air conditioning the grundfos way
DESCRIPTION
Air conditioning the Grundfos Way. Obtainable energy saving. 1. Constant pressure 2. Constant diff. pressure 3. Proportional diff. pressure (calculated) 4. Proportional diff. pressure (measured) 5. Temperature control. 100 80 60 40 20 0. 1. Effect in %. 2. 3. 4. H. 5. - PowerPoint PPT PresentationTRANSCRIPT
Grundfos FLOW THINKING
Air conditioningthe
Grundfos Way
Grundfos FLOW THINKING
Q100%25%
H
0 20 40 60 80 100
100
80
60
40
20
0
Flow in %Eff
ect i
n % 1.
2.
3.4.5.
Obtainable energy saving
1. Constant pressure2. Constant diff. pressure3. Proportional diff. pressure (calculated)4. Proportional diff. pressure (measured)5. Temperature control
Grundfos FLOW THINKING
Optimized operation cost often means LOWER ENERGY COSTAn effective way of checking the profitability of the pump system is to use Life Cycle Cost analysis. This will show not only the ”energy cost” but all costs related to the pump system.
Optimized operation cost
The result of the analysis can also show the pay-back time of a speed con- trolled solution compared to a traditional constant speed pump.
Result of Life Cycle Cost analysis
Grundfos FLOW THINKING
Controls For Variable Speed Application
• VARIOUS OPTIONS e.g.
• Pumps with built-in Frequency Converter & PLC…• Pumps with External Frequency Converter & External
PLC…
Grundfos FLOW THINKING
Chillers
Primary Pumps
Secondary Pumps
Load
Balancing Valve 2 – Way Valve
Panel with PLC & VFD`s
Air -Separator
Com
mon
Primary - Secondary Circuit With Variable Speed Secondary Pumps
Grundfos FLOW THINKING
Why Do We Need Variable Speed Secondary and Tertiary Pumps ???
•For Energy Saving….
•For better & smooth operation….
Grundfos FLOW THINKING
How Do We Achieve This Reduction In Power Consumption ??
By Using Variable Frequency Drive and Logic controller with the Secondary Pumps….
Grundfos FLOW THINKING
Basic Law which helps in achieving this – Affinity law
1. Flow2 = Flow1(Speed2/ Speed1)
2. Head2 = Head1(Speed2/ Speed1)2
3. BKW2 = BKW1(Speed2/ Speed1)3
If Diameter of Impeller is to be trimmed then instead of speed the same can be used in above formulas.
Grundfos FLOW THINKING
PFU
PMU
4 – 20 mA
Set Value
From Field Sensor (DPT)
PFU – Pump Functional Unit
PMU – Pump Management Unit
Basic Concept
Output
To
VFD/Pump
Grundfos FLOW THINKING
Opening/Closing of 2- Way Valve-Signal from the sensor, installed at load
regulates the valve opening & closing.
-This way differential across 2-way valve also
changes & accordingly output signal is given to
PLC.
Temperature Sensor
Load
Output to PFU from DPT
Grundfos FLOW THINKING
Chillers
Balancing Valve
Load
Primary Pumps
Com
mon Secondary
Pumps
Panel with PLC & VFD`s
DPT
An Example
Grundfos FLOW THINKING
APPROVAL FROM INTERNATIONAL AGENCIES
Approval from – CE, U/L Conforms to - Electromagnetic compatibility (89/336/EEC) to standard EN 50 081 – 1 and EN 50 082 – 2 and Electrical equipment design 73/23/EEC standard to EN 60 204-1.
Grundfos FLOW THINKING
Tertiary Pumping
In Air-conditioning Systems
Grundfos FLOW THINKING
Air conditioning systems
Chiller
Colling tower Cooling ceiling
Cooling surface
Secondarypumps
Heat recovery Fan coils M
Buffer tank
M
M
Primarypump
Pressureholding
Improved balancing by Tertiary pumps
Grundfos FLOW THINKING
psecondary
pumpp:
control valve
Airunit
Airunit
Airunit
Fancoils
Fancoils
Buffer tank
M M M M
Distance/pressure profile
psecondary
pump
p: pipes,control valvesfan coils etc.
Airunit
Airunit
Airunit
Fancoils
Fancoils
Distance/pressure profile
System with only secondary pumps
System with tertiary pumps
Buffer tank
Q
H
Qmax.
Max.p
Q
H
Qmax.
Max.p
p: connection point
p: connection point
M
Tertiary pumps
Grundfos FLOW THINKING
psecondary
pumpp:
control valve
Airunit
Airunit
Airunit
Fancoils
Fancoils
Buffer tank
M M M M
Distance/pressure profile
Hybrid System
Q
H
Qmax.
Max.p p: connection point
M
Tertiary pumps
Grundfos FLOW THINKING
Tertiary Systems….Few points
Tertiary pumps can be Variable speed……. Tertiary pumps can be fixed speed also…. Mixing loops are not mandatory in tertiary
loops… But mixing loops add flexibility in the overall air-
conditioning system… Tertiary pumps PLC should be controlled by DPT
signal (if variable speed panel is used)…
Grundfos FLOW THINKING
Tertiary Systems….Few points
For Secondary pumps only friction loss upto zone termination point should be taken care…
For Tertiary pumps friction loss of valves, coil etc should be taken care….
Grundfos FLOW THINKING
Advantages with Tertiary pumps
1. Smaller secondary pumps, motor and drives2. Lower differential pressure in all connection points3. Lower operation cost4. Higher flexibility if the system have to be redesigned5. Each to find the right location for the p sensor6. Minimized risk of “over sizing” secondary pumps
Grundfos FLOW THINKING
Mixing LoopsIn Air-conditioning
Systems
Grundfos FLOW THINKING
• Why mixing loops• Where can mixing loops be used• Different types of mixing loops• Design• Function• Energy saving by using mixing loops
Mixing loops
Grundfos FLOW THINKING
pp p p pPressureprofile
In large systems the diffential pressure will decrease/increase dependingupon the distance from the pump, and not reflect the actual need.
The source of unbalance in a system
Why mixing loops – Increase of hydraulic balance in large/Tertiary/district heating or cooling systems
Grundfos FLOW THINKING
Will adapt to use of the building:HolidaysLoad of the floor
Systems with zone division
Floor divided
Facade dividedWill adapt to weather conditions:SunWind
Why mixing loops – Increase of the control of different part of a building
Grundfos FLOW THINKING
In particulary District/large cooling systems a correct differetial temperature reduces the operation cost.
t 5oC
t 5oC
t 5oC
t 5oC
t 5oC
t 5oC
= m3/hkW x 0,86t
High differential temperature means lower flow.
Formula for calculating the flow in a cooling system
Why mixing loops – Correct differential temperature at the chiller return
Grundfos FLOW THINKING
Sun radiation
Electrical equipment
Other rooms
Other rooms
Light LightPeople
Wind
External parameter which haveinfluence on the cooling/heat demand
Internal parameter which haveinfluence on the cooling/heat demand
Why mixing loops – parameters which influence in the indoor temperature
Grundfos FLOW THINKING
•Heating systems
Where can mixing loops be used
•Heating systems•Radiator systems•Air handling units•Floor heating
•District Heating/Cooling•Building connection
•Cooling systems•Fan coils•Air handling units•Cooling ceilings
All circulating systems where there is a demand for improving the balance and controlling the temperatures
For Primary-Secondary as well as Secondary-Tertiary
Grundfos FLOW THINKING
System 1 System 2 System 3 System 4 System 5
Hydraulic separationTemperature control
InvestmentOperation cost LOW LOW LOW HIGH HIGH
NO
NO
MIDIUM
YES
YES
MIDIUM
NO
YES
HIGH
YES
YES
HIGH
YES
YES
HIGH
Secondary side
Tertiary side
tO
Load
tf
M
tO
Load
tf
M
tO
Load
tf
M
tO
Load
M
tf
tO
Load
M
Mixing loops overview
tr tr tr tr
Grundfos FLOW THINKING
Secondary side Tertiary side
M
Tf
Shut-off valve
Control valve
to
Thermometer
Out-door temperature sensor Loop
controllerFlow
temperature sensor
Non-return valve
Strainer Shut-off valve
Circulator pump
Design
Tr
Returntemperature sensor
Grundfos FLOW THINKING
By adding more or less chilled water to the tertiary side the Loop Controller is adjusting the flow temperature based on outdoor, zone supply and return temperature.
Loop controller
tto
M
Function of the Loop controller
tr
tf
Grundfos FLOW THINKING
Conclusion:1. Full hydraulic balance in the system:
It will also be possible to change the cooling/heating system in one of the buildings without disturbing the balance in in the other buildings.
2. Reduced power consumption: Experiences shown a reduction of chiller power consumption when
mixing loops are installed.
3. Reduced pump energy consumption: Can be reduced to up to 30-40%
Energy consumption in system with mixing loops pumps.
Grundfos FLOW THINKING
Conclusion:4. Better zone control:
Mixing loop will help in achieving better individual zone control.
5. Smaller Secondary pumps: In case of Primary-secondary-tertiary systems smaller secondary
pumps are used
6. Suitable for any application: Can be used for Primary-secondary-Tertiary, Primary-Tertiary as well as Primary- secondary
Energy consumption in system with mixing loops pumps.
Grundfos FLOW THINKING
THANK YOU