws with mounting bracket. Please prepare the screws for mounting bracket in the table below. 5) After confirming in dust not sticking to the separate surface on cores, put upper core and lower core together and assembling joining screws. Tighten a joining screw in right and left equality. 6) Tighten up short bar 7) Wiring secondary terminal (k, l). Wiring the test terminals (kt, lt) if necessary. 2.3 Torque Tighten the screw by the following prescribed torque Tightening too much or the lack of unpleasant clamping influences damage and the characteristic of the instrument. Secondary terminal Hole Joining screws Test terminals Short bar 2.1 The name of each part Upper core Lower core Mounting bracket Quantity CZ-22S 0.54 0.66 CZ-30S 0.59 0.72 CZ-55S M5 0.95 1.16 CZ-77S 2 CZ-112S 4 M4 1.32 1.62 Joining screws M6 M6 M4 0.98 1.35 Secondary Terminals Test terminals Short bar M5 Screws for mounting bracket 2 2.4 Instructions for use ZCT is a highly precise magnetic material. Don’t give a shock. Dust or rust on the split part can degrade the performance of the ZCT. Wipe the dirt from the surface with soft dry cloth. 2.5 Instructions for wiring Refer to the wiring diagram of the instruction manual of the measurement units combine with the ZCT. The electric wire diameter which go through hole is as follows. The official cross section of wire IV:Indoor PVC CV:Cross linked polyethylene PVC Because there is the case that I cannot penetrate by a finish external form, the transformation (curves) of the electric wire, Confirm dimensions. About the connection of the polarity (K, L) of ZCT, confirmit by the wiring diagramof the instruction manual of the measurement units put it together, and to use; Test terminals ( kt, lt ) are terminals for movement test with the measurement units. It is convenience at the time of the maintenance check, if it draws wiring to the surface of the cabinet with a terminal symbol. Do not be made to short - circuit at test terminals, the grounding is unnecessary, too. (ZCTcannot detect a leakage current definitely when it is grounding.) The biggest electric wire diameter and the tolerance current CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S P h a s e s y s t e m w i r e s C a b l e 22115) 60217) 250556) 500842) 22130) 38190) 200545) 500920) 10001465) 22115) 38162) 200496) 500842) 14100) 22135) 150455) 325760) 8001285) 1488) 38162) 150395) 325650) 872) 22130) 150455) 325725) 6001005) 4 The official cross section of wire [ 2 ] Current tolerance[A] 2 T h r e e p h a s e 4 w i r e S i n g l e p h a s e 2 w i r e S i n g l e p h a s e 3 w i r e T h r e e p h a s e 4 w i r e 3 Instructions for penetrating wiring through ZCT 1. In the case of single-phase 3 wire system or three phase 3 wire system, let wiring including neutral wire by all means be through ZCT hole. 2. Do not let penetrate the grounding wire when there is a grounding dedicated line in the electric circuit, go through ZCT hole. Do not let penetrate the electric wire which is not aimed at to turn on a load electric current, through ZCT hole. 3. Because it may give ZCT mechanical stress when a severe electric current flows by short circuit accidents, the electric wire penetrating ZCT bundles it up and tie it up by bands. 4. Do not bend an electric wire penetrating ZCT in a closely of ZCT. When it let ZCT penetrate primary wiring over 300A, keep wiring straight in line more than one side 30cm. 5. The secondary wiring of ZCT do not be grounding. Neutral wire through the ZCT Model CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S Hole dimensionsi o j 22 30 55 77 112 Rating primary current 50A AC 100A AC 300A AC 600A AC 1000A AC Maximum voltage 600V AC Frequency 50- 60Hz Rated short timecurrent 50kA 100kA Measurement ( installation) category CAT Pollution degree CE marking conformity standard EN61010-2-032 CE marking conformity combination unit This ZCT conform to CE marking standard in a condition use with EMU4-LG1-MB( Energy Measuring Unit Insulation Monitoring Model) Mass 0.5kg 0.6kg 1.8kg 2.8kg 6.0kg 3 Specification <Usage as the CE marking conformity article> Caution As for the Maximum voltage 600V AC, measurement category , pollution degree . Install the ZCT to the secondary of the circuit breaker. Install the current sensor in the cabinet Use the PVC insulation electric wire ( less than heat-resistant temperature 70 .) 4 Dimensions 5. Customer Service Dimensions CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S A 22 30 55 77 112 B 27 27 32 41 57 C 100 114 148 198 234 D 112 130 160 210 246 E 128 144 177 232 268 F 5 5 7 10 8 G 30 30 36 45 62 H 12 12 12 12 12 J 41 47 66 90 109 K 77 89 124 171 207 When exported from Japan, this manual dose noto require application to the Ministry of Economy, Trade and Industry for service transaction permission. Specifications subject to change without notice. Except CZ-112S For CZ-112S CZ-22S, CZ-30S, CZ-55S, CZ-77S, CZ-112S k t l t k l Model Size Size Size Torque[N¥ m] Torque[N¥ m] b f e g a c d k t l t k l j i [ m m ] b 3 0 f e g a c d 3 0 p Please refer to "catalog" for more detail. HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, Japan This ZCT conform to CE marking standard in a condition use with QE82LG ( Mitsubishi MELSEC-Q series programmable controllers Insulation Monitoring Module)

Upload: tranque

Post on 11-Jun-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ZERO PHASE CURRENT TRANSFORMER … PHASE CURRENT TRANSFORMER MODEL INSTRUCTION MANUAL <The model which can be combined with this ZCT> ・ Mi ts ubh El ec ro n- a gI m : 10NSFL

ZERO PHASE CURRENT TRANSFORMER

MODEL

INSTRUCTION MANUAL

<The model which can be combined with this ZCT>

・Mitsubishi Electronic Multi-Measuring Instrument:ME110NSFL

・Mitsubishi Programmable Controller MELSEC-Q

・Energy Measuring Unit

Insulation Monitoring Model:EMU4-LG1-MB

※Don't use this ZCT in state connected besides the model

 mentioned above.

Insulation Monitoring Module:QE82LG

Read this manual carefully, and use this instrument properly.Read this manual thoroughly before using the equipment for proper handling.This manual should be retained for the future reference.Be sure that the manual is delivered to the end users.1.Safety Precautions

1.1 Precautions concerning working environment and conditionsDo not use the unit in any of the following places. Doing so may cause malfunctions or a reduction in service life.

・Places where the ambient temperature exceeds the working temperature range(-20℃ to +50℃)Places where the daily average temperature exceeds 35℃

・Places where the humidity is 85%RH or more or where condensation occurs ・Places with a lot of dust, corrosive gas, salt or oily smoke・Places with a lot of vibration or impacts

・Places where the unit may be exposed to rain or drops of water, and direct sunlight・Places where the circuit with many harmonics.・Places with strong electromagnetic field or noise・Places where the out of the cabinet.・Place where the altitude exceeds 2000m

1.2 Precautions concerning preparations before using the equipment・Use the unit in the specified usage environment and conditions. ・Don’t give this product vibration, a shock at the time of the transportation as much as possible.・Check the current ratings of the equipment.

1.3 Precautions concerning installation and connectionFor safety, the unit must be installed and connected by experts in electrical work.

Danger ・Perform installation, disassembly, the wiring work after intercepting a power supply by all means. There might be the damage of an electric shock or the product.

Caution

<Precautions concerning installation and connection>・Carry out the clamping of the crimp-type terminal lugs by prescribed torque (refer to figure 1). The excessive clamping becomes the ruination of a terminal and the screw.・After tightening, be sure to check that all screws have been tightened. Failure to tighten any screw can cause unit malfunctions, fires, and electric shocks.・Connect the wires carefully, checking the wiring diagram. Incorrect wiring can cause unit failures, fires, and electric shocks.・Use an electric wire of the size of penetrating this ZERO PHASE CURRENT TRANSFORMER (ZCT) for primary side cable, do not use a non-insulation electric wire or a

metal for a primary cable・Lay the connection of the second terminal so that vibration / a shock does not depend on the terminal part directly.・Use an electric wire of the size of penetrating this ZCT for a primary side cable, do not use a non-insulation electric wire or a metal for a primary cable・Use the M4 screws crimp type terminals appropriate for for which is suitable for electric wire size (1.2-2.0mm2). The use of the infelicity causes malfunction of the machinery,

trouble, a damage by a fire, the fire by outbreak of the poor disconnection and contact.

・Read the manual of measuring units which is used with this ZCT , and is used well, and follow it・To avoid the influence of external magnetic fields, the installation shall be at least 45cm away from large current bus bars with serveral 1000A.

・Use this ZCT in cabinet certainly.・Arrange an electric wire so that the weight of the electric wire does not depend on ZCT.

<To avoid getting shock>・As for the panel, it be assumed that it was given the following matters・It is necessary to attach a key to the cabinet.・The structure that a power supply is intercepted automatically is necessary when opening a cabinet.・Degrees of protection (IP code) needs to higher than IP2X level.

Caution

<Precautions concerning usage>・Dust or rust on the split part can degrade the performance of the ZCT. Wipe the dirt from the surface with soft dry cloth.・Use this ZCT within the rated range stated here. Using the unit out of the rated range may cause not only malfunctions or unit failure, but also fires or burnout.・Do not open the secondary side of the ZCT while the primary current is running. When the secondary side of the ZCT is open, the primary current runs while the secondary

current does not, which induces high voltage on the secondary side and increases the temperature. This may cause an insulation breakdown of the secondary winding andresults in burnout.

1.4 Precautions concerning maintenance

Caution ・Protect the unit from a power failure. Failure to do so can cause unit failures, fires, or electric shocks.・Wipe off the surface dirt with tender cloth. Don’t let chemical cloths touch it for a long time, and do not wipe it with benzine or thinner.・Wipe off the separate surface on cores with tender cloth. Don’t use wet cloth.

1.5 Precautions concerning inspection

Caution ・Perform the care for ZCT at the time of a periodic inspection with the blackout.・When there is the loosen screws in a joint, fasten it again.

1.6 Precautions concerning storageWhen storing the ZCT, disconnect cables and wires, and put them in vinyl bags or the like.When storing the ZCT for a long time, avoid keeping it in the places shown below. ・Places where the ambient temperature is out of the range from -30℃ to +60℃ (Places where the daily average temperature exceeds 35℃)

・Places with a lot of vibration or impacts.

・Places where the humidity is 90%RH or more or where condensation occurs. ・Places where the unit is exposed directly to rain, water droplets.・Places with a lot of dust, corrosive gas, salt or oily smoke.

1.7 Precautions concerning disposalDispose this product appropriately in accordance with the national or community rule. mounting bracket can be recycled as iron.

2.Instllation2.2 Installation points1) Unscrew the short bar and take off the one side of the short bar.2) Loosen a joining screw of ZCT in right and left side alternation equality and take off upper core.3) Put a primary wire through lower core.4) Install lower core in the setting position and tighten screws with mounting bracket.

Please prepare the screws for mounting bracket in the table below.5) After confirming in dust not sticking to the separate surface on cores, put upper core and lower core

together and assembling joining screws. Tighten a joining screw in right and left equality.6) Tighten up short bar 7) Wiring secondary terminal (k, l). Wiring the test terminals (kt, lt) if necessary. 2.3 Torque・Tighten the screw by the following prescribed torque Tightening too much or the lack of unpleasantclamping influences damage and the characteristic of the instrument.

Secondary�terminal

HoleJoining screws

Test terminals

Short bar

2.1 The name of each part

Upper core

Lower core

Mountingbracket

QuantityCZ-22S 0.54~0.66CZ-30S 0.59~0.72CZ-55S M5 0.95~1.16CZ-77S 2

CZ-112S 4

M4

1.32~1.62

Joining screws

M6 M6

M4 0.98~1.35

Secondary Terminals�Test terminals�

Short bar

M5

Screws for�mounting bracket

2

2.4 Instructions for use・ZCT is a highly precise magnetic material. Don’t give a shock.・Dust or rust on the split part can degrade the performance of the ZCT. Wipe the dirt from the surface with soft dry cloth.

2.5 Instructions for wiring・Refer to the wiring diagram of the instruction manual of the measurement units combine with the ZCT.・The electric wire diameter which go through hole is as follows.(The official cross section of wire IV:Indoor PVC,CV:Cross linked polyethylene PVC) Because there is the case that I cannot penetrate by a finish external form, the transformation (curves) of the electric wire, Confirm dimensions.

・About the connection of the polarity (K, L) of ZCT, confirm it by the wiring diagram of the instruction manual of the measurement units put it together, and to use;

・Test terminals ( kt, lt ) are terminals for movement test with the measurement units. It is convenience at the time of the maintenance check, if it draws wiring to the surface of the cabinet with a terminal

symbol.

・Do not be made to short-circuit at test terminals, the grounding is unnecessary, too. (ZCT cannot detect a leakage current definitely when it is grounding.)

The biggest electric wire diameter and the tolerance current

CZ-22S CZ-30S CZ-55S CZ-77S CZ-112SPhase system wires Cable

I V 22(115) 60(217) 250(556) 500(842) -

CV 22(130) 38(190) 200(545) 500(920) 1000(1465)

I V 22(115) 38(162) 200(496) 500(842) -

CV 14(100) 22(135) 150(455) 325(760) 800(1285)

I V 14(88) 38(162) 150(395) 325(650) -

CV 8(72) 22(130) 150(455) 325(725) 600(1005)4

The official cross section of wire [㎜2] (Current tolerance[A])

2

Three phase 4 wire

Single phase 2 wire

Single phase 3 wireThree phase 4 wire

3

●Instructions for penetrating wiring through ZCT1. In the case of single-phase 3 wire system or three phase 3

wire system, let wiring including neutral wire by all means be through ZCT hole.

2. Do not let penetrate the grounding wire when there is agrounding dedicated line in the electric circuit, go throughZCT hole. (Do not let penetrate the electric wire which isnot aimed at to turn on a load electric current, through ZCThole.)

3. Because it may give ZCT mechanical stress when a severeelectric current flows by short circuit accidents, the electricwire penetrating ZCT bundles it up and tie it up by bands.

4. Do not bend an electric wire penetrating ZCT in a closely of ZCT.When it let ZCT penetrate primary wiring over 300A, keep wiring straight in line more than one side 30cm.

5. The secondary wiring of ZCT do not be grounding.

Neutral wire through the ZCT

Model CZ-22S CZ-30S CZ-55S CZ-77S CZ-112SHole dimensions(㎜) φ22 φ30 φ55 φ77 φ112

Rating primary current 50A AC~ 100A AC~ 300A AC~ 600A AC~ 1000A AC~

Maximum voltage 600V AC~

Frequency 50-60Hz Rated short timecurrent 50kA(100kA)

Measurement (installation) category CATⅢ

Pollution degree Ⅱ

CE marking conformity standard EN61010-2-032

CE marking conformity combination unit This ZCT conform to CE marking standard in a condition use with EMU4-LG1-MB(Energy Measuring Unit Insulation Monitoring�Model)

Mass 0.5kg 0.6kg 1.8kg 2.8kg 6.0kg

3.Specification

<Usage as the CE marking conformity article>

Caution・As for the Maximum voltage 600V AC, measurement category Ⅲ,pollution degree Ⅱ.

・Install the ZCT to the secondary of the circuit breaker.

・Install the current sensor in the cabinet・Use the PVC insulation electric wire (less than heat-resistant temperature 70℃.)

4.Dimensions 5. Customer Service

DimensionsCZ-22S CZ-30S CZ-55S CZ-77S CZ-112S

A φ22 φ30 φ55 φ77 φ112B 27 27 32 41 57C 100 114 148 198 234D 112 130 160 210 246E 128 144 177 232 268F 5 5 7 10 8G 30 30 36 45 62H 12 12 12 12 12J 41 47 66 90 109K 77 89 124 171 207

When exported from Japan, this manual dose noto requireapplication to the Ministry of Economy, Trade and Industryfor service transaction permission.Specifications subject to change without notice.

Except CZ-112S For CZ-112S

CZ-22S, CZ-30S, CZ-55S, CZ-77S, CZ-112S

kt lt

k

l

Model Size Size SizeTorque[N・m] Torque[N・m]

GF

kt lt

k

lK

[mm]

30 GF

30㎝

Please refer to "catalog" for more detail.HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, Japan

This ZCT conform to CE marking standard in a condition use with QE82LG (Mitsubishi MELSEC-Q series programmable �controllers Insulation Monitoring Module)