2000 lsc for assisted living handout
TRANSCRIPT
4/22/2014
1
2014 THCA LTC/AL Quality Symposium
Rebekah Eaddy, Architect
Architectural Unit
Survey Operations Section
512-438-2535
512-438-4623 FAX
DADS REGIONAL MAP
Facility Totals April 7, 2014
Adult Day Care 470
Assisted Living 1,747
ICF-IID/RC 861
Nursing 1,222
Total Facilities 4,300
HCSSA agencies 6,336
4/22/2014
2
Assisted Living___________1,747
• Large A 147 ( 139 in 9/06)
• Large B 545 (393 in 9/06)
• Small A 429 (485 in 9/06)
• Small B 582 (298 in 9/06)
• Type C 44 (119 in 9/06)
• Type E 0 ( 16 in 9/06)
LIFE SAFETY CODE (LSC) • The LSC’s purpose is to provide
minimum requirements for the design, operation, and maintenance of buildings and structures for safety to life from fire.
LIFE SAFETY CODE (LSC)
Protection of occupants is achieved by a combination of:
• Prevention of ignition
• Detection of fire
• Control of fire development
4/22/2014
3
LIFE SAFETY CODE (LSC)
Protection of occupants is achieved by a combination of:
• Extinguishment of fire
• Provision of refuge or
evacuation
• Staff reaction
• Provision of fire safety information
JUNE 13, 2013 DADS COUNCIL
TEXAS REGISTER
EFFECTIVE DATE
JANUARY 6, 2014
DADS adopts 2000 edition LSC for ALF
2000 edition of NFPA 101
Chapter 32 for New Residential Board and Care
All new ALF’s must have sprinklers Chapter 33 for Existing Residential Board and Care Small Type A’s sprinklers not req’d
4/22/2014
4
2000 edition of NFPA 101
Chapter 18 for New Healthcare All new ALF’s must have sprinklers
Chapter 19 for Existing Healthcare Only conversions of existing NF to
Large B would NOT require sprinklers
NFPA 101 2000 EDITION CODE BOOK COST $82.50 + S&H
http//catalog.nfpa.org
1-800-344-3555
http://www.nfpa.org/
4/22/2014
5
How sprinklers work
I got a great deal on insurance
Large Type A ALF’s
An existing Large Type A facility may have an NFPA 13 system. In a building not more than four stories high an NFPA 13R system may be permitted.
4/22/2014
6
Large Type A ALF’s
An existing Large Type A facility may have an NFPA 13 system. In a building not more than four stories high an NFPA 13R system may be permitted.
A new Large Type A facility must have an NFPA 13 system, however a building not more than four stories high may have an NFPA 13R system
Large Type B ALF’s
Existing Large Type B ALF’s must have a complete NFPA 13 system
Large Type B ALF’s
Existing Large Type B ALF’s must have a complete NFPA 13 system
New Large Type B ALF’s must have a complete NFPA 13 system
4/22/2014
7
Large Type B ALF’s
Plastic CPVC piping may be used if installed to meet manufacturers’ installation instructions
New Large Type B ALF’s must have a complete NFPA 13 system
Small Type A ALF’s
An existing small Type A facility may have a system that meets NFPA 13, 13D, or 13R requirements.
Small Type A ALF’s
An existing small Type A facility may have a system that meets NFPA 13, 13D, or 13R requirements.
A new small Type A facility must have a system that meets NFPA 13, 13D, or 13R requirements, installed in accordance with §32.2.3.5.2.
4/22/2014
8
§33.2.3.5.2. Exception No. 2
In existing slow evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered. Bath-rooms <55 sf are exempt.
§32.2.3.5.2. Exception No. 2
In new slow evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered.
Small Type B ALF’s
An existing small Type B facility must have a system that meets NFPA 13, 13D, or 13R requirements, in accordance with §33.2.3.5.2. .
4/22/2014
9
Small Type B ALF’s
An existing small Type B facility must have a system that meets NFPA 13, 13D, or 13R requirements, in accordance with §33.2.3.5.2. .
A new small Type B facility must have a system that meets NFPA 13, 13D, or 13R requirements, installed in accordance with §32.2.3.5.2.
§33.2.3.5.2. Exception No. 2
In existing impractical evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered. Bath-rooms <55 sf are exempt.
§32.2.3.5.2. Exception No. 2
In new impractical evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered.
4/22/2014
10
Thirty minute water supply
NFPA 13D has the minimum design discharge at 4-1.1, but it can be no less than the listing of the sprinkler, and the number of design sprinklers is at 4-1.2.
NFPA 13D Sprinkler Systems Installation of Sprinkler Systems in One- and Two-Fami ly Dwellings and Manufactured Homes
Only ten minute water supply required
No sprinklers required in:
• Bathrooms <55 sf,
• Closets <24 sf with dimension <3 ft
• Garages, porches, carports
• Attics, crawl spaces
• Entry foyers if not only means of egress
Sprinkler Maintenance
When installed or required, sprinkler systems must be inspected, tested, and maintained in accordance with NFPA 25.
4/22/2014
11
Sprinkler Maintenance
The facility must have a written contract with a fire protection sprinkler firm that has been issued a Sprinkler Certificate of Registration number (SCR) from the Texas State Fire Marshal's Office to perform the required services semiannually.
Sprinkler Maintenance
The facility must have documentation available to show that all the requirements of NFPA 25 have been met including the annual inspection, test, and maintenance by the registered fire sprinkler firm.
Sprinkler Maintenance
The facility must retain one set of the fire sprinkler system plans and hydraulic calculations on the property in accordance with NFPA 25.
4/22/2014
12
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
10. Failed to provide a written contract for maintaining the fire alarm system semi-annually §92.62(f)(1)(e)
Not ranked in FY12
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
9. Type B Large meets Health Care LSC §92.61(b)(4)(B)
#6 in FY12 & FY13
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
8. Failed to ensure interior wall and ceilings were sheathed with at least 20-minute fire-rating §92.62(e)(2)
Number 10 in FY12
4/22/2014
13
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
7. Dirty, rubbish, hazards, clean
floors, no storage in attic §92.62(h)(8) Top five last ten years
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
6. Fire drills conducted properly
§92.62(c)(2)
#8 in FY11
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
5. Fire alarm and smoke detection
system
§92.62(f)(1)
# 5 in FY10,
F11, & FY12
4/22/2014
14
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
4. Failed to meet other chapters of the Life Safety Code §92.61(b)(4)(C)
Ranked #6 in FY11 and #8 in FY12
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
3. Type A Large & Small must meet LSC
§92.61(b)(4)(A)
Top three last ten years
LSC 21-2.3.5.2 Impractical
All impractical facilities shall be protected throughout by an approved supervised automatic sprinkler system (supervised requires signal to sound at panel)
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
2. Sprinkler maintenance and testing §92.62(f)(2) Top 3 last 4 years
4/22/2014
15
TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013
1. Building, heating and air conditioning, electrical systems must be maintained. Use of electrical appliances, devices, and
lamps must be such as to not overload circuits..
§92.62(i)(2) Top five last ten years
Any questions?