alba critical floor area vibrational response

67
ALBA Critical Floor Area ALBA Critical Floor Area Vibrational Response Lluis Miralles i Verge Engineering Division Head CELLS ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10 th –13 th June 2008

Upload: others

Post on 27-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ALBA Critical Floor Area Vibrational Response

ALBA Critical Floor Area ALBA Critical Floor Area Vibrational Response

Lluis Miralles i Verge Engineering Division Head

CELLS

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 2: ALBA Critical Floor Area Vibrational Response

OUTLINE

• Introduction• Construction method

b l h• Vibrational characterization

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 3: ALBA Critical Floor Area Vibrational Response

Introduction

• Case• Site

l d d• Solution adopted

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 4: ALBA Critical Floor Area Vibrational Response

Lattice

Unit CellUnit Cell

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Matching Cell

Page 5: ALBA Critical Floor Area Vibrational Response

ALBA Lattice

* 8 unit cells 8 unit cells* 8 Matching cells* Straights:

4 LSS (8m). 12 MSS (4.2m).8 SSS (2.6m).

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 6: ALBA Critical Floor Area Vibrational Response

Design

Experimental Tunnel

Vibrations

Vibrations, affecting the behaviour of the test ring Experimental Tunnel

(ALBA Tunnel)

Critical Floor Slab

behaviour of the test ring

Service Tunnel

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 7: ALBA Critical Floor Area Vibrational Response

Critical Area Requirements

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 8: ALBA Critical Floor Area Vibrational Response

Site

ALBA: A Spanish

Synchrotron Light Source

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 9: ALBA Critical Floor Area Vibrational Response

A d

SiteTerrassa

A-7MadridTarragona Valencia

AndorraFrance

SabadellA-7

Cerdanyola

SantCugat

E-9

A-2y

A-18

A-17 ona-

Fran

ce

Ronda Giro

BARCELONA

A-19

Airport

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

RENFEF.G.C.

BARCELONA

Mediterranean sea

Page 10: ALBA Critical Floor Area Vibrational Response

Site

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 11: ALBA Critical Floor Area Vibrational Response

B i D th ( ) I t t ti

Measurements and instrumentation

Boring Depth (m) Instrumentation1A 70 Micrometer2A 70 Micrometer3A 70 Mi t3A 70 Micrometer4I 35 Slope indicator5P 70 Extensiometer6P 70 E i6P 70 Extensiometer1B 14,21,47,60 Piezometer2B 15,23,45,65 Piezometer3B 14 21 45 58 P3B 14,21,45,58 Piezometer

•Remote data acquisition m qu

•Periodically crosscheck manual/remote

M thl ts•Monthly reports

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 12: ALBA Critical Floor Area Vibrational Response

Measurements and instrumentation

QUATERNARY

Clay & Sand(0-27)

TERCIARY

Clay/Lime (27-40)

TERCIARY

Clay & Fossil (40-52)

40)

TERCIARY

Clay/Marl

(52-70)( )

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 13: ALBA Critical Floor Area Vibrational Response

Measurements and instrumentation

Deformations, TUB M1A Deformations, TUB M3A

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 14: ALBA Critical Floor Area Vibrational Response

Measurements and instrumentation

• Assumptions

- Deformation of the subsoil within the top 15 m of the ground with a resulting vertical differential

M1Adisplacement of the top surface of about 4 mmwithin the test area.

- Variation of the affected area within the critical floor area.

- Stiff floor slab founded on the ground.

M2A • Investigation of slab surface deformations.

• Calculation of resulting slab deformations with two different computer models.

M3A

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 15: ALBA Critical Floor Area Vibrational Response

Simulation

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 16: ALBA Critical Floor Area Vibrational Response

Simulation

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 17: ALBA Critical Floor Area Vibrational Response

Conclusion

Mechanical Stability/deformations Mechanical Stability/deformations main conclusion

The critical area stability specification, 0.25 mm over 10 m per year can not be guaranteed due to the autogenous p y g gmovements of the soil

Continue monitoring soil as much as possibleCont nue mon tor ng so l as much as poss ble

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 18: ALBA Critical Floor Area Vibrational Response

Solution

Cross section of the solution for the critical floor area

Diameters 20 mm to 40 mm

Cross section of the solution for the critical floor area

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 19: ALBA Critical Floor Area Vibrational Response

Solution

C i f h ALBA b ildiCross section of the ALBA buildings

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Top view of the critical floor area

Page 20: ALBA Critical Floor Area Vibrational Response

C i h dConstruction method

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 21: ALBA Critical Floor Area Vibrational Response

Initial StatusInitial Status

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 22: ALBA Critical Floor Area Vibrational Response

J 06’June 06’

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 23: ALBA Critical Floor Area Vibrational Response

June 06’

• Works started on the 26th May.

d V l l l• Site conditioning. Vegetal layer removal.

• Start excavation up to level 105,5 m.

Initial Status

Vegetal layer removal

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 24: ALBA Critical Floor Area Vibrational Response

After Vegetal layer removal

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Start excavation

Page 25: ALBA Critical Floor Area Vibrational Response

July 06’

• Excavation to level 105,5 m.

G h l • Geothecnical instrumentation movement.

• Start preparation for the execution of the deep conventional foundations (piles).

i P i i l d • Start sewage construction. Provisional and definitive.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Sewage works

Page 26: ALBA Critical Floor Area Vibrational Response

Soil movements

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 27: ALBA Critical Floor Area Vibrational Response

August 06’

• Soil movement to level 105,5 m finalized. Sewage provisional connection executedSewage provisional connection executed.

• Services tunnel excavation started.

• Preparation of conventional deep foundations finalizedfoundations finalized.

• 85 piles executed.

S il m v m ntsSoil movements

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 28: ALBA Critical Floor Area Vibrational Response

Piles execution

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 29: ALBA Critical Floor Area Vibrational Response

Sewage connection

Start services tunnel excavationStart services tunnel excavation

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 30: ALBA Critical Floor Area Vibrational Response

September 06’

• Services tunnel excavation. Collapse of slopes due to strong rainsslopes due to strong rains.

• 145 piles executed.

• Final sewage network works.

Sewage works

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Piles execution

Page 31: ALBA Critical Floor Area Vibrational Response

l Services tunnel excavation

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 32: ALBA Critical Floor Area Vibrational Response

October 06’

• Services tunnel excavation.

P l l d• Piles execution completed.

• Surface foundations start.

• Ground network start.

Services tunnel excavation

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 33: ALBA Critical Floor Area Vibrational Response

Piles execution

Surface foundations

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 34: ALBA Critical Floor Area Vibrational Response

November 06’

• Services tunnel slab execution.

C l fl • Critical floor area excavation.

• Surface foundations completion.

• Services tunnel walls construction start.

Services tunnel slab execution

Services tunnel walls construction

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 35: ALBA Critical Floor Area Vibrational Response

Critical floor area excavation

Surface foundations execution

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 36: ALBA Critical Floor Area Vibrational Response

December 06’

• Services tunnel slab execution.

C l fl • Critical floor area excavation.

• Services tunnel walls construction.

Critical floor area excavation

Services tunnel

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 37: ALBA Critical Floor Area Vibrational Response

January 07’

• Services tunnel slab execution.

C l fl l• Critical floor area excavation completion.

• Technical building slab start

• Technical building excavation completion.

• Services tunnel walls construction.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 38: ALBA Critical Floor Area Vibrational Response

February 07’

• Critical floor area gravel.

T h l b ld b • Technical building basement execution.

• Services tunnel walls construction.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 39: ALBA Critical Floor Area Vibrational Response

March 07’

• Critical floor area gravel.

T h l b ld b • Technical building basement execution.

• Services tunnel walls construction.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 40: ALBA Critical Floor Area Vibrational Response

1 2

40 cm layers40 cm layers

33 4

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 41: ALBA Critical Floor Area Vibrational Response

April 07’

• Critical floor area gravel.

C l fl l b • Critical floor area slab start.

• Services tunnel walls construction.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 42: ALBA Critical Floor Area Vibrational Response

Main data for one segmentMain data for one segment

Length along outer radius 18.85 m

Length along inner radius 11.30 m

Width of test ring approx. 24.0 m

Area of single segment 365 m2

Concrete quantity 365 m3

Ordinary reinforcement 32 tonsOrdinary reinforcement 32 tons

Total 20 segments for critical floor slabslab

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 43: ALBA Critical Floor Area Vibrational Response

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 44: ALBA Critical Floor Area Vibrational Response

April 07’

• Critical floor area slab.

l f • Services tunnel roof construction.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 45: ALBA Critical Floor Area Vibrational Response

May 07’

• Critical floor area slab.

h ld l • Shielding tunnel start.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 46: ALBA Critical Floor Area Vibrational Response

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 47: ALBA Critical Floor Area Vibrational Response

June 07’

• Critical floor area slab.

h ld l • Shielding tunnel execution.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 48: ALBA Critical Floor Area Vibrational Response

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 49: ALBA Critical Floor Area Vibrational Response

July 07’

• Critical floor area completion.

h ld l • Shielding tunnel execution.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 50: ALBA Critical Floor Area Vibrational Response

August 07’

• Shielding tunnel execution.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 51: ALBA Critical Floor Area Vibrational Response

September 07’

• Shielding tunnel execution.

h ld l f ll• Shielding tunnel roof installation.

• Front walls installation.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 52: ALBA Critical Floor Area Vibrational Response

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 53: ALBA Critical Floor Area Vibrational Response

Vibrational Response

• Measurements

C l i• Conclusion

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 54: ALBA Critical Floor Area Vibrational Response

Instrumentation. 2 units Güralp CMG-6TD

three component digital seismometersp g

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 55: ALBA Critical Floor Area Vibrational Response

C 1Case 1

• Measurements on 5th March 2008

• Measurements after site working time

• Sensors nearby the warehouse (S4), and on the critical floors area slab (S5)and on the critical floors area slab (S5)

• Measurements conditions

• Road traffic

• Truck on warehouse road

• Jackhammer.

• Factory activityS5 S4

T kTruck

Jackhammer

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 56: ALBA Critical Floor Area Vibrational Response

Road traffic evaluation at S4

• Difference between traffic at 17:50 and at midnight, 00:05 (15 minute averages),@ 1 Hz, 79 nm vs. 20 nm respectively. 12 Hz, 16 Hz, 24 Hz lines are seen in the midnight spectra, most probably due to motors running in the ceramic factoryfactory.

• Instantaneous substantial variations up to 123 nm )@ 1 Hz.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 57: ALBA Critical Floor Area Vibrational Response

Road traffic evaluation at S5

The slab registers the traffic as it is low frequency noise, but the amplitudes are lower. There are instantaneous fluctuations, for example, 67 nm at 1 Hz is registered and a very clear bump at 6 Hz, due to traffic in the road is detected.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 58: ALBA Critical Floor Area Vibrational Response

Road traffic simulated by truck at S4

•Truck driving on the road nearby the warehouse could simulate the traffic in the late afternoon Traffic at 17:50 @ 1 Hz is 79 nm compared with truck at 21:57 late afternoon. Traffic at 17:50 @ 1 Hz is 79 nm compared with truck at 21:57 which is 69 nm at this frequency region.

• Minute by minute fluctuations can get up to 85 nm.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 59: ALBA Critical Floor Area Vibrational Response

Road traffic simulated by truck at S5

Smaller amplitude of vertical vibration is registered at S5 wrt to S4. Two lines @ 16 and 24 Hz are however detected on the slab which are due to the motors of the 16 and 24 Hz are however detected on the slab which are due to the motors of the factory. @ 1 Hz, S5 registers a movement of 37 nm, S4 registers 68 nm (15 minutes average files).

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 60: ALBA Critical Floor Area Vibrational Response

Comparison S5 vs S4 due to jackhammer

The slab dampens all high frequency components generated by the jack hammer. The vertical vibration amplitude @ 1 Hz is 81 nm measured at S4 and 44 nm at S5.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 61: ALBA Critical Floor Area Vibrational Response

C 2Case 2

• Measurements on 6th March 2008

• Measurements after site working time

• Sensors on corridor (S5), and on the critical floors area slab (S4)critical floors area slab (S4)

• Measurements conditions

• Road traffic

• Truck on site path

• Jackhammer

• Factory activityS5

S4

Jackhammer

S4Truck

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 62: ALBA Critical Floor Area Vibrational Response

Comparison S5 vs S4 due to jackhammer

A jackhammer was used to generate high frequency noise (> 10 Hz). Many peaks are seen at 11, 18, 22, 33, 44, 55, 68 Hz which are due to jackhammer, plus the lines at 15 16 18 20 Hz due to mills and motors of the ceramic factory @ 1Hz lines at 15, 16, 18, 20 Hz due to mills and motors of the ceramic factory. @ 1Hz, 41 nm of vibration is registered on S5 compared with 135 nm on S4. The critical slab seems to dampen high frequency technical noise.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 63: ALBA Critical Floor Area Vibrational Response

Comparison S5 vs S4 due to road traffic

A comparison of 15 minute average files shows that the ALBA slab dampens high frequency noise, but the low frequency noise, due to traffic is not affected. @ 1 Hz, the amplitude measured at S5 is 54 nm at S4 is 64 nm

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 64: ALBA Critical Floor Area Vibrational Response

Comparison S5 vs S4 due to truck

15 minute average taken for S4 and S5. @ 1 Hz, the amplitude of the vibration is 65 nm and 52 nm respectively nm and 52 nm respectively.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 65: ALBA Critical Floor Area Vibrational Response

Measurements with accelerometers

• No attenuation up to 2 Hz.

• 5 dB up to 10 Hz.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

• Up to 30 dB at 100 Hz.

Page 66: ALBA Critical Floor Area Vibrational Response

CONCLUSIONS

• Critical Floor area foundation solution has dumping effects with increasing vibration frequency.

N d i ff t b l 2 H• No dumping effects below 2 Hz.

• 5 dB dumping effect up to 10 Hz.

• Up to 30 dB dumping up to 100 Hz.Up to 30 dB dump ng up to 00 Hz.

• Factor 3 amplitude dumping for above 1 Hz frequencies.

• Coherent results accelerometers vs seismometers.

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008

Page 67: ALBA Critical Floor Area Vibrational Response

THANKS FOR YOUR ATTENTION

ALBA Project

Special acknowledgement to R. Amirikas, A. Bertolini and W. Bialowons

Deutches Elektronen-Synchrotron DESY. Hamburg

ALBA Critical Floor Area Vibrational Response,Ll. Miralles MEDSI 2008. Saskatoon,10th –13th June 2008