cse & wte 800 - aermec

4
CSE & WTE 800 FLAT BED UNIT 1 OR 2 ROW OF FANS AIR COOLED CONDENSED UNIT | DRY COOLER UNIT

Upload: others

Post on 05-May-2022

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Cse & WTe 800 - Aermec

Cse & WTe 800FlaT bed uniT1 or 2 roW oF Fans

air cooLed condensed Unit | drY cooLer Unit

Page 2: Cse & WTe 800 - Aermec

AIR CONDENSER AND lIquID COOlERSwITH AxIAl fANS• Configuration: 1 or 2 exchangers• 1 or 2 circuits• 1 or 2 fans row• Wide range of capacity• 70 models available as condenser• 70 models available as dry cooler• Fan diameter: 800 mm• Number of fans: from 1 to 6• Vertical or horizontal installation

COSTRuCTION CHARACTERISTICSThey are realized with technologies and material which guarantee strength against atmospheric agents.High efficiency finned block heat exchangers realized with copper tubes and alluminium fins. New generation axial fans with 800 mm diameter both available version AC and EC chosen for minimizing the energy consumption. Standard unit are supplied with cabled fans and electrical box with clamps.

AVAIlAblE fANSBTD: 6-poles with delta connectionBTY: 6-poles with star connectionSTD: 8-poles with delta connectionSTY: 8-poles with star connectionETD: 12-poles with delta connectionETY: 12-poles with star connectionCTB: fan motor EC high powerCTE: fan motor EC low noise level

ACCESSORIESCSE and WTE unit could be equipped with main switch, switchboard, cut phase fan speed regulator (with 1 set point or 2 set point) or inverter with shielded cables, EC controller and temperature sensor, pressure sensor or 0-10V signal.All fan motors could be equipped with switch for each motor. Anti-vibration device are also available for reducing machine’s vibrations and only for dry coolers flanges in oreder to simplify hydraulic connection.

Models

Model

Main switch

Switch for each motor

Switchboard

Phase cut regulatori

Controller ec Inverter

Probe

Anti-vibration

device

CSE-WTE BTD p p p p p p p

CSE-WTE BTY p p p p p p p

CSE-WTE STD p p p p p p p

CSE-WTE STY p p p p p p p

CSE-WTE ETD p p p p p p p

CSE-WTE ETY p p p p p p p

CSE-WTE CTB p p p p p p

CSE-WTE CTE p p p p p p

Cse condenser and WTe dry cooler’s serie meet equipment’s power requirements.They are available from 1 up to 6 fans both version aC and eC

Page 3: Cse & WTe 800 - Aermec

CApACITYIn air condenser unit power range with refrigerant R134a is from 8.1 up to 135 tons (ambient air temperature +77°F, average condensing temperature +104°F according to EN 327)

In air condenseer unit power range with refrigerant R410A is from 9.2 up to 157.5 tons (ambient air temperature +77°F, average condensing temperature +104°F according to EN 327)

In dry cooler unit power range with ethylene glycol 30% is from 7 up to 116.6 tons (ambient air temperature +77°F, inlet liquid temperature +104°F outlet liquid temperature +95°F according to EN 1048)

eChniCal draWinG

Quota a

- CSE/WTE° 801(3/4) (single row of fans)

- CSE/WTE° 802(3/4) (single row of fans)

- CSE/WTE° 803(3/4) (single row of fans)

- CSE/WTE° 804(3/4) (double row of fans)

- CSE/WTE° 806(3/4) (double row of fans)

20 70 120

170

220

270

320

370

420

470

520

CTE

CTB

ETY

ETD

STY

STD

BTY

BTD

kW (T.air 25°C - T.cond 40°C)

CSE 800 R134a

20 70 120

170

220

270

320

370

420

470

520

570

CTE

CTB

ETY

ETD

STY

STD

BTY

BTD

kW (T.air 25°C - T.cond 40°C)

CSE 800 R410A

20 60 100

140

180

220

260

300

340

380

420

CTE

CTB

ETY

ETD

STY

STD

BTY

BTD

kW (T.air 25°C - T.liq 40/35°C)

WTE 800

66.7 in

132.3 in

197.8 in

132.3 in

197.8 in

Quota A

52.8 in

96 in

49.3 in

52.8 in

43.3 in

47.0 in

71.0 in

94.5 in

Page 4: Cse & WTe 800 - Aermec

AERMECAddress: 1608 Bonhill Road. Mississauga, Ontario, CA L5T 1C7 Website: www.aermec.usEmail: [email protected]: 1-800-567-2221US: 1-888-567-2227