The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

DUCTWORK SUBMITTALS

PROJECT:PROJECT NAME

CONTRACTOR:CONTRACTOR NAME

PROJECT MANAGER

ENGINEER:ENGINEER NAME

CONTENTS:

SUBMITTED BY:Habegger Fabrication Division

Mike Frazier

Phone: (513) 761-0383

Fax: (513) 761-1293

Submitted: 05-07-12

23 31 13 DUCTWORK

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

1" WG POS GALVANIZED FIBERGLASS

2" WG POS 304 STAINLESS ELESTOMERIC

3" WG POS 316 STAINLESS DOUBLE-WALL

4" WG POS ALUMINUM 1/2" 2# DENSITY

6" WG POS PAINTGRIP/GALVANEEL 1" 1.5# DENSITY

10" WG POS BLACK IRON 1.5" 2# DENSITY

1" WG NEG POLY COATED 2" 3# DENSITY

2" WG NEG UNDERDUCT PERFORATED WALL

3" WG NEG SOLID WALL

4" WG NEG MYLAR

6" WG NEG TDF/TDC

10" WG NEG SLIP & DRIVE

WELD FLANGE SINGLE BLADE DAMPER

SNAP LOCK DUCTMATE ACCESS DOORS

PITTSBURGH COMPANION FLANGE REINFORCEMENTS

WELDED DUST PROTECTION

LINER COMMENTS

Engineer:

UNITS SYSTEM WG MIN GA MAT

Representative:

RECTANGULAR DUCT SUBMITTALS

Specifications: 23 31 13

Addendum(s):

System(s):

PROJECT NAME

CONTRACTOR NAME

PROJECT MANAGER

ENGINEER NAME

Project Name:

Contractor:

RECTANGULAR DUCT CONSTRUCTION BREAK-DOWNLINER MATERIAL

INCLUSIONS

CONNECTORS

METAL MATERIALPRESSURE CLASS

SEAMS

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

M.P.A.: Center angle welded per SMACNA

If duct narrow side is to be TDF/X same is to be on wide side

SHOP STANDARDS1/2”WG & 1"WG CONSTRUCTION

(NOT FOR ALUMINUM)

(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)

73"-84" 20 56”

85"-96" 20 56”

DUCT

SIZE

0”-18”

25"-30"

31”-42”

43"-54"

DUCT

GAUGE

26

26

26

24

22

19"-24"

56”

56”

56”

55"-72"

97"-120"

120”-UP”

22

T-25a

TDC

T-25a

18

16

FULL

LENGTH

59”

59”/56"

56”

56”

WIDE SIDE CONNECTOR

1” Flat Slip

T-6 24GA

1-1/8” Standing Slip

T-11 26GA

TDC

T-25a

TDC w/ MPT & JTR

T-25a

TDC w/ (2)MPT & (2)JTR

T-25a

60"2”X2”X1/4” W/ MPA & (2) JTR

TDC

TDC

T-25a

TDC w/ MPT Tie-Rod

T-25a

TDC w/ MPA & (2)JTR

TDC w/ (2)MPT & (2)JTR

T-25a

T-25a

NARROW SIDE

CONNECTOR

Flat Drive

T-1 24GA

TDF/X

T-25A

TDC

T-25a

T-25a

2”X2”X1/4” W/ MPA & (2) JTR

T-25a

TDC

T-25a

TDC w/ MPT Tie-Rod

T-25a

TDC w/ MPA & (2)JTR

TDC w/ MPT & JTR

J.T.R.: Joint Tie Rod

M.P.T.: Center Tie Rod

NOTES:

If minimum is required, replace all thiner gauges with required minimum gauge

T-22 T-22

TIE RODS ARE 1/2" E.M.T.

If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

M.P.A.: Center angle welded per SMACNA

If duct narrow side is to be TDF/X same is to be on wide side

TDC w/ MPA & (2)JTR

T-25a T-25a

M.P.T.: Center Tie Rod

TIE RODS ARE 1/2" E.M.T.

97"-120" 18 56”TDC w/ MPA & (2)JTR

2”X2”X1/4” W/ MPA & (2) JTR

T-22

TDC w/ (2)MPT & (2)JTR TDC w/ (2)MPT & (2)JTR

T-25a T-25a

120”-UP” 16 60"2”X2”X1/4” W/ MPA & (2) JTR

T-22

85"-96" 20 56”

TDC

T-25a T-25a

TDC w/ MPT & JTR

56”TDC w/ (2)MPT & JTR TDC w/ (2)MPT & JTR

T-25a T-25a

T-25a

T-25a

(NOT FOR ALUMINUM)

1-1/8” Standing Slip TDF/X

T-11 26GA T-25A

(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)

0”-16” 26 59”1” Flat Slip Flat Drive

T-6 24GA T-1 24GA

17"-22" 26 59”/56"

TDC

24 56”

23"-26" 26 56”TDC

T-25a

TDC

NARROW SIDE

CONNECTOR

27"-30"

T-25a

73"-84" 20

T-25a T-25a

TDC w/ MPT & JTR

56”TDC w/ MPT & JTR

56”TDC

31"-37" 22

SHOP STANDARDS2”WG CONSTRUCTION

DUCT

SIZE

DUCT

GAUGE

FULL

LENGTHWIDE SIDE CONNECTOR

TDC

T-25a T-25a

T-25a T-25a

TDC w/ MPT Tie-Rod TDC w/ MPT Tie-Rod

56”TDC w/ MPT & JTR

55"-60" 20

38"-54" 22 56”

61"-72" 20

NOTES:

If minimum is required, replace all thiner gauges with required minimum gauge

J.T.R.: Joint Tie Rod

If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

M.P.A.: Center angle welded per SMACNA

If duct narrow side is to be TDF/X same is to be on wide side

(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)

(NOT FOR ALUMINUM)

NARROW SIDE

CONNECTOR

SHOP STANDARDS3”WG CONSTRUCTION

T-25a

17"-22" 24 59"/56”

T-1 24GA

0”-12” 26 59”1” Flat Slip Flat Drive

43"-54" 22 56”

T-25a

27"-30" 22 56”TDC TDC

T-25a

DUCT

SIZE

DUCT

GAUGE

FULL

LENGTHWIDE SIDE CONNECTOR

T-25a

61"-84" 20 56”

T-6 24GA T-1 24GA

13"-16" 24 59”1” Flat Slip Flat Drive

T-6 24GA

1-1/8” Standing Slip TDC

T-11 26GA T-25a

23"-26" 24 56”TDC TDC

T-25a

T-25a

31"-42" 22 56”TDC w/ MPT Tie-Rod TDC w/ MPT Tie-Rod

T-25a

TDC w/ MPT & JTR TDC w/ MPT & JTR

T-25a T-25a

55"-60" 20 56”TDC w/ MPT & JTR TDC w/ MPT & JTR

T-25a

TDC w/ (2)MPT & JTR TDC w/ (2)MPT & JTR

T-25a T-25a

85"-96" 18 56”TDC w/ (2)MPT & (2)JTR TDC w/ (2)MPT & (2)JTR

T-25a T-25a

97"-120" 18 56”TDC w/ MPA & (2)JTR TDC w/ MPA & (2)JTR

T-25a T-25a

120”-UP” 16 60"2”X2”X1/4” W/ MPA & (2) JTR 2”X2”X1/4” W/ MPA & (2) JTR

T-22 T-22

NOTES:

If minimum is required, replace all thiner gauges with required minimum gauge

J.T.R.: Joint Tie Rod

M.P.T.: Center Tie Rod

TIE RODS ARE 1/2" E.M.T.

If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

M.P.A.: Center angle welded per SMACNA

If duct narrow side is to be TDF/X same is to be on wide side

SHOP STANDARDS4”WG CONSTRUCTION

TDC

T-25a T-25a

(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)

(NOT FOR ALUMINUM)

DUCT

SIZE

DUCT

GAUGE

FULL

LENGTHWIDE SIDE CONNECTOR

NARROW SIDE

CONNECTOR

43"-54" 22 56”

T-25a

27"-28" 24 56"TDC TDC

T-25a

13"-26" 24 56"TDC

61"-84" 20 56”

T-25a

0”-12” 26 56"TDC TDC

T-25a T-25a

T-25a

29"-42" 24 56”TDC w/ MPT Tie-Rod TDC w/ MPT Tie-Rod

T-25a

TDC w/ MPT & JTR Tie-Rod TDC w/ MPT & JTR Tie-Rod

T-25a T-25a

55"-60" 20 56”TDC w/ MPT & JTR Tie-Rod TDC w/ MPT & JTR Tie-Rod

T-25a

TDC w/ (2)MPT & JTR TDC w/ (2)MPT & JTR

T-25a T-25a

85"-96" 18 56”TDC w/ (2)MPT & (2)JTR TDC w/ (2)MPT & (2)JTR

T-25a T-25a

97"-120" 18 56”TDC w/ MPA & (2)JTR TDC w/ MPA & (2)JTR

T-25a T-25a

120”-UP” 16 60"2”X2”X1/4” W/ MPA & (2) JTR 2”X2”X1/4” W/ MPA & (2) JTR

T-22 T-22

NOTES:

If minimum is required, replace all thiner gauges with required minimum gauge

J.T.R.: Joint Tie Rod

M.P.T.: Center Tie Rod

TIE RODS ARE 1/2" E.M.T.

If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

`

WASHER BOLT

WASHER

BOLT

LIGHT WALL CONDUIT DUCT

T-1 26GA T-6 24GA T-11 26GA T-25A

SEAMS, JOINTS AND TIE RODS

PITTSBURGH SNAP LOCK WELD SEAM

TIE ROD SECTION VIEW

TIE ROD ASSEMBLY DETAIL

WELD SEAMCOMPANION

FLANGE

STANDING SEAM

FLAT DRIVE FLAT SLIP TDF/X

1/2" OR 3/4"

CONDUIT

STANDING SLIP

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

Operating Temperature

Maximum Air Velocity

Water Vapor

Fungi Resistance

Bacteria Resistance

Corrosiveness

Thermal Conductivity

K @ 75 degrees F - Type 200

R-4.2

R-6.3

R-8.0

Surface Burning Characteristics

Flame Spread

Smoke Developed

LINER INFORMATION

20

ASTM C518 0.23

0.24

0.24

0.24

25

ASTM C665

250 degrees F

6,000 FPM (30.5 M/SEC)

<3% AT 120 Degrees F, 95% RH

Meets Requirements

Meets Requirements

Meets Requirements

Btu*in/hr*ft2*degrees F

Value

ASTM C411

ASTM C1104

ASTM C1338

ASTM G21

ASTM G22

ASTM E84, UL 723

CAN/ULC SI02

UL 181 Erosion Test

ASTM C1071

Owens Corning "QuietR Rotary DuctLiner"

Will not cause corrosion greater then by sterile

cotton on alum. or steel*

NOTE: Metal nosing will only be used where required by S.M.A.C.N.A. or as required by

specifications.

Property Test Method

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

3.25" - 6.5"

3.25"

45 45 45 45

6" 9" 6"

7" 7"

5" 5"

5" 5"

6"

18" DUCT (AND

SMALLER) 1 REQD

48" DUCT 3

REQD

36" DUCT 3

REQD

24" DUCT 2

REQD

TDF CONNECTION RECOMMENDED CLIP SPACING

DOUBLE WALL VANES

TDF/X CONNECTION AND DUCT DETAILS

SINGLE WALL VANES

60" DUCT 4

REQD

TURNING VANE INSTALLATION DETAILS

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

BEADS @ 12"

Finished Length (see below)

59" - FINISHED LENGTH WITH SLIP & DRIVE CONNECTIONS

56" - FINISH LENGTH WITH TDF/X CONNECTIONS

60" - FINISH LENGTH WITH RAW (UNFINISHED) CONNECTIONS

All ductwork is G-90 hat dipped Galvanized material unless otherwise noted

All ductwork is beaded per S.M.A.C.N.A, requirements unless otherwise noted

STRAIGHT DUCT LENGTH DESCRIPTIONS

GENERAL DUCTWORK INFORMATION

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

W2

W2 W2 X C2

X C2 X C2 D2

D2 D2 STR2

THR1

THR2 C1 THR2 C1 STR1 C1

THR1 THR1

W1 X D1 W1 X D1 W1 X D1

W2 X D2 W2 X D2 W2 X D2

C2 C2 C2

STR2

THR2 C1 THR2 C1 THR1 C1

THR1 THR1 STR1

W1 X D1 W1 X D1 W1 X D1

W2 X D2 W2 X D2 W2 X D2

O2 O2 THR2

L L

BOT BOT STR

O1 C1 O1 THR1

W1 X D1 W1 X D1 W1 X D1

L L L

S

W1 X D1 W1 X D1 W1 X D1

C2

C1

SQ THR/HEEL 90

SQ THR/RAD HEEL 45

SQ THR/RAD HEEL 90

SQ THR/HEEL 45

C2

RAD THR/HEEL 90

GENERAL FITTING INFORMATION

SQ THR/HEEL 45

OGEE OFFEST SQ OFFSET

C1

C2

EL OFFSET

CANVAS STR TAP SHOE/BOOT TAP

C2

C1

C1

C2

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

STR2 STR3

C2

W2 C2 C3 W3 O1 W2 W3

X X X C2 C3 X

D2 W3 L BOT D2 D3

THR2 THR3 C1 THR1 THR2

THR1 W1 X D1 STR1 W1 X D1

W2 X D2

C2 C3 C2 STR1 STR1

W3 W3 W4

L BOT1 BOT2 L C3 X X X

D3 D3 C3 C4 D4

O1 O2 C1 THR1 THR1 THR2

W1 X D1 W1 X D1 W1 X D1

W2 X D2

C2

C1

L

C1

W2 X D2

W1 X D1

C1

W2 X D2 W3 X D3

SQ TEE SQ TO RND RAD TEE

SQ PANTS RAD LAT TEE RAD CROSS

C1

O3

The Habegger Corporation

Sheet Metal Fabrication Division

925 Redna Terrace, Cincinnati, Ohio 45215

PH: (513) 761-0383

THE HABEGGER CORPORATION Fax: (513) 761-1451

SHEET METAL FABRICATION E-Mail:mikefrazier@habeggercorp.com

STANDARD CONSTRUCTION  DETAILS STANDARD CONSTRUCTION  DETAILS

FRAME: 16 GAUGE GALVANIZED STEEL FRAME: 16 GAUGE GALVANIZED STEEL

DIE FORMED AND WELDED FOR DIE FORMED AND WELDED FOR

STRUCTURAL INTEGRITY 6" WIDE STRUCTURAL INTEGRITY 6" WIDE

BLADES: 16 GAUGE GALVANIZED STEEL BLADES: 16 GAUGE GALVANIZED STEEL

AXELS: DIE CAST ZINC BOLTED WITH AXELS: DIE CAST ZINC BOLTED WITH

1/4" BOLT AND NUT 1/4" BOLT AND NUT

BUSHINGS: BRASS BUSHINGS: BRASS

LINKAGE: N/A LINKAGE: INTERNALLY MOUNTED PLATE

STEEL AND CRANK PLATES

BLADE STOPS: 16 GAUGE ANGLES AT HEAD BLADE STOPS: 16 GAUGE ANGLES AT HEAD

AND SILL AND SILL

HEAVY DUTY METAL QUAD ON 1.5" STAND-OFF HEAVY DUTY METAL QUAD ON 1.5" STAND-OFF

OPTIONAL FEATURES OPTIONAL FEATURES

JAMB AND BLADE SEALS JAMB AND BLADE SEALS

2” STANDOFF 2” STANDOFF

1/2" CONTROL ROD FOR MOTORIZED APPLICATION 1/2" CONTROL ROD FOR MOTORIZED APPLICATION

SINGLE-BLADE DAMPER MULTI-BLADE DAMPER

top related