1mrk502033-uen - en application manual generator protection reg650 iec
TRANSCRIPT
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
1/347
Relion 650 series
Generator protection REG650Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
2/347
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
3/347
Document ID: 1MRK 502 033-UENIssued: February 2011
Revision: -Product version: 1.1
Copyright 2011 ABB. All rights reserved
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
4/347
CopyrightThis document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.
TrademarksABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
http://http//WWW.ABB.COM/SUBSTATIONAUTOMATION -
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
5/347
DisclaimerThe data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
6/347
ConformityThis product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
7/347
Table of contentsSection 1 Introduction.....................................................................15
This manual......................................................................................15
Intended audience............................................................................1 5
Product documentation.....................................................................16
Product documentation set..........................................................16
Document revision history...........................................................17
Related documents......................................................................17
Symbols and conventions.................................................................18
Safety indication symbols............................................................18
Manual conventions.....................................................................19
Section 2 Application......................................................................21REG650 application..........................................................................21
Available functions............................................................................24
Main protection functions.............................................................24
Back-up protection functions.......................................................24
Control and monitoring functions.................................................25
Designed to communicate...........................................................27
Basic IED functions.....................................................................28
REG650 application examples.........................................................28Adaptation to different applications.............................................28
Single generator connected via a unit transformer to a
High Voltage (HV) system......................................................30
Single generator, including the auxiliary transformer,
connected via an unit transformer to a High Voltage
(HV) system............................................................................31
Generating unit, including both generator and unit
transformer, connected to a solidly earthed High
Voltage (HV) system..............................................................32
Generating unit, including both generator and unit
transformer, connected to a high impedance earthedHigh Voltage (HV) system......................................................33
Functionality table..................................................................34
Single generator/transformer unit, connected to a solidly
earthed High Voltage (HV) system, with redundant
protection................................................................................37
Single generator/transformer unit, connected to a high
impedance earthed High Voltage (HV) system, with
redundant protection..............................................................38
Two generators having one three-winding unit
transformer, connected to a solidly earthed High
Table of contents
1
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
8/347
Voltage (HV) system, with redundant protection with unit
differential protection including the generators.......................39
Two generators having one three-winding unit
transformer, connected to a solidly earthed High
Voltage (HV) system, with redundant protection with unit
transformer differential protection...........................................40
Functionality table..................................................................41
Section 3 REG650 setting examples..............................................45Calculating general settings for analogue TRM inputs 4I 1I 5U.......47
Calculating general settings for analogue AIM inputs 6I 4U.............48
Preprocessing blocks SMAI..............................................................49
Calculating settings for global base values for setting function
GBSVAL...........................................................................................50
Calculating settings for generator differential protectionGENPDIF..........................................................................................51
Calculating settings for underimpedance protection for
generators and transformers ZGPDIS .............................................52
Calculating settings for zone 1....................................................53
Calculating settings for zone 2....................................................53
Calculating settings for zone 3....................................................54
Calculating settings for the Load encroachment function............54
Calculating settings for out-of-step protection OOSPPAM ..............56
Calculating settings for loss of excitation LEXPDIS ........................61
Negative-sequence time overcurrent protection for machinesNS2PTOC ........................................................................................65
Calculating settings for four step phase overcurrent protection
OC4PTOC........................................................................................65
Calculating settings for generator phase overcurrent
protection.....................................................................................65
Calculating settings for step 1................................................65
Calculating settings for step 2................................................66
Calculating settings for auxiliary transformer phase
overcurrent protection..................................................................66
Calculating settings for step 1................................................67
Calculating settings for step 4................................................67
100% Stator earth fault protection, 3rd harmonic based
STEFPHIZ .......................................................................................68
Stator earth fault protection (neutral point voltage)..........................70
Section 4 Analog inputs..................................................................71Introduction.......................................................................................71
Setting guidelines.............................................................................71
Setting of the phase reference channel.......................................71
Example.................................................................................71
Setting of current channels.....................................................71
Table of contents
2
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
9/347
Example 1..............................................................................72
Example 2..............................................................................73
Examples how to connect, configure and set CT inputs
for most commonly used CT connections..............................74Example how to connect star connected three-phase
CT set to the IED....................................................................75
Example how to connect single-phase CT to the IED............77
Setting of voltage channels....................................................79
Example.................................................................................79
Examples how to connect, configure and set VT inputs
for most commonly used VT connections..............................80
Examples how to connect three phase-to-earth
connected VTs to the IED......................................................81
Example how to connect the open delta VT to the IED
for high impedance earthed or unearthed..............................82
Example how to connect the open delta VT to the IED
for low impedance earthed or solidly earthed power
systems..................................................................................84
Example how to connect the neutral point VT to the IED.......86
Section 5 Local human-machine interface.....................................89Local HMI.........................................................................................89
Display.........................................................................................90
LEDs............................................................................................91
Keypad........................................................................................92Local HMI functionality................................................................94
Protection and alarm indication..............................................94
Parameter management ........................................................96
Front communication..............................................................97
Single-line diagram.................................................................97
Section 6 Differential protection.....................................................99Transformer differential protection....................................................99
Identification................................................................................99
Application...................................................................................99
Setting guidelines......................................................................100
Inrush restraint methods.......................................................100
Overexcitation restraint method...........................................100
Cross-blocking between phases..........................................101
Restrained and unrestrained differential protection..............101
Elimination of zero sequence currents.................................102
External/Internal fault discriminator......................................103
Differential current alarm......................................................105
Switch onto fault feature.......................................................105
Setting example.........................................................................105
Table of contents
3
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
10/347
Summary and conclusions...................................................105
1Ph High impedance differential protection HZPDIF .....................107
Identification..............................................................................107
Application.................................................................................107The basics of the high impedance principle.........................107
Connection examples................................................................113
Connections for 1Ph restricted earth fault and high
impedance differential protection.........................................113
Setting guidelines......................................................................114
Configuration........................................................................114
Settings of protection function..............................................114
Restricted earth fault protection REF...................................115
Alarm level operation............................................................117
Generator differential protection GENPDIF ...................................118Identification..............................................................................118
Application.................................................................................118
Setting guidelines......................................................................120
General settings...................................................................120
Percentage restrained differential operation........................121
Negative sequence internal/external fault discriminator
feature..................................................................................123
Otheradditional options.......................................................124
Open CT detection...............................................................125
Section 7 Impedance protection...................................................127Underimpedance protection for generators and transformers
ZGPDIS .........................................................................................127
Identification..............................................................................127
Application.................................................................................127
Setting guidelines......................................................................127
Loss of excitation LEXPDIS............................................................129
Identification..............................................................................129
Application.................................................................................129
Setting guidelines......................................................................135
Out-of-step protection OOSPPAM .................................................138
Identification..............................................................................138
Application.................................................................................139
Setting guidelines......................................................................142
Load enchroachment LEPDIS........................................................145
Identification..............................................................................145
Application.................................................................................145
Setting guidelines......................................................................145
Resistive reach with load encroachment characteristic........145
Table of contents
4
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
11/347
Section 8 Current protection.........................................................147Four step phase overcurrent protection OC4PTOC.......................147
Identification..............................................................................147
Application.................................................................................147
Setting guidelines......................................................................148
Settings for steps 1 to 4 .......................................................149
Current applications.............................................................151
Four step residual overcurrent protection EF4PTOC.....................156
Identification..............................................................................156
Application.................................................................................156
Setting guidelines......................................................................157
Settings for steps 1 and 4 ....................................................158
Common settings for all steps..............................................1592nd harmonic restrain...........................................................161
Sensitive directional residual overcurrent and power protection
SDEPSDE......................................................................................161
Identification..............................................................................161
Application.................................................................................162
Setting guidelines......................................................................163
Thermal overload protection, two time constants TRPTTR............170
Identification..............................................................................170
Application.................................................................................170
Setting guideline........................................................................171Breaker failure protection CCRBRF...............................................173
Identification..............................................................................173
Application.................................................................................174
Setting guidelines......................................................................174
Pole discordance protection CCRPLD ..........................................177
Identification..............................................................................177
Application.................................................................................177
Setting guidelines......................................................................177
Directional over-/under-power protection GOPPDOP/
GUPPDUP......................................................................................178
Application.................................................................................178
Directional over-power protection GOPPDOP...........................180
Identification.........................................................................180
Setting guidelines.................................................................180
Directional under-power protection GUPPDUP.........................184
Identification.........................................................................184
Setting guidelines.................................................................184
Accidental energizing protection for synchronous generator
AEGGAPC......................................................................................187
Identification..............................................................................187
Table of contents
5
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
12/347
Application.................................................................................187
Setting guidelines......................................................................188
Negative-sequence time overcurrent protection for machines
NS2PTOC ......................................................................................189Identification..............................................................................189
Application.................................................................................189
Features...............................................................................190
Generator continuous unbalance current capability.............190
Setting guidelines......................................................................192
Operate time characteristic..................................................192
Start sensitivity.....................................................................194
Alarm function......................................................................194
Voltage-restrained time overcurrent protection VR2PVOC .... .......194
Identification..............................................................................194Application.................................................................................194
Base quantities.....................................................................195
Application possibilities........................................................195
Under-voltage seal-in...........................................................195
Setting guidelines......................................................................196
Voltage restrained overcurrent protection for generator
and step-up transformer.......................................................196
Overcurrent protection with undervoltage seal-in.................197
Section 9 Voltage protection........................................................199Two step undervoltage protection UV2PTUV ................................199
Identification..............................................................................199
Application.................................................................................199
Setting guidelines......................................................................200
Equipment protection, such as for motors and
generators............................................................................200
Disconnected equipment detection......................................200
Power supply quality ...........................................................200
Voltage instability mitigation.................................................200
Backup protection for power system faults...........................201
Settings for Two step undervoltage protection.....................201
Two step overvoltage protection OV2PTOV ..................................202
Identification..............................................................................202
Application.................................................................................202
Setting guidelines......................................................................203
Two step residual overvoltage protection ROV2PTOV..................205
Identification..............................................................................205
Application.................................................................................205
Setting guidelines......................................................................206
Table of contents
6
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
13/347
Equipment protection, such as for motors, generators,
reactors and transformers....................................................206
Stator earth-fault protection based on residual voltage
measurement.......................................................................206
Power supply quality............................................................210
High impedance earthed systems........................................210
Direct earthed system..........................................................211
Settings forTwo step residual overvoltage protection..........212
Overexcitation protection OEXPVPH.............................................213
Identification..............................................................................213
Application.................................................................................214
Setting guidelines......................................................................215
Recommendations for input and output signals...................215
Settings................................................................................215
Service value report.............................................................216
100% Stator earth fault protection, 3rd harmonic based
STEFPHIZ......................................................................................216
Identification..............................................................................216
Application.................................................................................216
Setting guidelines......................................................................221
Rotor earth fault protection 64R.....................................................222
Section 10 Frequency protection....................................................225Under frequency protection SAPTUF.............................................225
Identification..............................................................................225
Application.................................................................................225
Setting guidelines......................................................................225
Over frequency protection SAPTOF...............................................226
Identification..............................................................................226
Application.................................................................................227
Setting guidelines......................................................................227
Rate-of-change frequency protection SAPFRC..............................228
Identification..............................................................................228
Application.................................................................................228
Setting guidelines......................................................................228
Section 11 Secondary system supervision.....................................231Fuse failure supervision SDDRFUF...............................................231
Identification..............................................................................231
Application.................................................................................231
Setting guidelines......................................................................232
General.................................................................................232
Setting of common parameters............................................232
Negative sequence based....................................................233
Table of contents
7
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
14/347
Zero sequence based...........................................................234
Delta U and delta I ...............................................................234
Dead line detection...............................................................235
Breaker close/trip circuit monitoring TCSSCBR.............................235Identification..............................................................................235
Application.................................................................................235
Section 12 Control..........................................................................239Synchrocheck, energizing check, and synchronizing
SESRSYN......................................................................................239
Identification..............................................................................239
Application.................................................................................239
Synchronizing.......................................................................239
Synchrocheck.......................................................................240
Energizing check..................................................................242
Voltage selection..................................................................243
External fuse failure..............................................................244
Application examples.................................................................244
Single circuit breaker with single busbar..............................245
Single circuit breaker with double busbar, external
voltage selection...................................................................246
Single circuit breaker with double busbar, internal
voltage selection...................................................................247
Setting guidelines......................................................................247
Apparatus control ..........................................................................251
Identification..............................................................................251
Application.................................................................................251
Interaction between modules.....................................................254
Setting guidelines......................................................................255
Bay control (QCBAY)...........................................................256
Logic rotating switch for function selection and LHMI
presentation SLGGIO.....................................................................2 56
Identification..............................................................................256
Application.................................................................................256
Setting guidelines......................................................................256
Selector mini switch VSGGIO.........................................................257
Identification..............................................................................257
Application.................................................................................257
Setting guidelines......................................................................258
IEC61850 generic communication I/O functions DPGGIO.............258
Identification..............................................................................258
Application.................................................................................258
Setting guidelines......................................................................258
Single point generic control 8 signals SPC8GGIO.........................259
Table of contents
8
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
15/347
Identification..............................................................................259
Application.................................................................................259
Setting guidelines......................................................................259
Automation bits AUTOBITS............................................................260Identification..............................................................................260
Application.................................................................................260
Setting guidelines......................................................................260
Section 13 Logic.............................................................................261Tripping logic SMPPTRC................................................................261
Identification..............................................................................261
Application.................................................................................261
Three-phase tripping ...........................................................261
Lock-out................................................................................262
Blocking of the function block...............................................262
Setting guidelines......................................................................262
Trip matrix logic TMAGGIO............................................................263
Identification..............................................................................263
Application.................................................................................263
Setting guidelines......................................................................263
Configurable logic blocks................................................................264
Identification..............................................................................264
Application.................................................................................265
Configuration........................................................................265Fixed signals FXDSIGN..................................................................266
Identification..............................................................................266
Application.................................................................................266
Boolean 16 to integer conversion B16I...........................................267
Identification..............................................................................267
Application.................................................................................267
Setting guidelines......................................................................268
Boolean 16 to integer conversion with logic node
representation B16IFCVI................................................................268
Identification..............................................................................268
Application.................................................................................268
Setting guidelines......................................................................268
Integer to boolean 16 conversion IB16A........................................268
Identification..............................................................................268
Application.................................................................................269
Setting guidelines......................................................................269
Integer to boolean 16 conversion with logic node
representation IB16FCVB...............................................................269
Identification..............................................................................269
Application.................................................................................269
Table of contents
9
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
16/347
Settings......................................................................................269
Section 14 Monitoring.....................................................................271IEC61850 generic communication I/O functions SPGGIO....... ..... .271
Identification..............................................................................271
Application.................................................................................271
Setting guidelines......................................................................271
IEC61850 generic communication I/O functions 16 inputs
SP16GGIO.....................................................................................271
Identification..............................................................................271
Application.................................................................................271
Setting guidelines......................................................................272
IEC61850 generic communication I/O functions MVGGIO.............272
Identification..............................................................................272
Application.................................................................................272
Setting guidelines......................................................................272
Measurements................................................................................273
Identification..............................................................................273
Application.................................................................................273
Setting guidelines......................................................................275
Setting examples.......................................................................277
Measurement function application for a 400 kV OHL...........278
Measurement function application for a generator...............280
Event counter CNTGGIO................................................................282
Identification..............................................................................282
Application.................................................................................282
Setting guidelines......................................................................282
Disturbance report .........................................................................283
Identification..............................................................................283
Application.................................................................................283
Setting guidelines......................................................................284
Binary input signals..............................................................287
Analog input signals.............................................................287
Sub-function parameters......................................................288
Consideration.......................................................................288
Measured value expander block MVEXP.......................................289
Identification..............................................................................289
Application.................................................................................289
Setting guidelines......................................................................290
Station battery supervision SPVNZBAT.........................................290
Identification..............................................................................290
Application.................................................................................290
Insulation gas monitoring function SSIMG.....................................291
Identification..............................................................................291
Table of contents
10
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
17/347
Application.................................................................................291
Insulation liquid monitoring function SSIML....................................291
Identification..............................................................................291
Application.................................................................................291Circuit breaker condition monitoring SSCBR..................................291
Identification..............................................................................291
Application.................................................................................292
Section 15 Metering.......................................................................295Pulse counter PCGGIO..................................................................295
Identification..............................................................................295
Application.................................................................................295
Setting guidelines......................................................................295
Energy calculation and demand handling EPTMMTR....................296
Identification..............................................................................296
Application.................................................................................296
Setting guidelines......................................................................297
Section 16 Station communication.................................................299IEC61850-8-1 communication protocol .........................................299
Identification..............................................................................299
Application.................................................................................299
Horizontal communication via GOOSE................................301
Setting guidelines......................................................................303
DNP3 protocol................................................................................303
IEC 60870-5-103 communication protocol.....................................304
Section 17 Basic IED functions......................................................305Self supervision with internal event list ..........................................305
Identification..............................................................................305
Application.................................................................................305
Time synchronization......................................................................306
Identification..............................................................................306
Application.................................................................................306
Setting guidelines......................................................................307Parameter setting group handling..................................................309
Identification..............................................................................309
Application.................................................................................309
Setting guidelines......................................................................309
Test mode functionality TESTMODE..............................................310
Identification..............................................................................310
Application.................................................................................310
Setting guidelines......................................................................310
Change lock CHNGLCK.................................................................310
Table of contents
11
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
18/347
Identification..............................................................................310
Application.................................................................................310
Setting guidelines......................................................................311
IED identifiers TERMINALID..........................................................312Identification..............................................................................312
Application.................................................................................312
Customer specific settings...................................................312
Product information PRODINF.......................................................312
Identification..............................................................................312
Application.................................................................................312
Factory defined settings.......................................................312
Primary system values PRIMVAL...................................................313
Identification..............................................................................313
Application.................................................................................313Signal matrix for analog inputs SMAI.............................................313
Identification..............................................................................313
Application.................................................................................313
Setting guidelines......................................................................314
Summation block 3 phase 3PHSUM..............................................316
Identification..............................................................................316
Application.................................................................................316
Setting guidelines......................................................................317
Global base values GBASVAL.......................................................317
Identification..............................................................................317Application.................................................................................317
Setting guidelines......................................................................317
Authority check ATHCHCK.............................................................318
Identification..............................................................................318
Application.................................................................................318
Authorization handling in the IED.........................................318
Authority status ATHSTAT.............................................................319
Identification..............................................................................319
Application.................................................................................319
Denial of service.............................................................................320Identification..............................................................................320
Application.................................................................................320
Setting guidelines......................................................................320
Section 18 Requirements...............................................................321Current transformer requirements..................................................321
Current transformer classification..............................................321
Conditions..................................................................................322
Fault current..............................................................................323
Secondary wire resistance and additional load.........................323
Table of contents
12
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
19/347
General current transformer requirements................................323
Rated equivalent secondary e.m.f. requirements......................324
Transformer differential protection.......................................324
1 Ph high impedance differential protection.........................325Breaker failure protection.....................................................326
Non-directional instantaneous and definitive time, phase
and residual overcurrent protection......................................326
Non-directional inverse time delayed phase and residual
overcurrent protection..........................................................327
Directional phase and residual overcurrent protection.........328
Current transformer requirements for CTs according to
other standards..........................................................................329
Current transformers according to IEC 60044-1,
class P, PR...........................................................................329
Current transformers according to IEC 60044-1, class
PX, IEC 60044-6, class TPS
(and old British Standard, class X).......................................329
Current transformers according to ANSI/IEEE.....................329
Voltage transformer requirements..................................................330
SNTP server requirements.............................................................331
SNTP server requirements........................................................331
Section 19 Glossary.......................................................................333
Table of contents
13
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
20/347
14
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
21/347
Section 1 Introduction
1.1 This manualThe application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.
1.2 Intended audienceThis manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.
The protection and control engineer must be experienced in electrical power
engineering and have knowledge of related technology, such as communication
and protocols.
1MRK 502 033-UEN - Section 1Introduction
15
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
22/347
1.3 Product documentation1.3.1 Product documentation set
Planning&purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling&disposal
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocolmanual
Technical manual
Planning&purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling&disposal
Planning&purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling&disposal
Application manualApplication manual
Operation manualOperation manual
Installation manualInstallation manual
Service manualService manual
Engineering manualEngineering manual
Commissioning manualCommissioning manual
Communication protocolmanualCommunication protocolmanual
Technical manualTechnical manual
en07000220.vsd
IEC07000220 V1 EN
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 60870-5-103, IEC 61850and DNP3.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED.
The manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for checking
of external circuitry and energizing the IED, parameter setting and configuration as
Section 1 1MRK 502 033-UEN -Introduction
16
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
23/347
well as verifying settings by secondary injection. The manual describes the process
of testing an IED in a substation which is not in service. The chapters are organized
in chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The service manual contains instructions on how to service and maintain the IED.
The manual also provides procedures for de-energizing, de-commissioning and
disposal of the IED.
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The communication protocol manual describes a communication protocol
supported by the IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The service manual is not available yet.
1.3.2 Document revision historyDocument revision/date Product series version History-/February 2011 1.1 First release
1.3.3 Related documentsDocuments related to REG650 Identity numberApplication manual 1MRK 502 033-UEN
Technical manual 1MRK 502 034-UEN
Commissioning manual 1MRK 502 035-UEN
Table continues on next page
1MRK 502 033-UEN - Section 1Introduction
17
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
24/347
Documents related to REG650 Identity numberProduct Guide 1MRK 502 036-BEN
Type test certificate 1MRK 502 036-TEN
Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670 1MRG001910
650 series manuals Identity numberCommunication protocol manual, DNP3 1MRK 511 241-UEN
Communication protocol manual, IEC 61850 1MRK 511 242-UEN
Communication protocol manual, IEC 60870-5-103 1MRK 511 243-UEN
Point list manual, DNP3 1MRK 511 244-UEN
Engineering manual 1MRK 511 245-UEN
Operation manual 1MRK 500 093-UEN
Installation manual 1MRK 514 014-UEN
1.4 Symbols and conventions1.4.1 Safety indication symbols
The electrical warning icon indicates the presence of a hazard
which could result in electrical shock.
The warning icon indicates the presence of a hazard which could
result in personal injury.
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Section 1 1MRK 502 033-UEN -Introduction
18
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
25/347
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in this
manual.
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
Push button navigation in the LHMI menu structure is presented by using the
push button icons, for example:
To navigate between the options, use and .
HMI menu paths are presented in bold, for example:
Select Main menu/Settings.
LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press .
Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
1MRK 502 033-UEN - Section 1Introduction
19
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
26/347
20
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
27/347
Section 2 Application
2.1 REG650 applicationREG650 is used for the protection and monitoring of generating plants. The IED is
especially suitable for applications in distributed control systems with high
demands on reliability. It is intended mainly for small and medium size generation
stations.
REG670 may be used when more extensive protection systems are required or in
combination with REG650 to provide redundant schemes.
A wide range of protection functions is available to achieve full and reliable
protection for different types of generating plants, for example hydro power plants
and thermal power plants. This enables adaptation to the protection requirements of
most generating plants.
Protection functions are available for detecting and clearing internal faults, such as
generator stator short circuits and earth faults, generator rotor earth faults, unit
transformer short circuits and earth faults and faults in the external power system,
fed from the generating plant.
Two packages have been defined for the following applications:
Generator protection IED including generator differential protection (B01)
Generator-transformer unit protection IED including transformer differential
protection (B05)
In many generating plants, the protection system can be designed with a
combination of the two packages, that is, two IEDs of either same type or different
types, will give redundant protection for a generating unit (generator and unit
transformer) depending on the requirements for the plant design.
The packages are configured and ready for use. Analogue inputs and binary input/output circuits are pre-defined.
The pre-configured IED can be changed and adapted with the graphical
configuration tool.
1MRK 502 033-UEN - Section 2Application
21
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
28/347
A, B, C or D
~
59N UN>
STEF PHIZ
59THD U3d/N
REG650-B01
TR PTTR
49 Ith
LEX PDIS
40
OEX PVPH
24 U/f>
UV2 PTUV
27 3U
OC4 PTOC
51 3I>
GEN PDIF
87G 3Id/I
SA PTUF
81U f/U
OC4 PTOC
51 3I>
CC RPLD
52PD PD
CC RBRF
50BF 3I> BF
YY
Generator CB
Auxiliary
Transformer
Unit
Transformer
29MVA
121/11kV
YNd5
Excitation
Transformer
HV CB
ROV2 PTOV
59N 3Uo>
TR PTTR
49 Ith
OOS PPAM
78 Ucos
SESRSYN
25 SC
1)
2)
3)
3) Input for independent directional (sensitive) EF function. It can be used for different purposes
(e.g. as rotor EF with RXTTE4 or stator EF for generators operating in parallel)
FieldCB
HZ PDIF
87N IdN
2) Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protection for
generators with split winding or even HV side EF protection). Alternatively it can be used for High-Impedance REF protection.
ROV2 PTOV
59N 3Uo>
CV MMXN
Meter.
GOP PDOP
32
GOP PDUP
37 P
EF4 PTOC
67N
SDE PSDE
67N
Rotor EF protection 64R
GOP PDOP
32Q
SA PFRC
81R df/dt
390kVA
11/0.37kV
Dyn11
50/5
1600/5
1600/5
10/1
1.6MVA
11/0.4kV
EF4 PTOC
51N IN>
11 0.11 0.11/ /
33 3kV
11 0.11 0.11/ /
33 3kV
11/ 0.11
3kV
200/1
100/52500/5
1000
29MVA
11kV
150rpm
RXTTE4
D
C B
A
H J, G or H
200/5
G
Y200/1
J
C MSQI
Meter.
IEC10000299-1-en.vsd
Q
P
IN> IN>
UV2 PTUV
27 3U
T3D PDIF
87T 3Id/I
SA PTUF
81U f/U
OC4 PTOC51 3I>
CC RPLD52PD PD
CC RBRF50BF 3I> BF
YY
Generator CB
HV CB
ROV2 PTOV
59N 3Uo>
TR PTTR
49 Ith
OOS PPAM
78 Ucos
SES RSYN
25 SC
Note:
2) Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protectionfor generators with split winding or even HV side EF protection). Alternatively it can be used for High-Impedance REF protection.
1) Inputs for independent directional (sensitive) EF function. It can be used for different purposes(e.g. as rotor EF with RXTTE4 or stator EF for generators running in parallel)
1)
2)
FieldCB
TR PTTR
49 Ith
OC4 PTOC
51 3I>
HZ PDIF
87N IdN
EF4 PTOC
51N IN>
GT01
ROV2 PTOV
59N 3Uo>
59N UN>
YY
CV MMXNMeter.
GOP PDUP
37 P
EF4 PTOC
67N
SDE PSDE
67N
Rotor EF protection 64R
CV MMXN
Meter.
GOP PDOP
32Q
SA PFRC
81R df/dt
3)
3) Alternatively step-up transformer HV side open delta VT can be connected here
Generator CB
AuxiliaryTransformer
UnitTransformer
29MVA121/11kV
YNd5
ExcitationTransformer
390kVA11/0.37kV
Dyn11
50/5
1600/5
29MVA11kV
150rpm
200/1
100/5
1.6MVA11/0.4kV
11 0.11 0.11/ /
33 3kV
110 0.11 0.11/ /
33 3kV
11
/ 0.113
kV
2500/5
1000
RXTTE4
C
B
E
A
D
A or B
D or E
200/5
G
1600/5
10/1H J, G or H
Y200/1
J
SDD RFUF
60FL
C MSQI
Meter.
IEC10000300-1-en.vsd
IN> IN>
Q
P
On On On On
Two step residual overvoltage ProtectionROV2PTOV , U0>, instance 1
OnGen Term
OnGen Term
OnGen Neutr point
OnGen Neutr point
Two step residual overvoltage ProtectionROV2PTOV , U0>, instance 2
OnT sec side
OnT sec side
OnT sec side
OnT HV neutr point
Overexcitation protection OEXPVPH On On On On
100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based
On On Applicationdependent
Applicationdependent
Underfrequency protection SAPTUF , instance 1 On On On On
Underfrequency protection SAPTUF, instance 2 Off Off Off Off
Underfrequency protection SAPTUF, instance 3 Off Off Off Off
Underfrequency protection SAPTUF, instance 4 Off Off Off Off
Overfrequency protection SAPTOF, instance 1 On On On On
Overfrequency protection SAPTOF, instance 2 Off Off Off Off
Overfrequency protection SAPTOF, instance 3 Off Off Off Off
Overfrequency protection SAPTOF, instance 4 Off Off Off Off
Table continues on next page
1MRK 502 033-UEN - Section 2Application
35
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
42/347
Function Application 1 Application 2 Application 3 Application 4Rate-of-change frequency protection SAPFRC,instance 1
Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
Rate-of-change frequency protection SAPFRC ,
instance 2
Off Off Off Off
Synchrocheck, energizing check, and synchronizingSESRSYN
Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
1) The generator should have reverse power protection. If the generator consumes low reverse power at motor operation (< 1 % of SN),
low forward power protection should be used. In other cases, reverse power protection should be used.2) Voltage-restrained time overcurrent protection add (VR2PVOC) can be used instead of the underimpedance protection.
Section 2 1MRK 502 033-UEN -Application
36
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
43/347
2.3.1.6 Single generator/transformer unit, connected to a solidly earthedHigh Voltage (HV) system, with redundant protection
REG650 (B01)
3
3
3
3
1
1
3
1
1
3
Aux
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B05)
IEC10000128-1-en.vsd
IEC10000128 V1 EN
Figure 8: Single generator/transformer unit, connected to a solidly earthedHigh Voltage (HV) system, with redundant protection
REG650 (B01) is used as the main protection for the generator and REG650 (B05)
is used as the main protection for the unit transformer and as back-up protection for
the generator. The combination of the protections also gives redundant protection
for the auxiliary system transformer.
1MRK 502 033-UEN - Section 2Application
37
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
44/347
Table 6: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV
Transformer high voltage side rated voltage (UN,THV)
11 220 kV
Generator rated power (SN) 1 150 MVA
Short circuit power level infeed at HV-side 500 10000 MVA
2.3.1.7 Single generator/transformer unit, connected to a high impedanceearthed High Voltage (HV) system, with redundant protection
REG650 (B01)
3
3
3
3
1
1
3
1
3
Aux
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B05)
1
IEC10000129-1-en.vsd
IEC10000129 V1 EN
Figure 9: Single generator/transformer unit, connected to a high impedanceearthed High Voltage (HV) system, with redundant protection
Section 2 1MRK 502 033-UEN -Application
38
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
45/347
REG650 (B01) is used as the main protection for the generator and REG650 (B05)
is used as the main protection for the unit transformer and as back-up protection for
the generator. The combination of the protections also gives redundant protection
for the auxiliary system transformer.
Table 7: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV
Transformer high voltage side rated voltage (UN,
THV)
11 220 kV
Generator rated power (SN) 1 150 MV
Short circuit power level infeed at HV-side 500 5000 MVA
2.3.1.8 Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit differential protection including thegeneratorsREG650 (B05)
3
3
3
1
1
3
1
3
3
3
1
1
1
3
1
3
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B01)
Aux
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B01)
3
Aux
IEC10000130-1-en.vsd
IEC10000130 V1 EN
Figure 10: Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit differential protection including thegenerators
1MRK 502 033-UEN - Section 2Application
39
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
46/347
REG650 (B01) is used as the main protection for the generator and REG650 (B05)
is used as the main protection for the unit transformer and as back-up protection for
the generator. The combination of the protections also gives redundant protection
for the auxiliary system transformer.
Table 8: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV
Transformer high voltage side rated voltage (UN,
THV)
11 220 kV
Generator rated power (SN) 1 150 MVA
Short circuit power level infeed at HV-side 500 10000 MVA
2.3.1.9 Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit transformer differential protectionREG650 (B05)
3
3
3
1
1
3
1
3
3
3
1
1
1
3
1
3
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B01)
Aux
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B01)
3
Aux
IEC10000131-1-en.vsd
IEC10000131 V1 EN
Figure 11: Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit transformer differential protection
REG650 (B01) is used as the main protection for the generator and REG650 (B05)
is used as the main protection for the unit transformer and as back-up protection for
Section 2 1MRK 502 033-UEN -Application
40
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
47/347
the generator. The combination of the protections also gives redundant protection
for the auxiliary system transformer.
Table 9: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV
Transformer high voltage side rated voltage (UN,
THV)
11 220 kV
Generator rated power (SN) 1 150 MVA
Short circuit power level infeed at HV-side 500 10000 MVA
2.3.1.10 Functionality tableThe proposal for functionality choice for the different application cases are shownin table 10.
The recommendations have the following meaning:
On: It is recommended to have the function activated in the application.
Off: It is recommended to have the function deactivated in the application.
Application dependent: The decision to have the function activated or not is
dependent on the specific conditions in each case.
Application 5 8 in table10 are according to application examples
given in previous sections.
Tab le 10: Recommended funct ions in the d if fe rent app licat ion examp lesFunction Application 5 Application 6 Application 7 Application 8Generator differential protection GENPDIF (B01) On On On On
Transformer differential protection T3WPDIF (B05) On On On On
1Ph High impedance differential protection HZPDIF Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
Underimpedance protection for generators andtransformers ZGPDIS (B01)
On On On On
Underimpedance protection for generators andtransformers ZGPDIS (B05)
Off Off Off Off
Load encroachment LEPDIS Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
Out-of-step protection OOSPPAM (B01) On On On On
Out-of-step protection OOSPPAM (B05) Off Off Off Off
Loss of excitation (underexcitation) protectionLEXPDIS (A01)
On On On On
Loss of excitation (underexcitation) protectionLEXPDIS (B05)
Off Off Off Off
Table continues on next page
1MRK 502 033-UEN - Section 2Application
41
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
48/347
Function Application 5 Application 6 Application 7 Application 8Four step phase overcurrent protection OC4PTOC ,instance 1 (B01)
OnAux T
OnAux T
OnAux T
OnAux T
Four step phase overcurrent protection OC4PTOC ,
instance 1 (B05)
On On On On
Four step phase overcurrent protection OC4PTOC ,instance 2
Off Off Off Off
Four step residual overcurrent protection EF4PTOC ,instance 1 (B01)
Off Off Off Off
Four step residual overcurrent protection EF4PTOC ,instance 1 (B05)
OnT HV
OnT HV
OnT HV
OnT HV
Four step residual overcurrent protection EF4PTOC ,instance 2
Off Off Off Off
Sensitive directional residual overcurrent and powerprotection SDEPSDE (B01)
OnRotor EF
OnRotor EF
OnRotor EF
OnRotor EF
Sensitive directional residual overcurrent and power
protection SDEPSDE (B05)
Off Off Off Off
Thermal overload protection TRPTTR , instance 1 On On On On
Thermal overload protection TRPTTR , instance 2 Off Off Off Off
Breaker failure protection CCRBRF (B01) On On On On
Breaker failure protection CCRBRF (B05) OnHV CB
OnHV CB
OnHV CB
OnHV CB
Pole discordance protection CCRPLD Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
Directional under-power protection GUPPDUP (lowforward power protection), (B01)
1) 1) 1) 1)
Directional underpower protection GUPPDUP (Low
forward power protection), (B05)
Off Off Off Off
Directional overpower protection GOPPDOP ,instance 1 (reverse power protection), (B01)
1) 1) 1) 1)
Directional overpower protection GOPPDOP ,instance 1 (reverse power protection), (B05)
Off Off Off Off
Directional overpower protection GOPPDOP ,instance 2
Off Off Off Off
Accidental energizing protection for synchronousgenerator AEGGAPC (B01)
On On On On
Accidental energizing protection for synchronousgenerator AEGGAPC (B05)
Off Off Off Off
Negative-sequence time overcurrent protection formachines NS2PTOC On On On On
Voltage-restrained time overcurrent protectionVR2PVOC (B01)
2) 2) 2) 2)
Voltage-restrained time overcurrent protectionVR2PVOC (B05)
Off Off Off Off
Two step undervoltage protection UV2PTUV , U< On On On On
Two step overvoltage protection OV2PTOV , U> On On On On
Two step residual overvoltage protectionROV2PTOV , U0>, instance 1 (B01)
OnGen Neutr point
OnGen Neutr point
OnGen Neutr point
OnGen Neutr point
Table continues on next page
Section 2 1MRK 502 033-UEN -Application
42
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
49/347
Function Application 5 Application 6 Application 7 Application 8Two step residual overvoltage protectionROV2PTOV , U0>, instance 1 (B05)
OnT sec side
OnT sec side
OnT sec side
OnT sec side
Two step Residual Overvoltage Protection
ROV2PTOV , U0>, instance 2 (B01)
On
Gen Term
On
Gen Term
On
Gen Term
On
Gen Term
Two step residual overvoltage protectionROV2PTOV , U0>, instance 2 (B05)
Off OnT HV neutr point
OnT sec side 2
OnT sec side 2
Overexcitation protection OEXPVPH On On On On
100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based (B01)
On On On On
100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based (B05)
Off Off Off Off
Underfrequency protection SAPTUF , instance 1 On On On On
Underfrequency protection SAPTUF , instance 2 Off Off Off Off
Underfrequency protection SAPTUF, instance 3 Off Off Off Off
Underfrequency protection SAPTUF, instance 4 Off Off Off Off
Overfrequency protection SAPTOF, instance 1 On On On On
Overfrequency protection SAPTOF, instance 2 Off Off Off Off
Overfrequency protection SAPTOF, instance 3 Off Off Off Off
Overfrequency protection SAPTOF, instance 4 Off Off Off Off
Rate-of-change frequency protection SAPFRC,instance 1
Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
Rate-of-change frequency protection SAPFRC,instance 2
Off Off Off Off
Synchrocheck, energizing check, and synchronizingSESRSYN(B01)
Applicationdependent
Applicationdependent
Applicationdependent
Applicationdependent
Synchrocheck, energizing check, and synchronizingSESRSYN (B05)
Off Off Off Off
1) The generator should have reverse power protection. If the generator consumes low reverse power at motor operation (< 1 % of SN),
low forward power protection should be used. In other cases, reverse power protection should be used.2) Voltage-restrained time overcurrent protection add (VR2PVOC) can be used instead of the underimpedance protection.
1MRK 502 033-UEN - Section 2Application
43
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
50/347
44
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
51/347
Section 3 REG650 setting examples
The application example has a generation unit protected by one REG650 B01
(Main 1) and one REG650 B05 (Main 2) as shown in figure 12.
REG650 (B01)
3
3
3
3
1
1
3
1
1
3
Aux
Rotor
DC
Rotor EF
injection
IinjUinj
REG650 (B05)
145 kV
IEC10000155-1-en.vsd
IEC10000155 V1 EN
Figure 12: Power plant protection applicationThe following data is assumed:
Table 11: Data for the unit transformerItem DataTransformer rated power SN 25 MVA
Transformer high voltage side rated voltage UN1 145 kV
Transformer low voltage side rated voltage UN2 10.5 kV
Transformer vector group YNd11
Table continues on next page
1MRK 502 033-UEN - Section 3REG650 setting examples
45
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
52/347
Item DataTransformer short circuit voltage ek 12 %
Maximum allowed continuous overload 1.30 * SN
Phase CT ratio at 145 kV level 150/1 ACT at 145 kV earth point 150/1 A
Phase CT ratio at 10 kV level 1500/1 A
10 kV VT ratio11 0 11 0 11
kv33 3
. ./ /
High positive sequence source impedance at theHV side
10 ohm (about 2100 MVA) with a phase angle 85
High zero sequence source impedance at theHV side
j20 ohm
Table 12: Data for the generatorItem DataGenerator rated power SN 25 MVA
Generator rated voltage UN 10.5 kV kV
Rate power factor cosn 0.90
xd 1.0 per unit (pu)
xd 0.4 pu
xd 0.25 pu
Phase CT ratio at generator terminal side 1500/1 APhase CT ratio at generator neutral point side 1500/1 A
Generator neutral point VT ratio11
0.11 kV3
/
Generator 10 kV terminal VT ratio11 0 11 0 11
kV33 3
. ./ /
Table 13: Data for the auxiliary transform erItem DataTransformer rated power SN 1.0 MVA
Transformer high voltage side rated voltage UN1 10.5 kV
Transformer low voltage side rated voltage UN2 0.4 kV
Transformer vector group Dyn5
Transformer short circuit voltage ek 4 %
Phase CT ratio at 10.5 kV level 100/1 A
Section 3 1MRK 502 033-UEN -REG650 setting examples
46
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
53/347
Only settings that need adjustment due to the specific application
are described in setting examples. It is recommended to keep the
default values for all settings that are not described. Refer to
Technical manual for setting tables for each protection and control
function.
Refer to setting guideline section in Application manual for
guidelines on how to set functions that are not presented in setting
examples.
Use parameter setting tool in PCM600 to set the IED according to
calculations for the particular application.
3.1 Calculating general settings for analogue TRMinputs 4I 1I 5UThe transformer module (TRM) has the capability of 4 current inputs (tapped to 1
or 5 A), 1 current input (tapped to 0.1 or 0.5 A) and 5 voltage inputs.
The generator neutral point phase CTs (three-phase current transformer group) are
connected to inputs 1 3 (L1, L2 and L3).
The generator neutral point CT can be connected to input 4 (not used here).
The rotor earth fault current measurement is connected to input 5.
The generator terminal side phase VT is connected to inputs 6 - 8 (L1, L2 and L3).
The generator neutral point VT is connected to input 9.
The rotor earth fault voltage measurement is connected to input 10.
1. Set the current transformer inputs.
1.1. Set CTStarPoint1 to To Object.
The CT secondary is earthed towards the transformer.
1.2. Set CTSec1 to 1 A.
(The rated secondary current of the CT)
1.3. Set CTPrim1 to 1500 A.
(The rated primary current of the CT)
1.4. Set the same values for current inputs 2 and 3.
1.5. Set CTStarPoint4 to.
1.6. Set CTSec4 to.
1MRK 502 033-UEN - Section 3REG650 setting examples
47
Application Manual
-
7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec
54/347
1.7. Set CTPrim4 to.
1.8. Set CTStarPoint5 to To Object.
1.9. Set CTSec5 to 10 A.
1.10. Set CTPrim5 to 1 A.
2. Set the voltage transformer inputs.
2.1. Set VTSec6to 110 V.
(The