SPECIFICATIONS

Voltage 230 / 110 VAC (+10% / -15%)

Frequency 50 / 60 Hz (±5%)

Operating Temperature -5°C to +40 °C

Current Nom. 0.6 / 1.3 A, Max. 1.5 / 3.15 A

Fuse rating 2 / 4 A

Cable type 3 x 1.5 mm² (live, neutral, earth)

Outputs

General Fire + Fault supervised 2, 350mA / 19.5-28VDC (24 VDC nominal)General Fire + Fault relay 2Aux 1 resetable, 500mA / 19.5-28VDC (24VDC nominal)

Cable type Recommended 2 core 1.5 mm² twisted pair

End of Line resistor 15kohm

Maximum Load 150 mA

Colour RAL7035

Cable entries

(Top / Bottom / Back)

Small cabinet - 9 (20mm) / 2 (20mm) / 2 removable platesLarge cabinet - 18 (20mm) / 2 (20mm) / 2 removable plates

Batteries Max. 2 x 12V/7.2Ah (use supplied cables)

Storage temperature -10°C to +50 °C

Humidity Range Max. 95 % (non-condencing)

IP Rating IP30

Weight Small cabinet - 5.2 Kg (without batteries) Large cabinet - 7.4 Kg (without batteries)

ZitonAnalogue addressable systemsZiton is one of the world’s leading brands in the manufacturing of fi re alarm equipment, and at Channel are proud to be specialist distributors of the analogue fi re device ranges.

The ZP2 Series life safety control systems are bringing the speed and functionality of high-end intelligent processing to small to mid-sizedaddressable applications.

Features

• Eight programmable supervised outputs that can be dedicated to sounder control and fi re routing

• Intuitive front panel control with centrally-located Jog Dial• Ethernet port with TCP/IP connectivity for programming and

maintenance• Up to 127 devices may be connected to each ZP address loop.• EN54 compliant graphical LCD with icons and up to 256 zones• Up to 40 LED Zone indicators for Fire and Fault with ample text space• Easy-to-remove panel doors and electronics• Operating platform certifi ed for life safety system applications• Full line of addressable and conventional accessories• History log memory for 9999 events• Up to 72 hours standby time and 30 minutes alarm• Comes standard fi tted with network board• Local or global repeater with or without global control functionality• Auto confi guration, setup wizards and default EN54 setup modes• Jog Dial with 4 soft buttons for simple and intuitive user control• Aesthetic pleasing design with special paint able synthetic door• All plug-able connectors• 3 USB ports with memory stick support and RS232 for printer support• Email notifi cation for events directly from the panel (4 user accounts)• Auxiliary 24V DC supply output with reset support• 3 operator level menu structure (20 user names and passwords)

Approvals & Compliance

• CE / CPD / EN54-2 / EN54-4• NEN2535 / NBNS21-100 compliant• BS5839-1 compliant• VdS and LPCB certifi ed• WEEE / RoHS compliant

PRODUCT CODE DESCRIPTION

F/CH/ZP2-F1-S-99 ZP2 1 loop fi re panel - small cabinet (no zone LEDs) F/CH/ZP2-F2-S-99 ZP2 2 loop fi re panel - small cabinet (no zone LEDs) F/CH/ZP2-FR-S-99 ZP2 repeater panel - small cabinet (no zone LEDs) F/CH/ZP2-F1-99 ZP2 1 loop fi re panel - large cabinet (no zone LEDs) F/CH/ZP2-F2-99 ZP2 2 loop fi re panel - large cabinet (no zone LEDs) F/CH/ZP2-FR-99 ZP2 repeater panel - large cabinet (no zone LEDs) F/CH/ZP2-ZI-24-S 24 zone LEDs - small cabinet onlyF/CH/ZP2-ZI-20 20 zone LEDs - large cabinet onlyF/CH/ZP2-ZI-40 40 zone LEDs - large cabinet only

F/CH/ZP2-LB2 loop expansion PCB (can only be fi tted to a 2 zone panel only)

F/CH/2010-2-NB Network card for ZP2 panel (not required in repeaters)

Small Cabinet Panels

• Height 298mm• Width 410mm• Depth 162mm

Large Cabinet Panel

• Height 550mm• Width 449.6mm• Depth 171.2mm

GET INTERACTIVE

Scan the code for further information and technical documents on the Ziton range

www.channelsafety.co.uk/ziton/

The Panels

The fi re panels supplied in local language, with user interface, with 1 loop that supports up to 254 devices (127 addresses) in 64 zones, have standard 2supervised sounder/fi re-routing outputs, which can be used as freely programmable outputs as well. In addition 2 conventional relay outputs and 2 supervised outputs, working in pair and dedicated to common fi re and fault conditions, as well as 2 user confi gurable inputs for monitoring and control are available.

Options

The repeaters use a node on the network, similar like a normal panel with a maximum of 32 nodes / 32 loops network of fi re panels, fi re panel repeaters(including conventional fi re panels and fi re panel repeaters up to a maximum of 64 conventional zones). Last but not least, in case separate zone indications are required, a 20 or 40 zone fi re/fault LED indicator board can be mounted in the panel or repeater with ample space for text.

3 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Optical Sensor

PRODUCT CODE DESCRIPTION

F/CH/ZP730-2P Ziton polar white optical sensor

F/CH/ZP730-2BL Ziton black optical sensor

SPECIFICATIONS

Sensitivity

Level 1 - 58ºC fi xed temperatureLevel 2 - 58ºC rate compensatedLevel 3 - 75ºC rate of riseLevel 4 - 75ºC fi xed temperature

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, detec-tor removal and device type

Indication Alarm LED (red)

Operating voltageAddress line pulsed 20V (19.5V to 20.5V). Max line less 4V

Operating Temperature 58ºC to 75ºC (4 software settings)

Current600microA quiecent, 700microA alarm

Addressing Method 7 way DIL switches in head

Temperature Range -10ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP32

Weight 85g

SPECIFICATIONS

Area coverage 100m² subject to local codes

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, sensor removal and device type

Indication Alarm LED (red)

Operating voltageAddress line pulsed 20V (19.5V to 20.5V). Max line less 4V

Current 600uA quiecent, 700uA alarm

Addressing Method 7 way DIL switches in head

Detection Principle Photo electric light scatter

Temperature Range -10ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP32

Weight 105g

Heat Sensor

PRODUCT CODE DESCRIPTION

F/CH/ZP720-3P Ziton polar white heat sensor

The F/CH/ZP720-3P addressable thermal detector is a polar white, thermistor controlled device that responds to changes in its ambient temperature. The sensitivity of each detector is set by the control panel and can be adjusted between four levels ranging between 58°C and 75°C - either manually or automatically on a timed basis. Temperature levels are continuously sensed by the unit and transmitted via the wiring loop as electronic signals, which are assessed and verifi ed by the control panel prior to any alarm decision being taken.

Designed for early response to slow burning, smoldering fi res, the F/CH/ZP730 is available in either black or polar white, addressable smoke detector developed to provide reliable sensing for most fi re alarm applications. The detector’s proven stability in air movement associated with air conditioning systems has made it a popular selection for modern building interiors.

Operating on light scatter principles, the F/CH/ZP730 fully meets the sensitivity requirements of EN54 Pt 7 and is approved by several international approval bodies.

Product Dimensions

• Diameter 106mm• Depth 52mm

Product Dimensions

• Diameter 106mm• Depth 52mm

4 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Intelligent Multi-sensor

PRODUCT CODE DESCRIPTION

F/CH/ZX832-2P Ziton polar white intelligent multi-sensor (optical & heat)

F/CH/ZX832-2B Ziton black intelligent multi-sensor (optical & heat)

SPECIFICATIONS

Area coverageSmoke - 100m², heat - 50m², subject to local codes

Sensitivity

Smoke - m = 0.13dB/mHeat - software selectable 58ºC or 75ºC

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, sensor removal and device type

Indication Alarm LED (red)

Operating voltageAddress line pulsed 20V (19.5V to 20.5V). Max line less 4V

Current 600uA quiescent, 700uA alarm

Addressing Method 7 way DIL switches in head

Detection Principle Photo electric light scatter

Temperature Range -20ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP32

Weight 105g

SPECIFICATIONS

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, detec-tor removal and device type

Terminals

Loop +ve in/outLoop -ve in/outCable screen continuityREM LED +veREM LED -ve

Operating voltage 16-22 VDC

Temperature Range -10ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP42

Weight F/CH/ZP7-SB1-P - 52g F/CH/ZP7-SB1-BL - 61g

Surface Bases

PRODUCT CODE DESCRIPTION

F/CH/ZP7-SB1-P Ziton polar white surface mounting sensor base

F/CH/ZP7-SB1-BL Ziton black surface base

The F/CH/ZP7-SB1-BL and F/CH/ZP7-SB1-P are common mounting bases allowing any ZP7 addressable detector to be removed or replaced without disconnecting loop wiring from detector terminals. The detectors plug into the base unit with a simple twist and lock action, allowing quick and easy removal for cleaning and servicing of the device type should the usage of the protected area change.

All bases feature robust wiring terminals with captive clamping washers to ensure secure wiring termination. Terminals are provided inside themoulding for loop connections and the termination of cable screening. Provision is also made for the connection of a remote LED when required.

F/CH/ZP7-SB1-BL

Product Dimensions

• Diameter 108mm• Depth 18mm

F/CH/ZP7-SB1-P

Product Dimensions

• Diameter 108mm• Depth 18mm

Product Dimensions

• Diameter 106mm• Depth 59mm

The F/CH/ZX832- is an addressable optical/heat multi criteria detector for Ziton fi re alarm systems. The F/CH/ZX832 multisensor represents the next generation of fi re detectors giving an earlier warning of fi re or smoke with the ability to discriminate against false alarms. Fuzzy logic software using multi-criteria sensing form the basis of this advanced optical and heat detector. The detector consists of integrated high sensitivity smoke and thermal sensors. The system combines the dynamic results of rates of change patterns and absolute levels of smoke and heat, to identify real fi re criteria.

5 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Call Points

Sensor Base

PRODUCT CODE DESCRIPTION

F/CH/ZP7-85-3 Ziton red fl ush mounting analogue call point complete with EN54 marking

F/CH/ZP7-87-3 Ziton red weatherproof surface mounting analogue call point (IP67)

PRODUCT CODE DESCRIPTION

F/CH/ZP7-RB1-P Ziton recessed sensor base

SPECIFICATIONS

WiringZP loop - 2 core plus screen, continuity must be maintained

MonitoringOpen and short circuit loop wiring faults

Operating principle Micro switch

Indication Alarm LED (red)

Operating voltage 16 - 22 VDC

Current 600uA quiescent, 700uA alarm

Temperature Range -30°C to +70°C

Humidity Range 0% to 95% RH (non condensing)

IP Rating IP24 or IP67

Weight 125g 270g

SPECIFICATIONS

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, detec-tor removal and device type

Terminals

Loop +ve in/outLoop -ve in/outCable screen continuityREM LED +veREM LED –ve

Operating voltage 16-22 VDC

Temperature Range -10ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP42

Weight 110g

The Ziton Call points provide a manual means of initiating a fi re alarm on ZP3 addressable systems. Complying with EN 54 Part 11, these call points are suitable for installations meeting the recommendations of many local codes (e.g. BS 5839 Part 1).

The unit is operated either by pressing a resettable element (EN54 Part 11) or by breaking a frangible glass with fi nger pressure. Glass elements haveclear vinyl coatings on the front surface to prevent operator injury and to inhibit the release of loose fragments as the glass is broken. Both operatingelements are easily interchangeable.

For locations where malicious operation, or accidental impact from fl ying objects may occur (for example sports halls).

The ZP7-RB1-P detector base is a recess mounted fi re detector base allowing detectors to be semi- recessed into ceiling tiles when installed into buildings with suspended ceilings.

For ease of installation, the base moulding passes through a clearance hole in the ceiling tile where it is clamped between a retaining fl ange on the underside of the base moulding and a threaded collar tightened down from above. Tile sections of up to 25 mm can be accommodated. Common to all the detectors in the ZP7 range, the ZP7-RB1-P allows removal and replacement of detectors without disconnection of wiring from terminals. Detectors plug into the base with a simple twist and lock action, allowing quick and easy removal for cleaning and servicing, or reselection of device type should the usage of the protected area change.

Product Dimensions

• Diameter 138mm• Depth 38mm

F/CH/ZP7-85-3

Product Dimensions

• Height 93mm• Width 89mm• Depth 27.5mm recessed• Depth 59.5mm with surface

back box

F/CH/ZP7-87-3

Product Dimensions

• Height 93mm• Width 93mm• Depth 68.5mm

6 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Visual Sounder Indicator

PRODUCT CODE DESCRIPTION

F/CH/ZP755HAV-2P

Ziton white omnidirectional visual sounder indicator

SPECIFICATIONS

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, sound level - self test facility

Sound output 102 dBA (at 1m)

Frequency Flash rate 1.3 seconds

Operating voltageLoop 19.5 - 20.5 VDC, External 24 VDC (nominal)

Current 820microA quiescent, 9.6 mA active

Sound types

Tone 1 - continuous 980 HzTone 2 - intermittent 980 Hz (0.5 secs on/off ) Tone 3 - two tone warble 980 Hz/670 Hz

Detection Principle Photo electric light scatter

Temperature Range -10ºC to 60ºC

Humidity Range (at 40oC) 10% to 95% RH (non condensing)

IP Rating IP50

Weight 369g (including base)

Product Dimensions

• Diameter 127mm• Depth 47mm

F/CH/ZP755HAV-2P devices are perfectly suited for this application and any application involving high levels of background noise. It provides both audible and visual warnings from a single, addressable, loop wired unit. High effi ciency acoustic design and a low current LED visual element enables up to 20 sounder indicator to be connected to a 1 km loop of 1.5mm²cable with a wiring run of 50 m to the fi rst device. The range features a unique self test facility - automatically activated during routine sounder testing. A built in microphone circuit measures sound output and automatically signals the sounder address and location to the control panel, should the output test fail.

SPECIFICATIONS

External poweredZP7-SBB stand alone visual indicator base

Wiring 2 core loop or spur

Monitoring Open and short circuit fault

Indication Clear lens - illuminates red

Strobe frequency 20ms on, 1.1s off

Operating voltage Loop 19.5 - 20.5 VDC

Operating Temperature 58ºC to 75ºC (4 software settings)

External 24 VDC (nominal)

Current 400uA quiescent 2.5 mA active

Max number60 per 1km loop (1.5mm² cable, 50m to fi rst device)

Temperature Range -10ºC to 55ºC

Humidity Range(at 40oC) 10% to 95% RH (non condensing)

IP Rating IP21C

Weight 145g

Visual Alarm Indicator

PRODUCT CODE DESCRIPTION

F/CH/ZP755V-PZiton white surface mounting visual alarm indicator with clear lens

Product Dimensions

• Diameter 106mm• Depth 49mm

Designed to compliment audible alarms, F/CH/ZP755V-P visual indicator provides high intensity, visual signals for applications where alarm sounders alone would prove to be ineff ective or inappropriate for evacuating occupied premises. Residential establishments with occupants who may be infi rmed or hard of hearing or manufacturing areas where intense industrial noise demands the use of ear protection, the visual indication of alarms may be necessary. The unit is designed to meet the requirements of most local disability legislation.

7 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Product Dimensions

• Diameter 127mm• Depth 47mm

Base Sounder Visual Indicator

PRODUCT CODE DESCRIPTION

F/CH/ZP755B-2P Ziton surface mounting addressable base sounder

Product Dimensions

• Diameter 127mm• Depth 47mm

High effi ciency acoustic design and a low energy sound gun transducer enable up to 60 sensors with sounder bases to be connected to a 1km loop of 1.5mm² cable, with a wiring run of 50 metres to the fi rst device. In systems where loop lengths or current requirements are excessive, the sounder base can be powered directly from an external power supply. A built in microphone circuit measures sound output level and automatically signals the sounder address to the control panel, should the output test fail. Continuous, intermittent and two-tone audible outputs are available.

The ZP755BV combines a detector base, audible sounder and high intensity visual indicator in a single stylish moulding. It off ers both audible and visual warnings from a single, addressable, loop wired unit.

SPECIFICATIONS

Wiring 2 core loop or spur

MonitoringOpen/short circuit, sound output, removal, device type

Sound output (tone dependant) <75 dB(A)

Flash frequency 0.9 Hz

Operating voltageLoop powered 19.5 - 20.5VExternally powered 18 - 30VDC

Current

Quiescent (when loop powered) 500μAActive (when loop powered) 6mAQuiescent (when externally powered) 470μA Active (when externally powered) 500μA

Sound types

Tone 1 - continuous 980 HzTone 2 - intermittent 980 Hz (0.5 secs on/off ) Tone 3 - two tone warble 980 Hz/670 Hz

Operating temperature -10°C to 60°C

Storage temperature -20°C to 70°C

Humidity Range 10% to 95% RH (non condensing)

IP Rating IP21C

Weight 156g

SPECIFICATIONS

Wiring 2 core loop or spur

MonitoringOpen/short circuit, sound output, removal, device type

Sound output 102 dBA (at 1m)

Flash frequency 0.9 Hz

Operating voltageLoop powered 19.5 - 20.5VExternally powered 18 - 30VDC

Current

Quiescent (when loop powered) 500microA Active (when loop pow-ered) 6mA Quiescent (when externally powered) 470microA Active (when externally powered) 500microA

Sound output (tone dependant) <75 dB(A)

Operating temperature -10°C to 60°C

Storage temperature -20°C to 70°C

Humidity Range (10% to 95% RH (non condensing)

IP Rating IP21C

Weight 156g

Base Sounder

PRODUCT CODE DESCRIPTION

F/CH/ZP755BV-4PZiton white surface mounting addressable base sounder visual indicator

8 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

SPECIFICATIONS

Loop current

Quiescent (when loop powered) 820microA Active (when loop powered) 9.6mA Quiescent (when externally powered) 470microAActive (when externally powered) 500microA

Devices per loop (max)30 (1km loop of 1.5mm² cable, 50 m to fi rst device)

Sounder

Sound output (tone dependant) <90 dB(A)Sound types User confi gurable

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, detector removal and device type

Flash frequency 0.8 Hz

Operating voltageLoop powered 19.5 - 20.5VExternally powered 18 - 30VDC

Operating Temperature 58ºC to 75ºC (4 software settings)

Current600microA quiecent, 700microA alarm

Temperature Range -25°C to 70°C

Humidity Range 10% to 95% RH (non condensing)

IP Rating IP32

Weight 300g

Horn Visual Sounder Indicator

PRODUCT CODE DESCRIPTION

F/CH/ZP755WV-2R Ziton red weatherproof horn sounder indicator

Product Dimensions

• Diameter 120mm• Depth 150mm

Sounder

PRODUCT CODE DESCRIPTION

F/CH/ZP755R-2R Ziton red room sounder complete with cover

SPECIFICATIONS

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, sound level - self test facility

Sound output 90 dBA (at 1m)

Operating voltageLoop 19.5 - 20.5V, external supply 18 - 30 Vdc

Sound types

Continuous - 980 Hz, intermittent - 980 Hz 0.5 secs on/off , dual tone - 980/670 Hz 0.5 secs each

Current 500uA quiescent, 6mA active

Max number100 per 1km loop (1.5mm² cable, 50m to fi rst device)

Temperature Range -10ºC to 55ºC

Humidity Range(at 40ºC) 10% to 95% RH (non condensing)

IP Rating IP50

Weight 266g (including base)

The F/CH/ZP755R-2R features a unique self test facility - automatically ac-tivated during routine sounder testing. A built in microphone circuit mea-sures sound output level and automatically signals the sounder address and location to the control panel, should the output test fail. Continuous, intermittent and two-tone outputs are available, from which any combina-tion can be chosen to provide alert and evacuate, two stage alarms. Sound types comply with most international codes The F/CH/ZP755R-2R features a sound output of 90 dBA and a volume control for areas where a reduced sound output is required. Moulded in high impact thermoplastic, the sounder is available in either red or white.

Product Dimensions

• Diameter 127mm• Depth 76mm

9 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Horn Sounder

PRODUCT CODE DESCRIPTION

F/CH/ZP755W-R Ziton red weatherproof horn sounder

SPECIFICATIONS

Sound output 102dBA (at 1m)

Wiring 2 core loop or spur

MonitoringOpen and short circuit fault, sound level - self test facility

Sound types

Tone 1 - continuous 980 HzTone 2 - intermittent 980 Hz (0.5 secs on/off ) Tone 3 - two tone warble 980 Hz/670 Hz

Operating voltageLoop 19.5 - 20.5 Vdc, External 24 Vdc (nominal)

Current 600uA quiescent, 5.5mA active

Max number 40 per 1km loop (1.5mm2 cable, 50m to fi rst device)

Operating temperature -10ºC to +55ºC

Humidity Range(at 40oC) 10% to 95% RH (non condensing)

IP Rating IP50

Weight 339g (including base)

Product Dimensions

• Diameter 127mm• Depth 112mm

F/CH/ZP755W-R is designed with dual front and rear sound paths, providing an 'all around' sound output - ideal for open area coverage.

The units high effi ciency acoustic design, together with a low energy, 'sound gun' transducer, enables up to 40 sounders to be connected to a one kilometre loop of 1.5mm2 cable, with a wiring run of 50 metres to the fi rst device.

The F/CH/ZP755W-R produces a sound output of 102 dBA tested at 1 metre. The volume setting can be reduced for areas where a lower sound output is required.

Mini Input Interface Unit

PRODUCT CODE DESCRIPTION

F/CH/A45E-2 Ziton A series mini interface unit

SPECIFICATIONS

Wiring 2 core loop (screened)

MonitoringInput cable for open or short circuit fault by 3K9 ohm EOL resistor

Input signalNormally open - with 1K8 series resistor

Operating voltagePulsed ZP loop (19.5 – 20.5V) with max 4 Volt line loss.

Current 650uA quiescent, 700uA alarm

Indication LED (red) fl ashing on operation

Max cable distance

10m (from switching terminals) Cable must be screened and the screen terminated in the loop screen terminal

Temperature Range -10ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP20

Weight 40g

This unit is installed directly onto the ZP loop wiring, carries a system address and enables signals from associated equipment to be interfaced into the fi re alarm system. Input signals are fully displayed at the control panel and can be programmed to activate any system output. By routing loop wiring and installing interfaces adjacent to input equipment, system integrity is increased and the need for long spur wiring between equipment terminals and the fi re alarm interface is eliminated.

A red LED indicator positioned on the front moulding fl ashes when the interface has operated, providing clear identifi cation of the input signal source.

Product Dimensions

• Height 78mm• Width 45mm• Depth 28mm

10 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Mini Mains Switching Relay Unit

PRODUCT CODE DESCRIPTION

F/CH/A51E-1 Ziton A Series mini relay unit, mains switching

SPECIFICATIONS

MountingEquipment cabinet DIN rail, or SMB-DIN100, SMB-DIN200 surface boxes

Wiring 2 core loop

Relay contacts Double pole change over

Alarm 700uA

Operating voltagePulsed ZP loop (19.5 - 20.5V) with max 4 Volt line loss

Current Quiescent 600uA

Contact ratingsDC - max voltage 60Vdc, current 1AAC - max voltage 250Vac current 5 A

Indication LED (red) fl ashing on operation

Temperature range -10ºC to +55ºC

Humidity Range(at 40oC) 10% to 95% RH (non condensing)

IP Rating IP20

Weight 88g

Product Dimensions

• Height 80mm• Width 85mm• Depth 42mm

F/CH/A51E-1 is designed with dual front and rear sound paths, providing an 'all around' sound output - ideal for open area coverage.

The units high effi ciency acoustic design, together with a low energy, 'sound gun' transducer, enables up to 40 sounders to be connected to a one kilometre loop of 1.5mm2 cable, with a wiring run of 50 metres to the fi rst device.

The F/CH/A51E-1 produces a sound output of 102 dBA tested at 1 metre. The volume setting can be reduced for areas where a lower sound output is required.

SPECIFICATIONS

Wiring 2 core loop (screened)

Relay contacts Single pole, change over

Max switching current 1.0 A

Max switching voltage 30Vdc

Max switching voltage 40Vac

Indication LED (red) fl ashing on operation

Operating voltagePulsed ZP loop (19.5 – 20.5V) with max 4 Volt line loss

Current 600uA quiescent, 700uA alarm

Addressing Method 7 way DIL switches in head

Temperature Range -10ºC to +75ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP20

Weight 40g

Mini Relay Unit

PRODUCT CODE DESCRIPTION

F/CH/A50E-2 Ziton A series mini relay unit

The F/CH/A50E-2 is an addressable relay providing single pole, volt free, change over contacts. The unit is intended for installation within the equipment to be switched, thereby off ering savings in installation costs when compared to long, auxiliary circuit, wiring runs out from the control panel.A red LED indicator positioned on the front moulding fl ashes when the interface has operated, providing clear identifi cation of the input signal source. Installed as part of an analogue addressable system, up to 127 line devices (sensors, call points or interface units) can be connected to each of the control panel loops. All loop devices incorporate switch settings enabling them to be assigned a unique address, which is polled by the panel every two seconds.

Product Dimensions

• Height 78mm• Width 85mm• Depth 28mm

11 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Mini Isolator Unit

PRODUCT CODE DESCRIPTION

F/CH/A60E-2 Ziton A Series mini isolator unit

Isolators are connected at intervals along the length of the loop, dividing the wiring into a series of separate monitored sections. A maximum of 16 isolator units can be connected to each loop, (to meet the requirements of EN54 Pt2) which together with isolators at the beginning and end (internal to the panel), enable a maximum of 17 monitored sections.

Conventional Interface

PRODUCT CODE DESCRIPTION

F/CH/A70E-2 Ziton conventional interface

SPECIFICATIONS

Area coverage Max 15 Z600 detectors

Wiring

2 core loop screened loop to control panel, two core conventional zone to devices

Monitoring

Detector spurs - open and short circuit fault with 3K9 end of line resistor

Operating voltageLoop 19.5 to 20.5Vdc, external 24Vdc (nominal)

CurrentLoop powered 8.3mA quiescent, 24.6mA short circuit fault

Outputs

Output circuit switches external 24Vdc positive and negative to output contacts on alarm state

Temperature Range -10ºc to +80ºC

Humidity Range 20% to 95% RH (non condensing)

IP Rating IP20

Weight 78g

The A70E monitors its conventional zone wiring for open and short circuit faults, via end of line resistors supplied with the unit. When detectors are installed with Z6-BS5 bases the interface maintains complete operation of all other zone devices, should a detector from within the zone, be removed from its base. Clear, visual indication is shown on the front of the A70E moulding for alarm (red LED) and fault (amber LED).

Product Dimensions

• Height 78mm• Width 85mm• Depth 27mm

Product Dimensions

• Height 78mm• Width 85mm• Depth 28mm

SPECIFICATIONS

Wiring

2 core "Class-A" return loop. Total loop = 75 ohms maximum. Between isolators = 18 ohms maximum.

MountingDIN rail, or SMB-DIN100, SMB-DIN200 surface boxes

Monitoring Loop - Short circuit protection

Indication LED (red)

Operating voltagePulsed ZP loop (19.5 – 20.5V) with max 4 Volt line loss

Current 600uA quiescent, 800uA fault

Addressing MethodSoft addressed (does not require an address number)

Temperature Range -10ºC to +75ºC

Humidity Range (at 40oC) 10% to 95% RH (non condensing)

IP Rating IP20

Weight 64g

12 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ [email protected]

Enclosure

PRODUCT CODE DESCRIPTION

F/CH/Z7-IO Enclosure for A series modules

Ziton Enclosure for A series modules please note: will not accommodate A51E-1)

Simple DIN rail mounting - The Ziton ZP7-I/O enclosure provides a protec-tive means of surface mounting a single, A series module.

Designed for fi rst and second fi x installation, the Ziton ZP7-I/O enclosure comprises an open backbox containing all wiring terminals, together with a front plate of high impact plastic. Modules are clipped to the DIN rail mount on the reverse of the front plate and connected to the backbox wiring terminals, by means of fl ying leads - supplied with the unit - the two parts then simply plug together prior to system completion. To aid identifi cation, an indent is moulded into the front plate of the enclosure for applying an address label.

Features

• Compatible with A45, A50 and A60 modules• Flying lead connection• Clip in DIN rail fi xing• Address label indent

White Cap

PRODUCT CODE DESCRIPTION

F/CH/ZP755-COV-P Ziton white cover

Designed to be used with the ZP755B series base sounders and notifi cation devices, the F/CH/ZP755-COV-P is a white, plastic cap that allows these notifi cation devices to be used in standalone mode, as normal room devices i.e. without a device in the base.

Features

• Easy to install• Easy to clean• Allows base notifi cation devices to be used in standalone mode• Weight 120g

Product Dimensions

• Diameter 105mm• Depth 28mm

Surface Boxes

PRODUCT CODE DESCRIPTION

F/CH/SMB-DIN1Ziton surface box for A series modules, IP66 (2 single or 1 double)

F/CH/SIM-DIN2Ziton surface box for A series modules, IP66 (4 single or 2 double)

The F/CH/SMB-DIN1 and SIM-DIN2 are polystyrene IP66 ssurface mount boxes with DIN rail fi tted, for use with the A-Series I/O modules.

Features

• Operating temperature up to +70°C• Easy to install• Flush mounting• Impact resistant

Product Dimensions

• Height 110mm• Width 110mm• Depth 66mm

Product Dimensions