data center cooling efficiency: understanding the science of the 4 delta t's

39
Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T’s Lars Strong, P.E., Upsite Technologies Airflow Management Awareness Month June 22, 2016

Upload: upsite-technologies

Post on 15-Apr-2017

311 views

Category:

Technology


2 download

TRANSCRIPT

Page 1: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T’s

Lars Strong, P.E., Upsite Technologies

Airflow Management Awareness Month

June 22, 2016

Page 2: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Lars is a thought leader and recognized expert on data center optimization. He currently serves as the Senior Engineer and Company Science Officer of Upsite Technologies. Lars is a certified U.S. Department of Energy Data Center Energy Practitioner (DCEP) HVAC Specialist.

05/03/2023 © Upsite Technologies, Inc. 2

Lars Strong

Page 3: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Delta T PUE Bypass Airflow Commonly Known Delta T’s Less Known Delta T’s Remedial Considerations

05/03/2023 © Upsite Technologies, Inc. 3

Agenda

Page 4: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

DELTA T (ΔT)

© Upsite Technologies, Inc.05/03/2023 4

Page 5: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Delta T (ΔT)= change in temperature

“The ΔT” - Facilities: across cooling unit coils (Δ between supply and return)- IT: through IT equipment

There are actually 4 ΔT’s

05/03/2023 © Upsite Technologies, Inc. 5

Delta T (ΔT)

Page 6: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

The 4 ΔT’s

1. Through IT equipment2. IT equipment exhaust to

cooling unit3. Through cooling unit4. Cooling unit supply to IT

equipment intake

05/03/2023 © Upsite Technologies, Inc. 6

The 4 ΔT’s

Page 7: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

PUE – RELATION TO AIRFLOW MANAGEMENT

© Upsite Technologies, Inc.05/03/2023 7

Page 8: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

PUE

© Upsite Technologies, Inc.05/03/2023 8

Total Load

IT LoadPUE =

Other than IT load, cooling load is often the largest portion of total loadAirflow management is fundamental to both effective and efficient coolingMechanical plant + cooling fans: 35% of total load, 73% of non IT Load

Page 9: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

  Raised floor

area (sq ft)

# of running cooling units

Raised floor

bypass open

area (%)

Hot spots (%

of cabinets

)

Cold spots (%

of cabinets) (Data from 6 sites)

Proper perforated tile

placement (%)

Cooling Capacity Factor (CCF)

Averages 7,527 8 48% 20% 35% 77% 3.9Minimum 720 2 13% 0% 0% 7% 1.2Maximum 37,00

040 93% 86% 86% 100% 32.0

Recommended

n/a n/a <10% 0% 0% 100% 1.2Conclusion: Inefficient cooling configuration / airflow management is the problem; capacity is not the problem.

Airflow Management Research

© Upsite Technologies, Inc.05/03/2023 9

Page 10: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

BYPASS AIRFLOW

© Upsite Technologies, Inc.05/03/2023 10

Page 11: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Bypass Airflow Clarified

© Upsite Technologies, Inc.© Upsite Technologies, Inc.05/03/2023 11

Common ratios before raised floor open area management

Page 12: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Bypass Airflow Clarified

© Upsite Technologies, Inc.© Upsite Technologies, Inc.05/03/2023 12

Common ratios after raised floor open area management

Page 13: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Bypass Airflow Clarified

© Upsite Technologies, Inc.© Upsite Technologies, Inc.05/03/2023 13

Ratios after balancing supply flow rate to IT demand flow rate

Page 14: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

MORE COMMONLY KNOWN ΔT’S

© Upsite Technologies, Inc.05/03/2023 14

Page 15: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

The 4 ΔT’s

1. Through IT equipment2. IT equipment exhaust to

cooling unit3. Through cooling unit4. Cooling unit supply to IT

equipment intake

05/03/2023 © Upsite Technologies, Inc. 15

ΔT Through IT Equipment

Page 16: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Regardless of airflow management in the computer room, the IT equipment airflow temperature rise will be constant for a given work load.

Every kilowatt of electricity consumed by IT equipment becomes a kW of heat added to the flow of cooling air through the IT equipment.

There is a fixed relationship between airflow, temperature differential and heat (energy).

05/03/2023 © Upsite Technologies, Inc. 16

ΔT Through IT Equipment

Page 17: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

05/03/2023 © Upsite Technologies, Inc. 17

ΔT Through IT Equipment

Heat Transfer Equation

CFM =

CFM = cubic feet per minute of airflow through the server3.16 = factor for density of air at sea level in relation to F⁰ΔT = temperature rise of air through the server in F⁰

3.16 x W Delta T

Page 18: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

05/03/2023 © Upsite Technologies, Inc. 18

ΔT Through IT Equipment

CFM/kW

IT Equipment Required Flow Rate IT

Equipment Delta T

(deg F)15° 20° 25° 30° 35° 40°

Required flow rate (CFM/kW)

211

158

126

105

90

79

Page 19: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

“Blade” servers at 35 F ⁰ ΔT consume 90 CFM / kW

“Pizza box” servers at 20 F ⁰ ΔT consume 158 CFM / kW

UPS load (kW) x CFM/kW = Total IT CFM

UPS load (kW) x 100 CFM/kW = approximate IT cooling demand (CFM) Compare this to total cooling flowrate to determine room bypass airflow rate

05/03/2023 © Upsite Technologies, Inc. 19

ΔT Through IT Equipment

Examples

Page 20: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

The 4 ΔT’s

1. Through IT equipment2. IT equipment exhaust to

cooling unit3. Through cooling unit4. Cooling unit supply to IT

equipment intake

05/03/2023 © Upsite Technologies, Inc. 20

ΔT Through Cooling Unit

Page 21: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Ideally ΔT through cooling units would match ΔT through IT equipment, then total volumetric flow rate (CFM) of conditioned air could match the total flow rate of IT equipment

Legacy DX units ΔT was fixed at about 18˚ F

A 5˚ F increase in return air temperature might result in a 3˚ or 4˚ increase in the supply temperature

05/03/2023 © Upsite Technologies, Inc. 21

ΔT Through Cooling Unit

Page 22: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Chilled water cooling units have a much wider range of ΔT

Cooling units can be designed for much higher ΔT

Designers of high density data centers with high ΔT IT equipment are working with cooling unit manufactures to provide cooling units with a 45˚ F ΔT

05/03/2023 © Upsite Technologies, Inc. 22

ΔT Through Cooling Unit

Page 23: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

LESS COMMONLY KNOWN ΔT’S

© Upsite Technologies, Inc.05/03/2023 23

Page 24: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

The 4 ΔT’s

1. Through IT equipment2. IT equipment exhaust

to cooling unit3. Through cooling unit4. Cooling unit supply to IT

equipment intake

05/03/2023 © Upsite Technologies, Inc. 24

ΔT IT Equipment Exhaust to Cooling Unit

Page 25: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

In most data centers the ΔT from the servers back to the cooling source is negative, the temperature of the return air tends to decrease after it is exhausted from the IT equipment

The cause is very straightforward: excess cooling air is bypassing the IT equipment and returning to the cooling units, reducing the temperature of the return air along the way

05/03/2023 © Upsite Technologies, Inc. 25

ΔT IT Equipment Exhaust to Cooling Unit

Page 26: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

05/03/2023 © Upsite Technologies, Inc. 26

ΔT IT Equipment Exhaust to Cooling Unit

Page 27: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

© Upsite Technologies, Inc.© Upsite Technologies, Inc.05/03/2023 27

Hot area shows air that passed through IT equipment

Cooler area shows bypass airflow

ΔT IT Equipment Exhaust to Cooling Unit

Page 28: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

The 4 ΔT’s

1. Through IT equipment2. IT equipment exhaust to

cooling unit3. Through cooling unit4. Cooling unit supply to

IT equipment intake

05/03/2023 © Upsite Technologies, Inc. 28

ΔT Cooling Unit to IT Equipment Intakes

Page 29: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

It is surprising that the ΔT between the cooling unit supply/output and the server inlet is not on many radars

Supply temperatures around 55˚ F are fairly typical, approximately 9˚ F below the recommended minimum temperature for data processing equipment per the ASHRAE environmental guidelines

Low supply temperature is often not a problem because by the time it reaches the IT equipment it has warmed dramatically

05/03/2023 © Upsite Technologies, Inc. 29

ΔT Cooling Unit to IT Equipment Intakes

Page 30: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

05/03/2023 © Upsite Technologies, Inc. 30

ΔT Cooling Unit to IT Equipment Intakes

Page 31: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

© Upsite Technologies, Inc.© Upsite Technologies, Inc.05/03/2023 31

Infrared Image of Operating Data Center• Cold spots and hot

spots in every cabinet

• Trying to solve poor AFM with cold supply

ΔT Cooling Unit to IT Equipment Intakes

Page 32: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

REMEDIAL CONSIDERATIONS

© Upsite Technologies, Inc.05/03/2023 32

Page 33: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Any server inlet temperature that is more than 5˚F above the supply temperature being produced by cooling units means that there is hot air

If the return air intake of the cooling units is more than 5˚F lower than the exhaust temperature from the IT equipment, then there is a bypass airflow problem.

These 5˚F guidelines for calibrating ΔT’s are suggestions that will help move a data center into the top 20% of efficiently and effectively performing data centers.

05/03/2023 © Upsite Technologies, Inc. 33

Remedial Considerations

Page 34: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Monitoring all four ΔT’s can provide valuable assistance for optimizing the data center

The goal, particularly if free cooling is available to the data center, is to get the differentials between the cooling supply and IT intake, and server exhaust and the cooling unit return as close to zero as possible, this will increase free cooling hours.

Raise control temperatures to improve cooling unit capacity and efficiency

IR Thermometer and IR cameras are very valuable tools

05/03/2023 © Upsite Technologies, Inc. 34

Remedial Considerations

Page 35: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

A holistic approach An iterative process ‘Check in’ at the room level

after making any AFM improvements

Watch video at:upsite.com/resources/airflow-management/

Upsite’s 4 R’s of Airflow Management™

© Upsite Technologies, Inc.05/03/2023 35

Page 36: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Raised Floor: Manage openings in the raised floor so that all cold air is entering the room through supply tiles located in front of IT equipment

Rack: Manage all openings through and below the rack or cabinet enclosure, so air can only pass through the IT equipment.

Row: Manage all openings between cabinets so no air can pass between them, and manage openings at the end of the aisle and above cabinets to contain cold air and prevent hot air wrapping around the ends of rows or over cabinets.

Room: Manage the conditioned airflow (flow rate and temperature) so that the maximum established IT inlet temperature is not exceeded, and there are no hotspots.

05/03/2023 © Upsite Technologies, Inc. 36

Upsite’s 4 R’s of Airflow Management™

Page 37: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

37

Upsite’s 4 R’s of Airflow Management™Raised Floor

Integral GrommetP/N: 1010

Mini GrommetP/N: 10077

Round GrommetP/N: 40001 (4”) 40003 (6”)

Surface Mount Grommet

P/N: 2020 (Original) 2030 (Large)

2040 (Xlarge)

Extended Brush GrommetP/N: 10012 (3” x 24”) 10013 (6” x 24”) 10097 (3” x 60”) 10098 (6” x 60”)

Row

Under Rack Panel 10126 (27.5”) 10127 (31.5”) Adjustable Rack

Gap PanelP/N: 10164

Rack Top Baffles P/N: 10160/1

Bi-Directional DoorsP/N: 10163

Modular Containment

Room

Temp Sensor

Temp + Humidity

Sensor

Leak Detection Sensing

Rope

Temp Sensor w/ Digital InputTemp

Sensor

EMS 300 Wireless Network Manager

EMS 200 Wired Network Manager

Point Repeater

Rack

White Blanking PanelP/N: 10114 (1U) 10115 (2U)

1U Black Blanking PanelP/N: 10031 (19”) 10177 (23”)

2U Black Blanking Panel

P/N: 10033

Rack Airflow Management KitPass Through Blanking Panel

P/N: 10112 (1U) 10113 (2U)

Rack Mount GrommetP/N: 40002

Page 38: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

05/03/2023 © Upsite Technologies, Inc. 38

June 1: The Science Behind Airflow ManagementPresented by Lars Strong, P.E., and Mark Seymour

June 8: Myths of Data Center ContainmentPresented by Lars Strong, P.E.

June 15: How IT Decisions Impact FacilitiesPresented by Lars Strong, P.E., and Ian Seaton

June 22: The 4 Delta T’s of Airflow ManagementPresented by Lars Strong, P.E.

Watch all recordings at upsite.com/airflow-management-awareness-month

Airflow Management Awareness Month

Page 39: Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's

Thank you!

@UpsiteTech

blog.upsite.com

On LinkedIn

Lars Strong, P.E.Senior Engineer, Upsite [email protected]

Follow Upsite for the latest news and information on data center AFM.