chapter 4 pv-upqc based harmonics...

39
66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic controllers behave as nonlinear load and cause serious distortion in the distribution system and introduce unwanted harmonics in the system, leading to decreased efficiency of the power system network and equipment connected in the network. To meet the requirements of harmonic reduction, passive and active power filters are being used in combination with the conventional converters. Presently, active power filters are becoming more affordable due to cost reductions in power semiconductor devices, their auxiliary parts and integrated digital control circuits. Resent research focuses on use of the UPQC to compensate for power-quality problems. The performance of UPQC mainly depends upon how accurately and quickly reference signals are derived. After efficient extraction of the distorted signal, a suitable dc-link current regulator is used to derive the actual reference signals. Various control approaches, such as the PI, sliding-mode, predictive, unified constant frequency (UCF) controllers are in use. Modern control theory-based controllers are state feedback controllers, self-tuning controllers and model reference adaptive controllers. These controllers also need mathematical models and are therefore sensitive to parameter variations. In recent years, a major effort has been underway to develop new and unconventional control techniques that can often augment or replace conventional control techniques. A number of unconventional control techniques have evolved, offering

Upload: ngomien

Post on 01-Sep-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

66

CHAPTER 4

PV-UPQC BASED HARMONICS REDUCTION IN POWER

DISTRIBUTION SYSTEMS

INTRODUCTION

The use of electronic controllers in the electric power supply system

has become very common. These electronic controllers behave as nonlinear

load and cause serious distortion in the distribution system and introduce

unwanted harmonics in the system, leading to decreased efficiency of the

power system network and equipment connected in the network. To meet

the requirements of harmonic reduction, passive and active power filters

are being used in combination with the conventional converters. Presently,

active power filters are becoming more affordable due to cost reductions in

power semiconductor devices, their auxiliary parts and integrated digital

control circuits. Resent research focuses on use of the UPQC to

compensate for power-quality problems. The performance of UPQC

mainly depends upon how accurately and quickly reference signals are

derived. After efficient extraction of the distorted signal, a suitable dc-link

current regulator is used to derive the actual reference signals. Various

control approaches, such as the PI, sliding-mode, predictive, unified

constant frequency (UCF) controllers are in use.

Modern control theory-based controllers are state feedback

controllers, self-tuning controllers and model reference adaptive

controllers. These controllers also need mathematical models and are

therefore sensitive to parameter variations. In recent years, a major effort

has been underway to develop new and unconventional control techniques

that can often augment or replace conventional control techniques. A

number of unconventional control techniques have evolved, offering

67

solutions to many difficult control problems in industry and manufacturing

sectors.

However, at the same time, these advanced power electronics

systems also help in reducing the harmonics flowing in the power systems.

The THD value is the effective value of all the harmonics current added

together compared with the value of the fundamental current, as discussed

by John et al (2001). When excessive harmonic voltage and current are

generated, filters are usually installed to reduce the harmonic distortion

Fang et al (1990) and Helga et al (2004). Other methods of harmonic

reduction is considered such as current injected by active power filter,

discussed by Sangsun et al (2001) and Ambra et al (2003). Ideally, voltage

and current waveforms are pure sinusoids. However, because of the

increased usage of nonlinear loads, these waveforms become distorted.

This deviation from a pure sine wave can be represented by harmonic

components having a frequency that is an integral multiple of the

fundamental frequency. Thus, a pure voltage or current sine wave has no

distortion and no harmonics. In order to quantify the distortion, the term of

total harmonics distortion is used.

The inverter switches are connected and disconnected at discrete

time instant to generate desired output voltage of specific magnitude and

frequency. Such an output voltage in addition to its fundamental

component contains a lot of other undesired harmonic components as well.

Hamadi et al (2004) has discussed the minimization of the harmonic

injection from an inverter into the power system. But, his work did not

meet the IEEE Standard 519-1992 since the THD value high. IEEE

recommended practices and requirements for harmonic control in electrical

power systems address harmonics limits at the consumer and service

provider interface.

This standard provides procedure for controlling harmonics on the

power system along with recommended limits for customer harmonics

68

injection and overall power system harmonics levels to ensure overall

system voltage integrity. The utilities are responsible for maintaining the

quality of voltage on the overall system and for the voltage distortion at the

PCC. Excessive harmonic levels in voltage or current in the utility system

can result in increased equipment heating, equipment malfunction and

premature equipment failure, communication interference, fuse blowing in

capacitor banks and customer equipment and process problems.

Rizy et al (2003), has discussed about implementation of ANN

control strategy. But unfortunately, the methodology adopted by them has

some serious drawbacks. ANNs may not be suitable for a large distribution

system since many smaller subsystems are required and the training time

becomes excessive. However, once networks are trained, iterative

calculations are no longer required and a fast solution for a given set of

inputs can be provided.

Suresh Mikkili et al (2011) has discussed about implementation of

fuzzy control optimization approach. It is very simple and naturally fast as

compared to other optimization methods. However, for some problems the

procedure might get trapped in a local optimal point and fail to converge to

the global (or near global) optimal solution.

In order to sustain the constant frequency in the utility, utilized the

Fuzzy Logic Controller based constant frequency UPFC. A Constant

Frequency (CF) UPQC is composed of a UPQC and a matrix converter

based frequency changer. UPQC is a combination of series active and

shunt active filter. The series active filter and shunt active filter have been

employed to compensate the voltage, current imbalance and harmonics.

The Frequency Converter (matrix converter) has been used to control the

supply frequency when it exceeds the power quality limit.

Therefore, in order to overcome the flaws in the above mentioned

control, hysteresis control strategies are used for better performance. When

69

the distortion levels on the utility system cause a problem, the proposed

mitigation measures need to be implemented. In order to reduce the

harmonics injected into power system by PV-UPQC, harmonics reduction

technique is developed.

4.1 PROCEDURES FOR HARMONICS REDUCTION USING

UPQC WITH DIFFERENT CONTROLLERS

The shunt inverter filter using ANN current controller as discussed

by Jeno Paul et al (2011), is essentially a cluster of suitably interconnected

nonlinear elements of very simple form that possess the ability of learning

and adaptation. These networks are characterised by their topology, the

way in which they communicate with their environment, the manner in

which they are trained and their ability to process information. Their ease

of use, inherent reliability and fault tolerance has made ANNs a viable

medium for control.

An alternative to fuzzy controllers in many cases, neural

controllers share the need to replace hard controllers with intelligent

controllers in order to increase control quality. A feed forward neural

network works as compensation signal generator. This network is designed

with three layers. The input layer with seven neurons, the hidden layer with

21 neurons and the output layer with 3 neurons. Activation functions

chosen are tan sigmoidal and pure linear in the hidden and output layers

respectively. The training algorithm used is Levenberg Marquardt Back

Propagation (LMBP). The compensator output depends on input and its

evolution. The chosen configuration has seven inputs, three each for

reference load voltage and source current respectively and one for output of

error PI controller. The neural network trained for giving fundamental

reference currents output. The signals thus obtained are compared in a

70

current controller to give switching signals. The block diagram of ANN

compensator is shown in Figure 4.1.

Source currents

Figure 4.1 Block diagram of ANN-based compensator

4.1.1 Fuzzy Controller

Rama Rao et al (2010), has discussed the implementation of fuzzy

control optimization approach. Figure 4.2 shows the block diagram of the

fuzzy logic control scheme. The control scheme consists of fuzzy

controller, limiter and three phase sine wave generator for reference

current generation and generation of switching signals. The peak value of

reference currents is estimated by regulating the DC link voltage. In order

to implement the control algorithm of a shunt active power filter in a

closed loop, the dc capacitor voltage VDC is sensed and then compared with

the desired reference value VDC-ref. The error signal VDC-error = VDC-ref VDC

is passed through Butterworth design based LPF with a cut off frequency

of 50 Hz, that pass only the fundamental component. The error signal e(n)

and integration of error signal Ie(n) are used as inputs for fuzzy processing.

The output of the fuzzy logic controller limits the magnitude of peak

reference current Imax. This current takes care of the active power demand

of the non-linear load and losses in the distribution system. The switching

signals for the PWM inverter are generated by comparing the actual source

71

currents (isa ,isb,isc) with the reference current (isa*,isb*,isc *) The output of

the fuzzy controller is estimating the magnitude of peak reference current

Imax . This current Imax comprises of active power demand of the non-linear

load and losses in the distribution system. The peak reference current is

multiplied with PLL output for determining the desired reference current.

(a)

(b)

Figure 4.2 (a) and (b) Control block diagram of fuzzy controller

4.1.2 Proposed PI with Hysteresis Controller

The proposed control strategy, described in section 3.3.1 and shown

in figure 3.3, ensures fast elimination of higher order current harmonics of

the load. Hysteresis controller is designed for controlling the switching of

72

the shunt inverter. Based on the active power demand of the load, a suitable

sinusoidal reference is selected for the incoming utility current and in

addition, appropriate hysteresis band is selected. Narrower hysteresis band

ensures higher THD elimination, at the cost of higher switching frequency

of the inverter. Suitable trade off in design is required to optimize all

criteria. The constant bandwidth hysteresis current control technique is

widely used in voltage-source grid connected inverters. The hysteresis

current control block diagram is shown in figure 4.3

The measured phase current (iA) is subtracted from reference current

(iAref), and current error (ierror) is obtained. This error is compared with

hysteresis band and switching pulses are generated. The bandwidth value

(h) is constant and hysteresis control restricts the current in the band.

(a)

(b) Figure 4.3 (a) and (b) Hysteresis current control and waveforms

73

Hysteresis current controller compares the current error with lower

and upper hysteresis band. For phase- A, if iAerror > +h, upper switch is ON,

and iA increases. If iAerror< -h, upper switch is OFF.

As discussed earlier, the dc link voltage ideally should not decay,

unless some active power loss occurs in the PV-UPQC. Therefore, the

deviation of the DC link voltage acts as a measure of active power

requirement from utility supply. The error is processed through a PI

controller and a suitable sinusoidal reference signal in phase with the

supply voltage is multiplied with the output of the PI controller, to generate

the reference current for the supply. Hysteresis band is imposed on top and

bottom of this reference current. The width of the hysteresis band is

adjusted such that the supply current THD remains within that specified by

the standards. As the supply current hits the upper or lower band,

appropriate switching of the shunt inverter takes place so as to compel the

supply current to remain within the band, by either aiding its dc link

voltage to utility supply.

4.1.3 Simulation Parameter

The three-phase PV- UPQC system simulation model is described in

section 3.8 and shown in figure 3.6. In the simulation model, the following

data parameters are used for system simulation. The source voltage is 230V

in rms (325 peak voltage). A linear load of 6 KW and 4.5 KVAR is

connected to the system, in addition to a nonlinear load of 5 KW and 3.75

KVAR. The DC link capacitor of 2000 F is connected between two

inverters. 1.245 mH is the value of both shunt and series interface

inductors. The filter capacitors of the series and shunt branches are 140 F

and 20 F, respectively. A 4 damping resistor is connected in series with

the shunt filter capacitor. Coupling transformers are used to connect the

series and shunt active filters to the PCC.

74

4.2 RESULTS AND DISCUSSION

The three-phase PV- UPQC system simulation model is described in

section 3.8 and is shown in figure 3.6. The results obtained using the

simulation model is presented in this section.

The PV-UPQC model is simulated with following case studied:

Unbalanced supply voltage and nonlinear loads with sag

Unbalanced supply voltage and liner and nonlinear loads without

sag

Balanced supply voltage and liner and nonlinear loads with sag

4.2.1 Unbalanced Supply Voltage and Nonlinear Loads with Sag

The supply voltages are unbalanced, distorted and undergoing 30%

sag as shown in figure 4.4(a). The nonlinear load is connected in this case

to study the PV-UPQC steady-state performance. It is investigated and the

simulation results are illustrated in figures 4.4(a) to 4.4(f) and figures

4.5(a) to 4.5(d).

Case Study 1: Current

Figure 4.4(a) Supply voltage with sag

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-400

-300

-200

-100

0

100

200

300

400

Time(s)

SagNo Sag No Sag

75

Figure 4.4(b) Load current

Figure 4.4(c) Load current (THD=14.3%)

Figure 4.4 (d) Current injected by shunt active filter

76

Figure 4.4 (e) Supply current (THD=1.15%)

Figure 4.4(f) Phase A –Supply, Load and Injected currents

Figure 4.4 (c) shows the load currents, which are highly distorted.

The THD is 14.3%, whereas according to IEEE Standard 519-1992 they

should not exceed 5% in our case. The effects of the injection of

compensating currents are shown in figure 4.4 (d). Figure 4.4(e) shows the

harmonics minimization sinusoidal wave (THD=1.15%), which fulfills the

5% stipulated by the IEEE standard. From figure 4.5 (e), the supply current

77

is in-phase with the load voltage, which is due to the in-phase series

voltage injection. The injection is in-phase with the fundamental of the

supply voltage. Thus, no reactive power is drawn from the supply. In figure

4.4 (f), the supply current, load current and injected current of are plotted

together. If the injected current wave is subtracted from the load current

wave, the result will be the supply current wave.

Case Study 1: voltage

Figure 4.5 (a) Supply voltages (THD=7.7%)

Figure 4.5 (b) Voltages injected by series active filter

78

Figure 4.5 (c) Load voltage (THD=0.7%)

Figure 4.5 (d) DC link voltages

Figure 4.5 (e) Phase A load voltage and supply current

79

Figure 4.5(f) Phase A supply voltages, injected and load voltages

From figure 4.5 (a), the supply voltages are unbalanced, distorted

(THD=7.7%) and undergoing a sag. The series compensator injects

voltages as shown in figure 4.5 (b). Due to this series compensation, the

voltages on the load side are balanced sinusoidal. Figure 4.5(c) shows

THD of 0.7%, which is much below the 5% limit stipulated by the IEEE

Standard. It can be seen from figure 4.5 (c) that the load voltages are kept

at the nominal level of 325 volts. The load and injected voltages for phase

A are plotted together. The sum of the injected voltage and the supply

voltage is the load voltage.

In figure 4.5 (d), the concept of dc link voltage has been illustrated.

The shunt compensator is connected at 0.02s which causes a drop in dc link

voltage. After the sag from 0.02 s to 0.5s, the dc link voltage is restored.

From figure 4.5 (d), it is observed that the average dc link voltage is kept

constant at 400 V.

80

Case Study 2

4.2.2 Linear and nonlinear loads without sag

The supply voltages, as shown in figure 4.6(a), are unbalanced and

distorted (the 5th harmonic is present) but there is no sag this time. The

nonlinear load is permanently connected and the linear load is connected at

0.2s and disconnected at 0.5s. In this case study, the PV-UPQC dynamic

performance at load change is investigated and the simulation results are

illustrated through the figures 4.6 to 4.10.

Case Study 2: load currents

Figure 4.6 (a) Load current dynamics

81

Figure 4.6 (b) Load current with nonlinear load (THD =14.4%)

Figure 4.6 (c) Load current with Nonlinear and linear loads

(THD =7.9%)

82

Figure 4.6 (d) Load current with Nonlinear load (THD = 14.4%)

The simulated duration is composed of three sub-intervals:

0 s to 0.2 s, only with the nonlinear load connected to the system

0.2 s to 0.5 s, with both the linear and nonlinear loads connected to

the system

0.5 s to 0.8 s, only with the nonlinear load is connected to the

system

For clarity, the load current waveforms, shown in figure 4.6(a), for

each of these three subintervals is zoomed in figures 4.6 (b) to 4.6 (d). The

injected and supply currents are shown in figures 4.7 and 4.8. The load

current changes are reflected in both injected and supply currents. A

change in the load causes the system to go through a transient period after

which the supply currents become balanced sinusoids, as shown in figures

4.8(b) to 4.8(d), in phase with the load voltage as shown in figure 4.10.

Thus, the PV-UPQC adjusts the injected current according to the load

condition, ensuring that, in steady-state, the supply currents are always

balanced sinusoids and no reactive power is drawn from the supply.

83

Figure 4.7 (a) Injected current dynamics

Figure 4.7 (b) Injected current with nonlinear load

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-25

-20

-15

-10

-5

0

5

10

15

20

25

Time(s)

Nonlinearload

Nonlinear load

Linear and Nonlinear loads

84

Figure 4.7(c) Injected current with linear and nonlinear loads

Figure4.7 (d) Injected current for nonlinear load

Figure 4.8(a) Supply current with dynamics

85

Figure 4.8 (b) Source current with nonlinear load (THD =2.4%)

Figure 4.8 (c) Source current with nonlinear and linear loads

(THD =1.3%)

Figure 4.8(d) Source current with nonlinear load (THD=2.4%)

86

During the entire simulation period (from 0s to 0.8 s), the supply

voltages are unbalanced and distorted (THD=5.05%), as shown in figure

4.9 (a). The injected voltage by the series compensator is shown in figure

4.9 (b). Due to this series compensation, the voltages on the load side are

balanced sinusoidal waveforms, as shown in figure 4.9(c), with THD 1%,

which is much lower than the 5% limit recommended by IEEE Standard

519-1992. From figure 4.9(c), it can be seen that the load voltages are kept

at the nominal level (325 V).

Figure 4.9 (a) Supply voltage (THD = 5.05%)

Figure 4.9 (b) Inverter injected voltage

87

Figure 4.9 (c) Load voltage (THD=1%)

Figure 4.9 (d) DC link Voltage

The DC link voltage dynamics is shown in figure 4.6(d).The load

current increases at 0.2s and decreases at 0.5s. This is due to the connection

or disconnection of the linear load. Since it takes a finite time interval to

calculate the new reference current, the shunt compensator cannot

immediately respond to the load change. Some settling time is required to

stabilize the controlled parameter around its reference. During transient

periods, the DC link capacitor is supplying active power in order to ensure

the power balance.

88

Figure 4.10 (a) Load voltage and load current with nonlinear load

Figure 4.10(b) Load voltage and load current with nonlinear and

linear loads

Due to this transient supply of active power, the dc link voltage

decreases during the sag at the time interval of 0.2s – 0.4s and the swell in

the voltage occurs during the interval 0.5s – 0.7s. After clearing the

89

interruptions, as illustrated through the figure 4.6 (d), the dc link voltage is

restored back to its reference value (400 V).

The shunt compensator is controlled in such a way that the supply

current is in-phase with the fundamental of the supply voltage, which

means that no reactive power is drawn from the supply. The fundamental

of the series injected voltage is in-phase with the supply current, as shown

in figure 4.10.

Case study 3

4. 2.3 Balanced linear and nonlinear loads with sag

During the time interval from 0s to 0.8 s, both the linear and

nonlinear loads are connected with 30% of supply voltage sag, which is

generated at 0.2 s and cleared at 0.5 s. During the same time, the supply

voltage becomes balanced and distorted (the 5th harmonic is present). The

supply voltages are as shown in figure 4.11(a) and figure 4.11 (e) Supply

current during the sag with fuzzy logic control.

In this case study, the dynamic performance of the PV-UPQC

system, at the occurrence or clearance of the supply voltage sag, is

investigated and the simulation results are illustrated through figures 4.11

to 4.15.

The supply current is increased considerably during the sag, as

shown in figure 4.12. During the sag, the load should draw the same

amount of power from the supply as it does in the normal condition

(nominal power). Since the supply voltage is decreased during the sag, the

supply current should be accordingly increased in order to provide the

same nominal power to the load.

90

Figure 4.11 (a) Supply current with dynamics

Figure 4.11 (b) Supply current before sag (THD=3.8%)

Figure 4.11(c) Supply current during the sag (THD=1.1%)

91

Figure 4.11 (d) Supply current after the clearance sag (THD

=3.8%)

Figure 4.11 (e) Supply current during the sag with fuzzy logic

control (THD=1.2%)

The supply voltage dynamics are shown in figure 4.12(a). During

the sag condition from 0.2 s to 0.5s, the supply voltages undergo 60% sag.

They are unbalanced and distorted with THD of 7.7%, as shown in figure

4.12 (c). During the other two sub-intervals from 0s to 0.2s and from 0.5s

to 0.8s, the supply voltages are balanced sinusoidal waveforms at nominal

level (325V), as shown in the figures 4.12 and 4.13.

92

Figure 4.12 (a) Supply voltage with dynamics

Figure 4.12 (b) Supply voltage before sag (THD=0.55%)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-400

-300

-200

-100

0

100

200

300

400

Time(s)

SagNo Sag No Sag

93

Figure 4.12 (c) Supply voltage during sag (THD=7.7%)

Figure 4.12 (d) Load voltage after the clearance of sag (THD=0.55%)

Figure 4.13 (a) Voltages injected during sag

94

Figure 4.13(b) DC link voltage during sag

Figure 4.14 (a) Load voltage with dynamics

Figure 4.14 (b) Load voltage before sag (THD=1.4%)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-400

-300

-200

-100

0

100

200

300

400

Time(s)

No sag No sag Sag

95

Figure 4.14 (c) Load voltage during sag (THD=0.75%)

Figure 4.14 (d) Load voltage sag with ANN controller (THD=1.2%)

During the supply voltage sag, the series compensator injects

voltages, as shown in figure 4.14(a). Due to this series compensation, the

voltages on the load side are balanced sinusoidal waveforms with THD of

0.75%, which is much lower than the 5% limit recommended by IEEE

Standard 519-1992, as shown in figure 4.14(c) and figure 4.14 (d) shows

the load voltage sag with ANN controller. Figure 4.15 shows that the load

voltages are kept at the nominal voltage throughout the simulation time

interval.

96

The DC link voltage dynamics are shown in figure 4.13 (b). Due to

the occurrence of the supply voltage sag at 0.2 s, the supply current is

increased. With the clearance of sag at 0.5s, the supply current decreased.

Since it takes a finite time interval to calculate the new reference current,

the shunt compensator cannot immediately respond to this supply current

change. Some settling time is required to stabilize the controlled parameter

around its reference.

Consequently, after the occurrence or clearance of the sag instants

(0.2s and 0.5s), there exist some transient periods during which the DC link

capacitor is supplying active power in order to ensure the balanced power.

Due to this transient supply of active power, the DC link voltage is

undergoing sag during the time interval 0.2 s – 0.4 s and a swell during the

interval 0.5 s – 0.7 s. From figure 4.14 (d), it can be observed that after

clearing the transients, the DC link voltage is restored back to its reference

value (400 V).

Figure 4.15 (a) without sag the voltage and current

97

Figure 4.15 (b) during sag the voltage and current

Figure 4.15(c) after clearance of the sag voltage and current

Due to unity power factor compensation throughout the entire

simulated period, the supply current is in phase with the fundamental of the

supply voltage, as shown in figure 4.15, which implies that no reactive

power is drawn from the supply.

A complete summary of the results with and without the proposed

system is given in table 4.1 and in figures 4.16 to 4.21.

98

Table 4.1 Comparative percentage THD voltage and current with and

without PV-UPQC system.

Casestudy No’s

Events

Without PV-UPQC

With PV-UPQC

Current %THD

Voltage %THD

Current %THD

Voltage %THD

1Unbalanced supply voltage nonlinear loads with sag

14.3 7.7 1.15 0.7

2

Unbalanced supply voltage linear and nonlinear loads without sag

14.4 5.05 1.3 1

3

Balanced supply voltage linear and nonlinear loads with sag

14.18 7.7 1.1 0.55

99

Figure 4.16 Percentage THD with and without PV-UPQC for

nonlinear loads with sag and unbalanced supply voltage

Figure 4.17 Percentage THD with and without PV-UPQC for

unbalanced supply voltage linear without sag and nonlinear loads

100

Figure 4.18 Percentage THD with and without PV-UPQC for balanced

supply voltage with sag and linear and nonlinear loads

Figure 4.19 Percentage THD with and without PV-UPQC for

unbalanced supply voltage with sag and nonlinear loads

101

Figure 4.20 Percentage THD with and without PV-UPQC for

unbalanced supply voltage without sag with liner and nonlinear loads

Figure 4.21 Percentage THD with and without PV-UPQC for balanced

supply voltage with sag and nonlinear loads

102

Table 4.2 THD values of load current with fuzzy logic control Rama

Rao et al (2010) and proposed PI with hysteresis control

THD load current

without controller

Fuzzy logic control

THD load currents

Proposed PI with

hysteresis control THD

load currents

14.3% 1.2% 1.1%

Figure 4.22 Percentage THD for fuzzy logic control and proposed

hysteresis control

103

Table 4.3 THD value of load voltage Artificial Neural Networks

(ANN) Jeno Paul et al (2011) and proposed PI with hysteresis control

THD for load voltage without

controller

ANN control THD load voltage

PI with Hysteresis control THD load voltage

7.7% 1.2% 0.55%

Figure 4.23 Percentage THD for ANN control and proposed hysteresis

control

The performance evaluation of PV-UPQC system associated with

linear and nonlinear loads with sag using hysteresis control, in terms of the

THD of the load current, is given in table 4.2. Comparing with the results

of THD of 1.2% in the load current obtained using an ANN control by

Jeno Paul et al (2011), the proposed hysteresis control has achieved a lower

THD of 1.1%, which is shown in figure 4.22.

Comparing with the results of THD of 1.2% in the load voltage

obtained using a fuzzy logic control by Rama Rao et al (2010), the

proposed hysteresis control has achieved a lower THD of 0.55% as shown

in table 4.3 and figure 4.23. The analysis shows that the proposed

104

approach is more efficient with respect to ANN and fuzzy logic control

strategies.

On the basis of the research work presented in this chapter, a paper

entitled ‘Photovoltaic based improved power quality using unified power

quality conditioner’ has been published in the International Journal of

Electrical Engineering Vol.4, No.2, pp.227-242, July 2011.

On the basis of the research work presented in this chapter, a paper

entitled ‘Power Quality Improvement using Photovoltaic Compensation

Techniques’ has been published in the International Journal of Power

Engineering Vol.2, No.1, pp. 33-46, June 2010.

4.3 CONCLUSION

In this chapter, three significant case studies of an unbalanced

system with linear and nonlinear loads are presented. The first case is

supply voltage sag with nonlinear loads. The second case is linear and

nonlinear loads without sag. The third case is linear and nonlinear loads

with sag. The simulation results shows that the linear and nonlinear loads

are connected the voltage becomes unacceptably distorted due to the

switching frequencies in the supply current.

For comparative analysis of the proposed PI with hysteresis control,

the fuzzy logic and ANN control strategies of other researchers have been

considered. Among various control techniques, the proposed hysteresis

current control is the most preferable technique for shunt compensation.

The hysteresis control method has simpler implementation, enhanced

system stability and fast response. The proposed approach ensures that the

unwanted harmonics are reduced compared to the other control strategies.