Aritech is an Interlogix Company

© Interlogix B.V. 2001. All rights reserved. No part of this publication may be reproduced, transmitted, stored in a retrieval system, or transmitted in any form, or by any means – electronic, photocopying, recording, or otherwise – without the prior written permission of Interlogix B.V. reserve the right to change information without notice.

Page 3: ATS1250 inst rom - ETAS

ATS1250/1260 Installation Guide 3

CUPRINS

Instalare ............................................................................................................................. 4 1. Prezentare centrala control acces ATS1250/1260 .................................................................................. 4 2. Note importante la montare ..................................................................................................................... 4 3. LED-urile .................................................................................................................................................. 4 4. Cablare..................................................................................................................................................... 5

Cablarea recomandata a bus-ului de date............................................................................................... 5 5. Impamantare............................................................................................................................................ 6

Ecranarea................................................................................................................................................. 6 6. Conectarea cablurilor bus pentru ATS..................................................................................................... 6 7. Conectarea bus-ului local si impamantarea pentru ATS1250/1260 ........................................................ 6 8. Diagrama de conectare............................................................................................................................ 7

Circuitul ATS1250 .................................................................................................................................... 7 Setarile pentru comutatoarele DIP........................................................................................................... 8 Conectarea bus-ului de date local ........................................................................................................... 8 Conectarea bus-ului de date sistem ........................................................................................................ 8 Conectarea contactului de usa si a butonului de cerere de iesire........................................................... 8 Conectarea zavorului pentru usa............................................................................................................. 9 Conectarea cititorului ATS1190 Smart Card............................................................................................ 9 Conectarea cititorului ACI7xx (examplu ACI765) .................................................................................... 9

Zone si Iesiri .................................................................................................................... 10 1. Zone si iesiri ........................................................................................................................................... 10 2. Dispozitive iesiri ..................................................................................................................................... 10 3. Setarile initiale (implicite) pentru zone si relee la ATS1250/1260 ........................................................ 10 4. Tabel 3: ATS1250 implicit ...................................................................................................................... 10 5. Numerotarea usilor si lifturilor ................................................................................................................ 11

Specificatii Tehnice......................................................................................................... 11 1. Specificatii generale............................................................................................................................... 11 2. Valorile sigurantelor ............................................................................................................................... 11 6. Lungimi cabluri....................................................................................................................................... 12 7. Specificatie terminale externe................................................................................................................ 12

Procedura de Pornire...................................................................................................... 13

Accesarea Meniului de Programare Door/Lift............................................................... 13 1. Acesarea meniul de programare ........................................................................................................... 13 2. Meniul de programare pentru ATS1250/1260 ....................................................................................... 14 3. Secventa de programare ....................................................................................................................... 14

Setari minime ......................................................................................................................................... 14

Meniuri Programare ........................................................................................................ 15

Page 4: ATS1250 inst rom - ETAS

4 ATS1250/1260 Installation Guide

INSTALARE

1. Prezentare centrala control acces ATS1250/1260

(1) Conector impamantare pentru cablu de date

(2) Jumper reset

(3) EPROM (prezent din fabricatie)

(4) Flash RAM (optional)

(5) RAM sau IUM (optional)

(6) Borne alimentare

J1 Conector sursa J2 Conector sursa auxiliara si sirena J3 Conector bus RS485 si tamper

cutie J4 - J7 Conector relee usile 1-4 J8 - J12 Zone J13 - J16 Conector cititor usa J17 Releu sirena J18 Folosit numai la fabrica J19 - J20 RS232 (nefolosit) J21 Interfata Clock-out pentru

expandor de iesiri J22 RS485 bus date local J23 Nefolosit

Conector alimentare retea

Utilizati conectorul de alimentare pentru conectarea tensiunii de alimentare. Pentru aceasta se poate folosi cablu rigid sau flexibil. Pentru cablu rigid, utilizati o siguranta dedicata in tablou.

IMPORTANT: Deconectati tensiunea de alimentare inainte de interventie!

• Scoateti stecherul din priza , sau

• Intrerupeti tensiunea de la siguranta din tablou.

2. Note importante la montare Montarea centralei se face utilizand suruburi sau bolturi, prin cele patru gauri ale cutiei.

Verificati ca centrala sa fie montata pe o suprafata solida, plana, verticala, astfel incat cutia sa nu se deformeze la stringerea suruburilor.

Lasati o distanta de 50 mm intre cutiile echipamentelor si 25 mm de la cutie la zid.

+ Folositi centralele in locuri ferite de umezeala si praf.

3. LED-urile OK: Indica functionarea normala a procesorului.

RS232: Nefolosit.

Rx0: Palpairea LED-ului indica primirea de date de la centrala ATS pe bus-ul de date.

Tx0: Palpairea LED-ului indica trimiterea de date de la panoul de achizitii date la centrala ATS pe bus-ul de date.

Tx1: Palpairea LED-ului indica trimiterea de date catre cititoare/interfete pe bus-ul local. LED-ul Tx1 trebuie sa fie activ permanent.

Rx1: Palpairea LED-ului indica primirea de date de la cititoare/interfete.

L1-L4: Indica starea releelor.

Page 5: ATS1250 inst rom - ETAS

ATS1250/1260 Installation Guide 5

4. Cablare Cablarea recomandata a bus-ului de date

Legatura “TERM” se realizeaza la primul si ultimul dispozitiv de pe bus-ul de date. Intr-o configuratie de tip stea, legatura “TERM” se realizeaza numai la dispozitivele de la capatele celui mai lung cablu de bus.

+ Bus-ul local trebuie sa indeplineasca aceleasi conditii. Acesta se conecteaza la J22. Vezi de asemenea Conectarea bus-ului local si impamantarea pentru ATS1250/1260 de la pagina 6.

(1) Legatura TERM realizata (primul dispozitiv din bus-ul local)

(2) Conector impamantare

(3) Jumper GND (NU SE INTRODUCE)

(4) Centrala ATS4000

(5) Tastatura LCD ATS1105 (jumperul TERM nu este pe ON)

(6) Sursa auxiliara de 12 V. Este necesara daca RAS-urile sunt la o distanta mai mare de 100 m de cea mai apropiata centrala sau DGP. Se conecteaza “-“ la “-“ pe bus-ul de date.

(7) Cablu recomandat este de 2 perechi torsadat (Belden 8723).

(8) Legatura TERM este realizata (ultimul dispozitiv din bus-ul local)

(9) Conector impamantare

(10) Jumper GND (NU SE INTRODUCE)

(11) Orice DGP ca ATS1250.

Vezi Conectarea cablurilor bus pentru ATS , Conectarea bus-ului local si impamantarea pentru ATS1250/1260 si detalii impamantare pagina 6.

Page 6: ATS1250 inst rom - ETAS

6 ATS1250/1260 Installation Guide

5. Impamantare

ATENTIE! Procedura de realizare a impamantarii trebuie urmata corect.

• Impamantarea unei centrale ce contine mai multe dispozitive

Toate dispozitivele sistemului sunt prevazute cu conectoare metalice imbinate la carcasele metalice. Verificati buna conectare a lor (atentie la vopsea).

Conectorul pentru impamantare al fiecarui echipament din sistem poate fi utilizat pentru conectarea ecranului de la cablurile ecranate.

Daca un dispozitiv are cutie de plastic, impamantarea nu se conecteaza.

• Impamantarea centralelor dintr-o cladire

Intr-o cladire pot fi mai multe dispozitive cu impamantare. Impamantarea cladirii trebuie verificata de personal calificat.

• Impamantarea centralelor din mai multe cladiri

Daca sistemul se extinde in cladiri separate, cu impamantari separate, utilizati module izolator/repetor ATS1740 pentru a izola bus-ul de date. Acesta protejeaza sistemul de variatii ale potentialului de impamantare.

Ecranarea

Ecranele cablurilor utilizate in sistem trebuie conectate NUMAI intr-un singur capat la o singura impamantare comuna. Daca cablul de bus este ecranat si trece prin diferite dispozitive cu carcasa de plastic, ecranele cablurilor ce intra in dispozitive trebuie conectate la ecanele cablurilor ce ies din dispozitive.

6. Conectarea cablurilor bus pentru ATS

Bus-ul de date este utilizat pentru conectarea DGP-urilor (ATS1250/1260) si dispozitivelor de armare la centrala ATS. Statiile de armare pot fi pana la 1,5 km de centrala ATS.

Fiecarui dispozitiv indepartat ii este dedicata o adresa si este inregistrat secvential de centrala ATS. Se pot conecta un numar de maxim 12 DGP de tip 4-usi/4-lifturi se pot conecta la bus-ul de date (Vezi Conectarea bus-ului de date sistem, pagina 6)

Statiile de armare si DGP-urile trebuie conectate printr-un cablu ecranat, torsadat cu 2 perechi. (se recomanda Belden 8723).

Se conecteaza ecranul la impamantarea centralei ARS, iar la celalalt capat se lasa neconectat.

DGP-ul 4-usi/4-lifturi au alimentare proprie si nu necesita alimentarea din bus-ul de date. Sunt necesare numai conexiunile D+, D- si 0V intre centrala ATS si DGP-ul 4-usi/4-lifturi.

7. Conectarea bus-ului local si impamantarea pentru ATS1250/1260

ATS1250/1260 permite conectarea, prin J22, la bus-ul local a 16 statii de armare (tastaturi LCD, cititoare Smart Card) si 15 DGP-uri (NUMAI 4-lifturi).

Conectati contactele de usi si butoanele de cerere de iesire la intrarile ATS1250.

Wire the floor monitoring and lift override zones to the 4-lift DGP zones or zones on DGPs, which are connected to the local databus not on the ATS system databus. There are spare zones for other devices, such as PIRs.

Nici o zona folosit ca Usa deschisa prea mult (DOTL- Door Open Too Long) nu trebuie sa fie conectata.

Fiecare unitate are o adresa si este inregistrata secvential de ATS1250/1260. Unitatile indepartate pot fi amplasate pana la 1,5 km de ATS1250/1260 (vezi Conectarea bus-ului de date local , pagina 8).

(1) Alimentare retea cu impamantare locala (2) Conector alimentare retea (3) Bus date sistem (4) Conector impamantare

(5) Cladirea 1 (6) Cladirea 2 (7) Dispozitiv in cutie metalica (8) Dispozitiv in cutie din plastic

!

Page 7: ATS1250 inst rom - ETAS

ATS1250/1260 Installation guide 7

8. Diagrama de conectare Circuitul ATS1250

(1) Conector impamantare (la fel ca impamantarea J1) (2) Conector alimentare (3) Impamantare sistem (Vezi detalii pagina 6) (4) Acumulatori 2 x 12 V, 7.2 Ah. (5) Iesire sursa auxiliara (6) Iesire sursa comutata (7) Sirena exterioara (8) Bus date sistem si tamper centrala (pentru detalii vezi pagina 6) (9) Iesiri relee c-da zavoare usi (10) Intrari zone (11) Bus date local pentru conectare RAS-uri si DGP-uri (pentru detalii

vezi pagina 6) (12) Siguranta Acumulator 1 (F1, 3A Rapida) (13) Siguranta Acumulator 2 (F2, 3A Rapida) (14) Siguranta Sursa auxiliara 1 (F3, 3A Rapida) (15) EXT.siguranta cititoare (F4, 3A Rapida) (16) Siguranta iesire auxiliara comutata (F5, 1A Rapida) (17) Siguranta bus date local (F6, 3A Rapida) (18) Term 2. Folositi aceasta legatura pentru a inchide bus-ul de date

sistem (19) DIP switch-uri (vezi Setarile pentru comutatoarele DIP, pagina 6) (20) LK1/LK2/LK4/LK5 – Monitorizare zavor, nefolosit. (21) Interfata calculator, nefolosit (22) Clockout – Conectare la module iesiri. Alimentare +12 VCC si iesiri

open colector SAU iesiri date; pentru conectare cu controlere iesiri (23) Term 1. Folositi aceasta legatura pentru a inchide bus-ul de date

local (24) Reset - Pentru ATS1250/1260, in scurtcircuit din fabrica (25) Conectori cititoare (26) Alimentare +12VCC pentru ATS1810/ATS1811/ATS1820 (27) TST1 si TST2 –numai pentru utilizarea fabricantului (28) Iesire sirena, neutilizat (29) Conector seriala, nefolosit

Page 8: ATS1250 inst rom - ETAS

8 ATS1250/1260 Installation guide

DGP 4 DGP 5

1

ON SD

2 3 4 1

ON SD

2 3 4 1

ON SD

2 3 4 DGP 1 DGP 2

1

ON SD

2 3 4 DGP 3

1

ON SD

2 3 4 1

ON SD

2 3 4 1

ON SD

2 3 4 DGP 6

1

ON SD

2 3 4 DGP 7

DGP 8 1

ON SD

2 3 4 1

ON SD

2 3 4 1

ON SD

2 3 4 DGP 9 DGP 10

1

ON SD

2 3 4 DGP 11

1

ON SD

2 3 4 1

ON SD

2 3 4 1

ON SD

2 3 4 1

ON SD

2 3 4 DGP 12

DGP 0

(DGP 13 – DGP 16)

Setarile pentru comutatoarele DIP

Comutatoarele DIP 1 - 4 (Adrese DGP) sunt utilizate pentru identificarea DGP-urilor de catre centrala Advisor MASTER. Numai DGP-urile 4-usi/4-lifturi pot fi adresate intre 1 si 12 (vezi figura de mai jos).

Comutatoarele DIP 5 - 8 nu sunt folosite.

Conectarea bus-ului de date local

ATS1190: 12 V Rosu 0 V Negru D + Alb D - Verde

Conectarea bus-ului de date sistem

Conectarea contactului de usa si a butonului de cerere de iesire

(1) Contact usa

(2) Buton cecere iesire

Page 9: ATS1250 inst rom - ETAS

ATS1250/1260 Installation guide 9

Conectarea zavorului pentru usa

Conectarea cititorului ATS1190 Smart Card

Conexiune cititor Fir ATS1190 Conexiune cititor Fir ATS1190 +12 V Rosu 5 V Nefolosit 0 V Negru D0 Verde

D1 Alb L2 Maro L1 Galben BZ Albastru

Firul violet, (iesire open colector) poate fi conectat la o zona printr-o rezistenta de cap de linie

Conectarea cititorului ACI7xx (examplu ACI765)

Page 10: ATS1250 inst rom - ETAS

10 ATS1250/1260 Installation guide

ZONE SI IESIRI

1. Zone si iesiri Toate DGP-urile, zonele si iesirile sunt numerotate dupa o formula. Aceasta este folosita la programare, cand se doreste determinarea fizica a numarului/locatiei unui DGP, iesire, etc.

Tabel 1. Zone si iesiri alocate DGP-urilor

Centrala Advisor MASTER 1-16

DGP 1 17-32 DGP 7 113-128

DGP 2 33-48 DGP 8 129-144

DGP 3 49-64 DGP 9 145-160

DGP 4 65-80 DGP 10 161-176

DGP 5 81-96 DGP 11 177-192

DGP 6 97-112 DGP 12 193-208

Zone

Un DGP 4-usi/4-lifturi are 16 zone. Aceste zone sunt ca zonele standard.

Ex. ATS1250 1 este DGP 1 si are 16 zone, pe care centrala ATS le identifica cu zonele 17-32.

Vezi tabelele 3 si 4 de la pagina 10 pentru mai multe detalii despre zone si setarile releelor.

Iesiri

Un DGP 4-usi/4-lifturi are o singura iesire standard, disponibila ca sirena. Sunt de asemenea disponibile 4 relee, cate unul pentru fiecare usa (K2-K5).

Un DGP 4-usi/4-lifturi poate accesa in total 48 iesiri daca se utilizeaza macro-logica.

Controlerele de iesiri sunt utilizate pentru marirea numarului de iesiri ale unui DGP. Fiecare controler de iesiri mareste numarul acestora cu opt. Numarul iesirile si zonelor sunt intotdeauna la fel ca numarul primelor 16 zone ale DGP-ului la care sunt conectate.

Iesiri de sirene

Iesirea de sirena a ATS 1250/1260 este disponibila ca ultima din cele 16 iesiri asociate cu adresa DGP-ului. Ex, la DGP3 iesirea de sirena este iesirea 64 (vezi Tabel 2).

Tabel 2. Numarul iesirii de sirena alocat DGP-ului

Nr. DGP Nr. iesire sirena Nr. DGP Nr. iesire

sirena 1 2 3 4 5 6

32 48 64 80 96

112

7 8 9

10 11 12

128 144 160 176 192 208

Pentru a activa iesirea de sirena, numarul iesirii ce reprezinta iesirea de sirena trebuie dedicata unui numar de Flag-eveniment de Sirena (Siren Event Flag Number). Acest numar de Flag-eveniment de Sirena sunt programate in meniul de programare 2 – Area Databases, descrise in manualul de programare al centralei ATS.

2. Dispozitive iesiri ATS1810 modulul 4 relee va permite sa folositi iesirile cu numerele 5-8 din iesirile alocate unui DGP. Ex, DGP 1 foloseste releele 17,18,19 si 20 pentru deschiderea usilor si iesirile 21-24 pentru modulul 4 relee.

ATS1811 modulul 8 relee va permite sa folositi iesirile cu numerele 5-48 din iesirile alocate unui DGP. Ex, DGP 1 foloseste releele 17,18,19 si 20 pentru deschiderea usilor si iesirile 21-63 pentru modulul 8 relee.

ATS1820 modul 16 iesiri open-colector. La fel ca ATS1811. Un DGP 4-usi/4-lifturi poate activa iesirile 33-63 numai utilizand functii macro-logice.

Daca utilizati mai mult de 2 module ATS1811 sau 2 module ATS1820 trebuie sa folositi o sursa auxiliara.

3. Setarile initiale (implicite) pentru zone si relee la ATS1250/1260

4. Tabel 3: ATS1250 implicit

Prima Usa

A 2-a Usa

A 3-a Usa

A 4-a Usa

Contact usa 1 4 7 10

Liber 2 5 8 11

Zona cerere iesire 3 6 9 12

Zona DOTL 16 15 14 13

Releu usa K2 K3 K4 K5

Tabel 4: ATS1260 implicit

Primul

Lift Al 2-lea

Lift Al 3-lea

Lift Al 4-pea

Lift

Primul etaj 1 1 1 1

Ultimul etaj 64 64 64 64

Primul releu 1 65 129 193

Prima zona 1 65 129 193

Numarul zonelor din acest tabel se refera la numarul zonelor fizice la ATS1250/1260.

Numerele zonelor din sistem corespunzatoare acestor functii ale ATS1250/1260 se gasesc in Tabelul 1.

Page 11: ATS1250 inst rom - ETAS

ATS1250/1260 Installation Guide 11

5. Numerotarea usilor si lifturilor Numarul usilor sunt determinate de:

• Adresa RAS-ului sau a cititorului la conectarea la bus-ul sistem (usile 1-16)

• Adresa modulului 4-usi/4/lifturi (usile 17-64)

Usile 1-16 sunt rezervate pentru RAS-urile 1-16 si sunt conectate la bus-ul de date sistem. Acestea realizeaza numai functii de baza pentru control acces (deschiderea usilor).

Usile 17-64 sunt folosite pentru numerotarea usilor si lifturilor si sunt controlate de DGP-ul 4-usi/4-lifturi (ATS1250/1260). Aceste usi dispun de functii sporite de control acces (anti-passback, etc).

Tabel 5. Usi si lifturi alocate DGP-urilor

Dispozitiv/ Numarul usii adresa

RAS 1 - 16 1 - 16 (numai deschidere usa)

Usa sau lift

1-ul 2-lea 3-lea 4-lea

DGP1 17 18 19 20

DGP2 21 22 23 24

DGP3 25 26 27 28

DGP4 29 30 31 32

DGP5 33 34 35 36

DGP6 37 38 39 40

DGP7 41 42 43 44

DGP8 45 46 47 48

DGP9 49 50 51 52

DGP10 53 54 55 56

DGP11 57 58 59 60

DGP12 61 62 63 64

SPECIFICATII TEHNICE

1. Specificatii generale Acumulatori: 2 x 12 VCC 7.2 Ah, in functie de consumul dispozitivelor auxiliare.

Consumul placii 275 mA max.

Curent total extern 3 A max la toate dispozitivele externe.

Rezistente cap de linie: Implicit: 4.7 kΩ, 2 %, 0.25 W (Altele: 10kΩ, 2 %, 0.25W)

Dimensiuni fizice (L x l x A):

Cutie

Placa circuit

480 mm x 464 mm x 160 mm

260 mm x 218 mm x 48 mm

Temperatura de utilizare: 0°C la + 50°C

Umiditate: 95% fara condens.

2. Valorile sigurantelor

Sigurante F1 Acumulator 1 3 A, Rapida 20x5 F3 Sursa auxiliara si sirena 3 A, Rapida 20x5

F2 Acumulator 2 3 A, Rapida 20x5 F4 Alimentare cititoare 3 A, Rapida 20x5

F5 Iesire auxiliara ……… 1 A, Rapida 20x5 F6 Bus date local 3 A, Rapida 20x5

Retea* Siguranta retea 630 mA, 20x5

* Siguranta retea este localizata in conectorul de retea.

Atentie! Inainte de scoaterea sigurantei retea, trebuie deconectata alimentarea de la retea (vezi pagina 4)! !

Page 12: ATS1250 inst rom - ETAS

12 ATS1250/1260 Installation guide

6. Lungimi cabluri De la La Distanta Tip cablu

Centrala ATS bus date sistem (J10)

ATS1250/ATS1260 bus date sistem (J3)

1.5 km (Lungimea totala a bus-ului fara repetoare)

Belden 8723 sau echivalent

Intrfata cititor (J13 – J17) Cititor 75 m In functie de tipul cititorului

Bus date local (J22) RAS, DGP sau cititor 1.5 km Belden 8723 sau echivalent

7. Specificatie terminale externe

Locatie Terminal Descriere Min Tip Max

23 VCA AC Conector pentru secundarul transformatorului 100 VA

13.6 13.8 14.0 VCC

J1

BATT (2 conectori)

Conector acumulator (fiecare) 7.2 Ah

13.6 13.8 14.0 VCC ++ , -- Iesire sursa auxiliara

3 A 13.6 13.8 14.0 VCC SW Iesire sursa …….

1 A Sirena exterioara (speaker) 4 8 Omi

13.6 13.8 14.0 VCC

J2

AUX. POWER

S Sirena exterioara (self-exciting)

3 A

250 VCA C, NO sau NC

Contacte relee usi (fiecare) 2 A

13.6 13.8 14.0 VCC

J4 – J7 RELAY

+12 V Alimentare +12 V pentru relee usi (fiecare) 250 mA

13.6 13.8 14.0 VCC +12 V Alimentare +12 V pentru relee cititoare

(fiecare) 2 A 5 VCC

J13–J17 DOOR

+5 V Alimentare +5 V pentru relee cititoare (fiecare) 0.5 A

14.0 VCC J17 BELL C, NO, NC Contacte relee de joasa tensiune 2 A

13.6 13.8 14.0 VCC J22 COMMS +12 V Alimentare pentru bus-ul local

3 A

+ Nota: Curentul maxim total consumat de iesirile auxiliare (++/-) si de sirena exterioara nu trebuie sa depaseasca 3A.

Page 13: ATS1250 inst rom - ETAS

ATS1250/1260 Installation Guide 13

PROCEDURA DE PORNIRE

Dupa ce s-a finalizat instalarea, verificati adresa modulului la comutatoarele DIP 1-4.

La pornirea initiala, LED-urile DGP-ului 4-usi/4-lifturi trebuie sa arate astfel:

LED 6 Aprins

LED-urile indicatoare pentru bus-ul de date sistem ATS :

Rx0 Palpaie daca ATS1250/1260 primeste date de la centrala ATS Tx0 Stins daca ATS1250/1260 nu este adresat/programat pentru a fi inregistrat de centrala.

LED-urile indicatoare pentru bus-ul de date sistem ATS

4-door/4-lift DGP local databus indicator LEDs:

Tx1 Palpaie cand ATS1250/1260 este conectat pe bus-ul local la dispozitive indepartate (cititoare/interfete); TX1 trebuie sa fie intotdeauna activ.

Rx1 Palpaie daca dispozitivele indepartate raspund la conectare.

DGP-ul 4-usi/4-lifturi se initializeaza numai la prima pornire. Aceasta se face prin optiunea 3 din meniul door/lift data, Initialise database.

ATENTIE! Toate programarile si setarile vor reveni la valorile din initiale. Acestea sunt prezentate in manualul Programming Guide.

ACCESAREA MENIULUI DE PROGRAMARE DOOR/LIFT

1. Acesarea meniul de programare Accesarea meniului de programare Door se face prin Advisor MASTER, Installer menu 28, To remote devices. Cand programati din meniul 4-door, programati modulul ATS1250.

Pentru a avea acces la meniul 4-door prin "To remote devices", ATS1250 trebuie sa fie conectat, adresat si programat pentru conectare. De asemenea DGP-ul trebuie programat “4-door DGP” sau “4-lift DGP” in meniul 4 din Advisor MASTER Installer programing , DGP database.

Daca va este interzis accesul la "To remote devices”, aceasta se poate intampla daca una dintre cerintele hardware sau de programare prezentate mai sus nu au fost indeplinite.

1. Afisajul indica:

Introduceti tipul dispozitivului pe care doriti sa-l programati. Selectati 1 (DGP).

2. Introduceti numarul dispozitivului pe care doriti sa-l programati. Numarul DGP-ului este acelas cu adresa DGP-ulu.

3. Afisajul arata:

4. Acum aveti acces la meniul de programare al modulului ATS1250 pentru modulul ATS1250/1260 selectat. Afisajul va va arata meniul de programare pentru 4-door:

Pentru informatii suplimentare si optiuni disponibile vezi meniul de programare pentru ATS1250/1260.

!

Remote DGP Setup DGP No.:

Connecting… Enter to Abort

“*” –Move On “*” Move Menu

Remote Device: 1-DGP, 2-RAS Device:

Page 14: ATS1250 inst rom - ETAS

14 ATS1250/1260 Installation guide

2. Meniul de programare pentru ATS1250/1260 1. DGP Options Optiuni valide, comune pentru toate usile/lifturile selectate ca DGP-uri 4-usi/4-lifturi.

2. Door Options Optiuni valide pentru fiecare usa sau lift din ATS1250/1260.

3. Initialise Database Permite initializarea bazei de date pentru usi sau lifturi. Reseteaza toate informatiile DGP-ului la valorile initiale.

4. Display Card Afiseaza la LCD detalii despre ultima cartele.

5. Door Groups Permite vizualizarea detaliilor despre grupul de usi.

6. Floor Groups Permite vizualizarea detaliilor despre grupul de etaje.

7. System Options Permite activarea iesirilor ATS1250/1260 pentru indicarea defectiunilor la ATS1250/1260.

8. Program Macro Logic Permite generarea evenimentelor iesiri/interne de catre functii logice, folosind evenimentele ATS1250/1260.

9. Version Number ATS1250/1260 firmware and CPLD version number.

10. To Local Devices Permite accesarea dispozitivelor pe bus-ul local.

3. Secventa de programare DGP-ul 4-usi/4-lifturi, ATS1250/1260, este un panou de control acces versatil ce extinde sistemul Advisor MASTER cu functii avansate de control acces. La programare, este important sa fiti metodici, altfel puteti face greseli.

Setari minime

Setarile minime reprezinta configuratia necesara pentru validarea cartelelor pentru a fi citite si deschiderea usilor la prezentarea unei cartele valide.

1. Setati adresa DGP-ului pentru DGP-ul 4-usi/4-lifturi (1 - 12).

2. Verificati daca memoriile RAM din ATS1250/1260 si centala Advisor MASTER sunt la fel.

3. Setati adresele RAS-urilor (cititoare sau DGP-uri conectate la bus-ul local al DGP-ului 4-usi/4-lifturi.

4. In meniul 19, Installer programming al centralei Advisor MASTER :

• Activati conectarea pentru 4-door/4-lift DGP si setati tipul acestuia.

• Verificati si notati numarul digitilor din prefix (meniul 7, System options).

• In meniul 13. Timezones, programati timpul-zona necesar pentru accesarea functiilor de control acces (Request-to-Exit, Override Timezone si Door groups)

• In meniul 2, Area database, setati ce arie (arii) vor inhiba Request-to-Exit sau vor inhiba accesul la o usa cand aria (ariile) sunt armate.

5. Din meniul 28, To remote devices, selectati tipul 1 (DGP) si apasati [ENTER]. Introduceti adresa DGP-

ului si apasati [ENTER]. Acum sunteti in meniul de programare pentru 4-usi/4-lifturi.

6. Meniul 1, DGP options. Setati sau selectati urmatoarele optiuni:

• Batch Number (intre 1 to 40).

• Alarm Code Prefix Digits (la fel ca in centrala)

• Introduceti RAS-ul conectat pentru inregistrare

• Introduceti RAS-ul LCD conectat

• Setati tipul de zona Dual la fel ca in centrala

• Introduceti Re-lock delay time 7. Meniul 2, Door / Lift options 8. Selectati usa pe care doriti sa o programati. Numai

usile disponibile din DGP-ul selectat pot fi programate.

9. In meniul 4, Reader options.

• Selectati formatul cartelei 10. Apasati [ENTER] pana cand afisajul indica meniul

5. Hardware options. Apasati 0 [ENTER] [ENTER] pentru parasirea meniului 2, Door / Lift options

11. Avansati la meniul 4, Display card, si treceti cateva cartele valide pentru a verifica citirea acestora si numarul acertora va fi afisat.

Pentru mai multe optiuni, vezi Manualul Programming Guide, ATS1250/1260.

Page 15: ATS1250 inst rom - ETAS

ATS1250/1260 Installation Guide 15

MENIURI PROGRAMARE Numerele meniurilor de programare corespund cu numerele capitolelor din manualul de programare (ex. 1. este Capitolul 1).

XX, Output Controllers

Batch Number

XX, Alarm Code Prefix Digits

Poll RAS

RAS's with LCD

RAS's with Request to Exit Enabled

RAS's with Toggle Enabled

DGP's to be Polled

XX, Card to Pin Time

XX, Two Cards Time

XX, Multiple Badge Time

XX, Re-lock Delay Time

XX, Region Count Limit

1. Access Options

1. DGP Options

2. Door Options

XX, Unlock Time

XX, Extended Unlock Time

XX, Shunting

XX, Shunt Time

XX, Extended Shunt Time

XX, Shunt Warning Time

XX, Low Security Timezone

XX, In Reader Card & PIN

XX, Out Reader Card & PIN

XX, In Reader No PIN If TZ

XX, Anti Pass-Back

XX, In Region

XX, Out Region

XX, In Reader Two Cards

XX, Out Reader Two Cards

2. Request to Exit Options XX, RTE Timezone

XX, In RTE Disabled When Armed

XX, Out RTE Disabled When Armed

XX, RTE Times Door Open

XX, RTE Reporting

Select Door x, x, x, x

XX, Shunt Until Door CLosed

XX, Cancel Shunt After Door Secures

XX, Out Reader No PIN If TZ

XX, In Reader Inhibit Region 0 Users

XX, Out Reader Inhibit Region 0 Users

System Code

Start Card Number

Number of Cards

Start User Number

XX, Dual Zone

Page 16: ATS1250 inst rom - ETAS

14 5130 999-1

3. Alarm Control XX, Alarm Group

XX, Reader Has No Alarm Control

XX, Entry Denied if Area Armed

XX, Exit Denied if Area Armed

XX, RAS Number Disabled

5. Hardware Options

6. Lift Options

3. Initialise Database

4. Display Card

5. Door Groups

6. Floor Groups

7. System Options

8. Macro Logic

9. Version Number

4. Reader Options

10. To Local Devices

XX, Card Format

XX, Zone Holds Door Unlocked

XX, Unlock Timezone

XX, Unlock Timezone After Entry

XX, Report when door closed & locked

XX, Report Door Open/Close

XX, Report DOTL

XX, Reader LED Options

XX, Pulsed Lock & Unlock Relays

XX, Time & Attendance Reader

XX, Reader Duress

XX, Door Unlocked Until Door Opens

XX, Report open/unlocked as unlocked

XX, Unlock Relay Number

XX, Zone Number

XX, Forced Output Number

XX, Shunt Zone Number/s

XX, Warning Output Number

XX, DOTL Zone Number

XX, DOTL Output Number

XX, Request to exit Zone Number

XX, Fault Output Number

XX, Interlock Zone Numbers

XX, Ares(s) Assigned to Door

XX, Monitor 2nd Door Zone

XX, Report Forced Door

XX, First Physical Zone

XX, Wait For Floor Selection

XX, Zone Monitor Floor Selected

XX, First Physical Relay

XX,First Floor Number

XX, Last Floor Numbers

XX, Monitor High Level Floor Landing

Floor Landing Floors 33-64

Floor Landing Floors 1-32

XX, Lift Car Number

XX, Lift Bank Number

XX, Total Floors

XX, Lift Security Group number

XX, Lift Override Group

XX, Security Zone Number

Tamper Output Number

Low Battery Output Number

Mains Fail Output Number