G C PROFILE B DETAIL Fibre Cement 1:2.5 @ A4 DATE BGC Stratum™ and Stratum™ Duo (Vertical Installation) SCALE DETAIL NO. Foundation Detail SV-01 paving or 175mm min to unprotected ground 15 50 BGC stratum™ (fixed vertically) with all cut edges sealed before fixing. Durabarrier™ or aproved breather type building underlay. BGC Horizontal cavity batten. 65 x 2.87mm Roundrive ring shank nail fixings (typical). BGC Vermin proof vent strip or similar. Finished ground level. 100mm min to permanent 75 Conncrete Slab or blockwork. Timber bottom plate on D.P.C Timber framing May 2019

Upload: others

Post on 25-Mar-2020

17 views

Category:

Documents


0 download

TRANSCRIPT

GC

PROFILE

B

DETAIL

Fibre Cement

1:2.5 @ A4

DATE

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

SCALE

DETAIL NO.

Foundation Detail

SV-01

paving or 175m

m m

in to

unprotected ground

15

50

BGC stratum™ (fixed vertically) with

all cut edges sealed before fixing.

Durabarrier™ or aproved breather

type building underlay.

BGC Horizontal

cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixings (typical).

BGC Vermin proof

vent strip or similar.

Finished ground

level.

100m

m m

in to perm

anent

75

Conncrete Slab

or blockwork.

Timber bottom

plate on D.P.C

Timber framing

May 2019

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Typical Plank Joint Detail

SV-02

GCB Fibre Cement

300mm (plank width)

276 (effective cover)

50 16

12

6mm continuous bead of Bostik

Seal 'N' Flex FC to plank lap

(typical).

Durabarrier™ or approved

breather type building

underlay.

BGC Horizontal

cavity batten

Timber framing

65 x 2.87mm Roundrive

ring shank nail fixings (to

dwang/nog).

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal

cavity batten

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

May 2019

GCB Fibre Cement

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Internal Corner Detail

SV-03

30

45

BGC Horizontal

cavity batten.

Durabarrier™ or approved breather

type building underlay continuous

around corner.

Timber framing

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

65 x 2.87mm Roundrive ring

shank nail fixing.

6mm continuous bead of Bostik

Seal 'N' Flex FC to plank edges.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing (trimmed edge).

BGC Horizontal

cavity batten

BGC Internal aluminium corner

flashing.

65 x 2.87mm Roundrive ring

shank nail fixing.

Durabarrier™ or approved

breather type building underlay.

Timber framing (as indicated).

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Lap can be removed prior toinstallation if preferred

May 2019

GCB Fibre Cement

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

External Corner Detail

SV-04

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Timber framing

Durabarrier™ or approved breather type

building underlay continuous around corner.

Durabarrier™ or approved

breather type building

underlay.

BGC Horizontal

cavity batten.

45

45

65 x 2.87mm Roundrive ring

shank nail fixing.

6mm continuous bead of

Bostik Seal 'N' Flex FC to both

edges.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing (trimmed edge).

BGC External aluminium

corner flashing.

65 x 2.87mm

Roundrive ring shank

nail fixing.

BGC Horizontal

cavity batten.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

Lap can be removed prior toinstallation if preferred

May 2019

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Window Head Detail

SV-05

GCB Fibre Cement

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

5

g

a

p

Durabarrier™ or approved breather

type building underlay continuous

around corner.

BGC Horizontal cavity

batten.

65 x 2.87mm Roundrive ring

shank nail fixing.

BGC Horizontal cavity

batten

15

10

min.

min.

PC Aluminium head flashing with 15° slope and 20mm

stop ends. Ensure MS Sealant to flange head and head

flashing junction in very high & Extra High Wind Zones

and SD pressure.

PC Aluminium window joinery.

Flashing tape to corners.

Reveal head liner.

Timber framing (as indicated).

Internal wall lining.

Additional layer of flexible

flashing tape or building

underlay lapped over head

flashing.

Air seal over backing rod.

Temporary timber packer

remove after finishing.

7.5m

m m

in

35m

m

flashing

cover

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing (trimmed edge).

BGC Vermin proof vent

strip or similar

May 2019

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Window Jamb Detail

SV-06

GCB Fibre Cement

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

20 10

10mm min. cover to Stratum™ by

window joinery.

20mm min. overhang of

head flashing.

7.5mm min.

Reveal jamb liner

Air seal over backing rod.

H3.1 timber packer

Flexible flashing tape to corners - to

be continuous along sill, 100mm

min. up each jamb and 50mm into

face of building underlay.

Foam seal tightly finished against

Stratum.™

Line of head flashing above.

Internal wall lining.Timber framing (as

indicated).

BGC Horizontal cavity

batten.

Durabarrier or approved

breather type building underlay.

65 x 2.87mm Roundrive ring

shank nail fixing.

BGC Stratum™ (fixed

vertically) with all cut edges

sealed before fixing.

Note -

Continuous bead of

sealant to junction.

**1

**1

May 2019

Window Sill Detail

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

B

SV-07

GC Fibre Cement

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

7.5m

m m

in.

PC Aluminium window

joinery.

.

8mm min. cover to Stratum™ by

window joinery.

BGC 'J' Flashing sealed to top

of Stratum.™

Foam seal tightly finished against

'J' Flashing.

65 x 2.87mm Roundrive ring

shank nail fixing.

BGC Horizontal

cavity batten.

BGC Stratum™ (fixed vertically) with all cut

edges sealed before fixing.

Durabarrier™ or approved breather

type building underlay.

Timber framing (as indicated).

Internal wall lining

Flexible flashing tape wrapped around sill

- to be continuous around sill, 100mm

min. up each jamb and 50mm into face

of building underlay.

Reveal sill liner.

Air seal over backing rod.

H3.1 timber packer.

Sill support bar.

May 2019

812

Timber framing

(as indicated).

Polythene bond breaker

tape.

Durasheet™ soffit lining on

H1.2 framing.

Bostik Safe Seal or similar

BRANZ appraised sealand over

bond breaker.

BGC Stratum™ (fixed vertically) with

all cut edges sealed before fixing.

Durabarrier™ or approved

breather type building

underlay.

H3.1 treated timber

packer - continuous.

Nog / dwang - offset to

block airflow into roof

space.

65 x 2.87mm Roundrive ring

shank nail-fixing.

PROFILE

DETAIL

1:2.5 @ A4

DATE

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

SCALE

DETAIL NO.

Soffit Detail

SV-08

GCB Fibre Cement

May 2019

Profiled H3.1 Scotia by others.

(optional)

GCB

PROFILE

Fibre Cement

DETAIL

1:2.5 @ A4

DATE

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

SCALE

DETAIL NO.

Inter-storey Drainage Detail

SV-09

5

15

35

35

12

min cover

min cover

Durabarrier™ or approved

breather type building underlay.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal

cavity batten.

BGC Vermin proof vent strip or

similar (set to provide 15mm min

drop edge to cladding).

Custom made aluminium

inter-storey "z' flashing with

15° slope.

BGC Horizontal

cavity batten.

65 x 2.87mm Roundrive ring

shank nail-fixing.

65 x 2.87mm Roundrive ring

shank nail-fixing.

BGC Stratum™ (fixed vertically) with

all cut edges sealed before fixing.

Durabarrier™ or approved

breather type building underlay.

Flexible flashing tape or building

underlay lapped over flashing

upstand.

Mid floor flooring

- finish 10mm back from

external wall framing.

Timber framing (as indicated).

Timber framing (as indicated).

Mid floor structure

May 2019

BGC Stratum™ (fixed vertically) with

all cut edges sealed before fixing.

Durabarrier™ or approved

breather type building underlay.

Nog / dwang

GCB Fibre Cement

1:2 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Plank Joint Detail (Longitudinal)

SV-10

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

12

12

65 x 2.87mm Roundrive ring

shank nail fixing.

BGC Horizontal

cavity batten

65 x 2.87mm Roundrive ring

shank nail fixing.

BGC Stratum™ (fixed vertically) with

all cut edges sealed before fixing.

20°-45° end cuts, ensure primed or

sealed prior to adhering with Bostik

Seal 'N' Flex FC

May 2019

100m

m m

in

Enclosed deck

structure

15

mem

brane upstand

Floor structure

150m

m

Cavity Batten Note:

Refer to cavity batten layout

for batten sizes, types,

spacing's & fixings.

50m

m m

in

50m

m

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Enclosed Deck Detail

Cavity ConstructionSV-11

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

Durabarrier™ or approved

breather type building

underlay.

Timber Bottom plate

on D.P.C (concrete

floor only)

Continuous Vermin proof

BGC vent strip or similar.

Water proof decking

membrane to carry up

behind building wrap past

wall framing bottom plate.

Corner

fillet

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Window Head/Jamb Junction Detail

Cavity ConstructionSV-12

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Note where Durabarrier™ is used

flashing tape must be applied to the

entire opening

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

Fold ends of head flashing

to form stop ends

Flashing tape over wall

underlay fitted around

corner as shown

Durabarrier™ or

approved breather type

Building underlay with

flexible flashing tape to

corners.

BGC Stratum™ (fixed

vertically) with all cut

edges sealed before fixing.

Flashing tape over

flashing (alternatively

use extra layer of wall

underlay)

BGC Horizontal

cavity Batten.

Timber Lintel.

Vermin Proof BGC

20mm Vent strip

Head flashing with 15°

min slope 5mm min gap

below BGC Stratum™

Timber framing.

H3.1 treated

SG8 timber

cavity batten

Cut head flashing to continue

past window opening

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Window Sill/Jamb Junction Detail

Cavity ConstructionSV-13

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

50m

m m

in lap

5

0

m

m

m

i

n

l

a

p

Note where Durabarrier™ is used

flashing tape must be applied to the

entire opening

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

100m

m m

in lap

Flashing tape over

wall underlay full

width of opening.

Sill support bar

BGC Horizontal cavity batten.

BGC Stratum™ (fixed

vertically)with all cut

edges sealed before

fixing.

Durabarrier™ or approved

breather type building

underlay.

H3.1 treated SG8

timber cavity batten.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Eaves With No Soffit Detail

Cavity ConstructionSV-15

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

50mm

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

Roofing underlay draining into spouting.

Min over hang of roofing beyond fascia.

Eaves flashing as required in accordance

with NZBC Acceptable Solution E2/AS1

Fig 45 by roofer.

Ensure that Stratum™ projects

above top of fascia.

Spouting.

H3.2 timber fascia of width to suit

spouting brackets and falls by others.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

Durabarrier™ or approved

breather type building

underlay.

Internal linings.

Solid blocking.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Meter Box Head Detail

Cavity ConstructionSV-16

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

35mm Min upstand

to head flashing

35

10

5

15

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

Note. Where Durabarrier™ is used

flashing tape must be applied to the

entire opening

Timber framing

7.5m

m M

in.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

Continuous Vermin proof

BGC vent strip or similar.

15mm min overhang.

5mm min gap.

10mm min flashing cover.

Meter box by others.

Colorsteel head flashing

with 15° fall & 20mm stop

ends.

Aluminium angle to be continuous

around meter box. Screw fix and

seal.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

Durabarrier™ or approved

breather type building

underlay. dressed into

opening with flexible

flashing tape to corners.

Air seal over PEF rod.

H3.1 timber packer.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Meter Box Jamb Detail

Cavity ConstructionSV-17

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

20

10 min cover

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

Note. Where Durabarrier™ is used

flashing tape must be applied to the

entire opening

7.5mm Min.

Durabarrier™ or approved

breather type building

underlay. dressed into

opening with flexible

flashing tape to corners.

BGC Stratum™ (fixed

vertically) with all cut

edges sealed before

fixing.

Head flashing to extend

20mm min past meter box

angle.

Continuous sealant over

bond breaker to extend to

top of angle.

Optional 40 x 18 H3.2

precut timber scriber.

Meter box by others.

Line of head flashing over.

Aluminium angle to be continuous

around meter box. Screw fix and

seal.

H3.1 timber packer.

Air seal over PEF rod.

Timber framing.

BGC Horizontal cavity batten.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Meter Box Sill Detail

Cavity ConstructionSV-18

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

10 M

in.

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

Note. Where Durabarrier™ is used

flashing tape must be applied to the

entire opening

7.5m

m M

in.

Durabarrier™ or approved

breather type building

underlay. dressed into

opening with flexible

flashing tape to corners.

Continue wall underlay

around framing.

Meter box by others.

Air seal over PEF rod.

H3.1 timber packer.

Aluminium angle to be continuous

around meter box. Screw fix and

seal.

10mm min cover of Stratum™

to metal angle.

Wall underlay and

flexible flashing tape.

Continuous sealant over

bond breaker.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Enclosed Balustrade-Wall Junction 3D

Cavity ConstructionSV-19

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

1

0

0

m

m

m

i

n

50mm min

5° min

slope

5

0

m

m

m

i

n

SADDLE FLASHING

5° min

slope

FLEXIBLE FLASHING INSTALLATION

Timber framing.

Flexible flashing tape

dressed up and securely

adhered to building

underlay at rear of

cavity.

Flexible flashing tape

dressed min 50mm

down face of battens.

Flashing tape continuous

around corner over building

underlay (100mm wide

each side)

BGC Horizontal cavity

batten.

BGC Stratum™ (fixed

vertically)with all cut

edges sealed before

fixing.

BGC Horizontal cavity

batten

BGC Stratum™ (fixed

vertically) with cut edges

sealed before fixing.

Lower edge of cladding.

Rivet through sealant.

Capping flashing.

Flashing tape to separate

metal capping and treated

timber packer.

Timber framing.

Durabarrier™ or approved

breather type building

underlay.

Timber framing.

Durabarrier™ or approved

breather type building

underlay.

Saddle flashing

behind cladding.

Two lines of sealant to

capping and flashing.

BGC Internal aluminum

corner flashing behind

saddle flashing and

cladding.

Battens behind

saddle flashing

and cladding.

Two lines of

sealant to

capping and

flashing.

H3.1 treated SG8 timber

cavty batten set 40mm

back from corner.

Sloped packer to extend

across cavity at wall

junction.

Durabarrier™ or approved

breather type building

underlay.

6mm continuous bead

of Bostik Seal 'N' Flex

FC to plank edges.

May 2019

BGC Horizontal cavity batten.

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Enclosed Balustrade/Parapet Detail

Cavity ConstructionSV-20

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Z

Z

Note:

Z = Refer to NZBC E2 / AS1 Table 7 for flashing cover requirements

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

Flashing tape continuous around top of

framing over building underlay.

Sloping H3.1 treated timber

packer to form min 5°

slope.

Metal flashing with 5°

slope on flashing tape or

roof underlay to separate

metal capping and

treated timber packer. Fix

through sides only.

Metal flashing to have birds

beak fold if used as inside

face for enclosed decks.

Durabarrier™ or approved

breather type buidling

underlay.

H3.1 timber framing

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Enclosed Balustrade-Wall Junction Detail

Cavity ConstructionSV-21

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

150mm minimum to face

of window or door jamb stud

40mm min

BGC internal aluminium

corner flashing.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC horizontal cavity batten.

6mm continuous bead of Bostik

Seal 'N' Flex FC to plank edges

30

45

BGC horizontal cavity batten.

Line of sloping H3.1 treated

packer above show dashed.

Durabarrier™ or approved

breather type building underlay.

Flashing tape continuous

around corner over building

underlay (100mm each

side).

65x2.8mm Roundrive ring shank galv nail.

Timber framing as indicated.

Lap can be removed prior toinstallation if preferred

May 2019

Lap can be removed prior to

installation if preferred

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Gutter to Wall Junction

Cavity ConstructionSV-22

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

f

a

l

l

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

BGC horizontal cavity batten

BGC Verimn proof vent

strip or similar.

Durabarrier™ or approved

breather type building underlay.

BGC Stratum™ (fixed Vertically)

with all cut edges sealed before

fixing.

Flexible flashing tape lapped

over apron flashing upstand.

Parallel apron flashing to

extend over two crests.

Parallel apron flashing

with stop end to deflect

water into gutter.

Transition tray flashing

to underside of roofing

in accordance with

NZBC E2/AS1.

External gutter to

be kept 10mm

clear of cladding.

Fascia with

transition tray

flashing.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Parallel Apron Flashing Detail

Cavity ConstructionSV-23

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

35

mm

min

110m

m

75m

m

Note:

x = Refer to NZBC E2 / AS1 Table for

flashing cover requirements

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

x

15m

m

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

5mm max gap for

notched down turn.

110mm upstand flashing

with 10mm hem & cover

of two crests.

Vermin proof BGC

continuous vent

strip.

Durabarrier™ or approved

breather type building

underlay or flexible

flashing tape lapped over

apron flashing.

Support nog

Timber framing

Underlay carried up face of

framing behind upstand

flashing.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Transverse Apron Flashing Detail

Cavity ConstructionSV-24

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

x

125m

m

35m

m

min

Note:

x = Refer to NZBC E2 / AS1 Table for

flashing cover requirements

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

15

75m

m

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

Vermin proof BGC

continuous vent

strip.

Apron flashing 125mm upstand

flashing with hem.

Selected roofing material with upturn.

Roof framing.

Durabarrier™ or approved

breather type building

underlay or flexible flashing

tape lapped over apron

flashing.

Support nog

Timber framing

Underlay carried up face of

framing behind upstand

flashing.

May 2019

GCB Fibre Cement

1:5 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Pipe Penetration Detail

Cavity ConstructionSV-25

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Cavity Batten Note:

Refer to cavity batten

layout for batten sizes,

types, spacing's & fixings

Cladding fixing note:

Refer to cladding fixing

layout for all fixing types

& spacing's

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Stratum™ (fixed vertically)

with all cut edges sealed before

fixing.

BGC Horizontal cavity batten.

65 x 2.87mm Roundrive ring

shank nail fixing (typical).

Flexible flashing tape adhering around pipe

and onto building underlay (100mm lap to

underlay and 25mm to pipe)

Pipe with 5° slope.

Sealant with backing rod.

Flange to protect sealant

from exposure to sunlight.

Durabarrier™ or approved

breather type building

underlay.

Air seal all round

Where possible,

provide outwards fall

to pipework for

water run-off.

Air seal all round

Solid backing around

pipe penetration.

May 2019

GCB Fibre Cement

1:25 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Batten Layout - Elevation

SV-GA1

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

600

600

600

600

Max. nog / dw

ang spacings.

Inter-storey

Door

Window Opening

External

Corner

Typ. Plank Joint

Foundation

Internal

Corner

SoffitSV08

SV03

SV02

SV06

SV05

SV01

SV07

SV04

SV09

(over framing)

GCB Fibre Cement

1:25 @ A4

DATE

SCALE

DETAIL NO.

PROFILE

DETAIL

Plank Layout - Elevation

SV-GA2

BGC Stratum™ and Stratum™ Duo

(Vertical Installation)

Inter-storey

Door

Window Opening

External

Corner

Typ. Plank Joint

Foundation

Internal

Corner

Soffit

Longitudinal

Joint

SV08

SV03

SV02

SV06

SV05

SV01

SV07

SV10

SV04

SV09

(over framing and battens)

May 2019