113894818-transformer-protection.ppt

Upload: robert-lopez

Post on 08-Mar-2016

7 views

Category:

Documents


2 download

TRANSCRIPT

  • 7/21/2019 113894818-Transformer-Protection.ppt

    1/116

    GRID

    Technical Institute

    This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior

    written consent of Alstom Grid Technical Institute. All rights reserved.

    Transformer Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    2/116

  • 7/21/2019 113894818-Transformer-Protection.ppt

    3/116

    3 > Transformer Protection

    Transformer Protection (1)

    ransformer Connections

    !vercurrent "rotection

    #irectional "rotection of "arallel ransformers

    "artial #ifferential "rotection of "arallel ransformers

    $arth %aults on ransformer Windings

    &nrestricted $arth %ault "rotection

    'estricted $arth %ault "rotection

    (iased #ifferential "rotection of 2 and 3 Winding

    ransformers

  • 7/21/2019 113894818-Transformer-Protection.ppt

    4/116

    4 > Transformer Protection

    Transformer Protection (2)

    Combined #ifferential and 'estricted $arth %ault

    "rotection

    "rotection of Auto)ransformers

    *nter)urn %aults and (uchhol+ "rotection

    !verfluxing "rotection

    !verload "rotection

    ransformer %eeder "rotection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    5/116

    5 > Transformer Protection

    Transformer Connections

  • 7/21/2019 113894818-Transformer-Protection.ppt

    6/116

    6 > Transformer Protection

    Transformer Protection (3)

    A1

    I A2

    V EP

  • 7/21/2019 113894818-Transformer-Protection.ppt

    7/1167 > Transformer Protection

    A1

    I A2

    V EP

    a1

    a2

    ES

    Transformer Protection (4)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    8/1168 > Transformer Protection

    IS

    A1

    I A2

    V EP

    a1

    a2

    ES

    Transformer Protection (5)

    P

  • 7/21/2019 113894818-Transformer-Protection.ppt

    9/1169 > Transformer Protection

    A

    (

    C c

    b

    aa2a1

    b1 b2(1(2

    A2 A1

    C2 C1 c1 c2

    A

    (C

    C2

    C1 A2

    A1

    (2(1

    a

    b

    cc2

    c1

    a2

    a1

    b1 b2

    Cloc- face numbers refer to

    position of lo/ voltage phase )

    neutral vector /ith respect to high

    voltage phase ) neutral vector.

    0ine connections made to highest

    numbered /inding terminal available.

    0ine phase designation is same as

    /inding.

    Transformer Connections

  • 7/21/2019 113894818-Transformer-Protection.ppt

    10/11610 > Transformer Protection

    "hase displacement

    roup 1

    "hase displacement1

    roup 2

    0ag phase displacement3

    roup 3

    0ead phase displacement3

    roup 4

    5

    #d

    6d

    57

    #d7#+7

    d1

    #51

    +1

    d11

    #511

    +11

    Transformer Vector Groups

  • 7/21/2019 113894818-Transformer-Protection.ppt

    11/11611 > Transformer Protection

    Cloc- %ace numbers refer to position of lo/ voltage

    phase)neutral vector /ith respect to high voltage phaseneutral vector

    0ine connections made to highest numbered /inding

    terminal available

    0ine phase designation is same as /inding

    Example 1 !" 11 Transformer

    B1B2 b2b1

    a2a1A1A2

    C1C2 c2c1

    8uestion 9 :o/ to connect /indings ;

    HighVoltage

    Winings

    !o"Voltage

    Winings

    A PhaseWining

    s

    B PhaseWinings

    C PhaseWining

    s

    Transformer Connections

  • 7/21/2019 113894818-Transformer-Protection.ppt

    12/11612 > Transformer Protection

    3oltage >ectors

    #$%

    A

    C B

    a

    c

    b

    !ine Designation

    !" 11

  • 7/21/2019 113894818-Transformer-Protection.ppt

    14/11614 > Transformer Protection

    2. #ra/ #elta Connection

    a

    c

    b

    A

    BC

    !" 11

  • 7/21/2019 113894818-Transformer-Protection.ppt

    15/11615 > Transformer Protection

    3. #ra/ A "hase Windings

    A

    C B

    a

    b

    a2

    a1

    A2

    A1

    c

    !" 11

  • 7/21/2019 113894818-Transformer-Protection.ppt

    16/11616 > Transformer Protection

    4. Complete Connections ?a@

    A

    B

    a

    c

    b

    a2

    a1

    A1

    C1

    C2

    B1

    B2

    b2

    b1

    c1

    c2

    C

    A2

    !" 11

  • 7/21/2019 113894818-Transformer-Protection.ppt

    17/11617 > Transformer Protection

    4. Complete Connections ?b@

    c1

    c2

    b

    1

    b

    2

    a1 a2a

    b

    c

    A

    B

    CC2

    C1

    B

    2

    B

    1

    A2

    A1

    !" 11

    http://additional%20tx%20notes.ppt/
  • 7/21/2019 113894818-Transformer-Protection.ppt

    18/11618 > Transformer Protection

    ransformer rating %use

    ->A

    1

    2

    3

    1

    .2

    1.

    1.

    27.22.

    17

    2

    37

    B

    3.

    3.

    1.

    2.3.

    %ull load

    current ?A@

    'ated

    current ?A@

    !perating time at

    3 x rating?s@

    11#V !istri$ution TransformersT"pical Fuse %atings

  • 7/21/2019 113894818-Transformer-Protection.ppt

    19/11619 > Transformer Protection

    Tra&itional 'mall TransformerProtection Pac#age

    5

    1

    3.3k

    V200/5 5051

    1MVA

    3.3/0.44kV1500/5

    1500/564

    N5

    0N

    51

    N

  • 7/21/2019 113894818-Transformer-Protection.ppt

    20/11620 > Transformer Protection

    Tra&itional e&ium TransformerProtection Pac#age

    11&

    V'$

    '1

    '(VA11)#*#&V

    1$$$)'

    1$$$)'

    +,

    '

    1-

    +,

    #*#&

  • 7/21/2019 113894818-Transformer-Protection.ppt

    21/11621 > Transformer Protection

    *ercurrent Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    22/11622 > Transformer Protection

    'euirements

    %ast operation for primar5 short circuits

    #iscrimination /ith do/nstream protections

    !peration /ithin transformer /ithstand

    =on)operation for short or long term overloads

    =on)operation for magnetising inrush

    Transformer *ercurrent Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    23/116

    23 > Transformer Protection

    Source:>

    0>

    1

    set to 1.2 ) 1.3 x through fault level

    +se of ,nstantaneous *ercurrent Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    24/116

    24 > Transformer Protection

    Concerns rela5 response to offset /aveforms ?#C

    transient@

    #efinition

    I1 - I2

    I2 x 100

    I1 D Stead5 state

    rms pic- up

    current

    I2 D %ull5 offset

    rms

    pic-up

    current

    I1

    I2

    D.C.

    Transient *erreac-

  • 7/21/2019 113894818-Transformer-Protection.ppt

    25/116

    25 > Transformer Protection

    HV2

    '1

    '1

    '1

    !VHV1

    Ti.e !V

    HV1HV2

    Cu//entI0!V

    1*2I0!V

    I0HV

    ,nstantaneous .ig- 'et *ercurrent%ela" /pplie& to a Transformer

  • 7/21/2019 113894818-Transformer-Protection.ppt

    26/116

    26 > Transformer Protection

    I3 I3

    I3

    I3

    0.866

    20101 !istri$ution (1)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    27/116

    27 > Transformer Protection

    I3.77 I3

    .4 sec

    0> rela5

    :> rela5

    20101 !istri$ution (2)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    28/116

    28 > Transformer Protection

    rid suppl5%eeders

    1

    1

    7E

    7E

    1

    1

    Parallel Transformers!irectional %ela"s (1)

    P ll l T f

  • 7/21/2019 113894818-Transformer-Protection.ppt

    29/116

    29 > Transformer Protection

    11

    1

    1

    (usSection

    Parallel Transformers!irectional %ela"s (2)

    rid suppl5%eeders

    1

    P ll l T f

  • 7/21/2019 113894818-Transformer-Protection.ppt

    30/116

    30 > Transformer Protection

    Advantage 9 'educed number of gradingsta es

    +

    3

    +

    3 '1

    '1

    '1

    '1

    P1

    P1

    S1

    S1

    S2

    S2

    P2

    P2

    rid suppl5

    Parallel TransformersPartial !ifferential 'c-eme

  • 7/21/2019 113894818-Transformer-Protection.ppt

    31/116

    31 > Transformer Protection

    Eart- Fault Protection

    T f E t- F lt

  • 7/21/2019 113894818-Transformer-Protection.ppt

    32/116

    32 > Transformer Protection

    1 p.u. turns3 p.u. turns

    x*"

    "'

    ' *%"rotective'ela5

    :3ratioturnsEffective

    .3

    .currentFault:atfaultaFor

    .3

    current!"ri#ar$%&us!valuesloa'fulltocurrentE/Fli#its(esistor

    F.).2

    F.).

    F.).*

    =

    ==

    =

    secon'ar$+.%.t&enr!transfor#eofcurrentloa'

    fullon,ase'issi'e-"ri#ar$onratio+.%./f

    3

    circuit2

    =

    Transformer Eart- Faults

    t % l ' iti it

  • 7/21/2019 113894818-Transformer-Protection.ppt

    33/116

    33 > Transformer Protection

    I0

    51

    vercurrent

    (ela$

    I4as .ulti5le

    o4 I0*!*

    1*$

    $*6

    $*7

    $*3

    $*+

    $*'

    $*,

    $*#

    $*2

    $*1

    Sta/Sie

    DeltaSie

    $*1$*2 $*# $*, $*' $*+ $*3 $*7 $*6 1*$

    5*u**89e/cu//ent Rela: Setting ;

    I0*!*

    *ercurrent %ela" 'ensiti*it"to Eart- Faults (1)

    t % l ' iti it

  • 7/21/2019 113894818-Transformer-Protection.ppt

    34/116

    34 > Transformer Protection

    1$

    6

    7

    3

    +

    '

    ,

    #

    2 1

    $*1 $*2 $*# $*, $*' $*+ $*3 $*7 $*6 1*$

    5*u**

    I4as .ulti5le

    o4 I0*!*

    Sta/Sie

    DeltaSie

    *ercurrent %ela" 'ensiti*it"to Eart- Faults (2)

    I0

    51

    vercurrent

    (ela$

    t % l ' iti it

  • 7/21/2019 113894818-Transformer-Protection.ppt

    35/116

    35 > Transformer Protection

    I0

    IP I-

    1$

    6

    7

    3 +

    '

    ,

    #

    2 1

    $*1$*2 $*#$*,$*'$*+ $*3 $*7$*61*$

    5*u**

    I-

    IP

    I0

    *ercurrent %ela" 'ensiti*it"to Eart- Faults (3)

    I4as .ulti5le

    o4 I0*!*

    E t- F lt T f i &i

  • 7/21/2019 113894818-Transformer-Protection.ppt

    36/116

    36 > Transformer Protection

    #ifferential 'ela5 Setting F of Star Winding "rotected1F F

    2F 41F

    3F 2F

    4F 1EF

    F EF

    Eart- Fault on Transformer in&ing

    I

    #ifferential'ela5

    Setting < IS

    %or rela5 operation, IG IS

    e.g. *f ISD 2F, then G 2F for operation

    i.e.

    G BF

    hus BF of /inding is not protected

    2

    3ID

    2

    3

    +nrestricte& Eart-fault Protection (1)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    37/116

    37 > Transformer Protection

    "rovides bac-)up protection for s5stem

    ime dela5 reuired for co)ordination

    +nrestricte& Eart-fault Protection (1)

    '1

    '1

    '1

    '1-

    +nrestricte& Eart-fault Protection (2)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    38/116

    38 > Transformer Protection

    Can provide better sensitivit5

    ?C.. ratio not related to full load current@

    ?*mproved effective setting@

    "rovides bac- up protection for transformer and s5stem

    '1

    '1

    '1

    '1-'1

    -

    +nrestricte& Eart-fault Protection (2)

    'tar in&ing %EF

  • 7/21/2019 113894818-Transformer-Protection.ppt

    39/116

    39 > Transformer Protection

    "rotected

    6one

    '$

    %

    'ela5 onl5 operates for earthfaults /ithin protected +one.

    &ses high impedance principle.

    Stabilit5 level 9 usuall5 maximum through fault level of

    transformer

    'tar in&ing %EF

    %estricte& EF Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    40/116

    40 > Transformer Protection

    0> restricted $H%

    protection trips

    both :> and 0> brea-er

    'ecommended setting 9 1F

    rated

    %estricte& EF Protectiono Voltage in&ings (1)

    A ( C =

    %estricte& EF Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    41/116

    41 > Transformer Protection

    A ( C =

    0> restricted $H% protection trips both :> and 0> brea-er

    'ecommended setting 9 1F rated

    %estricte& EF Protectiono Voltage in&ings (2)

    !elta in&ing %estricte& Eart- Fault

  • 7/21/2019 113894818-Transformer-Protection.ppt

    42/116

    42 > Transformer Protection

    "rotected +one

    '$%

    Source

    #elta /inding cannot suppl5 +ero seuence current tos5stem

    Stabilit5 9 Consider max 0> fault level

    'ecommended setting 9 less than 3F minimum earth fault

    level

    !elta in&ing %estricte& Eart- Fault

    .ig- ,mpe&ance Principle

  • 7/21/2019 113894818-Transformer-Protection.ppt

    43/116

    43 > Transformer Protection

    P/otecteCi/cuit

    R

    =

    (

    RCT

    R!

    =

    (

    RCT

    R!I0

    IS

    RS

    T

    VS

    R! R!

    .ig- ,mpe&ance Principle

    >oltage Across 'ela5 Circuit >S D I%?'CI 2'0@

    Stabilising resistor 'Slimits spill current to IS?rela5 setting@

    'SD ) '' /here ''D rela5 burden

    C -nee point

    >J"

    D 2>SD 2I

    %?'

    CI 2'

    0@

    >S

    IS

    on0inear %esistors (etrosils)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    44/116

    44 > Transformer Protection

    #uring internal faults the high impedance rela5 circuit

    constitutes an excessive burden to the CKs.

    A ver5 high voltage develops across the rela5 circuit and

    the CKs.

    Causes damage to insulation of C, secondar5/inding and rela5.

    Lagnitude of pea- voltage >"is given b5 an approximate

    formula ?based on experimental results@

    >" D 2 2>J?>%) >J@

    Where >% D S/gr. %ault 'ating in amps x 6 of rela5

    circuit C ratio

    M setting

    Letrosil reuired if >" G 3->

    on0inear %esistors (etrosils)

    on0inear %esistors (etrosils)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    45/116

    45 > Transformer Protection

    I8P

    RST

    VSV(

    RR

    Letrosil Characteristic

    > D C *

    Suitable values of C N

    chosen based on 9

    Lax secondar5 current under fault conditions

    'ela5 setting voltage

    on0inear %esistors (etrosils)

    %EF Protection Example

  • 7/21/2019 113894818-Transformer-Protection.ppt

    46/116

    46 > Transformer Protection

    1(VA'>11$$$V,1'V

    1+$$)1

    RCTalue of stabilising

    resistor reuired

    3@ $ffective setting

    4@ "ea- voltage

    developed b5 CKs

    for internal fault

    %EF Protection Example

    'olution (1)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    47/116

    47 > Transformer Protection

    $arth fault calculation 9)

    &sing L>A base

    Source impedance D 1 p.u.

    ransformer impedance D . x D 4 p.u.

    1

    otal impedance D 14

    p.u.

    *1 D 1 D .E14 p.u. 14

    (ase current D x 17

    3 x 41

    D 1112B7 Amps

    *% D 3 x .E14 x 1112B7 D 234 Amps ?primar5@

    D 14.B Amps ?secondar5@

    1 ".&.1 4

    I1

    4

    I2

    4

    I

    Seuence #iagram

    'olution (1)

    'olution (2)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    48/116

    48 > Transformer Protection

    ?1@ Setting voltage>S D I%?'CI 2'0@

    Assuming earth C saturates,

    'C D 4. ohms

    2'0D 2 x 1 x E.41 x 1)3 D 1.42 ohms

    Setting voltage D 14.B ?4. I 1.42@

    D B3.7 >olts

    ?2@ Stabilising 'esistor ?'S@

    'S D >S ) 1

    IS IS2 Where *SD rela5 current setting

    'S D B3.7 ) 1 D 37 ohms

    .1 .12

    'olution (2)

    'olution (3)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    49/116

    49 > Transformer Protection

    1.7

    1.2

    .

    .4

    .4 .12.

    AHmm?multipl5 b5 Ji to obtain total

    exciting current in Amps@

    WeberHm2?esla@

    ?multipl5b5Jv

    toobtain'LS

    secondar5volts@

    Jv Ji

    0ine N 1 .341=eutral C

    $arth C 237 .2E

    'olution (3)

    'olution (4)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    50/116

    50 > Transformer Protection

    ?3@ $ffective setting I" D C ratio x ?IS I ILA@

    0ine N =eutral Cs

    %lux densit5 at B3.7> D B3.7 D .B2 esla

    1

    %rom graph, mag. %orce at .B2 esla D .1 AHmm

    Lag. Current D .1 x .341 D .1 Amps

    O$arthK C

    %lux densit5 at B3.7> D B3.7 D .3B7 esla

    237

    %rom graph, mag. %orce at .3B7 esla D .12 AHmm

    Lag. Current D .12 x .2E D .33 Amps

    hus, effective setting D 17 x ?.1 I P?4 x .1@ I .33Q@

    $ffective setting D 1B Amps

    ransformer full load current D 13B1 Amps

    $ffective setting D 1B x 1F D 14.2F x rated

    13B1

    'olution (4)

    'olution (5)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    51/116

    51 > Transformer Protection

    ?4@ "ea- voltage D 22>J?>% ) >J@

    >% D 14.B x >S D 14.B x B37 D 13B47 >olts

    IS

    %or O$arthK C, >J D 1.4 x 237 D 33 >olts ?from graph@

    >"$AJ D 22 x 33 x ?13B47 ) 33@

    D 7->hus, Letrosil voltage limiter /ill be reuired.

    'olution (5)

    Parallel Transformers

  • 7/21/2019 113894818-Transformer-Protection.ppt

    52/116

    52 > Transformer Protection

    A=

    1

    (us Section

    2

    41 >olt

    S/itchboard

    C(

    Parallel Transformers

    Parallel Transformers

  • 7/21/2019 113894818-Transformer-Protection.ppt

    53/116

    53 > Transformer Protection

    A=1

    (us Section!pen

    2

    41 >olt

    S/itchboar

    d

    C(

    1=

    1=

    Parallel TransformersCT in Eart-

    Parallel Transformers CT in

  • 7/21/2019 113894818-Transformer-Protection.ppt

    54/116

    54 > Transformer Protection

    1

    (us Section!pen

    2

    41 >olt

    S/itchboar

    d

    1=

    1=

    A= C(

    Parallel Transformers CT inEart- an& eutral

  • 7/21/2019 113894818-Transformer-Protection.ppt

    55/116

    Tra&itional arge Transformer

  • 7/21/2019 113894818-Transformer-Protection.ppt

    56/116

    56 > Transformer Protection

    Tra&itional arge TransformerProtection Pac#age

    33J

    >

    1

    2H

    1L>A33H11J> 1= E

    7H

    74

    7H

    HA

  • 7/21/2019 113894818-Transformer-Protection.ppt

    57/116

    57 > Transformer Protection

    !ifferential Protection

    !ifferential Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    58/116

    58 > Transformer Protection

    !verall differential protection ma5 be Rustified for

    larger transformers ?generall5 G L>A@. "rovides fast operation on an5 /inding

    Leasuring principle 9

    (ased on the same circulating current principle as the

    restricted earth fault protection

    :o/ever, it emplo5s the biasing techniue, to maintain

    stabilit5 for heav5 through fault current

    (iasing allo/s mismatch bet/een C outputs.

    *t is essential for transformers /ith tap changing

    facilit5.

    Another important reuirement of transformer

    differential protection is immunit5 to magnetising in

    rush current.

    6iase& !ifferential 'c-eme

  • 7/21/2019 113894818-Transformer-Protection.ppt

    59/116

    59 > Transformer Protection

    (*AS(*AS I2I1

    !"$'A$

    I1-

    I2

    #ifferential

    Current

    !"$'A$

    '$S'A*=

    Lean hroughCurrent

    I1+

    I2

    2

    I1-

    I2

    !ifferential Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    60/116

    60 > Transformer Protection

    0>

    '

    :>

    "'!$C$#

    6!=$

    Correct application of differential protection reuires C ratio

    and /inding connections to match those of transformer.

    C secondar5 circuit should be a replica of primar5 s5stem.

    Consider 9

    ?1@ #ifference in current magnitude

    ?2@ "hase shift

    ?3@ 6ero seuence currents

    !ifferential Connections

  • 7/21/2019 113894818-Transformer-Protection.ppt

    61/116

    61 > Transformer Protection

    "1 "2 A2 A1 a1 a2 "2 "1

    A ( C

    +se of ,nterposing CT

  • 7/21/2019 113894818-Transformer-Protection.ppt

    62/116

    62 > Transformer Protection

    ''

    '

    "1 "2 A2 A1 a1 a2 "2 "1

    S2 S1 "1 "2

    *nterposing C provides 9>ector correction

    'atio correction

    6ero seuence compensation

    S1 S2 S2 S1

    p g

    !ifferential Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    63/116

    63 > Transformer Protection

    S2S1

    "1"2A1A2 a2a1"2

    1L>A

    77-> H 11->1H H

    "1

    #51

    S1S2

    iven above9 =eed to consider )

    ?1@ Winding full load current ?2@ $ffect of tap changer ?if an5@

    ?3@ C.. polarities

    Assuming no tap changer

    %ull load currents9) 77->9 131 Amp D 4.3E Amps secondar5

    11->9 EE Amp D 4.B2 Amps secondar5

    :o/ever, reuire 11-> C..Ks to be connected in

    hus, secondar5 current D 3 x 4.B2 D .2A

    RATIO CORRECTION IS REQUIRED

    !ifferential Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    64/116

    64 > Transformer Protection

    ''

    '

    "1 "2 A2 A1 a1 a2 "2 "1

    S1 S2 "1 "2

    4.B2A

    S1 S2 S2 S1

    4.3EA

    ?2.7@ ?@

    1H H

    *t is usual to connect 11-> C..Ks in and utilise a H interposing C.. ?this

    method reduces lead >A burden on the line C..Ks@

    Current from 77-> side D 4.3E Amphus, current reuired from /inding of int. C.. D 4.3E Amp

    Current input to /inding of int. C.. D 4.B2 Amp

    'euired int C.. ratio D 4.B2 H 4.3E D 4.B2 H 2.2

    3

    La5 also be expressed as 9 H 2.7

    Effect of Tap C-anger

  • 7/21/2019 113894818-Transformer-Protection.ppt

    65/116

    65 > Transformer Protection

    e.g. Assume 77-> IF, )1F

    *nterposing C.. ratio should be based on mid tap position

    Lid ap ?)F@ D 72.E ->

    "rimar5 current ?1 L>A@ D 13 Amp

    Secondar5 current D 4.7 Amp

    *nterposing C.. ratio reuired D 4.B2 H 4.7

    3

    ? H @

    D 4.B2 H 2.77

    La5 also be expressed as 9 H 2.E

    Compared /ith H 2.7 based on nominal voltage

    Connections C-ec#

  • 7/21/2019 113894818-Transformer-Protection.ppt

    66/116

    66 > Transformer Protection

    /r$itrar" Current !istri$ution

    '

    '

    '

    S1 S2 S2 S1

    "1 "2 A2 A1 a1 a2 "2 "1

    S2 S1 "1 "2

    Connections C-ec#

  • 7/21/2019 113894818-Transformer-Protection.ppt

    67/116

    67 > Transformer Protection

    /&& !elta in&ing Current

    '

    '

    '

    "1 "2 A2 A1 a1 a2 "2 "1

    S2 S1 "1 "2

    S1 S2 S2 S1

    Connections C-ec#

  • 7/21/2019 113894818-Transformer-Protection.ppt

    68/116

    68 > Transformer Protection

    Complete Primar" !istri$ution

    '

    '

    '

    "1 "2 A2 A1 a1 a2 "2 "1

    S2 S1 "1 "2

    S1 S2 S2 S1

    Connections C-ec#

  • 7/21/2019 113894818-Transformer-Protection.ppt

    69/116

    69 > Transformer Protection

    Complete 'econ&ar" !istri$ution

    '

    '

    '

    "1 "2 A2 A1 a1 a2 "2 "1

    S2 S1 "1 "2

    S1 S2 S2 S1

    ,n07one Eart-ing Transformer

  • 7/21/2019 113894818-Transformer-Protection.ppt

    70/116

    70 > Transformer Protection

    "2"1a2a1

    A2A1 "1"2

    S1S2

    S1S2 12 "2"1

    ,n07one Eart-ing Transformer/lt ti (1)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    71/116

    71 > Transformer Protection

    /lternati*e (1)"2"1

    a2a1A2A1 "1"2

    S1S2

    "2"1S1S2

    ,n07one Eart-ing Transformer/lt ti (2)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    72/116

    72 > Transformer Protection

    3H1

    /lternati*e (2)

    BH1

    ! #*%%$'$=*A0

    '$0A

    $A':*=

    'A=S%.

    ,n07one Eart-ing Transformer/lt ti (3)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    73/116

    73 > Transformer Protection

    $A':*=

    'A=S%.

    3H1

    ! #*%%$'$=*A0

    '$0A

    1H.33

    /lternati*e (3)

    3H1

    Com$ine& !ifferential an&% t i t & E t- F lt P t ti

  • 7/21/2019 113894818-Transformer-Protection.ppt

    74/116

    74 > Transformer Protection

    o differential rela5

    S2

    S1

    "1

    "2'$%

    S2

    S1"1

    "2

    S2S1"1 "2

    a2a1A1A2

    %estricte& Eart- Fault Protection

    Com$ine& !ifferential an&E t- F lt P t ti

  • 7/21/2019 113894818-Transformer-Protection.ppt

    75/116

    75 > Transformer Protection

    &sing Summation Auxiliar5 Current ransformer

    'estricted earth

    fault rela5

    (ias /indings

    E E E#ifferential rela5

    operating /indings

    74

    Eart- Fault Protection

    *AE a

    %1

  • 7/21/2019 113894818-Transformer-Protection.ppt

    76/116

    76 > Transformer Protection

    A*AE ,

    A*AE c

    A

    N7 77

    EF%2

    %3

    %4

    (,

    2(,2

    (,2

    (o (o(o

    F

    VE(A)) 8FFE(EN%A)

    (E)A9

    %1

    T-ree in&ing Transformer

  • 7/21/2019 113894818-Transformer-Protection.ppt

    77/116

    77 > Transformer Protection

    2L>

    A

    11J>

    73L>

    A

    132J>

    17H3H

    L>

    A

    33J>

    1H

    4.B

    2.

    1.33

    2.

    .1

    All interp!in" C.T. r#ti$! re%ert &''n ()A *#!e 63()A,

    Tra&itional +se of ,nterposing CT

  • 7/21/2019 113894818-Transformer-Protection.ppt

    78/116

    78 > Transformer Protection

    #51?)3

  • 7/21/2019 113894818-Transformer-Protection.ppt

    79/116

    79 > Transformer Protection

    8ifferentialele#ent

    Nu#eric(ela$

    Virtual inter"osin +%

    Vectorialcorrection

    (atio

    correction

    Virtual inter"osin +%

    Compensation

    *o;er transfor#er

    Transformer agnetisingC-aracteristic

  • 7/21/2019 113894818-Transformer-Protection.ppt

    80/116

    80 > Transformer Protection

    /ice=ormal

    %lux

    =ormal

    %lux

    =ormal=o 0oadCurrent

    =o 0oad Currentat /ice =ormal

    %lux

    C-aracteristic

    agnetising ,nrus- Current'tea&" 'tate

  • 7/21/2019 113894818-Transformer-Protection.ppt

    81/116

    81 > Transformer Protection

    '

    '

    +

    -

    )

    'I

    'tea&" 'tate

    agnetising ,nrus- Current'itc- on at Voltage 7ero o resi&ual flux

  • 7/21/2019 113894818-Transformer-Protection.ppt

    82/116

    82 > Transformer Protection

    '

    '2

    )

    I

    'itc- on at Voltage 7ero 0 o resi&ual flux

    Transformer !ifferential ProtectionEffect of agnetising Current

  • 7/21/2019 113894818-Transformer-Protection.ppt

    83/116

    83 > Transformer Protection

    Effect of agnetising Current

    Appears on one side of transformer onl5

    Seen as fault b5 differential rela5

    =ormal stead5 state magnetising current is less thanrela5 setting

    ransient magnetising inrush could cause rela5 to

    operate

    Transformer !ifferential ProtectionEffect of agnetising ,nrus-

  • 7/21/2019 113894818-Transformer-Protection.ppt

    84/116

    84 > Transformer Protection

    Effect of agnetising ,nrus-

    S!0&*!= 1 9 *L$ #$0A

    Allo/s magnetising current to die a/a5 before rela5 canoperate

    Slo/ operation for genuine transformer faults

    Transformer !ifferential ProtectionEffect of agnetising ,nrus-

  • 7/21/2019 113894818-Transformer-Protection.ppt

    85/116

    85 > Transformer Protection

    Effect of agnetising ,nrus-

    S!0&*!= 2 9 2=# ?and :@ :A'L!=*C '$S'A*=

    La-es rela5 immune to magnetising inrush

    Slo/er operation ma5 result for genuine transformer faults

    if C saturation occurs

    &sed in LiC!L "73x

    Transformer !ifferential ProtectionEffect of agnetising ,nrus-

  • 7/21/2019 113894818-Transformer-Protection.ppt

    86/116

    86 > Transformer Protection

    Effect of agnetising ,nrus-

    S!0&*!= 3 9 A" L$AS&'$L$= $C:=*8&$

    *nhibits rela5 operation during magnetising inrush

    !perate speed for genuine transformer faults unaffected b5

    significant C saturation

    &sed in L(C: N J(C: rela5s

    T"pical agnetising ,nrus-a*eforms

  • 7/21/2019 113894818-Transformer-Protection.ppt

    87/116

    87 > Transformer Protection

    A

    C

    a*eforms

    !etection of T"picalagnetising ,nrus- (58.9)

  • 7/21/2019 113894818-Transformer-Protection.ppt

    88/116

    88 > Transformer Protection

    #ifferential

    comparator

    1 D ms 2 D 22ms

    rip

    (ias

    #ifferential

    hreshold

    agnetising ,nrus- (58.9)

    %estraint for Transformeragnetising ,nrus-

  • 7/21/2019 113894818-Transformer-Protection.ppt

    89/116

    89 > Transformer Protection

    agnetising ,nrus-

    #ifferential

    comparator

    (ias

    #ifferential

    hreshold

    rip

    1 D ms 2 D 22ms

    #ifferential input

    Comparator output

    rip

    'eset2

    1

    peration for Transformer Faults

  • 7/21/2019 113894818-Transformer-Protection.ppt

    90/116

    90 > Transformer Protection

    #ifferential

    comparator

    (ias

    #ifferential

    hreshold

    rip

    1 D ms 2 D 22ms

    #ifferential input

    Comparator output

    rip

    'eset2

    1

    Protection of /uto0Transformer $".ig- ,mpe&ance !ifferential %ela"s

  • 7/21/2019 113894818-Transformer-Protection.ppt

    91/116

    91 > Transformer Protection

    ?a@ $arth %ault Scheme

    A

    (

    C

    :igh impedance

    rela5E

    .ig- ,mpe&ance !ifferential %ela"s

    Protection of /uto0Transformer $".ig- ,mpe&ance !ifferential %ela"s

  • 7/21/2019 113894818-Transformer-Protection.ppt

    92/116

    92 > Transformer Protection

    A

    (

    C

    a

    b

    c

    E E E

    n

    .ig- ,mpe&ance !ifferential %ela"s

    ?b@ "hase and $arth %ault Scheme

  • 7/21/2019 113894818-Transformer-Protection.ppt

    93/116

    93 > Transformer Protection

    ,nter0Turn Fault Protection

    ,nter0Turn Fault

  • 7/21/2019 113894818-Transformer-Protection.ppt

    94/116

    94 > Transformer Protection

    =ominal turns ratio

    %ault turns ratio

    Current ratio

    ) 11, H 24

    ) 11, H 1

    ) 1 H 11,

    'euires (uchhol+rela5

    C

    $

    Shorted

    turn

    0oad

    ,nterturn Fault Current um$erof Turns '-ort Circuite&

  • 7/21/2019 113894818-Transformer-Protection.ppt

    95/116

    95 > Transformer Protection

    1

    7

    4

    2

    1 1 2 2

    1

    7

    4

    2

    %ault current in short

    circuited turns

    "rimar5 input current

    %ault current

    ?multiples ofrated current@

    "rimar5 current

    ?multiples ofrated current@

    urn short)circuited ?percentage of /inding@

    of Turns '-ort Circuite&

    6uc--ol9 %ela" ,nstallation

  • 7/21/2019 113894818-Transformer-Protection.ppt

    96/116

    96 > Transformer Protection

    x internal pipe

    diameter ?minimum@

    3 x internal pipe

    diameter ?minimum@

    ransformer

    3 minimum

    !il conservator

    Conservator

    6uc--ol9 %ela"

  • 7/21/2019 113894818-Transformer-Protection.ppt

    97/116

    97 > Transformer Protection

    "etcoc-

    Counter balance/eight

    !il level

    %rom transformer

    Aperture adRuster

    #eflector plate#rain plug

    rip buc-et

    o oilconservator

    Lercur5 s/itch

    Alarm buc-et

  • 7/21/2019 113894818-Transformer-Protection.ppt

    98/116

    98 > Transformer Protection

    *erfluxing Protection

    *erfluxing

  • 7/21/2019 113894818-Transformer-Protection.ppt

    99/116

    99 > Transformer Protection

    enerator transformers

    rid transformers

    &suall5 onl5 a problem during run)up or shut do/n, but can be

    caused b5 loss of load H load shedding etc.

    %lux >

    f

    $ffects of overfluxing 9 *ncrease in magnetising current

    *ncrease in /inding temperature

    *ncrease in noise and vibration

    !verheating of laminations and metal parts ?caused b5 stra5 flux@

    "rotective rela5 responds to >Hf ratio Stage 1 ) lo/er A.>.'.

    Stage 2 ) rip field

    *erfluxing 6asic T-eor"

  • 7/21/2019 113894818-Transformer-Protection.ppt

    100/116

    100 > Transformer Protection

    m2

    *e

    m

    > D -f

    CA&S$S0o/ freuenc5

    :igh voltage

    eomagnetic disturbances

    $%%$CS

    ripping of differential element ?ransient overfluxing@

    #amage to transformers ?"rolonged overfluxing@

    V.9 *erfluxing Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    101/116

    101 > Transformer Protection

    > f

    J

    rip and alarm outputs for clearing prolonged overfluxing

    Alarm 9 #efinite time characteristic to initiate corrective action

    rip 9 *#L or # characteristic to clear overfluxing condition

    Settings

    "ic-)up 1. to 3. i.e. 11> x 1. D 2.31

    :+

    # setting range .1 to 7 seconds

    V.9 C-aracteristics

  • 7/21/2019 113894818-Transformer-Protection.ppt

    102/116

    102 > Transformer Protection

    1

    1

    1

    11 1.1 1.2 1.3 1.4 1. 1.7

    L D

    !perating

    time ?s@

    > :+

    Setting

    J D 73J D 4

    J D 2

    J D

    J D 1

    t D . I .1 x J

    ?L ) 1@2

    $nables co)ordination /ith plant /ithstand characteristics

    *erfluxing %ela"

  • 7/21/2019 113894818-Transformer-Protection.ppt

    103/116

    103 > Transformer Protection

    '0

    A>'

    $x

    >

    /pplication of *erfluxing %ela"

  • 7/21/2019 113894818-Transformer-Protection.ppt

    104/116

    104 > Transformer Protection

    #C

    Circuit brea-erposition repeat rela5

    >AA rela5

    0o/er A>'

    *nhibit A>'raise

    Alarm

    enerator field circuitbrea-er trip coil

    '02)2Alarm

    '02)1

    '01)1

    #C

  • 7/21/2019 113894818-Transformer-Protection.ppt

    105/116

    105 > Transformer Protection

    T-ermal *erloa& Protection

    Effect of *erloa& on Transformer,nsulation ife

  • 7/21/2019 113894818-Transformer-Protection.ppt

    106/116

    106 > Transformer Protection

    B 1 11 12 13 14

    :ot spot temp C

    .1

    1.

    1

    1

    'elative

    rateof using

    life

    With ambient of 2 C.

    :ot spot rise of E C is

    design normal.

    A further rise of 7 C

    doubles rate of

    using life.

    B

    *er-eating Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    107/116

    107 > Transformer Protection

    * load

    #setting

    * loadop oil ofpo/ertransformer

    :eater

    hermalreplica

    emperaturesensing resistor

    'emote

    emp. indication0ocal

    !ff

    !n

    !ff

    !n

    Alarm

    rip

    "umpcontrol

    %ancontrol

    *erloa& Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    108/116

    108 > Transformer Protection

    Current

    ime

    !vercurrent protection designed for fault condition

    hermal replica provides better protection for overload

    Current based

    %lexible characteristics

    Single or dual time constant

    'eset facilit5

    =on)volatile

    T-ermal *erloa&il Fille& Transformers

  • 7/21/2019 113894818-Transformer-Protection.ppt

    109/116

    109 > Transformer Protection

    1

    1

    1

    1

    1 2 3 4 7

    rip time ?s@

    Current ?multiple of thermal setting@

    Single

    characteristic9

    D 12 mins

    #ual

    characteristic

    Single

    characteristic9

    D mins

    T-ermal Trip Time

  • 7/21/2019 113894818-Transformer-Protection.ppt

    110/116

    110 > Transformer Protection

    /here D heating time constantD actual current measured b5 rela5

    D continuous current rating of protected plant

    D previous thermal state

    D trip threshold

    D multiplier ?for actual temperature@K

    I

    %(*

    (EF

    KI

    I

    PI

    I

    ln%i#e%ri"

    %(*

    2

    (EF

    2

    REF

    =

    I

    *

  • 7/21/2019 113894818-Transformer-Protection.ppt

    111/116

    111 > Transformer Protection

    Transformer Fee&ers

    Protection of ParallelTransformer Fee&ers

    i &

  • 7/21/2019 113894818-Transformer-Protection.ppt

    112/116

    112 > Transformer Protection

    i&er :>CsCsCsCs

    '*"

    ransformer

    #ifferential

    "rotection

    %eeder

    #ifferential

    "rotection

    "*0!S%eeder

    #ifferential

    "rotection

    '*"&=SA(*0*S$

    '*"

    Transformer Fee&ers

  • 7/21/2019 113894818-Transformer-Protection.ppt

    114/116

    114 > Transformer Protection

    %$$#$

    '

    "*0!

    S"W"

    W

    %or use /here no brea-er separates the transformer from thefeeder.

    ransformer inrush current must be considered.

    *nrush is a transient condition /hich ma5 occur at the instant of

    transformer energisation.

    Lag. *nrush current is not a fault condition

    "rotection must remain stable.

    LC: provides a bloc-ing signal in the presence of inrush

    current and allo/s protection to be used on transformer feeders.

    Transformer Fee&er Protection

  • 7/21/2019 113894818-Transformer-Protection.ppt

    115/116

    115 > Transformer Protection

    8$11

    *2*1

    II

    III

    I

    1 2

    L>W

    2MFA+

    14

    *)% M+M+

    M+%M+%23

    24

    +

    A

    ii

    iii

    i*1*2

    2 1

    +

    A

    25

    2>

    26

    2?

    23

    24

    25

    2>

    26

    2?

    2>

    2?

    1?

    1@

    1>

    1>

    1@

    1?

    1@

    1314

    1>

    1@

    23

    24

    25

    2>

    26

    2?

    23

    2425

    2>

    26

    2?

    1?

    1>

    1

    P541 P542 0 Protectionof Transformer Fee&ers

  • 7/21/2019 113894818-Transformer-Protection.ppt

    116/116

    *o;er transfor#er

    *540

    c&e#e

    Virtual inter"osin +%

    Vectorialcorrection

    (atiocorrection

    Virtual inter"osin +%