UPS A1 & A2 Quick Guide User’s Manual Spare time 5 minutes (PC LOAD) Output mode Sockets 15] Copyright AST 2010 www.ast-global.com Safety Symbols Means Communication interface 1. Table 1 Safety Symbols and Means 2. Table 2 UPS Main Performance Index Secure alarm Specifications are subject to change without prior notice. Risk of electric shock A1 & A2 QUICK GUIDETRANSCRIPT
UPS A1 & A2 Quick Guide User’s Manual
A1 & A2 QUICK GUIDE
15] Copyright AST 2010 www.ast-global.com
1. Table 1 Safety Symbols and Means Safety Symbols Means
Secure alarm
Risk of electric shock
2. Table 2 UPS Main Performance Index
Index Model A1 A2
Rating voltage (V) In range 160~290V full load
Rating frequency (Hz) 50±5%
Input mode Single-phase three-line
Inpu
t
Cha
ract
eris
tic
Battery voltage (V) 36 72
Capacity (VA/W) 1000/700 2000/1400
Voltage (V) 230±2%
Frequency (Hz) 50±0.2% (Battery mode)
Waveform Sine wave
Voltage distortion
factor THD < 3% (Linear load)
Power factor 0.7 (Lag)
Switching time (ms) 0
Overload capacity 105%~130% Load, lasting 60 seconds. 135%~150% Load, lasting 30 seconds.≥150%
lasting 300 milliseconds
Out
put C
hara
cter
istic
Output mode Sockets
Spare time 5 minutes
(PC LOAD)
5 minutes
(PC LOAD)
Charge recovery time <12 hours (Standard time delay model)
Communication
interface
A1 & A2: RS232 & USB interface
RS232 interface supports UPS power management software UPSilon 2000 and SNMP
adapter
Panel display LED displays operation status of UPS
Warning function Battery low voltage, abnormal power supply, UPS malfunction
Protection function Battery low voltage protection, overload protection, short-circuit protection and excess
temperature protection
Frequency noise (dB) < 45
Working temperature 0 ~ 40℃
Relative humidity 0 ~ 95%, No condensation
Size (mm)(H × W × D) 88×440×500
Oth
er C
hara
cter
istic
s
Weight (kg) 14 11 ◆ Specifications are subject to change without prior notice.
A1 & A2 QUICK GUIDE
15] Copyright AST 2010 www.ast-global.com
3. Rear Panel
AC OUTPUT
FAN
AC OUTPUT SOCKET
(REAR PANEL)
RS232 PORTBREAKER
AC INPUT、DC INPUT TERMINAL
USB PORT
RS232 USBFUSE
AC INPUT
直流输入/DC INPUT
A1 Rear Panel
FANRS232 PORT FANBREAKER
AC INPUT、DC INPUT TERMINAL
REAR PANEL
USB PORT
RS232 USBFUSE
AC OUTPUT SOCKET
AC OUTPUTAC INPUT
(+) BATTERY (-) DC INPUT
A2 Rear Panel
A1 & A2 QUICK GUIDE
15] Copyright AST 2010 www.ast-global.com
(REAR PANEL)
RS232 PORT
BREAKER
USB PORT
RS
232
US
BFU
SE
AC OUTPUT SOCKET
AC
INPU
T
直流输入
/DC
INP
UT
FAN
DC INPUTLINE BAR
AC INPUT SOCKET
AC O
UTP
UT
RS232 PORT
BREAKER
USB PORT
RS2
32U
SB
FUS
E
AC OUTPUT SOCKET
FAN
AC INPUT、DC INPUT TERMINAL
(REAR PANEL)
AC
OU
TPU
T
AC
INPU
T
(+) B
ATT
ERY
(-)
DC
INPU
T
Horizontal A1 Horizontal A2
4. Preparations before First Start-up
To ensure normal operation of UPS, please confirm the following before use: A. Correct installation of input and output. B. If supply terminals connect to the rated power. . C. Confirm that UPS output does not short circuit, and the load capacity does not exceed UPS capacity. D. Confirm if computer or other instrument is turned off. E. Confirm if battery voltage is normal. F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by electric network directly.
5. UPS Start-up Sequence
After confirming all the above, please start the machine by following means:
A. Press the "POWER" button on the UPS panel to start UPS, the "INV" indicator light will light up. After retardation time, the "BYP." light goes out and the UPS is changed inversion power supply. By this time, the start-up is completed and the equipment starts operation. Wait for about 20 seconds after normal no-load operation to turn on the computer or other instrument. Start the load in the sequence of high-power to low power, first start the high-power equipment then in turns start equipment with lower power.
B. Start computer or other equipment.
A1 & A2 QUICK GUIDE
15] Copyright AST 2010 www.ast-global.com
6. Daily Start-up and Shutdown
During daily operation, operate as per the following for start-up or shut down: A. Press the "ON" button on the UPS panel to start UPS, after 20 seconds, turn on the computer or other
instrument. B. Normally, only when the UPS has been started and is working stably, can the loading equipment power switch be turned on. First turn on high-power equipment, then the equipment with lower power. Some equipment has large start current (such as monitors of some brands). When starting such equipment, overload protection (such as bypass operation) may occur. In this case, it's recommended to start this type of equipment before other equipment. C. Before shutdown, turn off the computer and other instrument first. Then press the "OFF" button on the
panel for seconds.
7. Maintenance Guide
The correct maintenance, including the preventative maintenance and remedial maintenance, is the key to the
best operation and longer usage life of the UPS. The preventive maintenance includes some regular programs
to avoid the faults of the power system and reach maximum efficiency. The remedial maintenance includes the
probing of the power system fault for the effective maintenance.
8. Safety Precaution
For safe and smooth maintenance on the power system, you must follow the related safety precautions, prepare the necessary gears and testing equipments and operate under the eligible maintainer’s control. Pay attention to the following safety operation regulations:
A. Do remember there always exits hazardous voltage inside UPS even when UPS do not run. B. Make sure persons manipulating or maintaining UPS are familiar with the manual and instrument. C. When UPS operation, no golden or sliver accouterments like ring, watch wore. D. Do assume the safe operation procedure as a matter of course. If any doubt, consult with persons being familiar with the instrument. E. Keep eye on the hazardous voltage inside the UPS every moment. Using voltmeter to check if the input power is completely cutoff and in safe status before maintenance and adjustability.
Please comply with the manual to use UPS. When UPS faults, please cut off the connection between battery cabinet and UPS immediately then deliver it to professional maintainer or station. Self-deal is prohibited.