39g - concepcion carrier€¦ · g8 df a3 26c1 af4a a 3 39g 39g series unit unit height module unit...
TRANSCRIPT
INTELLECTUALIZED CONTROL
Various of sense organs like VFD can be installed in units as requirements to auto control the unit.
EASY MAINTENANCE
The panels of 39G units are all removable panels. The access panel is low leak construction and easy
maintenance.
COMPUTER SELECTION
THC provides the double-quick and accurate computer selection. W e will get the reasonable coil, fan
and electric motor to meet the customer’s requirement.
CAPACITY
• The fan has the forwad curved and backward curved centrifugal type with low noise and high
efficiency. The fan wheel and pulley shall be statically and dynamically balanced.
The fan and motor assembly is mounted on a common base with shock absorber. The fan outletis
isolated from the casing by a flexible connection.
• Fins are the “dual sine-wave” form, and mechanically bonded with copper tubes. Headers have drain
and vent connections, So coil is drainable and has non air trapping circuits.
The water in the coil must be discharged in winter to avoid the frost crack of the coil.
If coil face air velocity higher than 2.5m/s, drift eliminator must be installed after coil.
• Primary filter is panel structure, the efficineey reaches G3.
medium filter is bag structure, the efficiency reaches F5.
CONSTRUCTION
• Modular design
All basic component parts are standard and interchangable.
• Double skin panel construction,heat preservation with PU foam.
The thickness of PU foam panel is 25mm, with light weight, good rigidity and the thermal conductivity
coefficient less than 0.0199 w/m.�.
• Downwards condensate drain pan
This design ensures to drain all the condensated water.
• Drain valve
The drain valve is at the bottom of the coil return circuit, this can discharge the seeper and avoid the frost
crack of the coil.
• Damper
The damper can be opened flexibly, it also can add the electric controller as the requirements.
• Unit base
Each section has the base, which enhance the intensity and make it easy to transport and assemble.
39G1
INTRODUCTIONINTRODUCTION
Horizontal Standard 1:
External Filter + Coil + Fan
Horizontal Standard 2:
Mixing Box + Panel Filter + Coil + Fan
Horizontal Standard 3:
Mixing Box + Panel Filter + Bag Filter + Coil + Fan
Horizontal Standard 4:
Mixing Box + Panel Filter + Bag Filter + Coil + Heating Coil + Fan
Horizontal Standard 5:
Mixing Box + Panel Filter + Bag Filter + Coil + Humidifier + Fan
Horizontal Standard 6:
Mixing Box + Panel Filter + Bag Filter + Coil + Heating Coil + Humidifier + Fan
Vertical Standard 1:
External Filter + Coil + Fan
Vertical Standard 2:
Mixing Box + Panel Filter + Coil + Humidifier + Fan
Vertical Standard 3:
Mixing Box + Panel Filter + Bag Filter + Coil + Humidifier + Fan
Vertical Standard 4:
Mixing Box + Panel Filter + Coil + Heating Coil + Humidifier + Fan
Vertical Standard 5:
Mixing Box + Panel Filter + Bag Filter + Coil + Humidifier Coil + Humidifier + Fan
STANDARD COMPONENT
19 sizes of standard units from 39G0609 to 39G2334 (Air flow 2209~57766m3/h), available with
different combination of air handling functions, arranged in both horizontal and vertical configuration.
39G2
CONFIGURATION
Fan
Cooling Coil
Heating Coil
Humidifier
External Panel Filter
Internal Panel Filter
Bag Filter
Damper
Casing
Drain Pan
Fins
Header
Standard-Forward/Backward Curve Blades
Standard-4,6,8 Rows W ith Combinations Of Circuit And Fins
Standard-2 Rows Hot Water Coil
Standard-Steam Humidifier
Standard-High Velocity Filter
Standard-Front Load Low Vciocity Filter
Standard-Intermedium Efficiency Bag Filter
Standard-Manual Operated Damper
Standard-Powder Painted Steel
Standard-Galvanized Steel
Standard-Aluminium
Standard-Steel Header
Option-Steam Coil
Option-High-pressure Spray Humidifiers
Option-Film Humidifiers
Option-Low Velocity Filter
Option-Initial Bag Filter
Option-Sub-HEPA Bag Filter
Option-Electric Actuated Damper
Option-Pre-Painted Steel
Option-Stainess Steel
Option-Pre-Coated Aluminum
Option-Copper Header
Option-Side WithdrawHigh Velocity Filter
Option-Side WithdrawLow Velocity Filter
(The max unit size 39G1518)
STANDARD UNITSTANDARD UNIT
The 39G Air Handling Unit is based on 15-digital-code system. The first five codes indicate unit type
and the last ten codes indicate the unit detail compenents.
To determine external dimensions, the following formula applies:
(1) External Height Dimensions = number of height modules x 100 + 50 + 100(base)
(2)External W idth Dimensions= number of weidth modules x 100 + 50
Example: 39G0712
07 Height Modules External Height Dimensions: 7 x 100 + 50 + 100 = 850mm
12 W idth Modules External W idth Dimensions: 12 x 100 + 50 = 1250mm
UNIT TYPE COMPONENTS
G 8 D F A 3 2 6 C 1 A F 4 A A
39G3
39G Series Unit
Unit Height Module
Unit W idth Module
Unit Type
Fan Arrangement
Panel Filter
Bag Filter
Cooling Coil Rows
Non-Standard Remark
Other Component(header, drain pan, fins)
Other Component(vibration isolator, eliminator,
damper)
Fan Type And Motor Poles
Humdifier
Heating Coil
Cooling Coil Circuit/FPI
LEFT HAND
RIGHT HAND
AIR FLOW
IDENTIFICATION & DIMENSIONIDENTIFICATION & DIMENSION
Unit handling orientation is determined
by location of pipe connection while
facing unit in the direction of air flow.
UNIT SIZE
0.24
0.34
0.49
0.70
0.81
1.05
1.15
1.44
1.68
2.07
2.36
2.55
2.93
3.30
3.59
3.96
4.63
5.48
6.42
2008
2755
3979
5663
6582
8495
9337
11632
13623
16837
19133
20664
23725
26786
29082
30143
37501
44388
52041
2209
3058
4417
6286
7306
9429
10364
12912
15121
18689
21238
22937
26335
29733
32281
35679
41626
49271
57766
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
200~800
UNIT
AIR VOLUME
m3/h 2.25m/sW IDTHHEIGHT 2.5m/s
650
650
750
850
950
1050
1050
1150
1350
1550
1550
1650
1850
1850
1850
2050
2250
2350
2350
950
1050
1250
1350
1450
1550
1650
1750
1750
1850
2250
2250
2250
2450
2550
2550
2650
3050
3450
2209
3058
4417
6286
7306
9429
10364
12912
15121
18689
21238
22937
26335
29733
32281
35679
41626
49271
57766
2430
3364
4859
6915
8037
10372
11400
14703
16633
20558
23362
25231
28968
32706
35509
39247
45789
54198
63543
2.75m/s
39G0609
39G0610
39G0712
39G0813
39G0914
39G1015
39G1016
39G1117
39G1317
39G1518
39G1522
39G1622
39G1822
39G1824
39G1825
39G2025
39G2226
39G2330
39G2334
39G4
DIMENSION
Note: 1. The “Height” does not include 100mm (unit base).
2. The unit length is determined by the coponents required.
3. It is recommended to provide coil drift eliminators when coil face velocity exceeds 2.5 m/s.
COIL FACE
AREA (m2)
AIR VOLUME m3/hEXTERNAL
STATIC
PRESSURE
Pa
QUICK SELECTIONQUICK SELECTION