113894818-transformer-protection.ppt
TRANSCRIPT
-
7/21/2019 113894818-Transformer-Protection.ppt
1/116
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Transformer Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
2/116
-
7/21/2019 113894818-Transformer-Protection.ppt
3/116
3 > Transformer Protection
Transformer Protection (1)
ransformer Connections
!vercurrent "rotection
#irectional "rotection of "arallel ransformers
"artial #ifferential "rotection of "arallel ransformers
$arth %aults on ransformer Windings
&nrestricted $arth %ault "rotection
'estricted $arth %ault "rotection
(iased #ifferential "rotection of 2 and 3 Winding
ransformers
-
7/21/2019 113894818-Transformer-Protection.ppt
4/116
4 > Transformer Protection
Transformer Protection (2)
Combined #ifferential and 'estricted $arth %ault
"rotection
"rotection of Auto)ransformers
*nter)urn %aults and (uchhol+ "rotection
!verfluxing "rotection
!verload "rotection
ransformer %eeder "rotection
-
7/21/2019 113894818-Transformer-Protection.ppt
5/116
5 > Transformer Protection
Transformer Connections
-
7/21/2019 113894818-Transformer-Protection.ppt
6/116
6 > Transformer Protection
Transformer Protection (3)
A1
I A2
V EP
-
7/21/2019 113894818-Transformer-Protection.ppt
7/1167 > Transformer Protection
A1
I A2
V EP
a1
a2
ES
Transformer Protection (4)
-
7/21/2019 113894818-Transformer-Protection.ppt
8/1168 > Transformer Protection
IS
A1
I A2
V EP
a1
a2
ES
Transformer Protection (5)
P
-
7/21/2019 113894818-Transformer-Protection.ppt
9/1169 > Transformer Protection
A
(
C c
b
aa2a1
b1 b2(1(2
A2 A1
C2 C1 c1 c2
A
(C
C2
C1 A2
A1
(2(1
a
b
cc2
c1
a2
a1
b1 b2
Cloc- face numbers refer to
position of lo/ voltage phase )
neutral vector /ith respect to high
voltage phase ) neutral vector.
0ine connections made to highest
numbered /inding terminal available.
0ine phase designation is same as
/inding.
Transformer Connections
-
7/21/2019 113894818-Transformer-Protection.ppt
10/11610 > Transformer Protection
"hase displacement
roup 1
"hase displacement1
roup 2
0ag phase displacement3
roup 3
0ead phase displacement3
roup 4
5
#d
6d
57
#d7#+7
d1
#51
+1
d11
#511
+11
Transformer Vector Groups
-
7/21/2019 113894818-Transformer-Protection.ppt
11/11611 > Transformer Protection
Cloc- %ace numbers refer to position of lo/ voltage
phase)neutral vector /ith respect to high voltage phaseneutral vector
0ine connections made to highest numbered /inding
terminal available
0ine phase designation is same as /inding
Example 1 !" 11 Transformer
B1B2 b2b1
a2a1A1A2
C1C2 c2c1
8uestion 9 :o/ to connect /indings ;
HighVoltage
Winings
!o"Voltage
Winings
A PhaseWining
s
B PhaseWinings
C PhaseWining
s
Transformer Connections
-
7/21/2019 113894818-Transformer-Protection.ppt
12/11612 > Transformer Protection
3oltage >ectors
#$%
A
C B
a
c
b
!ine Designation
!" 11
-
7/21/2019 113894818-Transformer-Protection.ppt
14/11614 > Transformer Protection
2. #ra/ #elta Connection
a
c
b
A
BC
!" 11
-
7/21/2019 113894818-Transformer-Protection.ppt
15/11615 > Transformer Protection
3. #ra/ A "hase Windings
A
C B
a
b
a2
a1
A2
A1
c
!" 11
-
7/21/2019 113894818-Transformer-Protection.ppt
16/11616 > Transformer Protection
4. Complete Connections ?a@
A
B
a
c
b
a2
a1
A1
C1
C2
B1
B2
b2
b1
c1
c2
C
A2
!" 11
-
7/21/2019 113894818-Transformer-Protection.ppt
17/11617 > Transformer Protection
4. Complete Connections ?b@
c1
c2
b
1
b
2
a1 a2a
b
c
A
B
CC2
C1
B
2
B
1
A2
A1
!" 11
http://additional%20tx%20notes.ppt/ -
7/21/2019 113894818-Transformer-Protection.ppt
18/11618 > Transformer Protection
ransformer rating %use
->A
1
2
3
1
.2
1.
1.
27.22.
17
2
37
B
3.
3.
1.
2.3.
%ull load
current ?A@
'ated
current ?A@
!perating time at
3 x rating?s@
11#V !istri$ution TransformersT"pical Fuse %atings
-
7/21/2019 113894818-Transformer-Protection.ppt
19/11619 > Transformer Protection
Tra&itional 'mall TransformerProtection Pac#age
5
1
3.3k
V200/5 5051
1MVA
3.3/0.44kV1500/5
1500/564
N5
0N
51
N
-
7/21/2019 113894818-Transformer-Protection.ppt
20/11620 > Transformer Protection
Tra&itional e&ium TransformerProtection Pac#age
11&
V'$
'1
'(VA11)#*#&V
1$$$)'
1$$$)'
+,
'
1-
+,
#*#&
-
7/21/2019 113894818-Transformer-Protection.ppt
21/11621 > Transformer Protection
*ercurrent Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
22/11622 > Transformer Protection
'euirements
%ast operation for primar5 short circuits
#iscrimination /ith do/nstream protections
!peration /ithin transformer /ithstand
=on)operation for short or long term overloads
=on)operation for magnetising inrush
Transformer *ercurrent Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
23/116
23 > Transformer Protection
Source:>
0>
1
set to 1.2 ) 1.3 x through fault level
+se of ,nstantaneous *ercurrent Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
24/116
24 > Transformer Protection
Concerns rela5 response to offset /aveforms ?#C
transient@
#efinition
I1 - I2
I2 x 100
I1 D Stead5 state
rms pic- up
current
I2 D %ull5 offset
rms
pic-up
current
I1
I2
D.C.
Transient *erreac-
-
7/21/2019 113894818-Transformer-Protection.ppt
25/116
25 > Transformer Protection
HV2
'1
'1
'1
!VHV1
Ti.e !V
HV1HV2
Cu//entI0!V
1*2I0!V
I0HV
,nstantaneous .ig- 'et *ercurrent%ela" /pplie& to a Transformer
-
7/21/2019 113894818-Transformer-Protection.ppt
26/116
26 > Transformer Protection
I3 I3
I3
I3
0.866
20101 !istri$ution (1)
-
7/21/2019 113894818-Transformer-Protection.ppt
27/116
27 > Transformer Protection
I3.77 I3
.4 sec
0> rela5
:> rela5
20101 !istri$ution (2)
-
7/21/2019 113894818-Transformer-Protection.ppt
28/116
28 > Transformer Protection
rid suppl5%eeders
1
1
7E
7E
1
1
Parallel Transformers!irectional %ela"s (1)
P ll l T f
-
7/21/2019 113894818-Transformer-Protection.ppt
29/116
29 > Transformer Protection
11
1
1
(usSection
Parallel Transformers!irectional %ela"s (2)
rid suppl5%eeders
1
P ll l T f
-
7/21/2019 113894818-Transformer-Protection.ppt
30/116
30 > Transformer Protection
Advantage 9 'educed number of gradingsta es
+
3
+
3 '1
'1
'1
'1
P1
P1
S1
S1
S2
S2
P2
P2
rid suppl5
Parallel TransformersPartial !ifferential 'c-eme
-
7/21/2019 113894818-Transformer-Protection.ppt
31/116
31 > Transformer Protection
Eart- Fault Protection
T f E t- F lt
-
7/21/2019 113894818-Transformer-Protection.ppt
32/116
32 > Transformer Protection
1 p.u. turns3 p.u. turns
x*"
"'
' *%"rotective'ela5
:3ratioturnsEffective
.3
.currentFault:atfaultaFor
.3
current!"ri#ar$%&us!valuesloa'fulltocurrentE/Fli#its(esistor
F.).2
F.).
F.).*
=
==
=
secon'ar$+.%.t&enr!transfor#eofcurrentloa'
fullon,ase'issi'e-"ri#ar$onratio+.%./f
3
circuit2
=
Transformer Eart- Faults
t % l ' iti it
-
7/21/2019 113894818-Transformer-Protection.ppt
33/116
33 > Transformer Protection
I0
51
vercurrent
(ela$
I4as .ulti5le
o4 I0*!*
1*$
$*6
$*7
$*3
$*+
$*'
$*,
$*#
$*2
$*1
Sta/Sie
DeltaSie
$*1$*2 $*# $*, $*' $*+ $*3 $*7 $*6 1*$
5*u**89e/cu//ent Rela: Setting ;
I0*!*
*ercurrent %ela" 'ensiti*it"to Eart- Faults (1)
t % l ' iti it
-
7/21/2019 113894818-Transformer-Protection.ppt
34/116
34 > Transformer Protection
1$
6
7
3
+
'
,
#
2 1
$*1 $*2 $*# $*, $*' $*+ $*3 $*7 $*6 1*$
5*u**
I4as .ulti5le
o4 I0*!*
Sta/Sie
DeltaSie
*ercurrent %ela" 'ensiti*it"to Eart- Faults (2)
I0
51
vercurrent
(ela$
t % l ' iti it
-
7/21/2019 113894818-Transformer-Protection.ppt
35/116
35 > Transformer Protection
I0
IP I-
1$
6
7
3 +
'
,
#
2 1
$*1$*2 $*#$*,$*'$*+ $*3 $*7$*61*$
5*u**
I-
IP
I0
*ercurrent %ela" 'ensiti*it"to Eart- Faults (3)
I4as .ulti5le
o4 I0*!*
E t- F lt T f i &i
-
7/21/2019 113894818-Transformer-Protection.ppt
36/116
36 > Transformer Protection
#ifferential 'ela5 Setting F of Star Winding "rotected1F F
2F 41F
3F 2F
4F 1EF
F EF
Eart- Fault on Transformer in&ing
I
#ifferential'ela5
Setting < IS
%or rela5 operation, IG IS
e.g. *f ISD 2F, then G 2F for operation
i.e.
G BF
hus BF of /inding is not protected
2
3ID
2
3
+nrestricte& Eart-fault Protection (1)
-
7/21/2019 113894818-Transformer-Protection.ppt
37/116
37 > Transformer Protection
"rovides bac-)up protection for s5stem
ime dela5 reuired for co)ordination
+nrestricte& Eart-fault Protection (1)
'1
'1
'1
'1-
+nrestricte& Eart-fault Protection (2)
-
7/21/2019 113894818-Transformer-Protection.ppt
38/116
38 > Transformer Protection
Can provide better sensitivit5
?C.. ratio not related to full load current@
?*mproved effective setting@
"rovides bac- up protection for transformer and s5stem
'1
'1
'1
'1-'1
-
+nrestricte& Eart-fault Protection (2)
'tar in&ing %EF
-
7/21/2019 113894818-Transformer-Protection.ppt
39/116
39 > Transformer Protection
"rotected
6one
'$
%
'ela5 onl5 operates for earthfaults /ithin protected +one.
&ses high impedance principle.
Stabilit5 level 9 usuall5 maximum through fault level of
transformer
'tar in&ing %EF
%estricte& EF Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
40/116
40 > Transformer Protection
0> restricted $H%
protection trips
both :> and 0> brea-er
'ecommended setting 9 1F
rated
%estricte& EF Protectiono Voltage in&ings (1)
A ( C =
%estricte& EF Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
41/116
41 > Transformer Protection
A ( C =
0> restricted $H% protection trips both :> and 0> brea-er
'ecommended setting 9 1F rated
%estricte& EF Protectiono Voltage in&ings (2)
!elta in&ing %estricte& Eart- Fault
-
7/21/2019 113894818-Transformer-Protection.ppt
42/116
42 > Transformer Protection
"rotected +one
'$%
Source
#elta /inding cannot suppl5 +ero seuence current tos5stem
Stabilit5 9 Consider max 0> fault level
'ecommended setting 9 less than 3F minimum earth fault
level
!elta in&ing %estricte& Eart- Fault
.ig- ,mpe&ance Principle
-
7/21/2019 113894818-Transformer-Protection.ppt
43/116
43 > Transformer Protection
P/otecteCi/cuit
R
=
(
RCT
R!
=
(
RCT
R!I0
IS
RS
T
VS
R! R!
.ig- ,mpe&ance Principle
>oltage Across 'ela5 Circuit >S D I%?'CI 2'0@
Stabilising resistor 'Slimits spill current to IS?rela5 setting@
'SD ) '' /here ''D rela5 burden
C -nee point
>J"
D 2>SD 2I
%?'
CI 2'
0@
>S
IS
on0inear %esistors (etrosils)
-
7/21/2019 113894818-Transformer-Protection.ppt
44/116
44 > Transformer Protection
#uring internal faults the high impedance rela5 circuit
constitutes an excessive burden to the CKs.
A ver5 high voltage develops across the rela5 circuit and
the CKs.
Causes damage to insulation of C, secondar5/inding and rela5.
Lagnitude of pea- voltage >"is given b5 an approximate
formula ?based on experimental results@
>" D 2 2>J?>%) >J@
Where >% D S/gr. %ault 'ating in amps x 6 of rela5
circuit C ratio
M setting
Letrosil reuired if >" G 3->
on0inear %esistors (etrosils)
on0inear %esistors (etrosils)
-
7/21/2019 113894818-Transformer-Protection.ppt
45/116
45 > Transformer Protection
I8P
RST
VSV(
RR
Letrosil Characteristic
> D C *
Suitable values of C N
chosen based on 9
Lax secondar5 current under fault conditions
'ela5 setting voltage
on0inear %esistors (etrosils)
%EF Protection Example
-
7/21/2019 113894818-Transformer-Protection.ppt
46/116
46 > Transformer Protection
1(VA'>11$$$V,1'V
1+$$)1
RCTalue of stabilising
resistor reuired
3@ $ffective setting
4@ "ea- voltage
developed b5 CKs
for internal fault
%EF Protection Example
'olution (1)
-
7/21/2019 113894818-Transformer-Protection.ppt
47/116
47 > Transformer Protection
$arth fault calculation 9)
&sing L>A base
Source impedance D 1 p.u.
ransformer impedance D . x D 4 p.u.
1
otal impedance D 14
p.u.
*1 D 1 D .E14 p.u. 14
(ase current D x 17
3 x 41
D 1112B7 Amps
*% D 3 x .E14 x 1112B7 D 234 Amps ?primar5@
D 14.B Amps ?secondar5@
1 ".&.1 4
I1
4
I2
4
I
Seuence #iagram
'olution (1)
'olution (2)
-
7/21/2019 113894818-Transformer-Protection.ppt
48/116
48 > Transformer Protection
?1@ Setting voltage>S D I%?'CI 2'0@
Assuming earth C saturates,
'C D 4. ohms
2'0D 2 x 1 x E.41 x 1)3 D 1.42 ohms
Setting voltage D 14.B ?4. I 1.42@
D B3.7 >olts
?2@ Stabilising 'esistor ?'S@
'S D >S ) 1
IS IS2 Where *SD rela5 current setting
'S D B3.7 ) 1 D 37 ohms
.1 .12
'olution (2)
'olution (3)
-
7/21/2019 113894818-Transformer-Protection.ppt
49/116
49 > Transformer Protection
1.7
1.2
.
.4
.4 .12.
AHmm?multipl5 b5 Ji to obtain total
exciting current in Amps@
WeberHm2?esla@
?multipl5b5Jv
toobtain'LS
secondar5volts@
Jv Ji
0ine N 1 .341=eutral C
$arth C 237 .2E
'olution (3)
'olution (4)
-
7/21/2019 113894818-Transformer-Protection.ppt
50/116
50 > Transformer Protection
?3@ $ffective setting I" D C ratio x ?IS I ILA@
0ine N =eutral Cs
%lux densit5 at B3.7> D B3.7 D .B2 esla
1
%rom graph, mag. %orce at .B2 esla D .1 AHmm
Lag. Current D .1 x .341 D .1 Amps
O$arthK C
%lux densit5 at B3.7> D B3.7 D .3B7 esla
237
%rom graph, mag. %orce at .3B7 esla D .12 AHmm
Lag. Current D .12 x .2E D .33 Amps
hus, effective setting D 17 x ?.1 I P?4 x .1@ I .33Q@
$ffective setting D 1B Amps
ransformer full load current D 13B1 Amps
$ffective setting D 1B x 1F D 14.2F x rated
13B1
'olution (4)
'olution (5)
-
7/21/2019 113894818-Transformer-Protection.ppt
51/116
51 > Transformer Protection
?4@ "ea- voltage D 22>J?>% ) >J@
>% D 14.B x >S D 14.B x B37 D 13B47 >olts
IS
%or O$arthK C, >J D 1.4 x 237 D 33 >olts ?from graph@
>"$AJ D 22 x 33 x ?13B47 ) 33@
D 7->hus, Letrosil voltage limiter /ill be reuired.
'olution (5)
Parallel Transformers
-
7/21/2019 113894818-Transformer-Protection.ppt
52/116
52 > Transformer Protection
A=
1
(us Section
2
41 >olt
S/itchboard
C(
Parallel Transformers
Parallel Transformers
-
7/21/2019 113894818-Transformer-Protection.ppt
53/116
53 > Transformer Protection
A=1
(us Section!pen
2
41 >olt
S/itchboar
d
C(
1=
1=
Parallel TransformersCT in Eart-
Parallel Transformers CT in
-
7/21/2019 113894818-Transformer-Protection.ppt
54/116
54 > Transformer Protection
1
(us Section!pen
2
41 >olt
S/itchboar
d
1=
1=
A= C(
Parallel Transformers CT inEart- an& eutral
-
7/21/2019 113894818-Transformer-Protection.ppt
55/116
Tra&itional arge Transformer
-
7/21/2019 113894818-Transformer-Protection.ppt
56/116
56 > Transformer Protection
Tra&itional arge TransformerProtection Pac#age
33J
>
1
2H
1L>A33H11J> 1= E
7H
74
7H
HA
-
7/21/2019 113894818-Transformer-Protection.ppt
57/116
57 > Transformer Protection
!ifferential Protection
!ifferential Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
58/116
58 > Transformer Protection
!verall differential protection ma5 be Rustified for
larger transformers ?generall5 G L>A@. "rovides fast operation on an5 /inding
Leasuring principle 9
(ased on the same circulating current principle as the
restricted earth fault protection
:o/ever, it emplo5s the biasing techniue, to maintain
stabilit5 for heav5 through fault current
(iasing allo/s mismatch bet/een C outputs.
*t is essential for transformers /ith tap changing
facilit5.
Another important reuirement of transformer
differential protection is immunit5 to magnetising in
rush current.
6iase& !ifferential 'c-eme
-
7/21/2019 113894818-Transformer-Protection.ppt
59/116
59 > Transformer Protection
(*AS(*AS I2I1
!"$'A$
I1-
I2
#ifferential
Current
!"$'A$
'$S'A*=
Lean hroughCurrent
I1+
I2
2
I1-
I2
!ifferential Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
60/116
60 > Transformer Protection
0>
'
:>
"'!$C$#
6!=$
Correct application of differential protection reuires C ratio
and /inding connections to match those of transformer.
C secondar5 circuit should be a replica of primar5 s5stem.
Consider 9
?1@ #ifference in current magnitude
?2@ "hase shift
?3@ 6ero seuence currents
!ifferential Connections
-
7/21/2019 113894818-Transformer-Protection.ppt
61/116
61 > Transformer Protection
"1 "2 A2 A1 a1 a2 "2 "1
A ( C
+se of ,nterposing CT
-
7/21/2019 113894818-Transformer-Protection.ppt
62/116
62 > Transformer Protection
''
'
"1 "2 A2 A1 a1 a2 "2 "1
S2 S1 "1 "2
*nterposing C provides 9>ector correction
'atio correction
6ero seuence compensation
S1 S2 S2 S1
p g
!ifferential Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
63/116
63 > Transformer Protection
S2S1
"1"2A1A2 a2a1"2
1L>A
77-> H 11->1H H
"1
#51
S1S2
iven above9 =eed to consider )
?1@ Winding full load current ?2@ $ffect of tap changer ?if an5@
?3@ C.. polarities
Assuming no tap changer
%ull load currents9) 77->9 131 Amp D 4.3E Amps secondar5
11->9 EE Amp D 4.B2 Amps secondar5
:o/ever, reuire 11-> C..Ks to be connected in
hus, secondar5 current D 3 x 4.B2 D .2A
RATIO CORRECTION IS REQUIRED
!ifferential Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
64/116
64 > Transformer Protection
''
'
"1 "2 A2 A1 a1 a2 "2 "1
S1 S2 "1 "2
4.B2A
S1 S2 S2 S1
4.3EA
?2.7@ ?@
1H H
*t is usual to connect 11-> C..Ks in and utilise a H interposing C.. ?this
method reduces lead >A burden on the line C..Ks@
Current from 77-> side D 4.3E Amphus, current reuired from /inding of int. C.. D 4.3E Amp
Current input to /inding of int. C.. D 4.B2 Amp
'euired int C.. ratio D 4.B2 H 4.3E D 4.B2 H 2.2
3
La5 also be expressed as 9 H 2.7
Effect of Tap C-anger
-
7/21/2019 113894818-Transformer-Protection.ppt
65/116
65 > Transformer Protection
e.g. Assume 77-> IF, )1F
*nterposing C.. ratio should be based on mid tap position
Lid ap ?)F@ D 72.E ->
"rimar5 current ?1 L>A@ D 13 Amp
Secondar5 current D 4.7 Amp
*nterposing C.. ratio reuired D 4.B2 H 4.7
3
? H @
D 4.B2 H 2.77
La5 also be expressed as 9 H 2.E
Compared /ith H 2.7 based on nominal voltage
Connections C-ec#
-
7/21/2019 113894818-Transformer-Protection.ppt
66/116
66 > Transformer Protection
/r$itrar" Current !istri$ution
'
'
'
S1 S2 S2 S1
"1 "2 A2 A1 a1 a2 "2 "1
S2 S1 "1 "2
Connections C-ec#
-
7/21/2019 113894818-Transformer-Protection.ppt
67/116
67 > Transformer Protection
/&& !elta in&ing Current
'
'
'
"1 "2 A2 A1 a1 a2 "2 "1
S2 S1 "1 "2
S1 S2 S2 S1
Connections C-ec#
-
7/21/2019 113894818-Transformer-Protection.ppt
68/116
68 > Transformer Protection
Complete Primar" !istri$ution
'
'
'
"1 "2 A2 A1 a1 a2 "2 "1
S2 S1 "1 "2
S1 S2 S2 S1
Connections C-ec#
-
7/21/2019 113894818-Transformer-Protection.ppt
69/116
69 > Transformer Protection
Complete 'econ&ar" !istri$ution
'
'
'
"1 "2 A2 A1 a1 a2 "2 "1
S2 S1 "1 "2
S1 S2 S2 S1
,n07one Eart-ing Transformer
-
7/21/2019 113894818-Transformer-Protection.ppt
70/116
70 > Transformer Protection
"2"1a2a1
A2A1 "1"2
S1S2
S1S2 12 "2"1
,n07one Eart-ing Transformer/lt ti (1)
-
7/21/2019 113894818-Transformer-Protection.ppt
71/116
71 > Transformer Protection
/lternati*e (1)"2"1
a2a1A2A1 "1"2
S1S2
"2"1S1S2
,n07one Eart-ing Transformer/lt ti (2)
-
7/21/2019 113894818-Transformer-Protection.ppt
72/116
72 > Transformer Protection
3H1
/lternati*e (2)
BH1
! #*%%$'$=*A0
'$0A
$A':*=
'A=S%.
,n07one Eart-ing Transformer/lt ti (3)
-
7/21/2019 113894818-Transformer-Protection.ppt
73/116
73 > Transformer Protection
$A':*=
'A=S%.
3H1
! #*%%$'$=*A0
'$0A
1H.33
/lternati*e (3)
3H1
Com$ine& !ifferential an&% t i t & E t- F lt P t ti
-
7/21/2019 113894818-Transformer-Protection.ppt
74/116
74 > Transformer Protection
o differential rela5
S2
S1
"1
"2'$%
S2
S1"1
"2
S2S1"1 "2
a2a1A1A2
%estricte& Eart- Fault Protection
Com$ine& !ifferential an&E t- F lt P t ti
-
7/21/2019 113894818-Transformer-Protection.ppt
75/116
75 > Transformer Protection
&sing Summation Auxiliar5 Current ransformer
'estricted earth
fault rela5
(ias /indings
E E E#ifferential rela5
operating /indings
74
Eart- Fault Protection
*AE a
%1
-
7/21/2019 113894818-Transformer-Protection.ppt
76/116
76 > Transformer Protection
A*AE ,
A*AE c
A
N7 77
EF%2
%3
%4
(,
2(,2
(,2
(o (o(o
F
VE(A)) 8FFE(EN%A)
(E)A9
%1
T-ree in&ing Transformer
-
7/21/2019 113894818-Transformer-Protection.ppt
77/116
77 > Transformer Protection
2L>
A
11J>
73L>
A
132J>
17H3H
L>
A
33J>
1H
4.B
2.
1.33
2.
.1
All interp!in" C.T. r#ti$! re%ert &''n ()A *#!e 63()A,
Tra&itional +se of ,nterposing CT
-
7/21/2019 113894818-Transformer-Protection.ppt
78/116
78 > Transformer Protection
#51?)3
-
7/21/2019 113894818-Transformer-Protection.ppt
79/116
79 > Transformer Protection
8ifferentialele#ent
Nu#eric(ela$
Virtual inter"osin +%
Vectorialcorrection
(atio
correction
Virtual inter"osin +%
Compensation
*o;er transfor#er
Transformer agnetisingC-aracteristic
-
7/21/2019 113894818-Transformer-Protection.ppt
80/116
80 > Transformer Protection
/ice=ormal
%lux
=ormal
%lux
=ormal=o 0oadCurrent
=o 0oad Currentat /ice =ormal
%lux
C-aracteristic
agnetising ,nrus- Current'tea&" 'tate
-
7/21/2019 113894818-Transformer-Protection.ppt
81/116
81 > Transformer Protection
'
'
+
-
)
'I
'tea&" 'tate
agnetising ,nrus- Current'itc- on at Voltage 7ero o resi&ual flux
-
7/21/2019 113894818-Transformer-Protection.ppt
82/116
82 > Transformer Protection
'
'2
)
I
'itc- on at Voltage 7ero 0 o resi&ual flux
Transformer !ifferential ProtectionEffect of agnetising Current
-
7/21/2019 113894818-Transformer-Protection.ppt
83/116
83 > Transformer Protection
Effect of agnetising Current
Appears on one side of transformer onl5
Seen as fault b5 differential rela5
=ormal stead5 state magnetising current is less thanrela5 setting
ransient magnetising inrush could cause rela5 to
operate
Transformer !ifferential ProtectionEffect of agnetising ,nrus-
-
7/21/2019 113894818-Transformer-Protection.ppt
84/116
84 > Transformer Protection
Effect of agnetising ,nrus-
S!0&*!= 1 9 *L$ #$0A
Allo/s magnetising current to die a/a5 before rela5 canoperate
Slo/ operation for genuine transformer faults
Transformer !ifferential ProtectionEffect of agnetising ,nrus-
-
7/21/2019 113894818-Transformer-Protection.ppt
85/116
85 > Transformer Protection
Effect of agnetising ,nrus-
S!0&*!= 2 9 2=# ?and :@ :A'L!=*C '$S'A*=
La-es rela5 immune to magnetising inrush
Slo/er operation ma5 result for genuine transformer faults
if C saturation occurs
&sed in LiC!L "73x
Transformer !ifferential ProtectionEffect of agnetising ,nrus-
-
7/21/2019 113894818-Transformer-Protection.ppt
86/116
86 > Transformer Protection
Effect of agnetising ,nrus-
S!0&*!= 3 9 A" L$AS&'$L$= $C:=*8&$
*nhibits rela5 operation during magnetising inrush
!perate speed for genuine transformer faults unaffected b5
significant C saturation
&sed in L(C: N J(C: rela5s
T"pical agnetising ,nrus-a*eforms
-
7/21/2019 113894818-Transformer-Protection.ppt
87/116
87 > Transformer Protection
A
C
a*eforms
!etection of T"picalagnetising ,nrus- (58.9)
-
7/21/2019 113894818-Transformer-Protection.ppt
88/116
88 > Transformer Protection
#ifferential
comparator
1 D ms 2 D 22ms
rip
(ias
#ifferential
hreshold
agnetising ,nrus- (58.9)
%estraint for Transformeragnetising ,nrus-
-
7/21/2019 113894818-Transformer-Protection.ppt
89/116
89 > Transformer Protection
agnetising ,nrus-
#ifferential
comparator
(ias
#ifferential
hreshold
rip
1 D ms 2 D 22ms
#ifferential input
Comparator output
rip
'eset2
1
peration for Transformer Faults
-
7/21/2019 113894818-Transformer-Protection.ppt
90/116
90 > Transformer Protection
#ifferential
comparator
(ias
#ifferential
hreshold
rip
1 D ms 2 D 22ms
#ifferential input
Comparator output
rip
'eset2
1
Protection of /uto0Transformer $".ig- ,mpe&ance !ifferential %ela"s
-
7/21/2019 113894818-Transformer-Protection.ppt
91/116
91 > Transformer Protection
?a@ $arth %ault Scheme
A
(
C
:igh impedance
rela5E
.ig- ,mpe&ance !ifferential %ela"s
Protection of /uto0Transformer $".ig- ,mpe&ance !ifferential %ela"s
-
7/21/2019 113894818-Transformer-Protection.ppt
92/116
92 > Transformer Protection
A
(
C
a
b
c
E E E
n
.ig- ,mpe&ance !ifferential %ela"s
?b@ "hase and $arth %ault Scheme
-
7/21/2019 113894818-Transformer-Protection.ppt
93/116
93 > Transformer Protection
,nter0Turn Fault Protection
,nter0Turn Fault
-
7/21/2019 113894818-Transformer-Protection.ppt
94/116
94 > Transformer Protection
=ominal turns ratio
%ault turns ratio
Current ratio
) 11, H 24
) 11, H 1
) 1 H 11,
'euires (uchhol+rela5
C
$
Shorted
turn
0oad
,nterturn Fault Current um$erof Turns '-ort Circuite&
-
7/21/2019 113894818-Transformer-Protection.ppt
95/116
95 > Transformer Protection
1
7
4
2
1 1 2 2
1
7
4
2
%ault current in short
circuited turns
"rimar5 input current
%ault current
?multiples ofrated current@
"rimar5 current
?multiples ofrated current@
urn short)circuited ?percentage of /inding@
of Turns '-ort Circuite&
6uc--ol9 %ela" ,nstallation
-
7/21/2019 113894818-Transformer-Protection.ppt
96/116
96 > Transformer Protection
x internal pipe
diameter ?minimum@
3 x internal pipe
diameter ?minimum@
ransformer
3 minimum
!il conservator
Conservator
6uc--ol9 %ela"
-
7/21/2019 113894818-Transformer-Protection.ppt
97/116
97 > Transformer Protection
"etcoc-
Counter balance/eight
!il level
%rom transformer
Aperture adRuster
#eflector plate#rain plug
rip buc-et
o oilconservator
Lercur5 s/itch
Alarm buc-et
-
7/21/2019 113894818-Transformer-Protection.ppt
98/116
98 > Transformer Protection
*erfluxing Protection
*erfluxing
-
7/21/2019 113894818-Transformer-Protection.ppt
99/116
99 > Transformer Protection
enerator transformers
rid transformers
&suall5 onl5 a problem during run)up or shut do/n, but can be
caused b5 loss of load H load shedding etc.
%lux >
f
$ffects of overfluxing 9 *ncrease in magnetising current
*ncrease in /inding temperature
*ncrease in noise and vibration
!verheating of laminations and metal parts ?caused b5 stra5 flux@
"rotective rela5 responds to >Hf ratio Stage 1 ) lo/er A.>.'.
Stage 2 ) rip field
*erfluxing 6asic T-eor"
-
7/21/2019 113894818-Transformer-Protection.ppt
100/116
100 > Transformer Protection
m2
*e
m
> D -f
CA&S$S0o/ freuenc5
:igh voltage
eomagnetic disturbances
$%%$CS
ripping of differential element ?ransient overfluxing@
#amage to transformers ?"rolonged overfluxing@
V.9 *erfluxing Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
101/116
101 > Transformer Protection
> f
J
rip and alarm outputs for clearing prolonged overfluxing
Alarm 9 #efinite time characteristic to initiate corrective action
rip 9 *#L or # characteristic to clear overfluxing condition
Settings
"ic-)up 1. to 3. i.e. 11> x 1. D 2.31
:+
# setting range .1 to 7 seconds
V.9 C-aracteristics
-
7/21/2019 113894818-Transformer-Protection.ppt
102/116
102 > Transformer Protection
1
1
1
11 1.1 1.2 1.3 1.4 1. 1.7
L D
!perating
time ?s@
> :+
Setting
J D 73J D 4
J D 2
J D
J D 1
t D . I .1 x J
?L ) 1@2
$nables co)ordination /ith plant /ithstand characteristics
*erfluxing %ela"
-
7/21/2019 113894818-Transformer-Protection.ppt
103/116
103 > Transformer Protection
'0
A>'
$x
>
/pplication of *erfluxing %ela"
-
7/21/2019 113894818-Transformer-Protection.ppt
104/116
104 > Transformer Protection
#C
Circuit brea-erposition repeat rela5
>AA rela5
0o/er A>'
*nhibit A>'raise
Alarm
enerator field circuitbrea-er trip coil
'02)2Alarm
'02)1
'01)1
#C
-
7/21/2019 113894818-Transformer-Protection.ppt
105/116
105 > Transformer Protection
T-ermal *erloa& Protection
Effect of *erloa& on Transformer,nsulation ife
-
7/21/2019 113894818-Transformer-Protection.ppt
106/116
106 > Transformer Protection
B 1 11 12 13 14
:ot spot temp C
.1
1.
1
1
'elative
rateof using
life
With ambient of 2 C.
:ot spot rise of E C is
design normal.
A further rise of 7 C
doubles rate of
using life.
B
*er-eating Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
107/116
107 > Transformer Protection
* load
#setting
* loadop oil ofpo/ertransformer
:eater
hermalreplica
emperaturesensing resistor
'emote
emp. indication0ocal
!ff
!n
!ff
!n
Alarm
rip
"umpcontrol
%ancontrol
*erloa& Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
108/116
108 > Transformer Protection
Current
ime
!vercurrent protection designed for fault condition
hermal replica provides better protection for overload
Current based
%lexible characteristics
Single or dual time constant
'eset facilit5
=on)volatile
T-ermal *erloa&il Fille& Transformers
-
7/21/2019 113894818-Transformer-Protection.ppt
109/116
109 > Transformer Protection
1
1
1
1
1 2 3 4 7
rip time ?s@
Current ?multiple of thermal setting@
Single
characteristic9
D 12 mins
#ual
characteristic
Single
characteristic9
D mins
T-ermal Trip Time
-
7/21/2019 113894818-Transformer-Protection.ppt
110/116
110 > Transformer Protection
/here D heating time constantD actual current measured b5 rela5
D continuous current rating of protected plant
D previous thermal state
D trip threshold
D multiplier ?for actual temperature@K
I
%(*
(EF
KI
I
PI
I
ln%i#e%ri"
%(*
2
(EF
2
REF
=
I
*
-
7/21/2019 113894818-Transformer-Protection.ppt
111/116
111 > Transformer Protection
Transformer Fee&ers
Protection of ParallelTransformer Fee&ers
i &
-
7/21/2019 113894818-Transformer-Protection.ppt
112/116
112 > Transformer Protection
i&er :>CsCsCsCs
'*"
ransformer
#ifferential
"rotection
%eeder
#ifferential
"rotection
"*0!S%eeder
#ifferential
"rotection
'*"&=SA(*0*S$
'*"
Transformer Fee&ers
-
7/21/2019 113894818-Transformer-Protection.ppt
114/116
114 > Transformer Protection
%$$#$
'
"*0!
S"W"
W
%or use /here no brea-er separates the transformer from thefeeder.
ransformer inrush current must be considered.
*nrush is a transient condition /hich ma5 occur at the instant of
transformer energisation.
Lag. *nrush current is not a fault condition
"rotection must remain stable.
LC: provides a bloc-ing signal in the presence of inrush
current and allo/s protection to be used on transformer feeders.
Transformer Fee&er Protection
-
7/21/2019 113894818-Transformer-Protection.ppt
115/116
115 > Transformer Protection
8$11
*2*1
II
III
I
1 2
L>W
2MFA+
14
*)% M+M+
M+%M+%23
24
+
A
ii
iii
i*1*2
2 1
+
A
25
2>
26
2?
23
24
25
2>
26
2?
2>
2?
1?
1@
1>
1>
1@
1?
1@
1314
1>
1@
23
24
25
2>
26
2?
23
2425
2>
26
2?
1?
1>
1
P541 P542 0 Protectionof Transformer Fee&ers
-
7/21/2019 113894818-Transformer-Protection.ppt
116/116
*o;er transfor#er
*540
c&e#e
Virtual inter"osin +%
Vectorialcorrection
(atiocorrection
Virtual inter"osin +%