REGULATORY INFORMATION REPORT
The fire resistance performance of Hilti Firestop Intumescent Sealant CP 611A protecting single cable penetrations in
apertures less or equal to Ø40mm in wall constructions if tested in accordance with
AS1530.4-2005 and assessed in accordance with AS4072.1-2005
EWFA Report No:
RIR 32796900
Report Sponsor:
Hilti (Aust.) Pty Ltd 1G Homebush Bay Drive,
Rhodes, NSW, 2138 Australia
AND
Hilti (New Zealand) Ltd
P.O, Box 112030 Penrose, Auckland 1642,
New Zealand
Report No. RIR 32796900 Page 2 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
DOCUMENT REVISION STATUS
Date Issued Issue No Description
21/09/2015 RIR 32796900 Initial Issue
CONTACT INFORMATION
Exova Warringtonfire Aus Pty Ltd – ABN 81 050 241 524
NATA Registered Laboratory
Unit 2, 409-411 Hammond Road Dandenong Victoria 3175 Australia
T: +61 (0)3 9767 1000 F: +61 (0)3 9767 1001
Victoria
Unit 2, 409-411 Hammond Road Dandenong Victoria 3175 Australia
T: +61 (0)3 9767 1000 F: +61 (0)3 9767 1001
New South Wales
Suite 2002a, 44 Market Street Sydney NSW 2000 Australia
T: +61 (0)2 8270 7600 F: +61 (0)2 9299 6076
Queensland
Northpoint, Unit 29, Level 6 231 North Quay Brisbane QLD 4000 Australia
T: +61 (0)7 3238 1700 F: +61 (0)7 3211 4833
Report No. RIR 32796900Page 3 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
CONTENTS
1 INTRODUCTION 4
2 TESTED PROTOTYPES 4
3 VARIATION TO TESTED PROTOTYPES 4
3.1 Distance Requirements 5
3.2 Penetrations in Flexible Walls 6
3.3 Penetrations in Rigid Walls 7
4 REFERENCED TEST PROCEDURES 10
5 FORMAL ASSESSMENT SUMMARY 10
6 DIRECT FIELD OF APPLICATION 11
7 REQUIREMENTS 11
8 VALIDITY 11
9 AUTHORITY 12
9.1 Applicant Undertakings and Conditions of Use 12
9.2 General Conditions of Use 12
9.3 Authorisation on Behalf of Exova Warringtonfire Aus Pty Ltd 12
9.4 Date of Issue 12
9.5 Expiry Date 12
Report No. RIR 32796900 Page 4 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
1 INTRODUCTION
This report contains the minimum information sufficient for regulatory compliance and refers to the Assessment report EWFA 32796900.
The referenced report presents an assessment of the fire resistance performance of Hilti Firestop Intumescent Sealant CP 611A protecting single cable penetrations in apertures less or equal to Ø40mm in wall constructions if tested in accordance with AS1530.4-2005 and assessed in accordance with AS4072.1-2005.
The tested prototypes described in Section 2 of this report, when subject to the proposed variations described in Section 3 and tested in accordance with the referenced test method described in Section 4. The conclusions of the referenced report are summarised in Section 5.
The validity of the referenced assessment is conditional on compliance with Sections 7, 8 and 9 of this report.
2 TESTED PROTOTYPES
The referenced assessment references to test No. 14244A describing test of cable penetrations protected with various Hilti products penetrating plasterboard lined wall and concrete wall constructions and tested in accordance with EN 1366-3: 2009. The test was sponsored by Hilti and was conducted by EFECTIS France.
3 VARIATION TO TESTED PROTOTYPES
The proposed construction is for single cable penetration protected with Hilti Firestop Intumescent Sealant CP 611A in walls as tested in No. 14244A subject to the following variations:
• The single PVC insulated copper conducted cable sizes and corresponding minimum and maximum allowable aperture sizes are summarised in Table 1.
• The minimum distance between the cable and seal edge may be zero.
• Aperture size up to Ø40mm or any opening/shape of equivalent area, backfilling material may be omitted, and the annular gap between wall substrate and single cable penetration shall be sealed with Hilti Intumescent sealant CP 611A with a depth of at least 25mm deep on each side..
• The backfilling material is omitted.
• The wall material can optionally be masonry, concrete, AAC, Speedpanel, Speedwall panel or plasterboard lined wall.
• The plasterboard lined wall shall be constructed from minimum two layers of 13mm or 16mm thick fire grade plasterboard each side with a minimum wall thickness of 100mm that has been tested or otherwise assessed to achieve an FRL of -/120/120 or 120/120/120.
• The assessed construction is summarised in sections 3.1, 3.2 and 3.3.
Report No. RIR 32796900Page 5 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
3.1 DISTANCE REQUIREMENTS
Figure 1 – Distance Requirements of Penetrations
Table 1 – Distance Requirements in Walls
Minimum distance valid for installations of services Wall (mm)
Distance between cable and seal edge s1 = 0
Distance between single cable services in grouped arrangement s2 = 40
Table 2 – Aperture Sizes for Sealant CP 611A (A) without Backfilling Material
PVC Insulated Copper Conducted Cable
Outside Diameter Ø (mm)
Min. Aperture Diameter Ø (mm)
Max. Aperture Diameter Ø (mm)
4 6 40 8 12 40
10 15 40 12 18 40 16 24 40 20 30 40 25 38 40
S1 A
S2
Report No. RIR 32796900 Page 6 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
3.2 PENETRATIONS IN FLEXIBLE WALLS
100mm Flexible Wall or Greater (E)
The wall shall have a minimum thickness of 100mm (tE) and comprise of timber or steel studs lined
on both faces with a minimum of two layers of 13mm or 16mm thick fire grade plasterboard and has
been tested or otherwise assessed to achieve an FRL of -/120/120 or 120/120/120 with or without
cavity insulation (E2).
Penetration Seal
For aperture sizes up to Ø40mm, the annular gap between separating element and cable penetration shall be sealed with Hilti Firestop Intumescent sealant CP 611A with a depth of at least 25mm on each side.
Additional Protection for Penetrations 50mm Hilti Firestop Intumescent sealant CP 611A sealant fillet at approximately 45 degree angles shall be applied on each side of the wall and fully covers the annular gap between separating element and cable penetration.
Figure 2 – Details for 100mm Flexible Wall
Item Description Item Description
A Hilti Firestop Intumescent Sealant CP 611A
C Single PVC insulated copper conducted cable penetration
tA Thickness (Depth) of sealant in annular gap, min. 25mm thick
E Support construction element
F Additional Hilti Firestop Intumescent Sealant CP 611A fillet at approximately 45 degree angles
E2 Wall cavity insulation, optional
tF Thickness (Depth) of additional sealant fillet min. 50mm deep
tE Thickness of the building element
A
E
tE
C F
tA
tF
Report No. RIR 32796900Page 7 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
3.3 PENETRATIONS IN RIGID WALLS
75mm Rigid Wall or Greater (E)
The bare wall (E) must have a minimum thickness of 75mm and comprise of concrete, aerated
concrete, Speedpanel panel, Speedwall panel or solid or hollow masonry with a minimum density of
550kg/m3.
Penetration Seal
For aperture sizes up to Ø40mm, the annular gap between separating element and cable penetration shall be sealed with Hilti Firestop Intumescent sealant CP 611A for the full depth of wall element.
Figure 3 – Details for 75mm Rigid Wall
Item Description Item Description
A Hilti Firestop Intumescent Sealant CP 611A
C Single PVC insulated copper conducted cable penetration
tA Thickness (Depth) of sealant in annular gap, min. 75mm thick (or full depth of the wall for thicker walls)
E Support construction element
tE Thickness of the building element
tE
E
A C
tA
Report No. RIR 32796900 Page 8 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
75mm Rigid Wall or Greater (E) with Additional Protection
The bare wall (E) must have a minimum thickness of 75mm and comprise of concrete, aerated
concrete, Speedpanel panel, Speedwall panel or solid or hollow masonry with a minimum density of
550kg/m3.
Penetration Seal
For aperture sizes up to Ø40mm, the annular gap between separating element and cable penetration shall be sealed with Hilti Firestop Intumescent sealant CP 611A with a depth of at least 25mm on each side.
Additional Protection for Penetrations 50mm Hilti Firestop Intumescent sealant CP 611A sealant fillet at approximately 45 degree angles shall be applied on each side of the wall and fully covers the annular gap between separating element and cable penetration.
Figure 4 – Details for 75mm Rigid Wall with Additional Protection
Item Description Item Description
A Hilti Firestop Intumescent Sealant CP 611A
C Single PVC insulated copper conducted cable penetration
tA Thickness (Depth) of sealant in annular gap, min. 25mm thick
E Support construction element
F Additional Hilti Firestop Intumescent Sealant CP 611A fillet at approximately 45 degree angles
tE Thickness of the building element
tF Thickness (Depth) of additional sealant fillet min. 50mm deep
tE
E
A C
F
tA
tF
Report No. RIR 32796900Page 9 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
100mm Rigid Wall or Greater (E)
The bare wall (E) must have a minimum thickness of 100mm and comprise of concrete, aerated
concrete or solid or hollow masonry with a minimum density of 550kg/m3.
Penetration Seal
For aperture sizes up to Ø40mm, the annular gap between separating element and cable penetration shall be sealed with Hilti Firestop Intumescent sealant CP 611A with a depth of at least 25mm on each side.
Additional Protection for Penetrations 50mm Hilti Firestop Intumescent sealant CP 611A sealant fillet at approximately 45 degree angles shall be applied on each side of the wall and fully covers the annular gap between separating element and cable penetration.
Figure 5 – Details for 100mm Rigid Wall
Item Description Item Description
A Hilti Firestop Intumescent Sealant CP 611A
C Single PVC insulated copper conducted cable penetration
tA Thickness (Depth) of sealant in annular gap, min. 25mm thick
E Support construction element
F Additional Hilti Firestop Intumescent Sealant CP 611A fillet at approximately 45 degree angles
tE Thickness of the building element
tF Thickness (Depth) of additional sealant fillet min. 50mm deep
tE
E
C A F
tF
tA
Report No. RIR 32796900 Page 10 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
4 REFERENCED TEST PROCEDURES
The referenced report is prepared with reference to the requirements of AS1530.4-2005 and AS4072.1-2005.
5 FORMAL ASSESSMENT SUMMARY
Based on the discussion presented in the referenced report, it is the opinion of this testing authority that if the specimen described in section 2 had been modified within the scope of section 3, it will achieve the performance as stated below when tested in accordance with the test method referenced in Section 4 and subject to the requirements of Section 7:
Table 5.1 – Single Cable in Rigid Walls in Section 3.3, tE ≥ 75mm
Cable Outside
Diameter (OD) Ø
Sealant in Annular Gap
Min. Sealant
Depth (tA)
Min. Depth of Additional Protection
(tF)
Aperture Size
Refer Figure
FRL
4
Hilti Firestop Intumescent
Sealant
CP 611A
75mm (or full depth of the wall for
thicker walls)
- Table 2 Figure 3 -/60/60
8
10
12
16
20
25
Table 5.2 – Single Cable in Rigid Walls with Additional Protection specified in Section 3.3, tE ≥ 75mm
Cable Outside
Diameter (OD) Ø
Sealant in Annular Gap
Min. Sealant
Depth (tA)
Min. Depth of Additional
Protection (tF)
Aperture Size
Refer Figure
FRL
4
Hilti Firestop Intumescent
Sealant
CP 611A
25mm 50mm Table 2 Figure 4 -/90/90
8
10
12
16
20
25
Table 5.3 – Single Cable in 2hr Flexible Walls specified in Section 3.2, tE ≥ 100mm
Cable Outside
Diameter (OD) Ø
Sealant in Annular
Gap
Min. Sealant Depth
(tA)
Lining Thickness
Min. Depth of
Additional Protection
(tF)
Aperture Size
Refer Figure
FRL
4
Hilti Firestop Intumescent
Sealant
CP 611A
25mm
2 × 13mm or
2 × 16mm 50mm Table 2 Figure 2 -/120/120
8
10
12
16
20
25
Report No. RIR 32796900Page 11 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
Table 5.4 – Single Cable in Rigid Walls specified in Section 3.3, tE ≥ 100mm
Cable Outside
Diameter (OD) Ø
Sealant in Annular
Gap
Min. Sealant Depth (tA)
Min. Depth of
Additional Protection
(tF)
Aperture Size Refer Figure FRL
4
Hilti Firestop Intumescent
Sealant
CP 611A
25mm 50mm Table 2 Figure 5 -/120/120
8
10
12
16
20
25
6 DIRECT FIELD OF APPLICATION
The referenced assessment applies to penetrations in walls exposed to fire from either side.
7 REQUIREMENTS
The referenced report details the methods of construction, test conditions and assessed results that would have been expected had the specific elements of construction described herein been tested in accordance with AS1530.4.
Any further variations with respect to size, constructional details, loads, stresses, edge or end conditions, other than those identified in this report, may invalidate the conclusions drawn in the referenced report.
It is required that the supporting construction be otherwise tested or assessed to achieve the required FRL of the penetration seal in accordance with AS1530.4-2005.
8 VALIDITY
The referenced assessment report does not provide an endorsement by Exova Warringtonfire Aus Pty Ltd of the actual products supplied.
The conclusions of the referenced assessment may be used to directly assess the fire resistance performance under such conditions, but it should be recognised that a single test method will not provide a full assessment of the fire hazard under all fire conditions.
Because of the nature of fire resistance testing, and the consequent difficulty in quantifying the uncertainty of measurement, it is not possible to provide a stated degree of accuracy. The inherent variability in test procedures, materials and methods of construction, and installation may lead to variations in performance between elements of similar construction.
The referenced assessment can therefore only relate only to the actual prototype test specimens, testing conditions and methodology described in the supporting data, and does not imply any performance abilities of constructions of subsequent manufacture.
The referenced assessment is based on information and experience available at the time of preparation. The published procedures for the conduct of tests and the assessment of test results are the subject of constant review and improvement and it is recommended that the referenced report be reviewed on or, before, the stated expiry date.
Report No. RIR 32796900 Page 12 of 12
© Copyright Exova Warringtonfire Aus Pty Ltd 2015
The information contained in this report shall not be used for the assessment of variations other than those stated in the conclusions above. The assessment is valid provided no modifications are made to the systems detailed in the referenced report. All details of construction should be consistent with the requirements stated in the relevant test reports and all referenced documents.
9 AUTHORITY
9.1 APPLICANT UNDERTAKINGS AND CONDITIONS OF USE
By using this report as evidence of compliance or performance, the applicant(s) confirms that:
• to their knowledge the component or element of structure, which is the subject of this assessment, has not been subjected to a fire test to the Standard against which this assessment is being made, and
• they agree to withdraw this assessment from circulation should the component or element of structure be the subject of a fire test by a test authority in accordance with the Standard against which this assessment is being made and the results are not in agreement with this assessment, and
• they are not aware of any information that could adversely affect the conclusions of this assessment and if they subsequently become aware of any such information, agree to ask the assessing authority to withdraw the assessment.
9.2 GENERAL CONDITIONS OF USE
This report may only be reproduced in full without modifications by the report sponsor. Copies, extracts or abridgments of this report in any form shall not be published by other organisations or individuals without the permission of Exova Warringtonfire Aus Pty Ltd.
9.3 AUTHORISATION ON BEHALF OF EXOVA WARRINGTONFIRE AUS PTY LTD
Prepared by: Reviewed by:
S. Hu K Nicholls
9.4 DATE OF ISSUE
21/09/2015 9.5 EXPIRY DATE
30/09/2020