live tank circuit breaker - sme-powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · live tank...

19
Rated voltages 72.5-245kV Rated currents 4000A Rated breaking currents 50kA Live Tank Circuit Breaker Auto-Puffer TM SF6 Circuit-breakers for outdoor installation

Upload: haminh

Post on 25-Mar-2018

255 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

Rated voltages 72.5-245kV

Rated currents 4000A

Rated breaking currents 50kA

Live Tank Circuit Breaker

Auto-PufferTM SF6

Circuit-breakers for

outdoor installation

Page 2: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Contents

I. Introduction..........................................................................................................1

II. Design Feature Auto-PufferTM ...........................................................................2

III. LTB Design Features and Advantages.............................................................4

IV.Technical Data According to ANSI................................................................12

V. Technical Data According to IEC.....................................................................13

VI. Dimensions-LTB ...............................................................................................14

VII. Shipping Data for LTB .................................................................................16

Content

Page 3: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

ABB has over a century of experience in developing,

testing and manufacturing high voltage circuit

breakers. Through the years, our circuit breakers

have acquired a reputation for high reliability and

long life in all climates and in all parts of the world.

ABB’s LTB circuit breaker family, with rated voltage

72.5-245 kV and breaking current up to 50 kA,

satisfies the highest demands. It is based on latest

developments in dielectric dimensioning and arc

physics research.

ABB produced the world’s first SF6 circuit breakers

with arc-assisted interrupters in the mid-1980’s -

Auto-PufferTM.The energy required for interrupting

short circuit currents is partly taken from the arc

itself,significantly reducing the energy required

from the operating mechanism. Lower operating

energy inherently reduces mechanical stresses,

on the circuit breaker itself as well as on the

foundation, and increases circuit breaker reliability.

For many years, ABB has used operating

mechanisms with energy mechanically stored in

springs. This solution offers considerable

advantages in that the energy in the tensioned

springs is always available.

The design of the LTB is a well-proven technology

(over 20,000 units are in service).

1

Introduction

Exceeding Customer Expectations -ABB Live Tank Circuit Breakers

= Brief Performance Data:�

Installation Outdoor/Indoor

Design SF6 Auto-PufferTM interrupter� spring operating mechanisms

Insulation SF6

Rated Voltage 72.5 - 245 kV

Rated Current 4,000 A

Breaking Current 50 kA

Short Time Current 50 kA/3 s

Insulators Composite or Porcelain

Creepage Distance 25 mm/kV (longer on request)

Service Condition�

Ambient Temperature - 30�to+40��Operation in temperature down to -55� or up to+70��

Design Altitude 1,000 m.a.s.l.�Higher altitude on reques�

Type of Operation Single- or Three- pole

Introduction

Page 4: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Design Feature Auto-PufferTM

Design Feature Auto-PufferTM Interrupters

Contact Parting

Closed Main Arcing ValveOperation Arc Extinction Open

1. Upper current carrier | 2. Stationary arcing contact | 3. Moving arcing contact | 4. Auto-PufferTM

volume | 5. Puffer volume | 6. Refill valve | 7. Stationary piston | 8. Nozzle | 9. Stationary maincontact | 10. Moving main contact | 11. Auto-puffer? valve | 12. Puffer cylinder | 13. Over-pressurerelief | 14. Lower current carrier

When interrupting high currents (e.g. rated short-

circuit current), Auto-PufferTM interrupters show the

advantage they were designed to provide.

On opening, the operation of an Auto-PufferTM

interrupter at high current begins the same way as

a puffer interrupter. It is not until after arcing begins

that a difference in the operation principle is seen

between the high and low current interrupting

cases.

When the arcing contacts part, an arc is drawn

between the moving and stationary arcing contacts.

As the arc flows, it to some degree blocks the flow

of SF6 gas through the nozzle. The arc drawn is

extremely hot and radiates a lot of heat and begins

to heat the SF6 gas in the interrupting gas volume.

Thus, the pressure inside the Auto-PufferTM and

puffer volumes increases due to the rise in

temperature as well as due to the com-pression of

gas between the puffer cylinder and stationary

piston.

Gas pressure inside the Auto-PufferTM volume

continues to increase until it is high enough to force

the Auto-PufferTM valve to the closed position. All

SF6 gas required for interruption is now trapped in

the fixed Auto-PufferTM volume and any further

increase in gas pressure in that volume is due solely

to heating from the arc. At about the same time,

the gas pressure in the puffer volume reaches a

level sufficient to push the overpressure valve open.

Since the gas in the puffer volume escapes through

the overpressure valve, Design Features Auto-

PufferTM Interrupters there is no need for a high

operating energy to overcome the compression of

2

Auto-PufferTM

Page 5: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

3

Auto-PufferTM

SF6 gas while at the same time maintaining the

contact speed necessary to withstand recovery

voltage.

When the current waveform crosses zero, the arc

becomes relatively weak. At this point, the

pressurized SF6 gas flows from the Auto-PufferTM

volume through the nozzle extinguishing the arc.

When interrupting low currents, Auto-PufferTM

interrupters act in much the same way as puffer

interrupters. That is, there is not sufficient gas

pressure generated to force the Auto-PufferTM valve

closed. Thus, the fixed Auto-PufferTM volume and

puffer volume form one large puffer volume. In such

a case, the SF6 gas pressure required for

interruption is built up by mechanical means as in

a puffer interrupter. Unlike a puffer nterrupter,

however, Auto-PufferTM need only mechanically

generate sufficient gas pressure to interrupt a

Design Feature Auto-PufferTM Interrupters

portion of the rated short-circuit current (i.e. 20%

to 30%)

In the open position, there is sufficient distance

between the stationary and moving contacts to

withstand rated dielectric levels.

On closing, the refill valve opens so that SF6 gas

can be drawn into the Auto-PufferTM and puffer

volumes.Because interruption of low currents

requires only moderate build up of SF6 gas pressure

by mechanical means and since high current

interruption uses heating from the arc to generate

necessary gas pressure in a fixed volume, Auto-

PufferTM interrupters require far less operating

energy than puffer interrupters (i.e. about 50% less).

ABB Auto-PufferTM interrupter is also a single

motion design.

Page 6: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

4

LTB Design Features and Advantages

Design Features

LTB is available for single- or three-pole operation.

Design Features and Advantages

For circuit breakers with one breaking element per

pole, both modes of operation are possible.

For three-pole operation, the circuit breaker poles

and the operating mechanism are linked together

with pull rods. On every pole there is an individual

opening spring controlled by the pull rod. There is

however one exception. In the LTB D three-pole

operation case there is only one opening spring

cntrolling all three poles and it is mounted on the

pole furthest away from the operating mechanism.

Each circuit breaker pole constitutes a sealed SF6

filled unit, which includes the breaking unit, the

hollow post insulator and the mechanism housing.

1

2

3

95

6

7

10

8

4

1

�Circuit Breaker type LTB D

1. Breaking Chamber 2.Support Insulator 3.Support Structure 4.Operating Mechanism type BLK

5. Trip Spring 6.Gas Tube with Protective Beam 7.Gas Supervision (On opposite side)

8. Drilled Holes for Connection to Ground 9. Pull rod with Protective Tube 10. Position Indicator

Note: 5, 6 ,9 are inside the horizontal beam

Page 7: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

The three poles of the circuit breaker can be mounted

on individual pole supports or in the case of LTB D on

a common support frame (pole beam).

BLK is used for:

LTB D 72.5-170 kV

LTB E 72.5-245 kV Single-pole operation

BLG is used for:

LTB E 72.5- 245 kV Three-pole operation

The operational reliability and the service life of an

SF6 circuit breaker is very much dependent on the

ability to ensure sealing of the SF6 gas volume and to

neutralize the effects of moisture and decomposition

products in the gas.

• The risk for gas leakage is negligible; double nitrile

rubber O-rings and X-rings are used with excellent

result.

• Each breaking unit is provided with a desiccant,

which absorbs the moisture and the decomposition

products from the interruption process.

• Since the interrupting capability is dependent on the

density of the SF6 gas, the LTB circuit breaker is

provided with a density monitor.The density monitor

consists of a temperature compensated pressure

switch. Therefore, alarm signal and blocking function

are activated only if the pressure drops due to

leakage.

The design corresponds with the demands in the

standards IEC and ANSI. Special design solutions to

meet other standards and/or specifications are also

available.

Current Switching Capability

All LTB circuit breakers are capable of interrupting

short-circuit currents in a maximum of 40 ms. We can

also guarantee restrike free interruption of capacitive

currents due to optimized contact design and

movement.

For inductive current switching the over-voltages are

low as a result of optimum quenching at current zero.

Dielectric Strength

LTB has high dielectric strength even at atmospheric

SF6 pressure, due to optimized contact gap.

Controlled Switching

As option LTB circuit breakers can be used for

controlled switching by applying our controlling device

type SwitchsyncTM.For further information please see

chapter O-1�Controlled Switching�.

Stable Operating Times

For controlled switching it is of the utmost importance

that the functional times for closing and tripping

operations are constant. We can guarantee � 1 ms

for all LTB circuit breakers.

5

Design Features and Advantages

Page 8: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Material

The selected components of aluminum (mechanism

housings, HV-terminals, cubicles) give a high degree

of resistance to corrosion, without the need of extra

protection. For use in extreme trying environments

LTB can be delivered with a protective painting.

The support structure and protective tubes for the pull

rods are made of hot-dipped galvanized steel

Insulators

LTB circuit breaker is as standard delivered with

insulators that consist of high-grade brown-glazed

porcelain or composite insulators (light gray). LTB

with light gray porcelain can be delivered on request.

LTB is available as standard with long creepage

distances.

Longer creepage distances can be quoted on

request.

Mechanical Strength

The mechanical durability gives a sufficient safety

margin for normal wind loads and static and dynamic

forces from conductors.

Seismic Withstand Strength

All LTB circuit breakers can in their standard versions,

withstand seismic accelerations up to 3 m/s2 (0.3 g),

LTBD up to 5 m/s2 in accordance with IEC 1166 and

IEEE 693.

Rating Plates

A rating plate, which includes data for the circuit

breaker, is placed on the operating mechanism

cubicle. The rating plate is made of stainless steel

with engraved text.

Operating Mechanism

The circuit breaker is operated by motor charged

spring operating mechanism(s), which is installed in a

compact splash proof and corrosion resistant housing,

attached to the structure.

• One BLK is used for three-pole operation for LTB D

72.5 - 170 kV.

• Three BLK’s are used for single pole operation for

LTB D 72.5 - 170 kV.

• Three BLK’s are used for single pole operation for

LTB E up to 245 kV.

• One BLG is used for three-pole operation for LTB E

up to 245 kV.

6

Design Features and Advantages

Page 9: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Sealing Systems for SF6 Volume

The sealing system consists of double nitrile rubber

O-rings in all static seals and double X-rings in all

dynamic seals.

This type of sealings has been used in our circuit

7

Design Features and Advantages

breakers for more than 30 years with excellent service

record at varying climatic conditions.

The SF6 gas leakage is less than 0.5% per year.

SF6 Density Monitoring

Since the interrupting capability is dependent on the

density of the SF6 gas, the LTB circuit breaker is

provided with density monitor(s).

The density monitor consists of a temperature

compensated pressure switch. Therefore, alarm signal

and blocking function are activated only if the

pressure drops due to leakage.

The standard version of LTB D for 72.5-170 kV has

one common density monitor for all three poles.

Alternatively LTB D can be provided with one density

monitor per pole.

All LTB E circuit breakers have one density monitor

per pole.

Climatic Withstand

The LTB circuit breakers are designed for, and are

installed in, widely shifting conditions from polar to

desert climate throughout the world.

For circuit breakers installed in areas with extreme low

temperatures there is a risk of condensation of the

SF6 gas. In order to avoid condensation

consequences, one of the following gas-mixtures is

used:

• SF6 and N2

• SF6 and CF

4

Page 10: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Support Structure

Support structures are included in the standard versions

of the LTB circuit breakers. The support structures are

made of hot-dipped galvanized steel. The standard

versions for structures are:

• LTB D 72.5-170 kV One support column per

• LTB E all types One support column per pole

• For detailed information see “Dimensions”

The support structures are prepared for connection to

ground by means of drilled holes on each leg.

High Voltage Terminals

The LTB circuit breakers are as standard equipped with

flat aluminum terminals with thickness 20 mm for LTB D

and 28 mm for LTB E.

The drilling pattern is in accordance with IEC and NEMA

standards. Other dimensions (e.g. DIN) by means of

adapters, are available on request.

Circuit breakers with vertically mounted breaking

elements have terminals on both sides for connection

in either direction.

Circuit breakers with horizontal breaking elements have

one terminal per breaking element. The terminals are

directed upwards.

44.5

22.25

40

40

23 40 40

125

28.5 44.5

14.5(13X)�

8

338

44.5

40

28

D=14(4X)

Design Features and Advantages

Drilled holes for connection

Page 11: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Controlled Switching Devices

The goal for controlled switching is to increase power

quality in the network systems by reducing switching

transients. All LTB circuit breakers are suitable for

controlled switching with ABB’s SwitchsyncTM device.

In order to obtain optimum result the switching instants

should be different for the three phases. For three-pole

operated circuit breakers this is achieved with

mechanically staggered poles.

Presently more than 1,000 HV live tank circuit breakers

manufactured by ABB are in operation with controlled

switching.

Type Tests

The LTB circuit breakers have been type tested in

accordance with IEC and/or ANSI standards. Type test

reports can be presented on request.

Routine Tests

All LTB circuit breakers are routine tested before delivery.

Our test program complies with IEC and ANSI standards.

Transport

The LTB circuit breakers are normally packed and

transported in seaworthy wooden crates.The circuit

breaker poles with one breaking element per pole are

transported as com-plete units.

For circuit breakers with two breaking elements per pole,

the breaking elements and the support insulators are

transported in two separate cases.

For detailed information regarding weights and

dimensions see “Shipping data”.

Breaking elements as well as support insulators are filled

with SF6 gas at a slight overpressure.

Arrival Inspection

On arrival the packaging and contents should be

checked against packing list. In the event of damage to

the goods, contact ABB for advice, before further

handling of the goods takes place. Any damage ought

to be documented (photographed).

SF6 gas

Gas for filling up to rated pressure can be delivered in

bottles, each containing 40 kg gas.

The quantity required for each type of LTB varies from

one circuit breaker type to an-other. This information is

given in the tender.

The pressurizing equipment can be delivered on request,

and is described under “Erection and Commissioning”.

9

Design Features and Advantages

Page 12: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Erection and Commissioning

Assembly instructions are provided with each delivery.

Erection work at site can be done in 1-4 days depending

on LTB type and size.

Filling of SF6 gas to specified rated pressure is done by

using the following pressuri-zing equipment, which can

be delivered on request:

• One special control valve, for connection to the gas

bottle, and a 20 m gas-filled hose with connectors.

• A complementary control valve for connection to CF4

or N2 gas bottle (for mixed gas filling).

When using above equipment gas filling can be carried

out without gas being released into the atmosphere.

For illustration of gas filling equipment see page I-6.

Maintenance

LTB is designed for a service life of more than 30 years

or 10,000 mechanical operations. For current switching

the number of operations before service is dependent

on the interrupted current and type of application.

Inspection, maintenance and overhaul should be carried

out at regular intervals de-pending on the ambient

conditions and the number of operations.

The general actions are described below:

• 1-2 years: Ocular inspection

• 7-10 years or 2,000 mechanical operations: Extended

ocular inspection and some lubrication of the operating

mechanism(s)

• 15-20 years or 5,000 mechanical operations Preventive

maintenance including general inspection of the circuit

breaker and operating mechanism. Operation test

including measurement of operating times and possible

adjustments.

• 30 years or 10,000 mechanical operation: A

comprehensive inspection is recommended to give

increased safety and continued problem-free operation.

The inspection methods and scope depend very

much on the local conditions.

For circuit breakers for special switching duties such as

switching of reactor banks overhaul of the breaking

chamber should be carried out more frequently,

approximately 5,000 operations

Overhaul and repair work must be performed by

authorized personnel only.

The instructions in the manual for operation and

maintenance should be observed.

ABB is available for discussions and advice.

10

Design Features and Advantages

Page 13: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Recommended Spare Parts

High operation frequency (e.g. circuit breakers for

reactor or capacitor switching) and/or large quantities

of circuit breakers:

• Complete poles

• Complete operating mechanisms

• Sets of contacts

• Sets of gaskets

• Density switches

• SF6 gas

Disposal

The disposal of wasted parts should be carried out in

accordance with local legal provisions.

The SF6 gas should not be released into the atmosphere

when the circuit breaker is scrapped. The SF6 gas can

be recycled.

The porcelain can, after it has been crushed, be used

as fill.

The metals used in the circuit breaker can be recycled.

11

Design Features and Advantages

Page 14: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Number of breaks per pole 1 1 1 1 1 1

Rated voltage kV 72.5 145 170 72.5 170 245

Rated frequency Hz 60 60 60 60 60 60

Power frequency withstand voltage

- To earth (Dry/Wet) kV 160/140 310/275 365/315 160/140 365/315 425/350

-Across open pole(Dry/Wet) kV 160/140 310/275 365/315 160/140 365/315 425/350

Lightning Impulse Withstand Voltage

- To earth kV 325 650 750 350 750 900

-Across open pole kV 325 650 750 350 750 900

Chopped Wave Impulse Withstand Voltage

To earth (2�s) kV 452 838 968 452 968 1160

Across open pole(2 �s) kV 452 838 968 452 968 1160

Switching Impulse Withstand Voltage

- To earth and/between phases kV - - - - - -

-Across open pole kV - - - - - -

Creepage distance mm/kV 25 25 25 25 25 25

Rated normal current A 3000 3000 3000 4000 4000 4000

Rated s.c current kA 40 40 40 50 50 50

First-pole-to-clear factor 1.5 1.5 1.5 1.5 1.5 1.5

Rated closing and latching current kA 104 104 104 104 104 104

Duration of short time withstand circuit s 3 3 3 3 3 3

Closing time ms < 40 < 40 < 40 < 55 < 55 < 55

Opening time ms 22 22 22 17 17 17

Break time ms 40 40 40 40 40 40

Dead time ms 300 300 300 300 300 300

Rated Standard Operating Duty - O-0.3s-CO-3min-CO or CO-15s-CO

12

Technical Data

LTB

72.

5D1/

B

LTB

145

D1/

B

LTB

170

D1/

B

LTB

72.

5E1

LTB

170

E1

LTB

245

E1

Technical Data According to ANSI

Page 15: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

13

Technical Data

Number of breaks per pole 1 1 1 1 1 1

Rated voltage kV 72.5 145 170 72.5 170 245

Rated frequency Hz 50 50 50 50 50 50

Power frequency withstand level1)

- To earth and between phases kV 140 275 325 140 325 460

-Across open pole kV 140 275 325 140 325 460

Lightning Impulse Withstand Level(LIWL)

- To earth and between phases kV 325 650 750 325 750 1050

-Across open pole kV 325 650 750 325 750 1050

Switching Impulse Withstand Level(SIWL)

- To earth and/between phases kV - - - - - -

-Across open pole kV - - - - - -

Creepage distance mm/kV 25 25 25 25 25 25

Rated normal current A 3150 3150 3150 4000 4000 4000

Rated s.c breaking current kA 40 40 40 50 50 50

First-pole-to-clear factor 1.5 1.5 1.5 1.5 1.5 1.5

Making current peak kA 100 100 100 125 125 125

Duration of short circuit s 3 3 3 3 3 3

Closing time ms < 40 < 40 < 40 < 55 < 55 < 55

Opening time ms 22 22 22 17 17 17

Break time ms 40 40 40 40 40 40

Dead time ms 300 300 300 300 300 300

Rated Operating Sequence - O-0.3s-CO-3min-CO or CO-15s-CO

LTB

72.

5D1/

B

LTB

145

D1/

B

LTB

170

D1/

B

LTB

72.

5E1

LTB

170

E1

LTB

245

E1L

Technical Data According to IEC

Page 16: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

A

2530

1740

D

2503

C

B

EF

E267

F

E

1750

E267

A

2503

C

B

D

Dimensions-LTBDimensions -LTBDLTB D1/B Two-Column Stand,

Three-pole Operation

Rated Voltage: 72.5 - 170 kV

Dimensions(mm)

Rated A B C D E F

Voltage

72.5 kV 4647 1164 670 3283 1050 3230

145 kV 5197 1164 1220 3833 1750 4630

170 kV 5808 1475 1520 4133 1750 4630

Available dimensions for phase distances

and heighes to lowest part of insulator(mm)

Rated phase distancesVoltage

72.5 kV 1050* 1500* 1750* 2000 2500

145 kV - 1500* 1750 2000 2500

170 kV - - 1750 2000 2500

*) Standard **)BIL550kV

ated Height to lowest part of insulator**Voltage

72.5 kV 1123 2503* 2945 3528

*) Standard

**) Other dimensions can be provided

LTB D1/B Three-Column Stand,Three-pole Operation

Rated Voltage: 72.5 - 170 kVDimensions(mm)

Rated A B C D E F

Voltage

72.5 kV 4647 1164 670 3283 1050 3266

145 kV 5197 1164 1220 3833 1750 4666

170 kV 5808 1475 1520 4133 1750 4666

Available dimensions for phase distances

and heighes to lowest part of insulator(mm)

Rated phase distancesVoltage

72.5 kV 1050* 1500* 1750* 2000 2500 3000

145 kV - 1500* 1750 2000 2500 3000

170 kV - - 1750 2000 2500 3000

*) Standard **)BIL550kV

Rated Height to lowest part of insulator**Voltage

72.5 kV 800 2503* 2950 3203

*) Standard

**) Other dimensions can be provided

Dimensions-LTB

14

Page 17: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Dimensions --LTBE

LTB E1 Three-pole Operation

Rated Voltage: 72.5 - 245 kV

Dimensions(mm)

Rated A B C D E F

Voltage

72.5 kV 4790 1292 655 3244 1100 3590

170 kV 5400 1292 1265 3854 3500 6390

245 kV 6703 1914 1955 4544 3500 8390

Available dimensions for phase distances

and heighes to lowest part of insulator(mm)

Rated phase distancesVoltage

72.5 kV 1100* 1500 2500 3000 3500 4000

170 kV - - 2500* 3000 3500 4000

245 kV - - 2500 3000 3500 4000

*) Standard

Rated Height to lowest part of insulator**Voltage

72.5-245 kV 1950 2508* 2992 3642 4142

*) Standard

LTB E1 Single-pole Operation

Rated Voltage: 72.5 - 245 kV

Rated A B C D E F

Voltage

72.5 kV 4790 1292 655 3244 2500 6298

170 kV 5400 1292 1265 3854 2500 6298

245 kV 6703 1914 1955 4544 3500 8298

*)Recommended phase distances

Available dimensions for phase distances

and heighes to lowest part of insulator(mm)

Rated Height to lowest part of insulator**Voltage

72.5-245 kV 1442 2508* 2992 3642 4142

*) Standard

15

Dimensions-LTB

Page 18: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY

Shipping Data for LTB

Shipping Data for LTBD

LTB 72.5D1/B,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weightcases L x W x H (m) (Kg)

Breaker Poles 1 3.26 x 1.78 x 0.72 1045Operating mechanism 1 1.18 x 1.05 x 1.00 250Support Structure 1 2.40 x 0.58 x 0.44 330Total 3 6.0 m3 1625

LTB 145D1/B,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weightcases L x W x H (m) (Kg)

Breaker Poles 1 3.26 x 1.78 x 0.72 1155Operating mechanism 1 1.18 x 1.05 x 1.00 250Support Structure 1 2.40 x 0.58 x 0.44 330Total 3 6.0 m3 1735

LTB 170D1/B,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weightcases L x W x H (m) (Kg)

Breaker Poles 1 3.90 x 1.78 x 0.72 1270Operating mechanism 1 1.18 x 1.05 x 1.00 250Support Structure 1 2.40 x 0.58 x 0.44 330Total 3 6.9 m3 1850

LTB 170D1/B,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weightcases L x W x H (m) (Kg)

Breaker Poles 1 3.26 x 1.78 x 0.72 1045Operating mechanism 1 1.18 x 1.05 x 1.00 250Pole Beam 1 2.69 x 0.57 x 1.00 200Support Structure 1 2.40 x 0.58 x 0.44 220Total 3 7.6 m3 1715

LTB 145D1/B,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weightcases L x W x H (m) (Kg)

Breaker Poles 1 3.26 x 1.78 x 0.72 1155Operating mechanism 1 1.18 x 1.05 x 1.00 250Pole Beam 1 4.09 x 0.57 x 1.00 250Support Structure 1 2.40 x 0.58 x 0.44 220Total 4 8.4 m3 1875

LTB 170D1/B,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weightcases L x W x H (m) (Kg)

Breaker Poles 1 3.90 x 1.78 x 0.72 1270Operating mechanism 1 1.18 x 1.05 x 1.00 250Pole Beam 1 4.09 x 0.57 x 1.00 250Support Structure 1 2.40 x 0.58 x 0.44 220Total 4 9.2 m3 1990

Shipping Data for LTB D

16

Page 19: Live Tank Circuit Breaker - SME-Powersme-power.com/pic/other/2014-11-05-14-37-424.pdf · Live Tank Circuit Breaker ... from the operating mechanism. ... Breaking Chamber 2.Support

LTB FAMILY Shipping Data for LTB E

17

Shipping Data for LTB

Shipping Data for LTBE

LTB 72.5 and 170E1,Three-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weight(Kg)

cases L x W x H (m) 72.5 170

LTB 72.5 Breaker Poles 1 on request on request -

LTB 170 Breaker Poles 1 5.90 x 1.90 x 0.97 - 3600

Operating Mechanism 1 1.80 x 0.97 x 1.07 550 550

Support Structure 1 2.38 x 1.10 x 0.36 280 280

LTB 72.5 3 on request on request -

LTB 170 3 13.7 m3 - 4430

LTB 72.5 and 170E1,Single-pole Operated, Three-Column Stand

Equipment Number of Dimensions Gross Weight(Kg)

cases L x W x H (m) 72.5 170

LTB 72.5 Breaker Poles 1 on request on request -

LTB 170 Breaker Poles 1 5.90 x 1.90 x 0.97 - 3600

Operating Mechanism 1 2.50 x 1.17 x 1.00 1000 1000

Support Structure 1 2.38 x 1.10 x 0.36 280 280

LTB 72.5 3 on request on request -

LTB 170 3 14.7 m3 - 4880

LTB 245 E1-Three-pole Operated

Equipment Number of Dimensions Gross Weight(Kg)

cases L x W x H (m)

Breaker Poles 1 5.90 x 1.90 x 0.97 3600

Operating Mechanism 1 1.80 x 0.97 x 1.07 550

Support Structure 1 2.38 x 1.10 x 0.36 280

Total 3 13.7 m3 4430

LTB 245 E1-Single-pole Operated

Equipment Number of Dimensions Gross Weight(Kg)

cases L x W x H (m)

Breaker Poles 1 5.90 x 1.90 x 0.97 3600

Operating Mechanism 1 2.50 x 1.17 x 1.00 1000

Support Structure 1 2.38 x 1.10 x 0.36 280

Total 3 14.7 m3 4880