agenda and objectives - trane.com...high-performance vav systems variable-air-volume (vav) systems...

57
Agenda and Objectives Trane Engineers Newsletter Live Series High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates. This course will discuss design and control strategies that can significantly reduce energy use and ensure proper ventilation in VAV systems. Topics will likely include: ventilation system design and control, optimized VAV system controls, cold air distribution, and other energy-saving strategies. By attending this ENL you will be able to: 1. Summarize ASHRAE Standard 189.1 requirements for a VAV system 2. Explain how to implement optimized VAV system control strategies 3. Summarize how to design and control cold-air VAV systems 4. Apply air-to-air energy recovery in a VAV system Agenda 1) Opening (welcome, agenda, introductions) 2) What does ASHRAE 189.1 (or the IGCC) require for a VAV system? 3) Optimized VAV system controls a) Optimal start/Optimal stop b) Fan-pressure optimization c) Supply-air-temperature reset d) Ventilation optimization 3) Cold-air Distribution a) Benefits b) Tips to maximize energy savings c) Minimizing comfort problems due to cold air “dumping” d) Avoiding condensation on air distribution system components 4) Air-to-air energy recovery 5) List of other energy-saving strategies (RTVAV and CHWVAV) 6) Share results of example TRACE analyses 4) Summary

Upload: others

Post on 23-Jun-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Agenda and Objectives

Trane Engineers Newsletter Live Series

High-Performance VAV Systems

Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates.

This course will discuss design and control strategies that can significantly reduce energy use and ensure proper

ventilation in VAV systems. Topics will likely include: ventilation system design and control, optimized VAV system controls,

cold air distribution, and other energy-saving strategies.

By attending this ENL you will be able to:

1. Summarize ASHRAE Standard 189.1 requirements for a VAV system

2. Explain how to implement optimized VAV system control strategies

3. Summarize how to design and control cold-air VAV systems

4. Apply air-to-air energy recovery in a VAV system

Agenda

1) Opening (welcome, agenda, introductions)

2) What does ASHRAE 189.1 (or the IGCC) require for a VAV system?

3) Optimized VAV system controls

a) Optimal start/Optimal stop

b) Fan-pressure optimization

c) Supply-air-temperature reset

d) Ventilation optimization

3) Cold-air Distribution

a) Benefits

b) Tips to maximize energy savings

c) Minimizing comfort problems due to cold air “dumping”

d) Avoiding condensation on air distribution system components

4) Air-to-air energy recovery

5) List of other energy-saving strategies (RTVAV and CHWVAV)

6) Share results of example TRACE analyses

4) Summary

Agenda_APPCMC042.ai 1 6/17/2014 11:15:26 AM

Page 2: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Presenters

Trane Engineers Newsletter Live Series

High-Performance VAV Systems (2011)

Dennis Stanke | staff application engineer | TraneWith a BSME from the University of Wisconsin, Dennis joined Trane in 1973, as a controls development engineer. He is now a Staff Applications Engineer specializing in airside systems including controls, ventilation, indoor air quality, and dehumidification. He has written numerous applications manuals and newsletters, has published many technical articles and columns, and has appeared in many Trane Engineers Newsletter Live broadcasts.

An ASHRAE Fellow, he currently serves as Chairman for ASHRAE Standard 189.1, Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings. He recently served as Chairman for ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality, and he served on the USGBC LEED Technical Advisory Group for Indoor Environmental Quality (the LEED EQ TAG).

John Murphy | applications engineer | TraneJohn has been with Trane since 1993. His primary responsibility as an applications engineer is to aid designengineers and Trane sales personnel in the proper design and application of HVAC systems. As a LEED AccreditedProfessional, he has helped our customers and local offices on a wide range of LEED projects. His main areas ofexpertise include energy efficiency, dehumidification, dedicated outdoor‐air systems, air‐to‐air energy recovery,psychrometry, and ventilation.

John is the author of numerous Trane application manuals and Engineers Newsletters, and is a frequent presenteron Trane’s Engineers Newsletter Live series of broadcasts. He also is a member of ASHRAE, has authored severalarticles for the ASHRAE Journal, and is a member of ASHRAE’s “Moisture Management in Buildings” and“Mechanical Dehumidifiers” technical committees. He was a contributing author of the Advanced Energy DesignGuide for K‐12 Schools and the Advanced Energy Design Guide for Small Hospitals and Health Care Facilities, andtechnical reviewer for The ASHRAE Guide for Buildings in Hot and Humid Climates.

Biographies_APPCMC042.ai 1 6/17/2014 11:14:31 AM

Page 3: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Ingersoll Rand

© 2011 Trane, a business of Ingersoll-Rand2

High-Performance VAV Systems Course ID: 0090005954

1.5

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 3

Page 4: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

“Trane” is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members Certificatesreported to CES Records for AIA members. Certificates of Completion for non-AIA members are available on request.

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or

© 2011 Trane, a business of Ingersoll-Rand3

product.

Copyrighted Materials

This presentation is protected by U.S. and international i h l R d i di ib i di l dcopyright laws. Reproduction, distribution, display, and

use of the presentation without written permission of Trane is prohibited.

© 2011 Trane, a business of Ingersoll-Rand. All rights reserved.

© 2011 Trane, a business of Ingersoll-Rand4

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 4

Page 5: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Today’s Topics

ASHRAE 189.1 requirements

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

Energy modeling results

Summary

© 2011 Trane, a business of Ingersoll-Rand5

Summary

Today’s Presenters

© 2011 Trane, a business of Ingersoll-Rand6

Dennis Stanke

Staff ApplicationsEngineer

John Murphy

Applications Engineer

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 5

Page 6: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

ASHRAE Standard 189.1-2009

What does the “high fperformance green

building” standard require in a “high performance VAV system?

For commercial, institutional and hi rise

© 2011 Trane, a business of Ingersoll-Rand7

institutional, and hi-rise residential buildings, the standard covers …

Std 189.1-2009 HPGB Provisions

Site sustainability: e.g., site location, heat island rainwaterheat island, rainwater

Water use efficiency: e.g., turf, fixtures, once-through, condensate recovery

Energy efficiency: Std 90.1 compliance plus…

Indoor environmental quality (IEQ): e.g., Std 62.1 all sections, plus OA sensing and no smoking, Std 55 compliance, acoustics, daylighting

© 2011 Trane, a business of Ingersoll-Rand8

Atmosphere, materials and resources: e.g., recycle, reuse, no CFC’s allowed

Construction and plans for operation

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 6

Page 7: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Std 189.1-2009 and high performance VAV HPGB VAV-Specific Provisions

Optimized VAV controls

Cold air distribution• Energy performance modeling shows value of HP VAV

cold air distribution

Air-to-air energy recovery

© 2011 Trane, a business of Ingersoll-Rand9

Energy Requirements

Std 189.1-2009 Provisions 90.1-2010

Topic 90.1-2007 Plus 189.1-2009

Optimal start/stop controls

6.4.3.3.3 Controls must automatically adjust start time for 10,000 cfm air

No additional requirements (i.e., sameas 90.1-2007)

Same as 189.1-2009

handlers, based on space temperature, occupied setpoint and time prior to occupancy

Fan pressure optimization

6.5.3.2 Prescriptiveoption must reset supply static pressure lower to keep one zone damper nearly wide open

No additional requirements (i.e., sameas 90.1-2007)

Same as 189.1-2009

Supply air temperature No mandatory or No mandatory or 6.5.3.4 Prescriptive

© 2011 Trane, a business of Ingersoll-Rand10

pp y preset

yprescriptive requirements

yprescriptive requirements

poption must reset supply air temperature by approximately 5°F

Demand controlled ventilation

6.4.3.9 Must use DCV in zones >500ft2 with >40 people/1000 ft2

7.4.3.2 Prescriptive option must include DCV in zones >500 ft2 with ≥25 people/1000 ft2

6.4.3.9 Must use DCV in zones >500ft2 with >40 people/1000 ft2

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 7

Page 8: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Energy Requirements

Std 189.1-2009 Provisions 90.1-2010

Topic 90.1-2007 Plus 189.1-2009

Ventilation reset control No mandatory or prescriptive requirements

No mandatory or prescriptive requirements

6.5.3.3 Prescriptive option must reset VAVsystem OA intake based on system ventilation efficiency

Cold-air distribution No mandatory or prescriptive requirements

No mandatory or prescriptive requirements

Same as 189.1-2009

Air-to-air energy recovery

6.5.6.1 Prescriptive option must recover enthalpy with ≥50% effectiveness in systems with ≥5000 cfm and OA

7.4.3.8 Prescriptive option must recover enthalpy with ≥60% effectiveness in systems ranging from 1000 to

6.5.3.4 Prescriptive option must recover enthalpy with ≥50% effectiveness in systems ranging from 1000 to

© 2011 Trane, a business of Ingersoll-Rand11

≥70% of design supply air

g g30,000 cfm and OA ranging from 10% to 80% of design supply air

g g26,000 cfm and OA ranging from 30% to 80% of design supply air

High-Performance VAV Systems

OptimizedSystem Controls

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 8

Page 9: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Today’s Topics

ASHRAE 189.1 requirements

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

Energy modeling results

Summary

© 2011 Trane, a business of Ingersoll-Rand13

Summary

Optimal start/stop

Optimized VAV System Controls

• Time-of-day scheduling

Fan-pressure optimization

Supply-air-temperature reset

Ventilation optimization • Demand-controlled ventilation (DCV)

at the zone level

© 2011 Trane, a business of Ingersoll-Rand14

• Ventilation reset controlat the system level (TRAQ dampers)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 9

Page 10: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Optimal Start

systemon

systemoffoccupied hourson offoccupied hours

occupiedheating

setpoint

unoccupiedheating

optimalstart

© 2011 Trane, a business of Ingersoll-Rand15

6 AM noon 6 PMmid mid

gsetpoint

Optimal Stop

systemon

systemoffoccupied hourson offoccupied hours

optimalstop

drift belowoccupied

occupiedheating

setpoint

unoccupiedheating

© 2011 Trane, a business of Ingersoll-Rand16

6 AM noon 6 PMmid mid

occupiedsetpoint

gsetpoint

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 10

Page 11: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Time-of-Day Scheduling

Avoid overly-conservative scheduling by i l di ti d id b ttincluding a timed override button on zone sensors

Use separate schedules for areaswith differing usage patterns

© 2011 Trane, a business of Ingersoll-Rand17

© 2011 Trane, a business of Ingersoll-Rand18

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 11

Page 12: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

© 2011 Trane, a business of Ingersoll-Rand19

measured energy savings for a small school district

Proper Scheduling, Night Setback

15,000,000 250,000Energy savings

Utility cost savings

En

erg

y sa

vin

gs

(kB

tu) 14,000,000

13,000,000

12,000,000

11 000 000

200,000

150,000

100,000

50 000

Utility co

st saving

s ($)

Utility cost savings

© 2011 Trane, a business of Ingersoll-Rand20

year one year two year three year four

11,000,000

10,000,000

50,000

0

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 12

Page 13: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

measured energy savings for a government office building

Proper Scheduling, Night Setback

2,500,000 25,000

2,000,000

1,500,000

1,000,000

500 000

20,000

15,000

10,000

5 000

Energy savings

Utility cost savings

En

erg

y sa

vin

gs

(kB

tu) U

tility cost savin

gs ($)

© 2011 Trane, a business of Ingersoll-Rand21

year one year two

500,000

0

5,000

0

Optimized VAV System Controls

Optimal start/stop• Time-of-day scheduling

Fan-pressure optimization

Supply-air-temperature reset

Ventilation optimization • Demand-controlled ventilation at zone level

• Ventilation reset at system level (and TRAQ dampers)

© 2011 Trane, a business of Ingersoll-Rand22

Ventilation reset at system level (and TRAQ dampers)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 13

Page 14: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Traditional VAV Fan Control

VAV boxes

supplyfan

PP

static

© 2011 Trane, a business of Ingersoll-Rand23

pressuresensor

staticpressure

Fan-Pressure Optimization

pressuresensor

supplyfan

PP

© 2011 Trane, a business of Ingersoll-Rand24

communicating BAS

VAV boxes

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 14

Page 15: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

surge

fan-pressure optimization

Part-Load Energy Savings

stat

ic p

ress

ure duct static pressure

control

1 i

© 2011 Trane, a business of Ingersoll-Rand25

airflow

fan-pressure optimization

1 in.wc.

siti

on

Room 204

zon

e V

AV

dam

per

po

s

© 2011 Trane, a business of Ingersoll-Rand26

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 15

Page 16: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Room 200

Room 201

Room 202

Room 203

Room 204

© 2011 Trane, a business of Ingersoll-Rand27

Room 205

staticpressure

Fan-Pressure Optimization

pressuresensor

supplyfan

PP

© 2011 Trane, a business of Ingersoll-Rand28

communicating BASVAV boxes

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 16

Page 17: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

fan-pressure optimization

Benefits

Part-load energy savings

Lower sound levels

Better zone control

Less duct leakage

Reduced risk of fan surge

Factory-installation and -commissioningof duct pressure sensor

© 2011 Trane, a business of Ingersoll-Rand29

of duct pressure sensor

Operator feedback to "tune the system"

Optimized VAV System Controls

Optimal start/stop• Time-of-day scheduling

Fan-pressure optimization

Supply-air-temperature reset

Ventilation optimization • Demand-controlled ventilation (DCV)

at the zone level

© 2011 Trane, a business of Ingersoll-Rand30

• Ventilation reset control at the system level (TRAQ dampers)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 17

Page 18: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Supply-Air-Temperature (SAT) Reset

Benefits

• Decreases compressor energy

• More hours when economizer provides all necessary cooling (compressors/chiller shut off)

• Decreases reheat energy

Drawbacks

• Increases fan energy

© 2011 Trane, a business of Ingersoll-Rand31

• Increases fan energy

• May raise humidity level in zones

SAT reset

General Principles

First reduce supply airflow• Significant energy savings

from unloading the fan

Raise SAT setpoint when it canenhance airside economizingand/or reduce reheat energy

© 2011 Trane, a business of Ingersoll-Rand32

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 18

Page 19: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

SAT reset based on VAV damper positions

Example #1

SAT

i ti BAS VAV boxes

pressuresensor

supplyfan PPTT

SATsensor

© 2011 Trane, a business of Ingersoll-Rand33

communicating BAS VAV boxes

First, reduce duct SP to minimum limit.

Then, raise SAT setpoint.

SAT reset based on VAV damper positions

Example #1

Benefits of this approach• Maximizes fan energy savings by waiting until you have

reset the duct SP as low as possible before you raise the SAT setpoint

• Ensures that no zone is over-heated (starved for air)

Drawbacks of this approach• SAT setpoint may not get reset upward very often,

© 2011 Trane, a business of Ingersoll-Rand34

so might not have much impact on reheat energy use Cooling load in every zone needs to be low enough that all

VAV dampers are partially closed, even when duct SP setpoint is at minimum

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 19

Page 20: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

SAT reset based on OA temperature

Example #2

F 61te

mp

erat

ure

set

po

int,

ºF

60

59

58

57

56

© 2011 Trane, a business of Ingersoll-Rand35

50 55 6045 757065

outdoor dry-bulb temperature,ºF

SA

55

SAT reset based on OA temperature

Example #2 When OA temperature > 65°F, no SAT reset

• When it is this warm outside, the economizer has not likely been activated yet and the cooling load in most zones is likely high enough that reheat is not yet required to prevent overcooling

• Takes advantage of significant energy savings from unloading supply fan

• The colder (and drier) supply air allows the system to provide sufficiently dry air to the zones, keeping indoor humidity levels lower

When OA temperature < 65°F, reset SAT upward (max SAT limit of 60°F)

• Supply fan is likely significantly unloaded by this point

• Increases benefit of airside economizer, allows compressors to shut off sooner

• Reduces any reheat required to prevent overcooling the zones

• Outdoor air is less humid so the risk of elevating indoor humidity by providing ( d tt ) l i i l d

© 2011 Trane, a business of Ingersoll-Rand36

warmer (and wetter) supply air is lessened

Limiting SAT reset to 60°F allows the system to satisfy cooling loads in interior zones without needing to substantially oversize VAV terminals and ductwork

Disable SAT reset when outdoor dew point is too high (e.g. above 60ºF or 65ºF) or when indoor humidity is too high (e.g. above 60% or 65% RH)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 20

Page 21: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

SAT reset based on OA temperature

Example #2

Benefits of this approach• Achieves fan energy savings by waiting until it is cool

outside before raising the SAT setpoint

• May achieve more reduction reheat energy by not waiting for duct SP to be reset to minimum

Drawbacks of this approach• “Open loop” control does not ensure that a zone is not

© 2011 Trane, a business of Ingersoll-Rand37

over-heated (starved for air)

SAT reset based on OA temperature and VAV damper positions

Example #3

F 61

tem

per

atu

re s

etp

oin

t, º

F

60

59

58

57

56

reset based onworst-case

zone

© 2011 Trane, a business of Ingersoll-Rand38

50 55 6045 757065

outdoor dry-bulb temperature, ºF

SA

55

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 21

Page 22: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

SAT reset based on OA temperature and VAV damper positions

Example #3

Benefits of this approach• Achieves fan energy savings by waiting until it is

cool outside before raising the SAT setpoint

• May achieve more reduction reheat energy by not waiting for duct SP to be reset to minimum

• Ensures that no zone is over-heated (starved for air)

Drawbacks of this approach

© 2011 Trane, a business of Ingersoll-Rand39

• Both sequences use the same input signal(position of the furthest-open VAV damper), so they require careful coordination

SAT reset

Humidity Override

BAS

RH

lounge restroom

storage office

rs

vestibule corridor

RH RH

© 2011 Trane, a business of Ingersoll-Rand40

office conference room computer roomreception area elev

ato

r

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 22

Page 23: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

SAT reset

Application Considerations

Will compressor and reheat energy savings outweigh additional fan energy?outweigh additional fan energy?

Consider impact on zone humidity

Design zones with nearly-constant coolingloads for warmer (reset) SAT • May require larger VAV terminals and ductwork

• Allows SAT reset while still providingd d li t th

© 2011 Trane, a business of Ingersoll-Rand41

needed cooling to these zones

Design an efficient air distribution system• Employ fan-pressure optimization

Optimized VAV System Controls

Optimal start/stop• Time-of-day scheduling

Fan-pressure optimization

Supply-air-temperature reset

Ventilation optimization (dynamic reset)• Demand-controlled ventilation at zone level

• Ventilation reset at system level (and TRAQ™

© 2011 Trane, a business of Ingersoll-Rand42

Ventilation reset at system level (and TRAQ dampers)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 23

Page 24: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

dynamic reset approaches – zone level

Demand Controlled Ventilation (DCV)

Estimate current population (Pz) based on:1. Time-of-day schedule (e.g., when a class is in

session)

2. Occupancy sensors (e.g., motion detectors)

3. Actual sense population (e.g., using turnstiles, ticket sales, and so on, or changes in CO2 levels)

Find required breathing zone OA flow (Vbz) using ti t d l ti

© 2011 Trane, a business of Ingersoll-Rand43

estimated population

Alternatively: 4. CO2-based: Estimate required breathing zone OA flow

(Vbz) directly based on CO2 levels

Estimate the current OA flow required using CO2

l l

dynamic reset approaches – zone level

Demand Controlled Ventilation (DCV)

levels• Steady state concentration equation

(Cr –Co) = k*m/(Vbz/Pz)

• Typical straight-line proportional controller

Vbz = slope*CO2 + offset

© 2011 Trane, a business of Ingersoll-Rand44

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 24

Page 25: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

dynamic reset approaches – system level

Outdoor Air Intake Flow w/DCV

For single zone systems:Vot = Vbz/Ez

For 100% zone systems:Vot = all zones(Vbz/Ez)

For multiple-zone systems:Vou = (Rp*Pz) + (Ra*Az)

Zdzcritical zone = Vbz/Vdz

© 2011 Trane, a business of Ingersoll-Rand45

Zdzcritical zone Vbz/Vdz

Ev = 1 + Vou/Vps – Zdzcritical zone

Vot = Vou/Ev

dynamic reset approaches – zone/system level

Ventilation Reset Control air-handling unit withflow-measuring OA damper

Reset outdoor airflow

SA RA

© 2011 Trane, a business of Ingersoll-Rand46

Required ventilationActual primary airflow (flow ring)

DDC VAV controllerscommunicating BASNew OA setpoint

…per ASHRAE 62

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 25

Page 26: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

dynamic reset approaches – zone/system level

CO2 Sensor in Every Zone?communicating BAS

lounge restroom

storage office

rs

vestibule corridor

CO2 CO2AHU

© 2011 Trane, a business of Ingersoll-Rand47

office conference room

computer roomreception area e

levato

r

CO2CO2

CO2 CO2

CO2 sensor in every zone

Drawbacks

Requires a CO2 sensor in every zone • Increases installed cost and maintenance

• Unnecessary use of sensors (CO2 level doesn’t change much in many of the zones, non-critical zones will always be over-ventilated)

• Increases risk of over-ventilating or under-ventilating

Requires BAS to poll all sensors to determine OA d iti

© 2011 Trane, a business of Ingersoll-Rand48

damper position

Requires some method to ensure minimum outdoor airflow

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 26

Page 27: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

dynamic reset approaches – zone/system level

Zone DCV with Ventilation Reset Control communicating BAS

lounge restroom

storage office

s

vestibule corridor

CO2 OCCAHU

© 2011 Trane, a business of Ingersoll-Rand49

office conference room

computer room

reception area

ele

vato

rs

CO2OCC

TOD TOD

air-handling unit withflow-measuring OA damper

Reset outdoor airflow

dynamic reset approaches – zone/system level

Zone DCV with Ventilation Reset Control

SA RA

© 2011 Trane, a business of Ingersoll-Rand50

CO2 OCC OCC

Required ventilation (TOD, OCC, CO2)Actual primary airflow (flow ring)

DDC VAV controllerscommunicating BASNew OA setpoint

…per ASHRAE 62

CO2TOD TOD

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 27

Page 28: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

ventilation optimization

Benefits

Saves energy during partial occupancy

Lower installed cost, less maintenance, and more reliable than installing a CO2 sensor in every zone• Use zone-level DCV approaches where they best fit

(CO2 sensor, occupancy sensor, time-of-day schedule)

• Combine with ventilation reset at the system level

© 2011 Trane, a business of Ingersoll-Rand51

“Occupied Standby” Mode

Use an occupancy sensor to:• Shut off lights

• Raise/lower zone temperaturesetpoint by 1ºF or 2ºF

• Reduce outdoor airflow requirement

• Lower minimum airflow settingto reduce or avoid reheat

© 2011 Trane, a business of Ingersoll-Rand52

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 28

Page 29: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

occupied standby mode

Example

1000-ft2 conference room(d i 50)(design occupancy = 50)

Lights on off

Zone cooling 75ºF 77ºFsetpoint

Outdoor airflow 310 cfm 60 cfm

occupiedmode

occupied standbymode

© 2011 Trane, a business of Ingersoll-Rand53

required (Rp Pz + Ra Az) (Ra Az)

Minimum primary 450 cfm 225 cfmairflow setting

outdoor airflow sensing

Traq™ Damper/Sensor Assembly

A damper assembly that …Controls airflo b• Controls airflow by modulating a set of round dampers

• Measures airflow at all conditions (as required indirectly by Std 62.1 and Std 90.1, and as required explicitly by Std 189 1

© 2011 Trane, a business of Ingersoll-Rand54

explicitly by Std 189.1 and for a LEED credit)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 29

Page 30: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

outdoor airflow sensing

Damper Assembly

Uses proven flow-sensing technology

• Flow ring senses differential (total inlet to “wake” outlet)

pressure), which can be very low

• Air doesn’t enter sensing ports, so filtration isn’t needed

• Transducer auto-calibrates once each minute, to correct for drift due to temperature changes

© 2011 Trane, a business of Ingersoll-Rand55

for drift due to temperature changes

• Bell mouth inlet directs air across flow ring to reduce turbulence and pressure drop

outdoor airflow sensing

Damper Assembly

AccuracyTested in accordance ith AMCA 610 “Airflo• Tested in accordance with AMCA 610 “Airflow Measurement Station Performance”

• ± 5% of actual airflow• Precision maintained from 100% down to 15% of

nominal (design) flow (or down to 5% in some configurations)

Damper leakage

© 2011 Trane, a business of Ingersoll-Rand56

Damper leakage

• “Low leak” class• Meets Std 90.1 requirements

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 30

Page 31: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

outdoor airflow sensing

Damper AssemblyFor a #25 air-handling unit, 12,500 cfm

Device ΔP in. wc.

Inlet Velocity

Traq™ 0.30 1,900 fpm

Blade assembly:

Filter 0.39

Sensor 0.00

Damper 0 25

© 2011 Trane, a business of Ingersoll-Rand57

Damper 0.25

Total Assembly 0.64 1,200 fpm

Example TRACE® 700 Analysis

Optimized VAV system controls

Optimal start

Fan-pressure optimization

Supply-air temperature reset

Ventilation optimization • DCV at zone level

• Ventilation reset at system level

© 2011 Trane, a business of Ingersoll-Rand58

• Ventilation reset at system level

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 31

Page 32: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

VAV system

Energy Savings Via Optimized Controls100

ase

9% 11%17% 18%

20

40

60

80

C e

ner

gy

use

, % o

f b

a

© 2011 Trane, a business of Ingersoll-Rand59

0

20

HV

AC

Houston Los Angeles Philadelphia St. Louis

typical VAV system with optimized controls

typical VAV system

High-Performance VAV Systems

Cold AirDistribution

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 32

Page 33: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Today’s Topics

ASHRAE 189.1 requirements

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

Energy modeling results

Summary

© 2011 Trane, a business of Ingersoll-Rand61

Summary

Lower Supply-Air Temperature

Benefits Reduces supply airflow

• Less supply fan energyand less fan heat gain

• Smaller fans, air handlers,VAV terminals, and ductwork

Lowers indoor humidity levels

Drawbacks

© 2011 Trane, a business of Ingersoll-Rand62

Drawbacks Fewer economizer hours

Increased reheat energy

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 33

Page 34: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

lower supply-air temperature

Maximize Energy Savings

Use supply-air temperature reset during mild weather• Maximizes benefit of airside economizer

• Reduces reheat energy use

© 2011 Trane, a business of Ingersoll-Rand63

Impact of SAT on Reheat Energyprimary air

55ºF

design primary airflow = 1000 cfmminimum primary airflow = 300 cfm

(30%) reheat activated when space coolingload drops below 30% of design

primary air48ºF

© 2011 Trane, a business of Ingersoll-Rand64

design primary airflow = 740 cfmminimum primary airflow = 300 cfm

(40%) reheat activated when space coolingload drops below 40% of design

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 34

Page 35: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

design(1000 cfm)

m

heating coil activated(48ºF SAT t )

heating coil activated(55ºF SAT system)

s

85

minimum(300 cfm)

pri

mar

y ai

rflo

w, c

fm

design(740 cfm)

(48ºF SAT system)

sup

ply-air tem

peratu

re, ºF

55

65

75

extra reheat energybut not if SAT reset is used

© 2011 Trane, a business of Ingersoll-Rand65

space loaddesign

cooling loaddesign heating load

45

but not if SAT reset is used

lower supply-air temperature

Maximize Energy Savings

Use supply-air temperature reset during mild weather

Raise space setpoint by 1ºF or 2ºF• Lower indoor humidity often allows zone dry-bulb temperature

to be slightly warmer

• Further reduces airflow and fan energy use

© 2011 Trane, a business of Ingersoll-Rand66

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 35

Page 36: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

lower supply-air temperature

Maximize Energy Savings

Use supply-air temperature reset during mild weather

Raise space setpoint by 1ºF or 2ºF

Keep same size ductwork• Further reduces fan energy use

• Allows SAT reset in systems that serve zones with near-constant cooling loads

• Capable of delivering more airflow if loads increase in the future

© 2011 Trane, a business of Ingersoll-Rand67

loads increase in the future

chilled-water VAV system

Example Office Building (Tampa)

100%

110%

% o

f b

ase

70%

80%

90%

VA

C e

ner

gy

con

sum

pti

on

, %

© 2011 Trane, a business of Ingersoll-Rand68

60%

HV

55ºFsupply air

48ºFsupply air

smaller ducts

raisespace

setpointby 1ºF

SAT reset48ºF

to55ºF

48ºFsupply air

same size ducts

raisespace

setpointby 1ºF

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 36

Page 37: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Velocity Round Ductwork

round duct6700 cfm at 45ºF

© 2011 Trane, a business of Ingersoll-Rand69

rectangular duct10000 cfm at 55ºF2000 fpm

4000 fpm

lower supply-air temperature

Maximize Energy Savings

Use supply-air temperature reset during mild weather

Raise space setpoint by 1ºF or 2ºF

Keep same size ductwork

Use parallel fan-powered VAV terminals• Reduces reheat energy use by recovering heat

from warm air in ceiling plenum

© 2011 Trane, a business of Ingersoll-Rand70

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 37

Page 38: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

lower supply-air temperature

Challenges

Minimize comfort problems d t “d i ”due to “dumping”

Avoid condensation on air distribution system components

© 2011 Trane, a business of Ingersoll-Rand71

lower supply-air temperature

Minimizing Comfort Problems (Dumping)

Use linear slot diffusers

linear slotdiffuser

“dumping”

conventional concentric diffuser

© 2011 Trane, a business of Ingersoll-Rand72

Implement supply-air-temperature reset

diffuser concentric diffuser

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 38

Page 39: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

lower supply-air temperature

Minimizing Comfort Problems (Dumping)

…or use fan-powered VAV terminals as “air blenders”

primary air (45ºF)

plenum air (80ºF) primary air

(45ºF)

© 2011 Trane, a business of Ingersoll-Rand73

parallel fan-poweredVAV terminal

supply air (55ºF)

series fan-poweredVAV terminal

supply air (55ºF)

plenum air (80ºF)

lower supply-air temperature

Avoiding Condensation

Properly insulate and vapor-seal d t k VAV t i l d l i diffductwork, VAV terminals, and supply-air diffusers

© 2011 Trane, a business of Ingersoll-Rand74

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 39

Page 40: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

surface temperatures on duct insulation (wrapped metal duct)• 44ºF supply air (Trane district office in Dallas, TX)• fully-ducted return air path (85ºF dry bulb above ceiling)

trunk duct (2 in. insulation)outer surface temp = 82ºF

© 2011 Trane, a business of Ingersoll-Rand75

p

branch duct (1 in. insulation)outer surface temp = 77ºF

lower supply-air temperature

Avoiding Condensation

Properly insulate and vapor-seal d t k VAV t i l d l i diffductwork, VAV terminals, and supply-air diffusers

Use an open ceiling plenum return, if possible

Maintain positive building pressure to reduce infiltration of humid outdoor air

Use linear slot diffusers to increase air motion

Monitor indoor humidity during unoccupied periods

© 2011 Trane, a business of Ingersoll-Rand76

Monitor indoor humidity during unoccupied periods and prevent it from rising too high

During startup, slowly ramp down the supply-air temperature to pull down indoor dew point

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 40

Page 41: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

examples

Humidity Pull-Down Sequence

SAT ramp-down schedule

SAT ramp down based on indoor dew point

supply airflow supply-airlimit temperature

2 hours before occupancy 40% of design 55ºF

1 hour before occupancy 65% of design 51ºF

Scheduled occupancy no limit 48ºFSource: ASHRAE Cold Air Distribution System Design Guide (pp 138-140)

© 2011 Trane, a business of Ingersoll-Rand77

SAT ramp-down based on indoor dew pointex: SAT = current indoor dew point – 3ºF

High-Performance VAV Systems

Air-to-AirEnergy Recovery

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 41

Page 42: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Today’s Topics

ASHRAE 189.1 requirements

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

Energy modeling results

Summary

© 2011 Trane, a business of Ingersoll-Rand79

Summary

Air-to-Air Energy Recovery

total-energywheel

EAEA

© 2011 Trane, a business of Ingersoll-Rand80

OAOA

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 42

Page 43: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Air-to-Air Energy Recovery

Benefits Drawbacks

Reduces cooling, dehumidification, heating, and humidification energy

Allows equipment downsizing

Increases fan energy

Requires exhaust air be routed back to the device

© 2011 Trane, a business of Ingersoll-Rand81

air-to-air energy recovery

Considerations for VAV Systems

Size energy-recovery device for minimum outdoor i fl i d t i i i flairflow required, not economizing airflow

Strive for balanced airflows

Ensure that the device is controlled properly• Turn off during mild weather to avoid wasting energy

• Provide a means of capacity control during heating

• Include bypass dampers for airside economizing

© 2011 Trane, a business of Ingersoll-Rand82

yp p g

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 43

Page 44: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Miami, FL(Mon - Fri, 6 AM - 6 PM)

wheel on (2560 hrs)

© 2011 Trane, a business of Ingersoll-Rand83

wheel off (560 hrs)

St. Louis, MO(Mon - Fri, 6 AM - 6 PM)

wheel on (1070 hrs)

wheel on,heating

© 2011 Trane, a business of Ingersoll-Rand84

wheel off (1473 hrs)

(577 hrs)

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 44

Page 45: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

air-to-air energy recovery

Capacity Control During Heating

RARAEAEA7000 cfm

30ºF 63ºF

70ºF

8000 cfmwheel on at

full capacitycooling coil on

© 2011 Trane, a business of Ingersoll-Rand85

SASAOAOA10000 cfm

18000 cfm55ºF

30ºF

66ºF

63ºF (66ºF to 55ºF)

air-to-air energy recovery

Capacity Control During Heating

RARAEAEAbypass damper

7000 cfm

30ºF 43ºF

8000 cfmwheel on at

partial capacity

both coils off

70ºF

© 2011 Trane, a business of Ingersoll-Rand86

OAOA

18000 cfm

30ºF

55ºF

43ºF both coils off

SASA55ºF10000 cfm

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 45

Page 46: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

air-to-air energy recovery

Considerations for VAV Systems

Size energy-recovery device for minimum outdoor i fl i d t i i i flairflow required, not economizing airflow

Strive for balanced airflows

Ensure that the device is controlled properly• Turn off during mild weather to avoid wasting energy

• Provide a means of capacity control during heating

• Include bypass dampers for airside economizing

© 2011 Trane, a business of Ingersoll-Rand87

yp p g

Provide a method for frost prevention in cold climates

High-Performance VAV Systems

Other Energy-Saving Strategies

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 46

Page 47: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Today’s Topics

ASHRAE 189.1 requirements

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

Energy modeling results

Summary

© 2011 Trane, a business of Ingersoll-Rand89

Summary

“High-Performance” Rooftop VAV System

High-efficiency rooftop

Evaporative condensing

Central relief/exhaust fan,rather than a return fan

Solar hot-water systemfor reheat

rooftop unit withevaporative condenser

© 2011 Trane, a business of Ingersoll-Rand90

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 47

Page 48: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

“High-Performance” Chilled-Water System

Low flow, low temperature

Ice storage

Variable primary flow

High-efficiency chillers

Optimized plant controls

Waterside heat recovery

Central geothermal

© 2011 Trane, a business of Ingersoll-Rand91

Central geothermal

High-Performance VAV Systems

ExampleEnergy Analyses

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 48

Page 49: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

High-Performance VAV Systems

Today’s Topics

ASHRAE 189.1 requirements

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

Energy modeling results

Summary

© 2011 Trane, a business of Ingersoll-Rand93

Summary

large office building

Example Energy Analysis

“Baseline” chilled-water VAV system• Per ASHRAE 90.1-2007, Appendix G

• 55ºF supply air

“High-performance” chilled-water VAV system• 48ºF supply air (no downsizing of ductwork)

• Optimized VAV system controls (ventilation optimization, SAT reset)

© 2011 Trane, a business of Ingersoll-Rand94

• Parallel fan-powered VAV terminals

• Low-flow, water-cooled chiller plant

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 49

Page 50: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

large office building

Example Energy Analysis (continued)

Active chilled beam (ACB) system Four-pipe active chilled beams

Separate primary AHUs for perimeter andinterior areas (with airside economizers)

Water-cooled chiller plant supplying the chilled beams

Separate low-flow, water-cooled chiller plant supplying the primary AHUs

© 2011 Trane, a business of Ingersoll-Rand95

8,000,000

10,000,000

12,000,000

rgy

Us

e, k

Btu

/yr

Pumps

Fans

Heating

Cooling

Houston Los Angeles Philadelphia St. Louis

2,000,000

4,000,000

6,000,000

An

nu

al B

uild

ing

En

er Plug Loads

Lighting

© 2011 Trane, a business of Ingersoll-Rand96

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 50

Page 51: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

small office building

Example Energy Analysis

“Baseline” rooftop VAV system• Per ASHRAE 90.1-2007, Appendix G

• 55ºF supply air

“High-performance” rooftop VAV system• High-efficiency, air-cooled packaged rooftop unit

• 52ºF supply air (no downsizing of ductwork)

• Optimized VAV system controls

© 2011 Trane, a business of Ingersoll-Rand97

Optimized VAV system controls (ventilation optimization, SAT reset)

• Parallel fan-powered VAV terminals

small office building

Example Energy Analysis (continued)

Variable refrigerant flow (VRF) system Heat recovery, air-cooled outdoor units

Packaged DX dedicated outdoor-air unitwith hot gas reheat

© 2011 Trane, a business of Ingersoll-Rand98

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 51

Page 52: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

2 500 000

3,000,000

4,000,000

rgy

Us

e, k

Btu

/yr

Fans

Heating

Cooling

Houston Los Angeles Philadelphia St. Louis

3,500,000

500,000

1,000,000

2,000,000

2,500,000

An

nu

al B

uild

ing

En

er Plug Loads

Lighting

1,500,000

© 2011 Trane, a business of Ingersoll-Rand99

Advanced Energy Design Guides

Funded by U.S. Dept of Energy

www.ashrae.org/freeaedg

Climate-specific recommendationsfor achieving 30% or 50% energy savings(envelope, lighting, HVAC, water heating)

Based on building energy simulations

© 2011 Trane, a business of Ingersoll-Rand100

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 52

Page 53: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Advanced Energy Design GuidesAEDG for Small or Medium Office Buildings

“High-performance” rooftop VAV systems are included as an option to achieve 50% energy savings

AEDG for K-12 Schools

Both rooftop VAV and chilled-water VAV systems are included as options to achieve 30% energy savings

AEDG for Small Hospitals and Healthcare Facilities

© 2011 Trane, a business of Ingersoll-Rand101

p

Both rooftop VAV and chilled-water VAV systems are included as options to achieve 30% energy savings

summary

High-Performance VAV Systems

Optimized VAV system controls

Cold-air distribution

Air-to-air energy recovery

Other energy-saving strategies

© 2011 Trane, a business of Ingersoll-Rand102

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 53

Page 54: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

References for This Broadcast

Where to Learn More

© 2011 Trane, a business of Ingersoll-Rand103

www.trane.com/EN

Watch Past Broadcasts

ENL Archives

Insightful topics on HVAC system design:• Chilled-water plants• Air distribution• Refrigerant-to-air systems• Control strategies• Industry standards and LEED• Energy and the environment• Acoustics• Ventilation• Dehumidification

© 2011 Trane, a business of Ingersoll-Rand104

www.trane.com/ENL

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 54

Page 55: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

LEED Continuing Education Courseson-demand, no charge, 1.5 CE credits

ASHRAE Standards 62.1 and 90.1 d VAV S tand VAV Systems

ASHRAE standard 62.1: Ventilation Rate Procedure

ASHRAE 90.1-2010

Energy Saving Strategies for Rooftop VAV Systems

Air-Handing Systems, Energy and IAQ

Central Geothermal System Design and Control

© 2011 Trane, a business of Ingersoll-Rand105

Central Geothermal System Design and Control

Ice Storage Design and Control

www.trane.com/ContinuingEducation

2011 ENL Programs

MarchU di E i ti Chill d W t S tUpgrading Existing Chilled-Water Systems

JuneHigh-Performance VAV Systems

October Dedicated Outdoor-Air Units

© 2011 Trane, a business of Ingersoll-Rand106

Trane Engineers Newsletter Live Series High-Performance VAV Systems

©2011 Trane a business of Ingersoll Rand 55

Page 56: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Trane Engineers Newsletter Live program

Bibliography

Page 1 of 2

Industry Standards American Society of Heating, Refrigerating, and Air-Conditioning

Engineers (ASHRAE). ANSI/ASHRAE Standard 62.1-2010: Ventilation for Acceptable Indoor Air Quality. Available at www.ashrae.org/bookstore

American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). ANSI/ASHRAE IESNA Standard 90.1-2010: Energy Standard for Buildings Except Low-Rise Residential Buildings. Available at www.ashrae.org/bookstore

American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). ANSI/ASHRAE/USGBC/IES Standard 189.1-2009: Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings. Available at www.ashrae.org/bookstore

Industry Articles, Papers, and Publications Advanced Energy Design Guides <www.ashrae.org/aedg>

American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (ASHRAE). 1996. Cold Air Distribution System Design Guide. Atlanta, GA: ASHRAE.

California Energy Commission (CEC). 2003. Advanced Variable Air Volume System Design Guide. Sacramento, CA: CEC.

Murphy, J. and N. Maldeis, “Using Time-of-Day Scheduling to Save Energy,” ASHRAE Journal 51(5), May 2009, pp. 42-48.

Stanke, D., “System Operation: Dynamic Reset Options,” ASHRAE Journal 48(12), December 2006, pp 18–32.

Stanke, D., “Single-Path Multiple-Zone System Design,” ASHRAE Journal 47(1) January 2005, pp 28-35.

Wei, G., Liu, M., and D. Claridge, “Optimize the Supply Air Temperature Reset Schedule for a Single-Duct VAV System,” Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, TX, May 2000.

Trane Application Manuals available to purchase from <www.trane.com/bookstore>

Murphy, J. and J. Harshaw. Rooftop VAV Systems, application manual SYS-APM007-EN, November 2009.

Murphy, J. and B. Bakkum. Chilled-Water VAV Systems, application manual SYS-APM008-EN, September 2009.

Murphy, J. and B. Bradley. Air-to-Air Energy Recovery, application manual SYS-APM003-EN, September 2008.

8 June 2011

High-Performance VAV Systems

Page 57: Agenda and Objectives - trane.com...High-Performance VAV Systems Variable-air-volume (VAV) systems have been used to provide comfort in a wide range of building types and climates

Trane Engineers Newsletter Live program

Bibliography

Page 2 of 2

Trane Engineers Newsletters available to download from <www.trane.com/engineersnewsletter>

Eppelheimer, D. “Cold Air Makes Good $ense.” Engineers Newsletter 29-2 (2000).

Murphy, J. “CO2-Based Demand-Controlled Ventilation with ASHRAE Standard 62.1.” Engineers Newsletter 34-5 (2005).

Murphy, J. “Energy-Saving Control Strategies for Rooftop VAV Systems.” Engineers Newsletter 35-4 (2006).

Stanke, D. “Potential ASHRAE Standard Conflicts: Indoor Air Quality and Energy Standards.” Engineers Newsletter 37-4 (2008).

Stanke, D. “VAV System Optimization: Critical Zone Reset.” Engineers Newsletter 20-2 (1991).

Trane Engineers Newsletter Live Broadcasts available to view online at <www.trane.com/ENL>

Stanke, D., Schwedler, M., Taylor, S., and J. Harshaw, “ASHRAE Standards 62.1 and 90.1, and VAV Systems,” Engineers Newsletter Live broadcast (November 2008).

Murphy, J., Stanke, D., Lee, T., and M. Schwedler, “CO2-Based Demand-Controlled Ventilation,” Engineers Newsletter Live broadcast (November 2005).

June 2011

High-Performance VAV Systems