Product Information Additional Resources: 1) Go to http://www.rockwellautomation.com/literature; 2) Go to Search, select Publication Number. Type in: 193-UM002 or 193-QR003 ATTENTION: Do not install, configure, operate or maintain this product until you have read the product documentation and the documents in the Additional Resources section for installing, configuring, operating or maintaining equipment. To get the product documentation go to http://www.rockwellautomation.com/literature or contact your local sales office or Rockwell Automation representative. ATTENTION: Ne pas installer, configurer, exploiter ou maintenir ce produit tant que vous n’avez pas lu sa documentation et les documents de la rubrique Documents connexes pour l’installation, la configuration, l’exploitation et la maintenance de l’équipement. Pour obtenir de la documentation, rendez-vous sur le site http://www.rockwellautomation.com/literature ou contactez votre agence commerciale Rockwell Automation locale ou son représentant. ACHTUNG: Für die Installation, Konfiguration, den Betrieb und die Wartung dieses Produkt lesen Sie sich bitte zunächst die Produktdokumentation sowie die Dokumente im Abschnitt „Weitere Informationen“ durch. Die entsprechende Produktdokumentation finden Sie unter http://www.rockwellautomation.com/literature oder kontaktieren Sie Ihr lokales Vertriebsbüro bzw. einen Rockwell Automation-Mitarbeiter. ATENCIÓN: No instale, configure, opere ni mantenga este producto hasta que haya leído la documentación del producto y los documentos en la sección Recursos adicionales para la instalación, configuración, operación o mantenimiento de equipo. Para conseguir la documentación, diríjase a http://www.rockwellautomation.com/literature o póngase en contacto con su oficina regional de ventas o representante de Rockwell Automation. ATENÇÃO: Não instale, configure, opere ou mantenha este produto até que você leia a documentação do produto e os documentos na seção Recursos adicionais para a instalação, configuração, operação ou manutenção do equipamento. Para conseguir a documentação, visite http://www.rockwellautomation.com/literature ou entre em contato con seu escritório de vendas regional ou representante da Rockwell Automation. ATTENZIONE: Non installare, configurare, attivare o riparare questo prodotto senza avere prima letto la relativa documentazione nonchè i documenti indicati nella sezione Ulteriori Risore riguardanti l’installazione, la configurazione, l’attivazione o la riparazione dell’apparecchiatura. Per la documentazione sul prodotto visitare il sito http://www.rockwellautomation.com/literature o contattare l’ufficio vendite o il rappresentate Rockwell Automation di zona. WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants. Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product. Terminal Designations Figure 1 - E3 and E3 Plus Feature Overview E3 PLUS S1 S2 13 14 23 24 95 96 1T1 1T2 1 2 3 4 5 6 NETWORK STATUS OUT A IN 1 IN 2 OUT B IN 3 IN 4 MSD LSD TRIP WARN TEST/ RESET D S/N FRN 4.XXX 1AOXXXXX XXX SER Test/Reset Button Voltage Input Module Connection (193/592 EC5 only) Ground Fault Sensor Input Output & PTC Terminals NOTE: On model EC5 devices, terminals 1T1 and 1T2 are marked 7 and 8, respectively. LED Status Indicators Node Address Switches (series B and later) DeviceNet Port Input Terminals Bulletin 193 / 592 E3 and E3 Plus Solid State Overload Relay (Cat 193-EC_ _ _; 592-EC_ _ _)

Upload: others

Post on 17-Apr-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Bul 193 / 592 E3 and E3 Plus Solid State Overload Relay...Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and 193/592-EC3). Available only on cat

Product Information

Additional Resources:1) Go to http://www.rockwellautomation.com/literature; 2) Go to Search, select Publication Number. Type in: 193-UM002 or 193-QR003

ATTENTION: Do not install, configure, operate or maintain this product until you have read the product documentation and the documents in the Additional Resources section for installing, configuring, operating or maintaining

equipment. To get the product documentation go to http://www.rockwellautomation.com/literature or contact your local sales office or Rockwell Automation representative.

ATTENTION: Ne pas installer, configurer, exploiter ou maintenir ce produit tant que vous n’avez pas lu sa documentation et les documents de la rubrique Documents connexes pour l’installation, la configuration, l’exploitation et la

maintenance de l’équipement. Pour obtenir de la documentation, rendez-vous sur le site http://www.rockwellautomation.com/literature ou contactez votre agence commerciale Rockwell Automation locale ou son représentant.

ACHTUNG: Für die Installation, Konfiguration, den Betrieb und die Wartung dieses Produkt lesen Sie sich bitte zunächst die Produktdokumentation sowie die Dokumente im Abschnitt „Weitere Informationen“ durch. Die

entsprechende Produktdokumentation finden Sie unter http://www.rockwellautomation.com/literature oder kontaktieren Sie Ihr lokales Vertriebsbüro bzw. einen Rockwell Automation-Mitarbeiter.

ATENCIÓN: No instale, configure, opere ni mantenga este producto hasta que haya leído la documentación del producto y los documentos en la sección Recursos adicionales para la instalación, configuración, operación o

mantenimiento de equipo. Para conseguir la documentación, diríjase a http://www.rockwellautomation.com/literature o póngase en contacto con su oficina regional de ventas o representante de Rockwell Automation.

ATENÇÃO: Não instale, configure, opere ou mantenha este produto até que você leia a documentação do produto e os documentos na seção Recursos adicionais para a instalação, configuração, operação ou manutenção do

equipamento. Para conseguir a documentação, visite http://www.rockwellautomation.com/literature ou entre em contato con seu escritório de vendas regional ou representante da Rockwell Automation.

ATTENZIONE: Non installare, configurare, attivare o riparare questo prodotto senza avere prima letto la relativa documentazione nonchè i documenti indicati nella sezione Ulteriori Risore riguardanti l’installazione, la configurazione,

l’attivazione o la riparazione dell’apparecchiatura. Per la documentazione sul prodotto visitare il sito http://www.rockwellautomation.com/literature o contattare l’ufficio vendite o il rappresentate Rockwell Automation di zona.

WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.

Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or

damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.

Terminal Designations

Figure 1 - E3 and E3 Plus Feature Overview

E3 PLUS

S1

S2

13 14 23 24 95 96 1T1 1T2

1 2 3 4 5 6

NETWORKSTATUS

OUT A

IN 1

IN 2

OUT B

IN 3

IN 4MSD

LSD

TRIPWARN

TEST/RESET

D S/NFRN 4.XXX

1AOXXXXX XXX

SER

Test/Reset Button

Voltage Input ModuleConnection(193/592 EC5 only)

Ground FaultSensor Input

Output & PTC Terminals

NOTE: On model EC5 devices,terminals 1T1 and 1T2 aremarked 7 and 8, respectively.

LED StatusIndicators

Node Address Switches(series B and later)

DeviceNet Port

InputTerminals

Bulletin 193 / 592 E3 and E3 Plus Solid State Overload Relay(Cat 193-EC_ _ _; 592-EC_ _ _)

Page 2: Bul 193 / 592 E3 and E3 Plus Solid State Overload Relay...Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and 193/592-EC3). Available only on cat

Control Terminals

The following table defines the E3 Overload Relay control terminaldesignations.

� Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and 193/592-EC3).

� Available only on cat. nos. 193/592-EC5_ _.

� An earth ground connection to this terminal will assist in obtaining compliance with electromagnetic compatibility requirements.

� The use of shielded cable is recommended for the positive PTC thermistor circuit to assist in obtaining compliance with electromagnetic compatibility requirements.

� Available only on cat. nos. 193/592-EC3_ _ and 193/592-EC4_ _.

DeviceNet Terminals

The following table defines the DeviceNet connector terminal designations.

Table 1 - Control Terminal Designation

Terminal

Designation

Reference Description

1 IN 1 General-purpose sinking input number 1

2 IN 2 General-purpose sinking input number 23 IN 3 General-purpose sinking input number 3 ��4 IN 4 General-purpose sinking input number 4 �� 5 V+

+24V DC supply for inputs6 V+7 IN 5 General-purpose sinking input number 5 � 8 IN 6 General-purpose sinking input number 6 �

End Earth Ground �

13/14 OUT A Output A23/24 OUT B Output B �� 95/96 Trip Relay Trip Relay

1T1/1T2 PTC Thermistor (PTC) input �� S1/S2 -- External ground fault sensor input ��

Table 2 - DeviceNet Terminal Designation

Terminal Signal Function Color

BlackCommonV-1

BlueSignal Low

Signal High

CAN_L2

Non-insulatedShieldDrain3

WhiteCAN_H4

RedPower SupplyV+5

Grounding

The following grounding recommendations are provided to ensure electromagnetic compatibility compliance during installation:

· The earth ground terminal of the E3 Overload Relay shall be connected to a solid earth ground via a low-impedance connection.

· Installations employing an external ground fault sensor shall ground the cable shield at the sensor with no connection made at the E3 PlusOverload Relay.

· The PTC thermistor cable shield shall be grounded at the E3 Plus Overload Relay with no connection made at the opposite end.

Wiring Diagrams

WARNING: When working on energized circuits, do not rely on the voltage and current information provided by the E3 and E3 Plus for personal safety. Always

use a portable voltage or current measurement device and measure the signal locally.

Bulletin 193 / 592 E3 and E3 Plus Solid State Overload Relay2

Publication 193-IN055A-EN-P - May 2012 PN-154492 DIR 10000279804 (Version 00)

Figure 2 - Three-Phase D.O.L &

Single-Phase Wiring Diagrams

E3/E3 PlusE3/E3 Plus

L1 L2L1 L3L2

2/T1 6/T3

MM

S.C.P.D.

Single-Phase Full-VoltageThree-Phase Direct-On-Line

T 2T 2T 3

T 1T 1

L 2 L 3L 1Voltage Input Module

(For 193/592-EC5 only)

L 2L 1Voltage Input Module

(For 193/592-EC5 only)4/T22/T1 6/T34/T2

Page 3: Bul 193 / 592 E3 and E3 Plus Solid State Overload Relay...Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and 193/592-EC3). Available only on cat

Short Circuit Ratings

Table 3 - Standard Fault Short-Circuit Ratings

per UL 508 and CSA 22.2, No. 14

Max. Available

Fault Current [A]

Cat. No.

5000193-EC_B, 592EC_T

193-EC_D, 592EC_C

193-EC_E, 592EC_D

193-EC_F

193-EC_G

193-EC_H

193-EC_Z

600

5000

10000

10000

18000

42000

5000

Table 4 - High Fault Short-Circuit Ratings per UL 508 and CSA 22.2,

No. 14 with Bulletin 100-C and 100-D contactors

Cat. No Max. Available

Fault Current [A]

Max.

Voltage [V]

Max. Class J or

CC Fuse [A]

193-EC1193-EC2193-EC3193-EC4193-EC5

_B

100-C09

100-C12

100-C16

100-C23

100-C30

100-C37

100-C43

100-C60

100-C72

100-C85

100-D95

100-D110

100-D140

100-D180

100-D210

100-D250

100-D300

100-D210

100-D250

100-D300

100-D300

100-D420

9

12

16

100000 600

20

20

30

30

50

50

70

80

100

150

200

200

250

300

400

400

500

400

400

500

500

600

23

_D

30

37

43

60

72

85

95

110

140

180

210

250

300

210

250

300

300

420

_E

FF, ZZ

FF, ZZ

FF, ZZ

GG, ZZ

GG, ZZ

HG, ZZ

JG, ZZ

Max. Starter

FLC [A]

Contactor

Table 5 - IFC Short-Circuit Ratings per EN60947-4-1

Cat. No.

Cat. No.

Contactor

Size

Max.

Voltage [V]

Max.

Voltage [V]

193-EC_B, 592EC_T

100000

193-EC_D, 592EC_C

193-EC_E, 592EC_D

193-EC_F

193-EC_G

193-EC_H

193-EC_Z

1000

3000

5000

00 100000 600

10000

18000

30000

1000

690

Prospective

Short-Circuit

Current Ir [A]

Conditional

Short-Circuit

Current Iq [A]

Table 6 - High Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14

with NEMA contactors

Max. Available

Fault Current [A]

Max.

Voltage [V]

Circuit Breaker/

Limiter

Max. UL Fuse [A]

R J

592-EC1592-EC2592-EC3592-EC5

---- ----20

600 30 ----30

600 30 ----50

480 60 ----100

600 60 ----100

240 100 200

_T

0 100000_C

1 100000_C

2 100000_C

3 100000_D

240 30 FDB 3025/LFB3070R30

240 60 FDB 3050/LFB3035R100

480 30 FDB 3050/LFB3035R

FDB 3100/LFB3150R

240 200 350 FDB 3150/LFB3150R

480 100 200 FDB 3125/LFB3150R

600 100 200 FDB 3100/LFB3150R

50

480 30 FDB 3025/LFB3070R30

3Bulletin 193 / 592 E3 and E3 Plus Solid State Overload Relay

Publication 193-IN055A-EN-P - May 2012 PN-154492 DIR 10000279804 (Version 00)

Page 4: Bul 193 / 592 E3 and E3 Plus Solid State Overload Relay...Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and 193/592-EC3). Available only on cat

PN-154492DIR 10000279804 (Version 00)

Copyright © 2012 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

Publication 193-IN055A-EN-P - May 2012

Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Fuse Coordination

Cat. No Conditional

Short-Circuit

Current Iq [A]

Prospective

Short-Circuit

Current Ir [A]

Max.

Voltage [V]

Type I

with Class J

Fuse [A]

193-EC1193-EC2193-EC3193-EC4193-EC5

_B 1000

3000

5000

10000

100-C09

100-C12

100-C16

100-C23

100-C30

100-C37

100-C43

100-C60

100-C72

100-C85

100-D95

100-D110

100-D140

100-D180

100-D210

100-D250

100-D300

100-D210

100-D250

100-D300

100-D300

100-D420

9

12

16

100000 600

20

20

30

40

50

50

70

80

100

150

200

200

250

300

400

400

500

400

400

500

500

600

Type II

with Class J

Fuse [A]

15

20

30

40

50

50

70

80

100

150

200

200

250

300

400

400

500

400

400

500

500

600

23

_D

30

37

43

60

72

85

95

110

140

180

210

250

300

210

250

300

300

420

_E

FF, ZZ

FF, ZZ

FF, ZZ

GG, ZZ

GG, ZZ

HG, ZZ

JG, ZZ

Max. Starter

FLC [A]

Contactor

Cat. No Conditional

Short-Circuit

Current Iq [A]

Prospective

Short-Circuit

Current Ir [A]

Max.

Voltage [V] Type I

with Class J

Fuse [A]

592-EC_T 1000

3000

00

0,1592-EC_C

592-EC_C

592-EC_D

2

3

9

18, 27

45600

20

30

60

Type II

with Class J

Fuse [A]

20

30

60

200

100000

20090

3000

5000

Max. Starter

FLC [A]

Contactor

Size

Table 7 - IEC Type 1 and Type II Fuse Coordination with Bulletin 100-C and 100-D Contactors per EN60947-4-1

Table 8 - Type 1 and Type II Fuse Coordination with NEMA Contactors

Page 5: Bul 193 / 592 E3 and E3 Plus Solid State Overload Relay...Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2 and 193/592-EC3). Available only on cat

CONFIDENTIAL AND PROPRIETARY INFORMATION. THIS DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF

ROCKWELL AUTOMATION, INC. AND MAY NOT BE USED, COPIED OR DISCLOSED TO OTHERS, EXCEPT WITH THE AUTHORIZED WRITTEN

PERMISSION OF ROCKWELL AUTOMATION, INC.

Sheet

Size Ver

Of 11

A 001000021660Dr. DateG. USHAKOW 2-10-10

SPECIFICATIONS FOR4 PAGE INSTRUCTION SHEET8-1/2” W x 5-1/2” H - FINAL FOLD

MATERIALSIZE

FOLD

TWO SIDES PRINTEDBODY STOCK WHITE

BODY INK BLACK8-1/2" W x 5-1/2" H

FLAT

17" W x 11" H

8-1/2"

PAGE 2

PAGE 1

11"

8-1/2"

PAGE 3

PAGE 4

Page Layout

Note: After folding---Printed in (Country where printed)* and instruction sheet number in lower left corner should be visible.

* The printing vendor may change the instruction sheet files to show the correct country.

Final Fold

5-1/2”

8-1/2”

PN-12345DIR 100000000 (Version 00)Printed in U.S.A.