20 1, 2, 3, 4
20 1, 2, 3, 4
24x24
0 200 24X12
AIR DEVICE SCHEDULE
NOTES
1, 2, 3, 4
1, 2, 3, 4
150
2150
280
MARK
200R
A 0
151B
C
NOTES: 1. PROVIDE WITH FACTORY-APPLIED, OFF-WHITE ENAMEL FINISH.2. PROVIDE WITH FLUSH MOUNT FRAME OR T-BAR MOUNT FRAME AS REQUIRED TO MATCH CEILING CONDITION. 3. PROVIDE WITH MITERED CORNERS. 4. PROVIDE SQUARE TO ROUND DUCT TRANSITIONS AS REQUIRED.
MAX. NC LEVEL
20
MAKE / MODELMIN. MAX.
FACE SIZE (IN.)
NECK SIZE (IN.)
20
CFM RANGEMAX S.P.
(IN.)
24x24 6"Ø 0.10
- 0.10
8"Ø24x24 0.10
- 0.01
EAT LAT COIL LOADDESIGN MIN. IN. ° ° KW
FTU-10-1FAN POWERED TERMINAL UNIT
250 100 12 55 90 1.1TRANE VCEF
OR APPROVED ALTERNATE
1,2,3
FTU-10-2FAN POWEREDTERMINAL UNIT
480 192 4 55 90 2.1TRANE VCEF
OR APPROVED ALTERNATE
1,2,3
FAN POWERED AIR TERMINAL UNIT SCHEDULEINLET SIZE
NOTES:1. PROVIDE UNIT WITH 480 VOLT, THREE PHASE SINGLE POINT POWER CONNECTION WITH FUSED DISCONNECT.2. PROVIDE SOLID STATE COMULATING HEAT CONTROL FOR ALL HEATING COILS.3. PROVIDE 1" FOIL-FACED FIBROUS GLASS DUCT LINER COMPLYING WITH UL181 AND NFPA 90A.
MARK TERMINAL TYPECFM
NOTESHEATING COIL
MAKE/MODEL
DESIGN MIN. IN.
VAV-7-1SINGLE DUCT
TERMINAL UNIT285 0 6
KRUEGER LMHSOR APPROVED ALTERNATE
1,2
VAV-7-2SINGLE DUCT
TERMINAL UNIT380 0 6
KRUEGER LMHSOR APPROVED ALTERNATE
1,2
VAV-7-3SINGLE DUCT
TERMINAL UNIT200 0 6
KRUEGER LMHSOR APPROVED ALTERNATE
1,2
VAV-10-1SINGLE DUCT
TERMINAL UNIT150 0 6
KRUEGER LMHSOR APPROVED ALTERNATE
1,2
VARIABLE AIR TERMINAL UNIT SCHEDULE
NOTES:1. PROVIDE UNIT WITH 277 VOLT, THREE PHASE SINGLE POINT POWER CONNECTION WITH FUSED DISCONNECT.2. PROVIDE 1" FOIL-FACED FIBROUS GLASS DUCT LINER COMPLYING WITH UL181 AND NFPA 90A.
INLET SIZEMARK TERMINAL TYPE
CFMNOTESMAKE/MODEL
PLUMBING FIXTURE SCHEDULESYMBOL DESCRIPTION MANUFACTURER / MODEL NUMBER WASTE VENT CW HW REMARKS
SK-1 SINK: COUNTER-MOUNTED, SELF-RIMMING, 3-HOLE, 4" CENTERS, ELKAY: LRAD 1918 2" 1-1/2" 3/4" 3/4" OFF-CENTERED REAR DRAIN OPENING(ADA) #18 GAUGE, TYPE 304 STAINLESS STEEL, 6-1/2" DEEP, SINGLE-BOWL
FAUCET: SWING NECK, 3-HOLE WITH DECK PLATE MOEN: 8701 PROVIDE 1.5 GPM VANDAL-RESISTANT AERATORSTRAINER: GRID-TYPE w/ DRAIN COVER McGUIRE: 1151AWCTRAP McGUIRE: 8903 1-1/2" INLET X 2" OUTLETSUPPLIES: BRASS STOPS & COPPER RISERS, CHROME PLATED McGUIRE: 2167CCLK LOOSE KEY, 1/2" RISERSCOVERS (NOT REQ'D IF ARCHITECTURAL COVER PROVIDED) TRUBRO: LAV GUARD2, 103 E-Z FOR STOPS, STRAINER, AND P-TRAP
IMB ICE MACHINE BOX: SIOUX CHIEF: 696-10 SERIES "OX BOX" - - 3/4" - INCLUDE WATER HAMMER ARRESTOR.
IM ICE MAKER (BY OTHERS) - - 1/2" - INCLUDE CHROME-PLATED VACUUM BREAKER IN WATER SUPPLY:CHICAGO MODEL 892-G OR APPROVED EQUAL. LOCATE 6" MIN.ABOVE TOP OF ICE MAKER & ALL DOWNSTREAM PIPING.
DW DISHWASHER (BY OTHERS) 5/8" - - 1/2" CONNECT WASTE TUBE THROUGH CHROME-PLATED AIR-GAP FITTING ABOVE COUNTERTOP TO SINK TAILPIECE.
NOTES:
1) REFER TO THE ARCHITECTURAL DRAWINGS FOR EQUIPMENT AND ACCESSORY LOCATIONS. NOTIFY ARCHITECT AND ENGINEER OF ANY CONFLICTS.
2) REFER TO THE ARCHITECTURAL DRAWINGS FOR SPECIFIC MOUNTING HEIGHTS FOR ALL FIXTURES.