1mrk502033-uen - en application manual generator protection reg650 iec

Upload: john-karlo-reynante

Post on 03-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    1/347

    Relion 650 series

    Generator protection REG650Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    2/347

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    3/347

    Document ID: 1MRK 502 033-UENIssued: February 2011

    Revision: -Product version: 1.1

    Copyright 2011 ABB. All rights reserved

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    4/347

    CopyrightThis document and parts thereof must not be reproduced or copied without written

    permission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

    The software or hardware described in this document is furnished under a license

    and may be used or disclosed only in accordance with the terms of such license.

    TrademarksABB and Relion are registered trademarks of ABB Group. All other brand or

    product names mentioned in this document may be trademarks or registered

    trademarks of their respective holders.

    WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    ABB AB

    Substation Automation Products

    SE-721 59 Vsters

    Sweden

    Telephone: +46 (0) 21 32 50 00

    Facsimile: +46 (0) 21 14 69 18

    http://www.abb.com/substationautomation

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    5/347

    DisclaimerThe data, examples and diagrams in this manual are included solely for the concept

    or product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in this

    manual must satisfy themselves that each intended application is suitable and

    acceptable, including that any applicable safety or other operational requirements

    are complied with. In particular, any risks in applications where a system failure and/

    or product failure would create a risk for harm to property or persons (including but

    not limited to personal injuries or death) shall be the sole responsibility of the

    person or entity applying the equipment, and those so responsible are hereby

    requested to ensure that all measures are taken to exclude or mitigate such risks.

    This document has been carefully checked by ABB but deviations cannot be

    completely ruled out. In case any errors are detected, the reader is kindly requested

    to notify the manufacturer. Other than under explicit contractual commitments, in

    no event shall ABB be responsible or liable for any loss or damage resulting from

    the use of this manual or the application of the equipment.

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    6/347

    ConformityThis product complies with the directive of the Council of the European

    Communities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerning

    electrical equipment for use within specified voltage limits (Low-voltage directive

    2006/95/EC). This conformity is the result of tests conducted by ABB in

    accordance with the product standards EN 50263 and EN 60255-26 for the EMC

    directive, and with the product standards EN 60255-1 and EN 60255-27 for the low

    voltage directive. The IED is designed in accordance with the international

    standards of the IEC 60255 series.

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    7/347

    Table of contentsSection 1 Introduction.....................................................................15

    This manual......................................................................................15

    Intended audience............................................................................1 5

    Product documentation.....................................................................16

    Product documentation set..........................................................16

    Document revision history...........................................................17

    Related documents......................................................................17

    Symbols and conventions.................................................................18

    Safety indication symbols............................................................18

    Manual conventions.....................................................................19

    Section 2 Application......................................................................21REG650 application..........................................................................21

    Available functions............................................................................24

    Main protection functions.............................................................24

    Back-up protection functions.......................................................24

    Control and monitoring functions.................................................25

    Designed to communicate...........................................................27

    Basic IED functions.....................................................................28

    REG650 application examples.........................................................28Adaptation to different applications.............................................28

    Single generator connected via a unit transformer to a

    High Voltage (HV) system......................................................30

    Single generator, including the auxiliary transformer,

    connected via an unit transformer to a High Voltage

    (HV) system............................................................................31

    Generating unit, including both generator and unit

    transformer, connected to a solidly earthed High

    Voltage (HV) system..............................................................32

    Generating unit, including both generator and unit

    transformer, connected to a high impedance earthedHigh Voltage (HV) system......................................................33

    Functionality table..................................................................34

    Single generator/transformer unit, connected to a solidly

    earthed High Voltage (HV) system, with redundant

    protection................................................................................37

    Single generator/transformer unit, connected to a high

    impedance earthed High Voltage (HV) system, with

    redundant protection..............................................................38

    Two generators having one three-winding unit

    transformer, connected to a solidly earthed High

    Table of contents

    1

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    8/347

    Voltage (HV) system, with redundant protection with unit

    differential protection including the generators.......................39

    Two generators having one three-winding unit

    transformer, connected to a solidly earthed High

    Voltage (HV) system, with redundant protection with unit

    transformer differential protection...........................................40

    Functionality table..................................................................41

    Section 3 REG650 setting examples..............................................45Calculating general settings for analogue TRM inputs 4I 1I 5U.......47

    Calculating general settings for analogue AIM inputs 6I 4U.............48

    Preprocessing blocks SMAI..............................................................49

    Calculating settings for global base values for setting function

    GBSVAL...........................................................................................50

    Calculating settings for generator differential protectionGENPDIF..........................................................................................51

    Calculating settings for underimpedance protection for

    generators and transformers ZGPDIS .............................................52

    Calculating settings for zone 1....................................................53

    Calculating settings for zone 2....................................................53

    Calculating settings for zone 3....................................................54

    Calculating settings for the Load encroachment function............54

    Calculating settings for out-of-step protection OOSPPAM ..............56

    Calculating settings for loss of excitation LEXPDIS ........................61

    Negative-sequence time overcurrent protection for machinesNS2PTOC ........................................................................................65

    Calculating settings for four step phase overcurrent protection

    OC4PTOC........................................................................................65

    Calculating settings for generator phase overcurrent

    protection.....................................................................................65

    Calculating settings for step 1................................................65

    Calculating settings for step 2................................................66

    Calculating settings for auxiliary transformer phase

    overcurrent protection..................................................................66

    Calculating settings for step 1................................................67

    Calculating settings for step 4................................................67

    100% Stator earth fault protection, 3rd harmonic based

    STEFPHIZ .......................................................................................68

    Stator earth fault protection (neutral point voltage)..........................70

    Section 4 Analog inputs..................................................................71Introduction.......................................................................................71

    Setting guidelines.............................................................................71

    Setting of the phase reference channel.......................................71

    Example.................................................................................71

    Setting of current channels.....................................................71

    Table of contents

    2

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    9/347

    Example 1..............................................................................72

    Example 2..............................................................................73

    Examples how to connect, configure and set CT inputs

    for most commonly used CT connections..............................74Example how to connect star connected three-phase

    CT set to the IED....................................................................75

    Example how to connect single-phase CT to the IED............77

    Setting of voltage channels....................................................79

    Example.................................................................................79

    Examples how to connect, configure and set VT inputs

    for most commonly used VT connections..............................80

    Examples how to connect three phase-to-earth

    connected VTs to the IED......................................................81

    Example how to connect the open delta VT to the IED

    for high impedance earthed or unearthed..............................82

    Example how to connect the open delta VT to the IED

    for low impedance earthed or solidly earthed power

    systems..................................................................................84

    Example how to connect the neutral point VT to the IED.......86

    Section 5 Local human-machine interface.....................................89Local HMI.........................................................................................89

    Display.........................................................................................90

    LEDs............................................................................................91

    Keypad........................................................................................92Local HMI functionality................................................................94

    Protection and alarm indication..............................................94

    Parameter management ........................................................96

    Front communication..............................................................97

    Single-line diagram.................................................................97

    Section 6 Differential protection.....................................................99Transformer differential protection....................................................99

    Identification................................................................................99

    Application...................................................................................99

    Setting guidelines......................................................................100

    Inrush restraint methods.......................................................100

    Overexcitation restraint method...........................................100

    Cross-blocking between phases..........................................101

    Restrained and unrestrained differential protection..............101

    Elimination of zero sequence currents.................................102

    External/Internal fault discriminator......................................103

    Differential current alarm......................................................105

    Switch onto fault feature.......................................................105

    Setting example.........................................................................105

    Table of contents

    3

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    10/347

    Summary and conclusions...................................................105

    1Ph High impedance differential protection HZPDIF .....................107

    Identification..............................................................................107

    Application.................................................................................107The basics of the high impedance principle.........................107

    Connection examples................................................................113

    Connections for 1Ph restricted earth fault and high

    impedance differential protection.........................................113

    Setting guidelines......................................................................114

    Configuration........................................................................114

    Settings of protection function..............................................114

    Restricted earth fault protection REF...................................115

    Alarm level operation............................................................117

    Generator differential protection GENPDIF ...................................118Identification..............................................................................118

    Application.................................................................................118

    Setting guidelines......................................................................120

    General settings...................................................................120

    Percentage restrained differential operation........................121

    Negative sequence internal/external fault discriminator

    feature..................................................................................123

    Otheradditional options.......................................................124

    Open CT detection...............................................................125

    Section 7 Impedance protection...................................................127Underimpedance protection for generators and transformers

    ZGPDIS .........................................................................................127

    Identification..............................................................................127

    Application.................................................................................127

    Setting guidelines......................................................................127

    Loss of excitation LEXPDIS............................................................129

    Identification..............................................................................129

    Application.................................................................................129

    Setting guidelines......................................................................135

    Out-of-step protection OOSPPAM .................................................138

    Identification..............................................................................138

    Application.................................................................................139

    Setting guidelines......................................................................142

    Load enchroachment LEPDIS........................................................145

    Identification..............................................................................145

    Application.................................................................................145

    Setting guidelines......................................................................145

    Resistive reach with load encroachment characteristic........145

    Table of contents

    4

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    11/347

    Section 8 Current protection.........................................................147Four step phase overcurrent protection OC4PTOC.......................147

    Identification..............................................................................147

    Application.................................................................................147

    Setting guidelines......................................................................148

    Settings for steps 1 to 4 .......................................................149

    Current applications.............................................................151

    Four step residual overcurrent protection EF4PTOC.....................156

    Identification..............................................................................156

    Application.................................................................................156

    Setting guidelines......................................................................157

    Settings for steps 1 and 4 ....................................................158

    Common settings for all steps..............................................1592nd harmonic restrain...........................................................161

    Sensitive directional residual overcurrent and power protection

    SDEPSDE......................................................................................161

    Identification..............................................................................161

    Application.................................................................................162

    Setting guidelines......................................................................163

    Thermal overload protection, two time constants TRPTTR............170

    Identification..............................................................................170

    Application.................................................................................170

    Setting guideline........................................................................171Breaker failure protection CCRBRF...............................................173

    Identification..............................................................................173

    Application.................................................................................174

    Setting guidelines......................................................................174

    Pole discordance protection CCRPLD ..........................................177

    Identification..............................................................................177

    Application.................................................................................177

    Setting guidelines......................................................................177

    Directional over-/under-power protection GOPPDOP/

    GUPPDUP......................................................................................178

    Application.................................................................................178

    Directional over-power protection GOPPDOP...........................180

    Identification.........................................................................180

    Setting guidelines.................................................................180

    Directional under-power protection GUPPDUP.........................184

    Identification.........................................................................184

    Setting guidelines.................................................................184

    Accidental energizing protection for synchronous generator

    AEGGAPC......................................................................................187

    Identification..............................................................................187

    Table of contents

    5

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    12/347

    Application.................................................................................187

    Setting guidelines......................................................................188

    Negative-sequence time overcurrent protection for machines

    NS2PTOC ......................................................................................189Identification..............................................................................189

    Application.................................................................................189

    Features...............................................................................190

    Generator continuous unbalance current capability.............190

    Setting guidelines......................................................................192

    Operate time characteristic..................................................192

    Start sensitivity.....................................................................194

    Alarm function......................................................................194

    Voltage-restrained time overcurrent protection VR2PVOC .... .......194

    Identification..............................................................................194Application.................................................................................194

    Base quantities.....................................................................195

    Application possibilities........................................................195

    Under-voltage seal-in...........................................................195

    Setting guidelines......................................................................196

    Voltage restrained overcurrent protection for generator

    and step-up transformer.......................................................196

    Overcurrent protection with undervoltage seal-in.................197

    Section 9 Voltage protection........................................................199Two step undervoltage protection UV2PTUV ................................199

    Identification..............................................................................199

    Application.................................................................................199

    Setting guidelines......................................................................200

    Equipment protection, such as for motors and

    generators............................................................................200

    Disconnected equipment detection......................................200

    Power supply quality ...........................................................200

    Voltage instability mitigation.................................................200

    Backup protection for power system faults...........................201

    Settings for Two step undervoltage protection.....................201

    Two step overvoltage protection OV2PTOV ..................................202

    Identification..............................................................................202

    Application.................................................................................202

    Setting guidelines......................................................................203

    Two step residual overvoltage protection ROV2PTOV..................205

    Identification..............................................................................205

    Application.................................................................................205

    Setting guidelines......................................................................206

    Table of contents

    6

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    13/347

    Equipment protection, such as for motors, generators,

    reactors and transformers....................................................206

    Stator earth-fault protection based on residual voltage

    measurement.......................................................................206

    Power supply quality............................................................210

    High impedance earthed systems........................................210

    Direct earthed system..........................................................211

    Settings forTwo step residual overvoltage protection..........212

    Overexcitation protection OEXPVPH.............................................213

    Identification..............................................................................213

    Application.................................................................................214

    Setting guidelines......................................................................215

    Recommendations for input and output signals...................215

    Settings................................................................................215

    Service value report.............................................................216

    100% Stator earth fault protection, 3rd harmonic based

    STEFPHIZ......................................................................................216

    Identification..............................................................................216

    Application.................................................................................216

    Setting guidelines......................................................................221

    Rotor earth fault protection 64R.....................................................222

    Section 10 Frequency protection....................................................225Under frequency protection SAPTUF.............................................225

    Identification..............................................................................225

    Application.................................................................................225

    Setting guidelines......................................................................225

    Over frequency protection SAPTOF...............................................226

    Identification..............................................................................226

    Application.................................................................................227

    Setting guidelines......................................................................227

    Rate-of-change frequency protection SAPFRC..............................228

    Identification..............................................................................228

    Application.................................................................................228

    Setting guidelines......................................................................228

    Section 11 Secondary system supervision.....................................231Fuse failure supervision SDDRFUF...............................................231

    Identification..............................................................................231

    Application.................................................................................231

    Setting guidelines......................................................................232

    General.................................................................................232

    Setting of common parameters............................................232

    Negative sequence based....................................................233

    Table of contents

    7

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    14/347

    Zero sequence based...........................................................234

    Delta U and delta I ...............................................................234

    Dead line detection...............................................................235

    Breaker close/trip circuit monitoring TCSSCBR.............................235Identification..............................................................................235

    Application.................................................................................235

    Section 12 Control..........................................................................239Synchrocheck, energizing check, and synchronizing

    SESRSYN......................................................................................239

    Identification..............................................................................239

    Application.................................................................................239

    Synchronizing.......................................................................239

    Synchrocheck.......................................................................240

    Energizing check..................................................................242

    Voltage selection..................................................................243

    External fuse failure..............................................................244

    Application examples.................................................................244

    Single circuit breaker with single busbar..............................245

    Single circuit breaker with double busbar, external

    voltage selection...................................................................246

    Single circuit breaker with double busbar, internal

    voltage selection...................................................................247

    Setting guidelines......................................................................247

    Apparatus control ..........................................................................251

    Identification..............................................................................251

    Application.................................................................................251

    Interaction between modules.....................................................254

    Setting guidelines......................................................................255

    Bay control (QCBAY)...........................................................256

    Logic rotating switch for function selection and LHMI

    presentation SLGGIO.....................................................................2 56

    Identification..............................................................................256

    Application.................................................................................256

    Setting guidelines......................................................................256

    Selector mini switch VSGGIO.........................................................257

    Identification..............................................................................257

    Application.................................................................................257

    Setting guidelines......................................................................258

    IEC61850 generic communication I/O functions DPGGIO.............258

    Identification..............................................................................258

    Application.................................................................................258

    Setting guidelines......................................................................258

    Single point generic control 8 signals SPC8GGIO.........................259

    Table of contents

    8

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    15/347

    Identification..............................................................................259

    Application.................................................................................259

    Setting guidelines......................................................................259

    Automation bits AUTOBITS............................................................260Identification..............................................................................260

    Application.................................................................................260

    Setting guidelines......................................................................260

    Section 13 Logic.............................................................................261Tripping logic SMPPTRC................................................................261

    Identification..............................................................................261

    Application.................................................................................261

    Three-phase tripping ...........................................................261

    Lock-out................................................................................262

    Blocking of the function block...............................................262

    Setting guidelines......................................................................262

    Trip matrix logic TMAGGIO............................................................263

    Identification..............................................................................263

    Application.................................................................................263

    Setting guidelines......................................................................263

    Configurable logic blocks................................................................264

    Identification..............................................................................264

    Application.................................................................................265

    Configuration........................................................................265Fixed signals FXDSIGN..................................................................266

    Identification..............................................................................266

    Application.................................................................................266

    Boolean 16 to integer conversion B16I...........................................267

    Identification..............................................................................267

    Application.................................................................................267

    Setting guidelines......................................................................268

    Boolean 16 to integer conversion with logic node

    representation B16IFCVI................................................................268

    Identification..............................................................................268

    Application.................................................................................268

    Setting guidelines......................................................................268

    Integer to boolean 16 conversion IB16A........................................268

    Identification..............................................................................268

    Application.................................................................................269

    Setting guidelines......................................................................269

    Integer to boolean 16 conversion with logic node

    representation IB16FCVB...............................................................269

    Identification..............................................................................269

    Application.................................................................................269

    Table of contents

    9

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    16/347

    Settings......................................................................................269

    Section 14 Monitoring.....................................................................271IEC61850 generic communication I/O functions SPGGIO....... ..... .271

    Identification..............................................................................271

    Application.................................................................................271

    Setting guidelines......................................................................271

    IEC61850 generic communication I/O functions 16 inputs

    SP16GGIO.....................................................................................271

    Identification..............................................................................271

    Application.................................................................................271

    Setting guidelines......................................................................272

    IEC61850 generic communication I/O functions MVGGIO.............272

    Identification..............................................................................272

    Application.................................................................................272

    Setting guidelines......................................................................272

    Measurements................................................................................273

    Identification..............................................................................273

    Application.................................................................................273

    Setting guidelines......................................................................275

    Setting examples.......................................................................277

    Measurement function application for a 400 kV OHL...........278

    Measurement function application for a generator...............280

    Event counter CNTGGIO................................................................282

    Identification..............................................................................282

    Application.................................................................................282

    Setting guidelines......................................................................282

    Disturbance report .........................................................................283

    Identification..............................................................................283

    Application.................................................................................283

    Setting guidelines......................................................................284

    Binary input signals..............................................................287

    Analog input signals.............................................................287

    Sub-function parameters......................................................288

    Consideration.......................................................................288

    Measured value expander block MVEXP.......................................289

    Identification..............................................................................289

    Application.................................................................................289

    Setting guidelines......................................................................290

    Station battery supervision SPVNZBAT.........................................290

    Identification..............................................................................290

    Application.................................................................................290

    Insulation gas monitoring function SSIMG.....................................291

    Identification..............................................................................291

    Table of contents

    10

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    17/347

    Application.................................................................................291

    Insulation liquid monitoring function SSIML....................................291

    Identification..............................................................................291

    Application.................................................................................291Circuit breaker condition monitoring SSCBR..................................291

    Identification..............................................................................291

    Application.................................................................................292

    Section 15 Metering.......................................................................295Pulse counter PCGGIO..................................................................295

    Identification..............................................................................295

    Application.................................................................................295

    Setting guidelines......................................................................295

    Energy calculation and demand handling EPTMMTR....................296

    Identification..............................................................................296

    Application.................................................................................296

    Setting guidelines......................................................................297

    Section 16 Station communication.................................................299IEC61850-8-1 communication protocol .........................................299

    Identification..............................................................................299

    Application.................................................................................299

    Horizontal communication via GOOSE................................301

    Setting guidelines......................................................................303

    DNP3 protocol................................................................................303

    IEC 60870-5-103 communication protocol.....................................304

    Section 17 Basic IED functions......................................................305Self supervision with internal event list ..........................................305

    Identification..............................................................................305

    Application.................................................................................305

    Time synchronization......................................................................306

    Identification..............................................................................306

    Application.................................................................................306

    Setting guidelines......................................................................307Parameter setting group handling..................................................309

    Identification..............................................................................309

    Application.................................................................................309

    Setting guidelines......................................................................309

    Test mode functionality TESTMODE..............................................310

    Identification..............................................................................310

    Application.................................................................................310

    Setting guidelines......................................................................310

    Change lock CHNGLCK.................................................................310

    Table of contents

    11

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    18/347

    Identification..............................................................................310

    Application.................................................................................310

    Setting guidelines......................................................................311

    IED identifiers TERMINALID..........................................................312Identification..............................................................................312

    Application.................................................................................312

    Customer specific settings...................................................312

    Product information PRODINF.......................................................312

    Identification..............................................................................312

    Application.................................................................................312

    Factory defined settings.......................................................312

    Primary system values PRIMVAL...................................................313

    Identification..............................................................................313

    Application.................................................................................313Signal matrix for analog inputs SMAI.............................................313

    Identification..............................................................................313

    Application.................................................................................313

    Setting guidelines......................................................................314

    Summation block 3 phase 3PHSUM..............................................316

    Identification..............................................................................316

    Application.................................................................................316

    Setting guidelines......................................................................317

    Global base values GBASVAL.......................................................317

    Identification..............................................................................317Application.................................................................................317

    Setting guidelines......................................................................317

    Authority check ATHCHCK.............................................................318

    Identification..............................................................................318

    Application.................................................................................318

    Authorization handling in the IED.........................................318

    Authority status ATHSTAT.............................................................319

    Identification..............................................................................319

    Application.................................................................................319

    Denial of service.............................................................................320Identification..............................................................................320

    Application.................................................................................320

    Setting guidelines......................................................................320

    Section 18 Requirements...............................................................321Current transformer requirements..................................................321

    Current transformer classification..............................................321

    Conditions..................................................................................322

    Fault current..............................................................................323

    Secondary wire resistance and additional load.........................323

    Table of contents

    12

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    19/347

    General current transformer requirements................................323

    Rated equivalent secondary e.m.f. requirements......................324

    Transformer differential protection.......................................324

    1 Ph high impedance differential protection.........................325Breaker failure protection.....................................................326

    Non-directional instantaneous and definitive time, phase

    and residual overcurrent protection......................................326

    Non-directional inverse time delayed phase and residual

    overcurrent protection..........................................................327

    Directional phase and residual overcurrent protection.........328

    Current transformer requirements for CTs according to

    other standards..........................................................................329

    Current transformers according to IEC 60044-1,

    class P, PR...........................................................................329

    Current transformers according to IEC 60044-1, class

    PX, IEC 60044-6, class TPS

    (and old British Standard, class X).......................................329

    Current transformers according to ANSI/IEEE.....................329

    Voltage transformer requirements..................................................330

    SNTP server requirements.............................................................331

    SNTP server requirements........................................................331

    Section 19 Glossary.......................................................................333

    Table of contents

    13

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    20/347

    14

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    21/347

    Section 1 Introduction

    1.1 This manualThe application manual contains application descriptions and setting guidelines

    sorted per function. The manual can be used to find out when and for what purpose

    a typical protection function can be used. The manual can also be used when

    calculating settings.

    1.2 Intended audienceThis manual addresses the protection and control engineer responsible for

    planning, pre-engineering and engineering.

    The protection and control engineer must be experienced in electrical power

    engineering and have knowledge of related technology, such as communication

    and protocols.

    1MRK 502 033-UEN - Section 1Introduction

    15

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    22/347

    1.3 Product documentation1.3.1 Product documentation set

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manual

    Operation manual

    Installation manual

    Service manual

    Engineering manual

    Commissioning manual

    Communication protocolmanual

    Technical manual

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manualApplication manual

    Operation manualOperation manual

    Installation manualInstallation manual

    Service manualService manual

    Engineering manualEngineering manual

    Commissioning manualCommissioning manual

    Communication protocolmanualCommunication protocolmanual

    Technical manualTechnical manual

    en07000220.vsd

    IEC07000220 V1 EN

    Figure 1: The intended use of manuals in different lifecycles

    The engineering manual contains instructions on how to engineer the IEDs using

    the different tools in PCM600. The manual provides instructions on how to set up a

    PCM600 project and insert IEDs to the project structure. The manual also

    recommends a sequence for engineering of protection and control functions, LHMI

    functions as well as communication engineering for IEC 60870-5-103, IEC 61850and DNP3.

    The installation manual contains instructions on how to install the IED. The

    manual provides procedures for mechanical and electrical installation. The chapters

    are organized in chronological order in which the IED should be installed.

    The commissioning manual contains instructions on how to commission the IED.

    The manual can also be used by system engineers and maintenance personnel for

    assistance during the testing phase. The manual provides procedures for checking

    of external circuitry and energizing the IED, parameter setting and configuration as

    Section 1 1MRK 502 033-UEN -Introduction

    16

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    23/347

    well as verifying settings by secondary injection. The manual describes the process

    of testing an IED in a substation which is not in service. The chapters are organized

    in chronological order in which the IED should be commissioned.

    The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controlling

    and setting the IED. The manual also describes how to identify disturbances and

    how to view calculated and measured power grid data to determine the cause of a

    fault.

    The service manual contains instructions on how to service and maintain the IED.

    The manual also provides procedures for de-energizing, de-commissioning and

    disposal of the IED.

    The application manual contains application descriptions and setting guidelines

    sorted per function. The manual can be used to find out when and for what purpose

    a typical protection function can be used. The manual can also be used when

    calculating settings.

    The technical manual contains application and functionality descriptions and lists

    function blocks, logic diagrams, input and output signals, setting parameters and

    technical data sorted per function. The manual can be used as a technical reference

    during the engineering phase, installation and commissioning phase, and during

    normal service.

    The communication protocol manual describes a communication protocol

    supported by the IED. The manual concentrates on vendor-specific implementations.

    The point list manual describes the outlook and properties of the data points

    specific to the IED. The manual should be used in conjunction with the

    corresponding communication protocol manual.

    The service manual is not available yet.

    1.3.2 Document revision historyDocument revision/date Product series version History-/February 2011 1.1 First release

    1.3.3 Related documentsDocuments related to REG650 Identity numberApplication manual 1MRK 502 033-UEN

    Technical manual 1MRK 502 034-UEN

    Commissioning manual 1MRK 502 035-UEN

    Table continues on next page

    1MRK 502 033-UEN - Section 1Introduction

    17

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    24/347

    Documents related to REG650 Identity numberProduct Guide 1MRK 502 036-BEN

    Type test certificate 1MRK 502 036-TEN

    Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670 1MRG001910

    650 series manuals Identity numberCommunication protocol manual, DNP3 1MRK 511 241-UEN

    Communication protocol manual, IEC 61850 1MRK 511 242-UEN

    Communication protocol manual, IEC 60870-5-103 1MRK 511 243-UEN

    Point list manual, DNP3 1MRK 511 244-UEN

    Engineering manual 1MRK 511 245-UEN

    Operation manual 1MRK 500 093-UEN

    Installation manual 1MRK 514 014-UEN

    1.4 Symbols and conventions1.4.1 Safety indication symbols

    The electrical warning icon indicates the presence of a hazard

    which could result in electrical shock.

    The warning icon indicates the presence of a hazard which could

    result in personal injury.

    The caution icon indicates important information or warning related

    to the concept discussed in the text. It might indicate the presence

    of a hazard which could result in corruption of software or damage

    to equipment or property.

    The information icon alerts the reader of important facts and

    conditions.

    The tip icon indicates advice on, for example, how to design your

    project or how to use a certain function.

    Section 1 1MRK 502 033-UEN -Introduction

    18

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    25/347

    Although warning hazards are related to personal injury, it is necessary to

    understand that under certain operational conditions, operation of damaged

    equipment may result in degraded process performance leading to personal injury

    or death. Therefore, comply fully with all warning and caution notices.

    1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in this

    manual.

    Abbreviations and acronyms in this manual are spelled out in the glossary. The

    glossary also contains definitions of important terms.

    Push button navigation in the LHMI menu structure is presented by using the

    push button icons, for example:

    To navigate between the options, use and .

    HMI menu paths are presented in bold, for example:

    Select Main menu/Settings.

    LHMI messages are shown in Courier font, for example:

    To save the changes in non-volatile memory, select Yes and press .

    Parameter names are shown in italics, for example:

    The function can be enabled and disabled with the Operation setting.

    The ^ character in front of an input or output signal name in the function block

    symbol given for a function, indicates that the user can set an own signal name

    in PCM600.

    The * character after an input or output signal name in the function block

    symbol given for a function, indicates that the signal must be connected to

    another function block in the application configuration to achieve a valid

    application configuration.

    1MRK 502 033-UEN - Section 1Introduction

    19

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    26/347

    20

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    27/347

    Section 2 Application

    2.1 REG650 applicationREG650 is used for the protection and monitoring of generating plants. The IED is

    especially suitable for applications in distributed control systems with high

    demands on reliability. It is intended mainly for small and medium size generation

    stations.

    REG670 may be used when more extensive protection systems are required or in

    combination with REG650 to provide redundant schemes.

    A wide range of protection functions is available to achieve full and reliable

    protection for different types of generating plants, for example hydro power plants

    and thermal power plants. This enables adaptation to the protection requirements of

    most generating plants.

    Protection functions are available for detecting and clearing internal faults, such as

    generator stator short circuits and earth faults, generator rotor earth faults, unit

    transformer short circuits and earth faults and faults in the external power system,

    fed from the generating plant.

    Two packages have been defined for the following applications:

    Generator protection IED including generator differential protection (B01)

    Generator-transformer unit protection IED including transformer differential

    protection (B05)

    In many generating plants, the protection system can be designed with a

    combination of the two packages, that is, two IEDs of either same type or different

    types, will give redundant protection for a generating unit (generator and unit

    transformer) depending on the requirements for the plant design.

    The packages are configured and ready for use. Analogue inputs and binary input/output circuits are pre-defined.

    The pre-configured IED can be changed and adapted with the graphical

    configuration tool.

    1MRK 502 033-UEN - Section 2Application

    21

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    28/347

    A, B, C or D

    ~

    59N UN>

    STEF PHIZ

    59THD U3d/N

    REG650-B01

    TR PTTR

    49 Ith

    LEX PDIS

    40

    OEX PVPH

    24 U/f>

    UV2 PTUV

    27 3U

    OC4 PTOC

    51 3I>

    GEN PDIF

    87G 3Id/I

    SA PTUF

    81U f/U

    OC4 PTOC

    51 3I>

    CC RPLD

    52PD PD

    CC RBRF

    50BF 3I> BF

    YY

    Generator CB

    Auxiliary

    Transformer

    Unit

    Transformer

    29MVA

    121/11kV

    YNd5

    Excitation

    Transformer

    HV CB

    ROV2 PTOV

    59N 3Uo>

    TR PTTR

    49 Ith

    OOS PPAM

    78 Ucos

    SESRSYN

    25 SC

    1)

    2)

    3)

    3) Input for independent directional (sensitive) EF function. It can be used for different purposes

    (e.g. as rotor EF with RXTTE4 or stator EF for generators operating in parallel)

    FieldCB

    HZ PDIF

    87N IdN

    2) Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protection for

    generators with split winding or even HV side EF protection). Alternatively it can be used for High-Impedance REF protection.

    ROV2 PTOV

    59N 3Uo>

    CV MMXN

    Meter.

    GOP PDOP

    32

    GOP PDUP

    37 P

    EF4 PTOC

    67N

    SDE PSDE

    67N

    Rotor EF protection 64R

    GOP PDOP

    32Q

    SA PFRC

    81R df/dt

    390kVA

    11/0.37kV

    Dyn11

    50/5

    1600/5

    1600/5

    10/1

    1.6MVA

    11/0.4kV

    EF4 PTOC

    51N IN>

    11 0.11 0.11/ /

    33 3kV

    11 0.11 0.11/ /

    33 3kV

    11/ 0.11

    3kV

    200/1

    100/52500/5

    1000

    29MVA

    11kV

    150rpm

    RXTTE4

    D

    C B

    A

    H J, G or H

    200/5

    G

    Y200/1

    J

    C MSQI

    Meter.

    IEC10000299-1-en.vsd

    Q

    P

    IN> IN>

    UV2 PTUV

    27 3U

    T3D PDIF

    87T 3Id/I

    SA PTUF

    81U f/U

    OC4 PTOC51 3I>

    CC RPLD52PD PD

    CC RBRF50BF 3I> BF

    YY

    Generator CB

    HV CB

    ROV2 PTOV

    59N 3Uo>

    TR PTTR

    49 Ith

    OOS PPAM

    78 Ucos

    SES RSYN

    25 SC

    Note:

    2) Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protectionfor generators with split winding or even HV side EF protection). Alternatively it can be used for High-Impedance REF protection.

    1) Inputs for independent directional (sensitive) EF function. It can be used for different purposes(e.g. as rotor EF with RXTTE4 or stator EF for generators running in parallel)

    1)

    2)

    FieldCB

    TR PTTR

    49 Ith

    OC4 PTOC

    51 3I>

    HZ PDIF

    87N IdN

    EF4 PTOC

    51N IN>

    GT01

    ROV2 PTOV

    59N 3Uo>

    59N UN>

    YY

    CV MMXNMeter.

    GOP PDUP

    37 P

    EF4 PTOC

    67N

    SDE PSDE

    67N

    Rotor EF protection 64R

    CV MMXN

    Meter.

    GOP PDOP

    32Q

    SA PFRC

    81R df/dt

    3)

    3) Alternatively step-up transformer HV side open delta VT can be connected here

    Generator CB

    AuxiliaryTransformer

    UnitTransformer

    29MVA121/11kV

    YNd5

    ExcitationTransformer

    390kVA11/0.37kV

    Dyn11

    50/5

    1600/5

    29MVA11kV

    150rpm

    200/1

    100/5

    1.6MVA11/0.4kV

    11 0.11 0.11/ /

    33 3kV

    110 0.11 0.11/ /

    33 3kV

    11

    / 0.113

    kV

    2500/5

    1000

    RXTTE4

    C

    B

    E

    A

    D

    A or B

    D or E

    200/5

    G

    1600/5

    10/1H J, G or H

    Y200/1

    J

    SDD RFUF

    60FL

    C MSQI

    Meter.

    IEC10000300-1-en.vsd

    IN> IN>

    Q

    P

    On On On On

    Two step residual overvoltage ProtectionROV2PTOV , U0>, instance 1

    OnGen Term

    OnGen Term

    OnGen Neutr point

    OnGen Neutr point

    Two step residual overvoltage ProtectionROV2PTOV , U0>, instance 2

    OnT sec side

    OnT sec side

    OnT sec side

    OnT HV neutr point

    Overexcitation protection OEXPVPH On On On On

    100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based

    On On Applicationdependent

    Applicationdependent

    Underfrequency protection SAPTUF , instance 1 On On On On

    Underfrequency protection SAPTUF, instance 2 Off Off Off Off

    Underfrequency protection SAPTUF, instance 3 Off Off Off Off

    Underfrequency protection SAPTUF, instance 4 Off Off Off Off

    Overfrequency protection SAPTOF, instance 1 On On On On

    Overfrequency protection SAPTOF, instance 2 Off Off Off Off

    Overfrequency protection SAPTOF, instance 3 Off Off Off Off

    Overfrequency protection SAPTOF, instance 4 Off Off Off Off

    Table continues on next page

    1MRK 502 033-UEN - Section 2Application

    35

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    42/347

    Function Application 1 Application 2 Application 3 Application 4Rate-of-change frequency protection SAPFRC,instance 1

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Rate-of-change frequency protection SAPFRC ,

    instance 2

    Off Off Off Off

    Synchrocheck, energizing check, and synchronizingSESRSYN

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    1) The generator should have reverse power protection. If the generator consumes low reverse power at motor operation (< 1 % of SN),

    low forward power protection should be used. In other cases, reverse power protection should be used.2) Voltage-restrained time overcurrent protection add (VR2PVOC) can be used instead of the underimpedance protection.

    Section 2 1MRK 502 033-UEN -Application

    36

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    43/347

    2.3.1.6 Single generator/transformer unit, connected to a solidly earthedHigh Voltage (HV) system, with redundant protection

    REG650 (B01)

    3

    3

    3

    3

    1

    1

    3

    1

    1

    3

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B05)

    IEC10000128-1-en.vsd

    IEC10000128 V1 EN

    Figure 8: Single generator/transformer unit, connected to a solidly earthedHigh Voltage (HV) system, with redundant protection

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)

    is used as the main protection for the unit transformer and as back-up protection for

    the generator. The combination of the protections also gives redundant protection

    for the auxiliary system transformer.

    1MRK 502 033-UEN - Section 2Application

    37

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    44/347

    Table 6: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,THV)

    11 220 kV

    Generator rated power (SN) 1 150 MVA

    Short circuit power level infeed at HV-side 500 10000 MVA

    2.3.1.7 Single generator/transformer unit, connected to a high impedanceearthed High Voltage (HV) system, with redundant protection

    REG650 (B01)

    3

    3

    3

    3

    1

    1

    3

    1

    3

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B05)

    1

    IEC10000129-1-en.vsd

    IEC10000129 V1 EN

    Figure 9: Single generator/transformer unit, connected to a high impedanceearthed High Voltage (HV) system, with redundant protection

    Section 2 1MRK 502 033-UEN -Application

    38

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    45/347

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)

    is used as the main protection for the unit transformer and as back-up protection for

    the generator. The combination of the protections also gives redundant protection

    for the auxiliary system transformer.

    Table 7: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,

    THV)

    11 220 kV

    Generator rated power (SN) 1 150 MV

    Short circuit power level infeed at HV-side 500 5000 MVA

    2.3.1.8 Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit differential protection including thegeneratorsREG650 (B05)

    3

    3

    3

    1

    1

    3

    1

    3

    3

    3

    1

    1

    1

    3

    1

    3

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    3

    Aux

    IEC10000130-1-en.vsd

    IEC10000130 V1 EN

    Figure 10: Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit differential protection including thegenerators

    1MRK 502 033-UEN - Section 2Application

    39

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    46/347

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)

    is used as the main protection for the unit transformer and as back-up protection for

    the generator. The combination of the protections also gives redundant protection

    for the auxiliary system transformer.

    Table 8: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,

    THV)

    11 220 kV

    Generator rated power (SN) 1 150 MVA

    Short circuit power level infeed at HV-side 500 10000 MVA

    2.3.1.9 Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit transformer differential protectionREG650 (B05)

    3

    3

    3

    1

    1

    3

    1

    3

    3

    3

    1

    1

    1

    3

    1

    3

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    3

    Aux

    IEC10000131-1-en.vsd

    IEC10000131 V1 EN

    Figure 11: Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit transformer differential protection

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)

    is used as the main protection for the unit transformer and as back-up protection for

    Section 2 1MRK 502 033-UEN -Application

    40

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    47/347

    the generator. The combination of the protections also gives redundant protection

    for the auxiliary system transformer.

    Table 9: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,

    THV)

    11 220 kV

    Generator rated power (SN) 1 150 MVA

    Short circuit power level infeed at HV-side 500 10000 MVA

    2.3.1.10 Functionality tableThe proposal for functionality choice for the different application cases are shownin table 10.

    The recommendations have the following meaning:

    On: It is recommended to have the function activated in the application.

    Off: It is recommended to have the function deactivated in the application.

    Application dependent: The decision to have the function activated or not is

    dependent on the specific conditions in each case.

    Application 5 8 in table10 are according to application examples

    given in previous sections.

    Tab le 10: Recommended funct ions in the d if fe rent app licat ion examp lesFunction Application 5 Application 6 Application 7 Application 8Generator differential protection GENPDIF (B01) On On On On

    Transformer differential protection T3WPDIF (B05) On On On On

    1Ph High impedance differential protection HZPDIF Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Underimpedance protection for generators andtransformers ZGPDIS (B01)

    On On On On

    Underimpedance protection for generators andtransformers ZGPDIS (B05)

    Off Off Off Off

    Load encroachment LEPDIS Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Out-of-step protection OOSPPAM (B01) On On On On

    Out-of-step protection OOSPPAM (B05) Off Off Off Off

    Loss of excitation (underexcitation) protectionLEXPDIS (A01)

    On On On On

    Loss of excitation (underexcitation) protectionLEXPDIS (B05)

    Off Off Off Off

    Table continues on next page

    1MRK 502 033-UEN - Section 2Application

    41

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    48/347

    Function Application 5 Application 6 Application 7 Application 8Four step phase overcurrent protection OC4PTOC ,instance 1 (B01)

    OnAux T

    OnAux T

    OnAux T

    OnAux T

    Four step phase overcurrent protection OC4PTOC ,

    instance 1 (B05)

    On On On On

    Four step phase overcurrent protection OC4PTOC ,instance 2

    Off Off Off Off

    Four step residual overcurrent protection EF4PTOC ,instance 1 (B01)

    Off Off Off Off

    Four step residual overcurrent protection EF4PTOC ,instance 1 (B05)

    OnT HV

    OnT HV

    OnT HV

    OnT HV

    Four step residual overcurrent protection EF4PTOC ,instance 2

    Off Off Off Off

    Sensitive directional residual overcurrent and powerprotection SDEPSDE (B01)

    OnRotor EF

    OnRotor EF

    OnRotor EF

    OnRotor EF

    Sensitive directional residual overcurrent and power

    protection SDEPSDE (B05)

    Off Off Off Off

    Thermal overload protection TRPTTR , instance 1 On On On On

    Thermal overload protection TRPTTR , instance 2 Off Off Off Off

    Breaker failure protection CCRBRF (B01) On On On On

    Breaker failure protection CCRBRF (B05) OnHV CB

    OnHV CB

    OnHV CB

    OnHV CB

    Pole discordance protection CCRPLD Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Directional under-power protection GUPPDUP (lowforward power protection), (B01)

    1) 1) 1) 1)

    Directional underpower protection GUPPDUP (Low

    forward power protection), (B05)

    Off Off Off Off

    Directional overpower protection GOPPDOP ,instance 1 (reverse power protection), (B01)

    1) 1) 1) 1)

    Directional overpower protection GOPPDOP ,instance 1 (reverse power protection), (B05)

    Off Off Off Off

    Directional overpower protection GOPPDOP ,instance 2

    Off Off Off Off

    Accidental energizing protection for synchronousgenerator AEGGAPC (B01)

    On On On On

    Accidental energizing protection for synchronousgenerator AEGGAPC (B05)

    Off Off Off Off

    Negative-sequence time overcurrent protection formachines NS2PTOC On On On On

    Voltage-restrained time overcurrent protectionVR2PVOC (B01)

    2) 2) 2) 2)

    Voltage-restrained time overcurrent protectionVR2PVOC (B05)

    Off Off Off Off

    Two step undervoltage protection UV2PTUV , U< On On On On

    Two step overvoltage protection OV2PTOV , U> On On On On

    Two step residual overvoltage protectionROV2PTOV , U0>, instance 1 (B01)

    OnGen Neutr point

    OnGen Neutr point

    OnGen Neutr point

    OnGen Neutr point

    Table continues on next page

    Section 2 1MRK 502 033-UEN -Application

    42

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    49/347

    Function Application 5 Application 6 Application 7 Application 8Two step residual overvoltage protectionROV2PTOV , U0>, instance 1 (B05)

    OnT sec side

    OnT sec side

    OnT sec side

    OnT sec side

    Two step Residual Overvoltage Protection

    ROV2PTOV , U0>, instance 2 (B01)

    On

    Gen Term

    On

    Gen Term

    On

    Gen Term

    On

    Gen Term

    Two step residual overvoltage protectionROV2PTOV , U0>, instance 2 (B05)

    Off OnT HV neutr point

    OnT sec side 2

    OnT sec side 2

    Overexcitation protection OEXPVPH On On On On

    100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based (B01)

    On On On On

    100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based (B05)

    Off Off Off Off

    Underfrequency protection SAPTUF , instance 1 On On On On

    Underfrequency protection SAPTUF , instance 2 Off Off Off Off

    Underfrequency protection SAPTUF, instance 3 Off Off Off Off

    Underfrequency protection SAPTUF, instance 4 Off Off Off Off

    Overfrequency protection SAPTOF, instance 1 On On On On

    Overfrequency protection SAPTOF, instance 2 Off Off Off Off

    Overfrequency protection SAPTOF, instance 3 Off Off Off Off

    Overfrequency protection SAPTOF, instance 4 Off Off Off Off

    Rate-of-change frequency protection SAPFRC,instance 1

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Rate-of-change frequency protection SAPFRC,instance 2

    Off Off Off Off

    Synchrocheck, energizing check, and synchronizingSESRSYN(B01)

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Synchrocheck, energizing check, and synchronizingSESRSYN (B05)

    Off Off Off Off

    1) The generator should have reverse power protection. If the generator consumes low reverse power at motor operation (< 1 % of SN),

    low forward power protection should be used. In other cases, reverse power protection should be used.2) Voltage-restrained time overcurrent protection add (VR2PVOC) can be used instead of the underimpedance protection.

    1MRK 502 033-UEN - Section 2Application

    43

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    50/347

    44

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    51/347

    Section 3 REG650 setting examples

    The application example has a generation unit protected by one REG650 B01

    (Main 1) and one REG650 B05 (Main 2) as shown in figure 12.

    REG650 (B01)

    3

    3

    3

    3

    1

    1

    3

    1

    1

    3

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B05)

    145 kV

    IEC10000155-1-en.vsd

    IEC10000155 V1 EN

    Figure 12: Power plant protection applicationThe following data is assumed:

    Table 11: Data for the unit transformerItem DataTransformer rated power SN 25 MVA

    Transformer high voltage side rated voltage UN1 145 kV

    Transformer low voltage side rated voltage UN2 10.5 kV

    Transformer vector group YNd11

    Table continues on next page

    1MRK 502 033-UEN - Section 3REG650 setting examples

    45

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    52/347

    Item DataTransformer short circuit voltage ek 12 %

    Maximum allowed continuous overload 1.30 * SN

    Phase CT ratio at 145 kV level 150/1 ACT at 145 kV earth point 150/1 A

    Phase CT ratio at 10 kV level 1500/1 A

    10 kV VT ratio11 0 11 0 11

    kv33 3

    . ./ /

    High positive sequence source impedance at theHV side

    10 ohm (about 2100 MVA) with a phase angle 85

    High zero sequence source impedance at theHV side

    j20 ohm

    Table 12: Data for the generatorItem DataGenerator rated power SN 25 MVA

    Generator rated voltage UN 10.5 kV kV

    Rate power factor cosn 0.90

    xd 1.0 per unit (pu)

    xd 0.4 pu

    xd 0.25 pu

    Phase CT ratio at generator terminal side 1500/1 APhase CT ratio at generator neutral point side 1500/1 A

    Generator neutral point VT ratio11

    0.11 kV3

    /

    Generator 10 kV terminal VT ratio11 0 11 0 11

    kV33 3

    . ./ /

    Table 13: Data for the auxiliary transform erItem DataTransformer rated power SN 1.0 MVA

    Transformer high voltage side rated voltage UN1 10.5 kV

    Transformer low voltage side rated voltage UN2 0.4 kV

    Transformer vector group Dyn5

    Transformer short circuit voltage ek 4 %

    Phase CT ratio at 10.5 kV level 100/1 A

    Section 3 1MRK 502 033-UEN -REG650 setting examples

    46

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    53/347

    Only settings that need adjustment due to the specific application

    are described in setting examples. It is recommended to keep the

    default values for all settings that are not described. Refer to

    Technical manual for setting tables for each protection and control

    function.

    Refer to setting guideline section in Application manual for

    guidelines on how to set functions that are not presented in setting

    examples.

    Use parameter setting tool in PCM600 to set the IED according to

    calculations for the particular application.

    3.1 Calculating general settings for analogue TRMinputs 4I 1I 5UThe transformer module (TRM) has the capability of 4 current inputs (tapped to 1

    or 5 A), 1 current input (tapped to 0.1 or 0.5 A) and 5 voltage inputs.

    The generator neutral point phase CTs (three-phase current transformer group) are

    connected to inputs 1 3 (L1, L2 and L3).

    The generator neutral point CT can be connected to input 4 (not used here).

    The rotor earth fault current measurement is connected to input 5.

    The generator terminal side phase VT is connected to inputs 6 - 8 (L1, L2 and L3).

    The generator neutral point VT is connected to input 9.

    The rotor earth fault voltage measurement is connected to input 10.

    1. Set the current transformer inputs.

    1.1. Set CTStarPoint1 to To Object.

    The CT secondary is earthed towards the transformer.

    1.2. Set CTSec1 to 1 A.

    (The rated secondary current of the CT)

    1.3. Set CTPrim1 to 1500 A.

    (The rated primary current of the CT)

    1.4. Set the same values for current inputs 2 and 3.

    1.5. Set CTStarPoint4 to.

    1.6. Set CTSec4 to.

    1MRK 502 033-UEN - Section 3REG650 setting examples

    47

    Application Manual

  • 7/28/2019 1mrk502033-Uen - En Application Manual Generator Protection Reg650 Iec

    54/347

    1.7. Set CTPrim4 to.

    1.8. Set CTStarPoint5 to To Object.

    1.9. Set CTSec5 to 10 A.

    1.10. Set CTPrim5 to 1 A.

    2. Set the voltage transformer inputs.

    2.1. Set VTSec6to 110 V.

    (The