cable spreading room (csr) sprinkler system.fixed, sprinkler system will provide protection...
TRANSCRIPT
![Page 1: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/1.jpg)
Progress Energy 2/25/2003 1
i
![Page 2: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/2.jpg)
Agenda- -.
* Introduction
* Presentation
David Hinds
o Licensing Basis Lenny Belier
o Present Concern Roger
Rogero Resolution
* Conclusion
Sims Sims
David Hinds
SlProgress Energy 2
2/25/2003
EZZ
![Page 3: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/3.jpg)
Licensing Bases i March 1981: Exemption Requested for
Automatic Suppression in Control Room (CR)and CSRs
* November 1981: Exemption Granted for CRo CSR Addressed Separately
* July 1982: NRC-CP&L Meeting
9 November 1982: NRC Denied ExemptionRequest
SsProgress Energy 32/25/2003
![Page 4: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/4.jpg)
Licensing Bases
e May 1983 Exemption Request o "We propose the installation of a manually
operated, fixed sprinkler system located below the cable trays for these zones. The suppression systems will be designed to extinguish a transient combustible fire. We believe the proposed manually operated, fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R."
C Progress Energy 2/25/2003 4
![Page 5: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/5.jpg)
Licensing Bases
* July 1983 SER o "However, you have proposed to install a manually
operated sprinkler system in the cable spreading room of each Brunswick unit. This type of fixed fire suppression meets the requirements of Section III.G.3 and therefore, an exemption is not needed.... Based on this discussion, we understand that you will begin modification of the Diesel Generator Building equipment hatches and the installation of fixed floor-mounted suppression systems in the Cable Spreading Rooms within six months."
SvProgress Energy 2/25/2003 5
![Page 6: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/6.jpg)
Licensing Bases
. Resident Inspector ConsideredConfiguration a Risk Concern
* Task Interface Agreement Sent to NRC Headquarters
* Violation Proposed Against GDC 3
Progress Energy 62/25/2003
![Page 7: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/7.jpg)
Present Concern - Initial Response
. Technical Study Performedi Correlated Sprinkler
Damage TimeResponse Vs. Cable
* Due to Lack of Validated Analysis Study Assumed Sprinkler System Actuate for Fire between Heads.
D Resident Inspector Provided a [ of Study
Method Would Not
Draft Copy
SJProgress Energy 72/25/2003
I-
![Page 8: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/8.jpg)
Plan View
Sprinkler Heads
SJProgress Energy 82/25/2003
ISO=Islam
![Page 9: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/9.jpg)
Section ViewN a- m,, - -.
TraysPlume
y _-------Sprinkler Head
Fire
Progress Energy 92/25/2003
![Page 10: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/10.jpg)
Present Concern - Study Results
o 146 kW FireP No Cable Damage in 30 Minutes
o639 SCi
o783
kW Fire tble Damage in 30 Minutes
kW FireI Cable
9 In NoDamage in
Cases20 Minutes
Were both TrainsDamaged Due to a Single Fire
Progress Energy 102/25/2003
47,
8
![Page 11: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/11.jpg)
Present Concern
* 10/2/02 NRC Inspection Report 02-03 o The licensee failed to install fixed fire suppression
systems that were capable of minimizing damage to safe shutdown cabling caused by floor level transient combustible fires in the Unit 1 and Unit 2 Cable Spreading Rooms (CSRs). The systems were determined to be unable to fulfill their intended function of limiting fire damage to the preferred trains of safe shutdown cables and safety-related cables in the CSRs.
SProgress Energy 2/25/2003 11
![Page 12: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/12.jpg)
Alternatives for ResolutionEZZ.
* Install C System
,ode Compliant Sprinklerabove and within Cable Trays
Code )ssible
o May Not Satisfy FSAR Commitment
8 Progress Energy 2/25/2003 12
SSprinkler Contractor Stated Compliance May Not Be Pc
![Page 13: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/13.jpg)
Alternatives for Resolution
* Remove Sprinkler Links o System Will Not Support All Heads Flowing
Hydraulically
Drainage Is a Problem
Progress Energy 132/25/2003
rzzz
I
![Page 14: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/14.jpg)
Alternatives for Resolution
. Strengthen Other Areas of Defense-In-Depth P Requires NRC Approval
o No Physical Changes to Sprinkler System
Progress Energy 142/25/2003
![Page 15: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/15.jpg)
Resolution- 1,. - 4.....�
"* Restrict Transient Combustibles below that Analyzed as Capable of Causing Cable Damage
"* Install Incipient Fire Detection System
"* Convert System from Manual to Automatic
. Submit Change to Licensing BasisRemove Term "and Extinguish"
Progress Energy 152/25/2003
LITI
to
![Page 16: Cable Spreading Room (CSR) Sprinkler System.fixed, sprinkler system will provide protection equivalent to Section IiI.G.3, 1 OCFR50, Appendix R." C Progress Energy 2/25/2003 4 Licensing](https://reader036.vdocument.in/reader036/viewer/2022063008/5fbd10c6e31e2d208b1c9b9a/html5/thumbnails/16.jpg)
Conclusions77-E
. Questions?
SJProgress Energy 162/25/2003