Dead Tank Circuit Breaker 362PMR-BEngineered to reduce switching transients

2 | 362PMR-B Dead Tank Circuit Breaker

ABB (www.abb.com) is a leader in power and automation technologies that enables utility and industry customers to improve their performance while lowering environmental impact.

The ABB Group of companies operates in approximately 100 countries and employs around 145,000 people.

ABB innovations for changing demands

A complete range of high voltage circuit breakersABB offers the widest range of high voltage circuit breakers on the market. Our portfolio of dead tank circuit breakers ranges from 72.5 kV to 800 kV.

ABB has a long history of developing innovative technologies to address the changing demands of power systems. As these systems continue to evolve, switching solutions must be designed to meet present-day applications as well as anticipate the future state of the grid.

362PMR-B Dead Tank Circuit Breaker | 3

Engineered to reduce switching transients

ABB is proud to offer the type 362PMR-B SF6 power circuit breaker, based on the well-established 362PMI-B platform, for applications requiring closing resistors.

StandardsThe 362PMR-B Dead Tank Circuit Breaker is tested for high transient recovery voltage (TRV) performance, ultimate mechanical endurance and is certified for class C2 capacitive switching.

– ANSI/IEEE C37.09– ANSI/IEEE C37.04– ANSI/IEEE C37.06– ANSI/IEEE C37.06.1

Certifications– ISO 9001– ISO 14001– OHSAS 18001

ApplicationsThe 362PMR-B was designed for:– overhead transmission lines, especially long transmission applications, with a potential for transient overoltage – transformer applications with a potential for inrush current– capacitive switching applications

Type PM circuit breaker familyWith just under 50,000 breakers delivered to date, spanning voltages up to 800 kV, the ABB type PM dead tank circuit breakers remain the most purchased brand in the industry. This is due to their low cost of ownership and strong performance, backed by industry-leading service and support.

Benefits of ABB’s advanced technology

Endurance to reduce extreme transientsThe 362PMR-B circuit breaker is designed with integrated pre-insertion resistors providing overvoltage protection for capacitor bank, transmission line and transformer switching.

Pre-insertion resistors (closing resistors) are used to limit over-voltages in the network during switching operations. The pre-insertion resistors are only used during closing and consist of resistor blocks that are connected in parallel with the breaking chamber. The resistor blocks will close the circuit approximately 8-12 ms before the arcing contacts. Pre-insertion resistors are mainly used at higher system voltages (≥362 kV).

Simple and reliable HMB mechanismEach fully integrated hydraulic mechanism is self lubricating, hermetically sealed from the atmosphere and weather protected, affording excellent reliability and long term stability.

– Longer lifetime and ease of service due to reduced lead content, more interchangeability of parts– Higher reliability due to fewer pump starts – Robust, compact design with non anodized sealing surfaces and a minimum number of moving parts– Simple adaptation to breakers

ABB backs the HMB mechanism with an industry-best 10 year warranty.

Easy installation and retrofit, saving time and money Installation time of approximately 16 hours as the breaker is shipped in only 4 sections (3 pressurized poles with bushing and mechanism attached, and frame with associated control housing).

No external capacitors needed except for short line faultFor short-line fault, the type 362PMR-B does not require any external capacitors up to the maximum rated fault current of 63kA, saving cost, installation time, and further substation space. For special fast-rate-of-rise applications per ANSI/IEEE C37.06.1, the circuit breaker requires no capacitance for the 7% short circuit rating and 2 nF capacitors for the 30% short-circuit current rating.

Enhanced safetyABB supplies shatter-proof composite bushings and ASME pressure vessel code certified tanks. Overpressure relief devices, designed to rupture in case of internal pressure build up, are also included as an enhanced safety feature.

4 | 362PMR-B Dead Tank Circuit Breaker

Single-break interrupter with pre-insertion resistorOur single piece high performance puffer interrupter utilizes state-of-the-art technology with dual-motion contacts, allowing for greater reliability. For questions on pre-insertion resistor options, contact the factory.

TanksSingle-piece tanks are ultrasonically cleaned, then leak tested in a vacuum sealed chamber using highly accurate helium mass spectrometer leak detection. Each tank is ASME pressure vessel tested and certified.

Control cubicleABB prides itself on offering generously sized control cubicles at workable heights to vastly improve access to the equipment over its lifetime.

Insulating mediumThe type PMR-B uses SF6 as the insulating medium. ABB has invested in monitoring technology, manufacturing techniques, and innovative designs to reduce SF6 gas leaks.

Features

BushingsABB offers a variety of bushing options, including silicone and porcelain insulators, to meet customer application needs and environmental conditions. ABB utilizes tapered designs where feasible to reduce the SF6 volume and therefore installed inventory in our customer’s fleet.

Bushing current transformersABB utilizes slipover bushing current transformer (BCT) designs for our dead tank product line which allow for cost effective, efficientand safe removal or exchange without removing the bushings.

HMB 4.1 mechanismThe moving contacts of each separate pole unit are driven by a type HMB-4 spring hydraulic mechanism that is mounted at one end of each interrupter tank. Mechanical energy is stored in a column of compression disk springs and is translated hydraulically to the pole’s operating shaft. Spring charge is automatically maintained by the operation of a universal motor and hydraulic pump.

362PMR-B Dead Tank Circuit Breaker | 5

Rated per ANSI and IEC standards

Maximum continuous voltage kV 380

Operating frequency Hz 50 / 60

Interrupting time 2 cycles

Impulse withstand voltage

2 µ-sec chopped wave kV Peak 1680

Full wave lightning impulse (BIL) kV Peak 1300

Switching impulse close / open kV Peak 825 / 900

Power frequency withstand voltage

60 Hz 1 minute dry withstand kV 555

Continuous current A 2000, 3000, 4000, 4400, 5000, 5500 (1)

Close and latch current kA 170

Short circuit breaking current kA 63

Minimum operating gas pressure @ 20° C psig 72

Normal operating gas pressure @ 20° C psig 87

Permissible ambient temperature °C -55 to +50 (2)

Interrupter enclosure dead tank

Configuration 3 pole units on individual frames

Design outdoor

Expected lifetime yrs ≥30

Dimensions (H x W x L) ft / mm 19.91 x 27.72 x 17.94 / 6069 x 8448 x 5469

Weight, SF6 gas lbs / kg 621 / 282

Operating mechanism

Type spring-hydraulic, type HMB-4.1

Quantity per breaker 3

Energy storage spring column, disc spring

Standard operating duty O-0.3s-CO-180s-CO

Stored operations 2

Seismic rating 0.5g value per IEEE 693

Charging source universal motor

Charging motor

Available voltages

VDC VAC

110 - 125220 - 250

110 - 125220 - 250

Power 650 W 1000 W

Operating current6 A @ 125 3 A @ 250

9 A @ 1254.5 A @ 250

Starting current 30 / 20 A 40 / 25 A

Max recharge time 88 seconds

Trip and close coils

Available voltages110-125 VDC220-250 VDC

Current

Trip3.5 A @ 120 V1.6 A @ 240 V

Close3.5 A @ 120 V1.6 A @ 240 V

Technical data

Above are not necessarily limiting values; further information available upon request.

Notes(1) 5000 A and above requires polymer insulators(2) Requires tank heaters on applications with ambient temperatures less than 30º C(3) Typical weight includes porcelain bushings and the maximum BCT load

6 | 362PMR-B Dead Tank Circuit Breaker

Physical data

Dimensions and specifications

Phase spacing 12 ft (5657.6 mm)

Height - installed 19.91 ft (6069 mm)

Width - installed 27.72 ft (8448 mm)

Length - installed 17.94 ft (5469 mm)

Shipping weight 22,473 lbs (10193.58 kg)

Footprint of frame 26.62 ft (8113 mm) x

7.98 ft (2433 mm)

Centerline to centerline 12 ft (3657.6mm)

Minimum height to live parts 19.30 ft (5884 mm)

Typical installed weight with porcelain bushings and maximum BCT’s

25,000 lbs (11,339.81 kg)

12’ (3657.6)

Phase Spacing12’ (3657.6)

Phase Spacing

27.38’ (8348)Installed

10.77’ (3283)Metal to Metal

5.55’ (1693)

2.5’ (762)Bottom of

Cabinet

13.03’ (3973)Clearance to Remove Interrupter

6.79’

10.77’ (3283)Metal to Metal

(2069)

4.50’(1371)

6.48’(1975)

7.64’ (2328)Center

Lineof

Breaker10.54’ (3214)Height

toUngrounded

Parts

19.30’ (5884)Height

toLiveParts

19.91’ (6069)8.96’

(2730)Strike

BushingCreep

9.87’ (3008)Metal to Metal

11.09’ (3381)Shipping Length

16.65’ (5075)

17.94’ (5469)

12’ (3657.6)

Phase Spacing12’ (3657.6)

Phase Spacing

27.38’ (8348)Installed

10.77’ (3283)Metal to Metal

5.55’ (1693)

2.5’ (762)Bottom of

Cabinet

13.03’ (3973)Clearance to Remove Interrupter

6.79’

10.77’ (3283)Metal to Metal

(2069)

4.50’(1371)

6.48’(1975)

7.64’ (2328)Center

Lineof

Breaker10.54’ (3214)Height

toUngrounded

Parts

19.30’ (5884)Height

toLiveParts

19.91’ (6069)8.96’

(2730)Strike

BushingCreep

9.87’ (3008)Metal to Metal

11.09’ (3381)Shipping Length

16.65’ (5075)

17.94’ (5469)

362PMR-B Dead Tank Circuit Breaker | 7

Typical electrical drawings

Protection and control interfaces

Popular CT options

Accessory Tier 1 Tier 2 Tier 3

Dual trip coils

125 VDC

AC / DC transfer

Mini-monitor (Qty.) 3 3 3

Emergency trip

EB-27 CT terminal blocks

Cabinet light - door activated

20 A GFI (cabinet exterior)

20 A receptacle (panel mounted)

Non-insulated wire terminals

Circuit breakers

Push buttons

Undervoltage relays

DC visible disconnect

Local remote switch

Screw down device nameplates

Fiber optic merging unit

SF6 monitor

Ratio

Accuracy

ANSI

IECRelaying Metering

600:5 MR C-400 / C-800 0.3B-0.5 5P10@15VA

1200:5 MR C-400 / C-800 0.3B-1.0 CLASS 0.5@30VA

2000:5 MR C-400 / C-800 0.3B-1.0 10P20@50VA

3000:5 MR C-400 / C-800 0.3B-1.8 CLASS 0.5@30VA

4000:5 MR C-400 / C-800 0.3B-2.0 CLASS 0.2@15VA

Typical controls features

125 / 250 VDC

(+)

52X152Y1 52CC-1

(LOW GAS)

52X1 52X1

52Y1

5A

5B

52Y152B

52B

52Y1

63

63 (LOW SPRING)

(-)

1

2

52B

DC close - pole 152X1 X relay, closing52Y1 Y relay, anti pump52B Auxiliary switch contact5A – 5B Remote close and reclose52CC-1 Close coil63 Permissive contact / alarm contact

125 / 250 VDC

/ (+)

11A

9A 9B 9C

52A

52A

52TC1

11B

52A

52A

52TC2

11C

52A

52A

52TC3

(-)

21

22

Primary DC trip9A – 11A Remote trip pole 19B – 11B Remote trip pole 29C – 11C Remote trip pole 352A Auxiliary switch contact52TC1, 52TC2, 52TC3 Trip coil

Notes:1) Secondary trip is same as primary2) DC close for poles 2 and 3 is same as pole 1

AC schematic42-1, 42-2, 42-3 Motor contactor88-1, 88-2, 88-3 Motor23-1 Non-adjustable thermostat

120 / 240 VAC

88-1MECH

HEATER70 W

4 2 - 1

4 2 - 1

4 2 - 2

4 2 - 2

4 2 - 3

4 2 - 3

88-2 88-3MECH

HEATER70 W

MECH HEATER

70 WCABINET HEATER

75 W

23-1

CABINET HEATER

75 W

CABINET HEATER

75 W

CABINET HEATER

75 W

8 | 362PMR-B Dead Tank Circuit Breaker

Installation and commissioningThe compact design is ideal for new or existing substation layouts for voltages up to 362 kV. The breaker fits within most existing footprints and can be used to quickly address the need for greater protection for minimal cost.

Those familiar with the PM line of breakers can typically install and commission the breaker within 2 days given a prepared foundation. The pole assemblies are shipped complete with positive SF6 pressure, and are installed on frames with control cabinet on site.

ABB offers supervision, installation, commissioning, and maintenance service on all ABB breakers.

The type 362PMR-B is shipped with completely assembled pole units filled with positive SF6 pressure. For domestic deliveries, all components are transported to the customer on a double-drop, air ride trailer. For non-domestic deliveries, the bushings are removed and packaged for shipping. Weight of gas at shipping pressure is provided with test report.

Shipping and installation

Representative installation of a 362 kV PMR breaker in the United States.

362PMR-B Dead Tank Circuit Breaker | 9

Notes

Note:We reserve the right to make technical changes or modify the contents of thisdocument without prior notice. With regard to purchase orders, the agreedparticulars shall prevail. ABB does not accept any responsibility whatsoever forpotential errors or possible lack of information in this document. We reserveall rights in this document and in the subject matter and illustrations containedtherein. Any reproduction–in whole or in parts–is forbidden without ABB’s priorwritten consent.

Copyright 2014 ABB.

All rights reserved.