demolition / relocation designations this is a...
TRANSCRIPT
Revisions
No. Date Description
A B C D E F G H
1
2
3
4
5
6
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors
or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any
purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Drawing
No.
Scale
7
I
8
CONFIDENTIAL INFORMATION: The information set forth hereon constitutes confidential proprietary technology of PPG INDUSTRIES, Inc. In
consideration of the opportunity to supply goods or services to or on behalf of PPG requiring the use of said information, the recipient of this document agrees: (1)
not to copy or reproduce said document in whole or in part without prior written authorization by PPG; (2) to return said document upon demand by PPG; (3) to
make no use of said information other than for supplying goods or services in connection with the installation shown in the title without prior written authorization by
PPG; (4) not to disclose said document or the information it includes to any third party.
DISCIPLINE ITEM NO.
DO NOT SCALE THIS PRINT
DRAWN BY
CHECKED
APPROVED
FRAME NO.
DATE
DATE
1 2 3 4 5 60
THIS PRINT SUPERSEDES ALL PRINTS
PRIOR TO REVISION
WORKS NO. OPERABLE UNITLINE NO.
Seal:
1
2
3
4
5
6
7
8
J
DATE
Title:
SUBJECT
INDEX
KEY PLAN
2820
FOX
BURBANK, CA 91504
2890 WEST EMPIRE AVENUE
PPG AEROSPACE
(724) 285-4761
(724) 285-6815
400 Morgan Center
101 East Diamond Street
Butler, PA 16001-5923
www.stantec.com
Tel:
Fax:
Stantec Architecture Inc.
2017.08.041 PACKAGE 2
FOX PROPERTY - PHASE 2
E-001NTS
L1
S
CR
ELECTRICAL COVER SHEET
ELECTRICAL SYMBOLS SCHEDULE
PENDANT TUBE FIXTURE
1X1 FIXTURE
1X4 FIXTURE
OF FIXTURES AS INDICATED ON PLAN.
LIGHTING TRACK - LENGTH OF TRACK AND NO.
'a' - INDICATES REMOTE FIXTURES POWERED
BATTERY PACK W/ NO. OF HEADS AS SHOWN.
BATTERY PACK.
REMOTE EMERGENCY HEAD - 'a' INDICATES
BATTERY PACK.
REMOTE EMERGENCY DNLT - 'a' INDICATES
BRANCH CIRCUIT RUN CONCEALED
HOME RUN TO PANEL 2A CKTS 1, 3, & 5
NORMAL & EMERGENCY BRANCH CIRCUIT
EMERGENCY ONLY BRANCH CIRCUIT
NIGHT LIGHT BRANCH CIRCUIT
LOW VOLTAGE CIRCUIT
THERMITE WELD OF GROUND CONDUCTORS
GROUND CONDUCTOR RUN CONCEALED
LIGHTNING PROTECTION
CONNECTION TO AIR TERMINAL FOR
THERMITE WELD TO GROUND ROD
GROUND ROD TRIODE
BRANCH CIRCUIT UP OR DOWN
JUNCTION BOX OR PULL BOX
KEY-LOCK SWITCH
PILOT-LIGHT SWITCH
LIGHTED-HANDLE SWITCH
EXPLOSION-PROOF SWITCH
TIMER SWITCH
TIMECLOCK
EXTERIOR PHOTOCELL
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SAFETY TYPE DUPLEX RECEPTACLE
ISOLATED GROUND TYPE DUPLEX RECEPTACLE
SINGLE RECEPTACLE
COORDINATE LOCATION WITH SUPPLIER
DUPLEX FOR ELECTRIC WATER COOLER
OUTLET ON WALL SWITCH
DUPLEX SPLIT WIRED WITH BOTTOM
RECEPTACLE WITH WEATHERPROOF COVER
EXPLOSION-PROOF RECEPTACLE
SURFACE MTD PANELBOARD
FLUSH MTD PANELBOARD
MOTOR CONNECTION
DISCONNECT SWITCH
MAGNETIC STARTER
COMBINATION STARTER/DISCONNECT
MANUAL PULL STATION
FIRE ALARM SPEAKER - CEILING MTD
PHOTOELECTRIC TYPE SMOKE DETECTOR
THERMAL TYPE DETECTOR
FLOW SWITCH
TAMPER SWITCH
ELECTROMAGNETIC SHUTTER HOLDER
ELECTROMAGNETIC DOOR HOLDER
PRESSURE SWITCH FOR DRY TYPE SYSTEM
REMOTE TROUBLE BELL
FIREMANS TELEPHONE JACK
FIRE ALARM CONTROL PANEL
FIRE ALARM COMMAND CENTER
FIRE ALARM ANNUNCIATOR
FIRE ALARM PUNCH TAPE RECORDER
POWER COMPANY METER
C. T. CABINET
EMERGENCY POWER OFF SWITCH
GENERAL SYMBOLS
KEY NOTE INDICATOR
DRAWING REVISION INDICATOR
6
2
E
NL
NE
EM
LV
2A-1,3,5
J
G
G
G
G G
G
G
G
G
S S2
S3S4
S
T
S
S
SD
S
S
SP
SK
L
EXP
T
PC
S
EPO
IG
IG/SP
EWC
WP
EXP
FF
FP
M
C T
M
TRANSFORMER
FIRE ALARM BELL
FS
FS
FS
FS
ID
ID
RI
PD
PD
TD
TD
D
D
R
FS
TS
PS
SH
TB
DH
DC
FT
FACC
FAA
FTR
GROUNDING AND LIGHTNING PROTECTION
FACP
FDGP FIRE ALARM DATA GATHERING PANEL
a
a
a
DROP CORDD
AUTOMATIC DOOR
MD
PP
KS
PR
PS
PUSH PLATE
KEY SWITCH
POWER RESET
PRESENCE SENSOR
OHJ
H
C
FSCP FIRE SUPPRESSION CONTROL PANEL
SI DOOR MOUNTED SAFETY INTERLOCK
KEY OPERATED REMOTE CONTROL UNIT
2 SCHEDULED ITEM INDICATOR
BRANCH CIRCUIT RUN UNDER FLOOR
UP
EXEXISTING BRANCH CIRCUIT
INDICATES CONNECTION TO EXISTING
PE
EP
PNEUMATIC TO ELECTRIC DEVICE
ELECTRIC TO PNEUMATIC DEVICE
2A-2
KR
RI REMOTE INDICATOR
ES ELECTRIC STRIKE
NO. OF CONDUCTORS TO BE INSTALLED
SURFACE METAL RACEWAY SIZED FORSMR
CT CABLE TRAY
FIRE, SMOKE OR FIRE/SMOKE DAMPER
RA
CONDUIT AND WIRING
ELECTRICAL DEVICES
COMMUNICATIONS
FIRE ALARM SYSTEMLIGHTING
SECURITY SYSTEM
EMERGENCY BATTERY PACK
M
G
FS
TD
PD
PDD
R
FLUSH-FLOOR MOUNTED RECEPTACLE
PEDESTAL-FLOOR MOUNTED RECEPTACLE
FLUSH MOUNTED DISTRIBUTION PANEL
SURFACE MOUNTED DISTRIBUTION PANELBOARD
MANUAL MOTOR STARTER
FUSED DISCONNECT SWITCH
GROUNDING BUS BAR
GROUND CONNECTION
DUPLEX RECEPTACLE ON NORMAL/EMERGENCY
OPERATOR HEAD JUNCTION POWER CONNECTION
HORN (ONLY)
HORN AND STROBE LIGHT
CHIME AND STROBE LIGHT
STROBE LIGHT
FIRE ALARM SPEAKER
FIRE ALARM SPEAKER WITH TRUMPET
IONIZATION TYPE SMOKE DETECTOR
E THERMAL TYPE DETECTOR FOR ELEVATOR SHUNT TRIP
E
THERMAL TYPE DETECTOR MOUNTED TO DUCT
IONIZATION TYPE DETECTOR MOUNTED TO DUCT
REMOTE ANNUNCIATOR FOR DETECTOR
PHOTOELECTRIC TYPE SMOKE DETECTOR WITH RELAY
REMOTE TEST SWITCH FOR DETECTOR
FAEP FIRE ALARM EXTENDER PANEL
BD
BDT
BEAM DETECTOR - RECEIVER
BEAM DETECTOR - TRANSMITTER
PS
SINGLE-POLE DOUBLE-POLE 3-WAY & 4-WAY SWITCHES
AC
1 MECHANICAL EQUIPMENT INDICATOR
ISOLATED GROUND TYPE WITH SURGE SUPRESSION
GROUND CONDUCTOR RUN UNDER FLOOR
THERMITE WELD TO BLDG OR EQUIPMENT
FIRE ALARM SYSTEM ACTIVATED DOOR CLOSER
CLGRECEPTACLE MOUNTED ON CEILING
DETAIL INDICATOR
ELEVATION/SECTION INDICATOR
V F D VARIABLE FREQUENCY DRIVE
M
MEDIUM VOLTAGE SWITCH
MEDIUM VOLTAGE SWITCH AND FUSE
2
STSHUNT TRIP CIRCUIT BREAKER
LOW VOLTAGE DRY TYPE TRANSFORMER
AUTOMATIC TRANSFER SWITCH
G EMERGENCY GENERATOR
DIGITAL METER
CURRENT TRANSFORMER
600
4
DM
ELECTRICAL SINGLE LINE
CONTACT CLOSURE INTERFACE
S
SOS INTEGRAL WALL SWITCH/ OCCUPANCY SENSOR
OS-2P
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
PD
????
??
????
??
THIS LIST OF ABBREVIATIONS IS PROVIDED FOR
CONVENIENCE ONLY. ITEMS LISTED HERE MAY OR
MAY NOT BE USED ON THIS PROJECT.
A/C AIR CONDITIONING UNITAC ALTERNATING CURRENTACT ABOVE CEILING TILE
AFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNIT
ATS AUTOMATIC TRANSFER SWITCH
ALT ALTERNATE
AVG AVERAGE
BKR BREAKERBLDG BUILDINGBTM BOTTOM
CAP CAPACITYCFM CUBIC FEET/MINUTECIRC CIRCULATINGCKT CIRCUIT
CLG CEILING
CONC CONCRETECONN CONNECTION
CONT CONTINUOUS
DED DEDICATED
DIAM DIAMETERDIM DIMENSIONDISC DISCONNECT
DPR DAMPER
EC ELECTRICAL CONTRACTORELEC ELECTRICALELEV ELEVATOR
EXH EXHAUSTEXIST EXISTING
FACP FIRE ALARM CONTROL PANELFBO FURNISHED BY OTHERS
FPC FIRE PROTECTION CONTRACTOR
FAB FABRICATE
FIXT FIXTURE
FLR FLOOR
HW HOT WATER
HORIZ HORIZONTAL
HTG HEATING
MECH MECHANICAL
RECEPT RECEPTACLE
TEMP TEMPERATURE
XFMR TRANSFORMER
ABBREVIATIONS
ELECTRICAL
SECT SECTIONSIM SIMILARSQ FT SQUARE FOOTSTAT THERMOSTATSTD STANDARDSTL STEEL
SUSP CLG SUSPENDED CEILING
RM ROOMREQD REQUIRED
REC RECESSEDRA RETURN AIR
SW SWITCH
SUSP SUSPENDEDSURF SURFACESTRUCT STRUCTURALSTOR STORAGE
T-STAT THERMOSTATTV TELEVISION
TYP TYPICAL
TERM TERMINAL
UG UNDERGROUNDUH UNIT HEATERUV UNIT VENTILATOR
VT VAPOR TIGHT
VERT VERTICALVDT VISUAL DISPLAY TERMINAL
WP WEATHERPROOFWT WEIGHT
PTs POTENTIAL TRANSFORMERS
PRESS SW PRESSURE SWITCHPNL PANELPLBG PLUMBING
PS PULL SWITCH
PH PENTHOUSEPEND PENDANT
PC PLUMBING CONTRACTORPE PNEUMATIC-ELECTRIC
OH OVERHEAD
OC ON CENTER
OPNG OPENING
NTS NOT TO SCALE
NO NUMBERNOM NOMINAL
MTG MOUNTINGMTD MOUNTEDMLO MAIN LUG ONLYMISC MISCELLANEOUSMIN MINIMUM
MFR MANUFACTURER
MAX MAXIMUM
MH MANHOLE
MC MECHANICAL CONTRACTORMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTER
MER MECHANICAL EQUIPMENT ROOM
LVR LOUVER
LTS LIGHTSLTG LIGHTING
LV LOW VOLTAGE
JT JOINT
JAN JANITORJB JUNCTION BOX
INSUL INSULATIONINST INSTANTANEOUSINCL INCLUDE
HZ HERTZ
HP HORSEPOWER
HGT HEIGHT
HV HIGH VOLTAGE
GA GAUGE
GC GENERAL CONTRACTORGFI GROUND FAULT INTERRUPTER
FU FUSEFTN FOUNTAIN
FLUOR FLUORESCENT
FLASH FLASHING
FIN FINISH
FP FIRE PROTECTION
F & I FURNISHED AND INSTALLED
EXTER EXTERIOR
EQUIP EQUIPMENTEP ELECTRIC-PNEUMATICENCL ENCLOSUREEM GEN EMERGENCY GENERATOREM EMERGENCY ONLY
EA EACH
EWC ELECTRIC WATER COOLER
DWG DRAWING
DN DOWNDIV DIVISION
DHW DOMESTIC WATER HEATERDF DRINKING FOUNTAINDET DETAIL
CU COPPER
CRT CATHODE RAY TUBECPU CENTRAL PROCESS UNITCONTR CONTRACTOR
CONST CONSTRUCTION
CO COMPANY
CL CENTERLINE
CT CURRENT TRANSFORMERS
C CONDUIT
AUTO AUTOMATIC
ARCH ARCHITECTURAL
ADJ ADJUSTABLE
AL ALUMINUM
A AMPS
1/C SINGLE CONDUCTOR
NIC NOT IN CONTRACTNE NORMAL/EMERGENCY
"H" - HEAD MOUNTED; "C" - CEILING MOUNTED
MOTION DETECTOR
- CEILING MOUNTED
COMBINATION SPEAKER/STROBE LIGHT
COMBINATION SPEAKER/STROBE LIGHT
PHOTOELECTRIC TYPE DETECTOR MOUNTED TO DUCT
RECAPTURE
PHOTOELECTRIC TYPE DETECTOR FOR ELEVATOR
NOT BE USED ON THIS PROJECT.
REFERENCE ONLY. SYMBOLS SHOWN HERE MAY OR MAY
THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS FOR
HEIGHT. TYPICAL UNLESS NOTED OTHERWISE
INDICATES OUTLET TO BE MOUNTED 8" ABOVE COUNTER
OTHERWISE NOTED
OUTLETS MOUNTED ON 1'-0" CENTERS UNLESS
SURFACE MOUNTED MULTI-OUTLET ASSEMBLY DUPLEX
TO PIPING OR EQUIPMENT
BONDING PLATE OR CLAMP CONNECTION
MOTORIZED DAMPER
CONTROL MODULE
MONITOR MODULE
DHSMOKE DETECTOR FOR DOOR HOLDS
POWER DISTRIBUTION
DRAW OUT MEDIUM VOLTAGE (15KV OR 5KV) CIRCUIT BREAKER
DRAW OUT LOW VOLTAGE (480V OR 208) CIRCUIT BREAKER
LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER
STARTER SIZECOMBINATION MOTOR STARTER- NUMBER INDICATES
MEDIUM VOLTAGE LIQUID FILLED TRANSFORMER
CC
TWO-POLE OCCUPANCY SENSOR WITH INTEGRAL SWITCH
CM
MM
FEEDER SIZE INDICATOR
DUPLEX RECEPTACLE FLOOR BOX
DOUBLE DUPLEX RECEPTACLE FLOOR BOX
EMERGENCY PUSH BUTTON
EXISTING SURFACE MTD PANELBOARD
EXISTING FLUSH MTD PANELBOARD
GENERAL NOTES
AFCI ARC FAULT CIRCUIT INTERRUPTER
GAL GALLONS
GRD GROUND
DEMOLITION / RELOCATION DESIGNATIONS
RELOCATED DEVICE.
EXISTING DEVICE TO REMAIN.
RR
RR
ER
ER
ETR
ETR
REMOVE EXISTING ELECTRICAL DEVICE.
REMOVE & RELOCATE EXISTING ELECTRICAL DEVICE.
SINGLE LINE DRAWING, AS APPLICABLE.)
(SHOWN FOR CLARITY/COORDINATION WITH
EXISTING ELECTRICAL PANEL REMOVED BY OWNER. RX/OD
RX
RX
AND DEVICES SHOWN ON PLANS.)
(NOTATIONS SHOWN ABOVE TO BE TYPICAL FOR ALL EQUIPMENT
ETL EXISTING TO BE RELOCATEDETR EXISTING TO REMAIN
ETD EMERGENCY TRANSFER DEVICE
DT
MMOTOR-RATED SWITCH/DISCONNECT
CIRCUIT (GRAY RECEPTACLE)
DUPLEX RECEPTACLE ON DEDICATED
CIRCUIT
NORMAL CIRCUIT & ONE DUPLEX (GRAY) ON DEDICATED
DOUBLE DUPLEX RECEPTACLE WITH ONE DUPLEX ON
TELE TELEPHONE
THK THICKTRF TRANSFORMER
VOL VOLUMEVFD VARIABLE FREQUENCY DRIVE
RX REMOVE
JPF
POWER FEED AT MOVEABLE PARTITION
FHPOWER FEED AT LABORATORY FUME HOOD
(COORDINATE MTG. HT. W/ARCH.)
RECEPTACLE FOR DISPLAY SCREEN/TV
J
PFPT POKE-THRU ASSEMBLY W/"PF" DESIGNATING POWER FEED
PEDESTAL-COUNTER MOUNTED RECEPTACLE
FVNR FULL VOLTAGE NON-REVERSING (MOTOR STARTER)
RVNR REDUCED VOLTAGE NON-REVERSING (MOTOR STARTER)
PP POWER POLE
GENERAL DEMOLITION NOTES
FB FLOOR BOX WITH POWER FEED AT MOVEABLE PARTITION
CONTROLLED RECEPTACLE
S
S
ONE UNCONTROLLED RECEPTACLE
SPLITWIRED RECEPTACLE WITH ONE CONTROLLED AND
DUPLEX AND ONE UNCONTROLLED DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE WITH ONE CONTROLLED
GFI DEADFRONT GFCI DEVICE
GFCI DUPLEX RECEPTACLE
WPWEATHERPROOF HORN AND STROBE LIGHT
HW
HWHALLWAY COVERAGE PATTERN
WALL MOUNTED PASSIVE INFRARED OCCUPANCY SENSOR,
OCCUPANCY & DAYLIGHT SENSORS
FaS
Sa'a' SWITCH NO.
'S' SWITCH TYPE
SWITCH DESIGNATIONS:
(ON/OFF, RAISE, LOWER)
LOW VOLTAGE WALL DIMMER SWITCH - 3 BUTTON
LV2 (ON, OFF)
LOW-VOLTAGE WALL SWITCH - 2 BUTTON
SLV3
(FULL ON, PARTIAL ON, OFF)
LOW-VOLTAGE WALL SWITCH - 3 BUTTON
STS
SSC LIGHTING SCENE CONTROL STATION
LIGHTING CONTROL SYSTEM TOUCHSCREEN INTERFACE
DL
'DL' AUTOMATIC DAYLIGHTING CONTROLLED FIXTURE
'2A-2' PANEL 2A CKT #2
'a' SWITCH NO.
'F' FIXTURE TYPE
FIXTURE DESIGNATIONS:
FB FLOOR BOX
F
RELOCATED BY THE OWNER.
PROCESS EQUIPMENT WITH OWNER. EQUIPMENT IS EXISTING AND
COORDINATE EXPLOSION-PROOF RECEPTACLE REQUIREMENTS FOR 30.
LEAVING THE CLASSIFIED AREA.
AREAS, PROVIDE RIGID CONDUIT AND CONDUIT SEALS ON CONDUIT
AS REQUIRED BY CALIFORNIA ELECTRICAL CODE IN HAZARDOUS / LISTED 29.
APPLICABLE.
SPACES. INSTALL CONDUIT TIGHT TO CEILING OR BUILDING STEEL, AS
GRID LINES, PARTICULLARLY IN OPEN CEILING OR LABORATORY CEILING
INSTALL RACEWAYS PARALLEL AND/OR PERPENDICULAR TO BUILDING 28.
SHOWN.
AND THE SPECIFICATIONS, PROVIDE THE HIGHEST RATING SPECIFIED OR
UPSTREAM DEVICE. IF THERE IS A CONFLICT BETWEEN THE DRAWINGS
DEVICES OR EQUIPMENT SHALL BE RATED THE SAME AS THE NEAREST
WHERE NO SHORT CIRCUIT INTERRUPT/WITHSTAND RATING IS INDICATED, 27.
OPERATIONAL.
BALANCE PANEL PHASES ONCE USER EQUIPMENT IS INSTALLED AND 26.
EQUIPMENT. MAINTAIN ACCESSIBILITY TO CONTROLS.
CONTRACTORS FOR LOCATION AND POWER REQUIREMENTS OF
COORDINATE WITH HVAC, PLUMBING, AND FIRE PROTECTION 25.
CEILINGS.
MAINTAIN ACCESS TO ALL COMMUNICATIONS RACEWAYS ABOVE LAY-IN 24.
CENTER OF THE CEILING TILES, UNLESS OTHERWISE NOTED.
CEILING MOUNTED ELECTRICAL DEVICES SHALL BE MOUNTED IN THE 23.
SEE ARCHITECTURAL FLOOR PLANS FOR WALL CONSTRUCTION TYPES.22.
ARCHITECTURAL REFLECTED CEILING PLANS.
DRYWALL OR PLASTER CEILINGS. COORDINATE CEILING TYPES WITH
PROVIDE PLASTER FLANGES FOR RECESSED LIGHTING FIXTURES IN 21.
ARE NOT ACCEPTABLE.
SMR SHALL BE ATTACHED TO WALL WITH PLUGS AND SCREWS. TAP CONS 20.
STRUCTURE.
FIXTURES. 2x4 PENDANT FIXTURES SHALL HAVE 4-POINT SUPPORT ON
PROVIDE MINIMUM 2 POINT SUPPORT FROM STRUCTURE TO LIGHTING 19.
WELL AS FACTORY ELBOWS AND MISCELLLANEOUS END PLATES.
PROVIDE RISER DUCTS AS REQUIRED WHEN SMR ELEVATION CHANGES AS
VERIFY SMR LOCATIONS IN REFERENCE TO CASEWORK LOCATIONS. 18.
ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION.
COORDINATE ELEVATION AND LOCATION OF ELECTRICAL DEVICES WITH 17.
HAVE ITS OWN INDIVIDUAL FULL SIZE NEUTRAL BACK TO PANEL.
EACH DESIGNATED CIRCUIT HOMERUN SERVING RECEPTACLES SHALL 16.
ON ALL RACEWAYS WHICH CROSS ANY BUILDING EXPANSION JOINTS.
THE USE OF APPROVED TYPE EXPANSION FITTINGS SHALL BE REQUIRED 15.
OF USE.
PROVIDE A GREEN GROUND WIRE FOR EACH COMMON NEUTRAL TO POINT
HAVING EXISTING CIRCUITS SERVING AREAS BEYOND THIS PROJECT,
CONDUITS DESIGNATED BY THE ELECTRICAL TRADE TO BE REUSED, AND
AND ALL EXISTING CIRCUITS TO BE REUSED IN THIS PROJECT. IN EXISTING
PROVIDE A GREEN GROUND WIRE FROM PANEL FOR ALL NEW CIRCUITS 14.
EXACT LOCATIONS WITH THE MECHANICAL TRADE.
MECHANICAL EQUIPMENT AND DUCTWORK IS INSTALLED. COORDINATE
LOCATE JUNCTION BOXES AS REQUIRED TO ALLOW ACCESS AFTER 13.
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
FIXTURES, ETC. TO MEET THE CONSTRUCTION SCHEDULE SHALL BE THE
ANY ADDITIONAL COST TO ENSURE DELIVERY OF PANELS, LIGHT 12.
MOUNTED.
INSTALLED IN GYPSUM BOARD CONSTRUCTION, THEY SHALL BE RECESS
RACEWAY. WHERE DUPLEX RECEPTACLES ARE SHOWN AND CAN BE
WALLS WITH SURFACE MOUNTED OUTLET BOX AND SURFACE METAL
DUPLEX RECEPTACLES SHALL BE SURFACE MOUNTED ON MASONRY 11.
OF EACH SHIFT.
AREAS SHALL BE CLEANED AND LEFT IN ORIGINAL CONDITION AT THE END 10.
END OF THAT SHIFT.
BEING PERFORMED DURING THAT SHIFT AND SHALL BE REPLACED AT THE
CEILING TILE SHALL ONLY BE REMOVED FROM AREAS WHERE WORK IS 9.
PAINTING, CONCRETE, ETC. REQUIRED TO COMPLETE THIS PROJECT.
ELECTRICAL TRADE SHALL BE RESPONSIBLE FOR CUTTING, PATCHING, 8.
ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE.
EQUIPMENT SHALL BEAR U.L. LABELS AND BE GROUNDED AND BONDED IN 7.
MINIMUM CONDUIT SIZE SHALL BE 3/4"6.
POWER CIRCUITS.
WIRES SMALLER THAN #12 AWG SHALL NOT BE USED FOR LIGHTING OR 5.
PAY ALL FEES.
ELECTRICAL CONTRACTOR AND THE ELECTRICAL CONTRACTOR SHALL
PERMITS NECESSARY FOR THIS WORK SHALL BE OBTAINED BY THE 4.
WORK SHALL MEET THE APPROVAL OF THE OWNER'S REPRESENTATIVE.3.
RULES AND REGULATIONS OF THE LOCAL MUNICIPALITY.
WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE N.E.C. AND ALL 2.
TO THE PHASING AS OUTLINED BY THE OWNER.
BEEN DIVIDED INTO SEVERAL PHASES AND ALL TRADES MUST CONFORM
THE DEMOLITION AND CONSTRUCTION WORK FOR THIS PROJECT HAVE 1.
DOJ POWER FEED AT DOOR OPERATOR
ASENSOR, HALLWAY COVERAGE PATTERN
CEILING MOUNTED PASSIVE INFRARED OCCUPANCY
DT/DS SENSOR WITH INTEGRAL DAYLIGHT SENSOR
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY
DS CEILING MOUNTED DAYLIGHT SENSOR
"x" INDICATES SWITCH LEG (TYPICAL)
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
DTx
2X4 FIXTURE
CENTER DIFFUSER, IF PRESENT ON FIXTURE
2X2 FIXTURE - LINE INDICATES ORIENTATION OF
EMERGENCY BATTERY PACK)
2X4 FIXTURE (" " - DESIGNATES FIXTURE WITH
EMERGENCY BATTERY PACK)
2X2 FIXTURE (" " - DESIGNATES FIXTURE WITH
WITH EMERGENCY BATTERY PACK)
1X1 FIXTURE (" " - DESIGNATES FIXTURE
WITH EMERGENCY BATTERY PACK)
1X4 FIXTURE (" " - DESIGNATES FIXTURE
WITH EMERGENCY BATTERY PACK)
FLUORESCENT STRIPLIGHT (" " - DESIGNATES FIXTURE
WITH EMERGENCY BATTERY PACK)
PENDANT TUBE FIXTURE (" " - DESIGNATES FIXTURE
LED STRIPLIGHT
CEILING MOUNTED LIGHT FIXTURE
CEILING MOUNTED WALL WASHER
WALL MOUNTED FIXTURE
POLE MOUNTED FIXTURE
CEILING MOUNTED EXIT SIGN W/ ARROWS AS INDICATED
WALL MOUNTED EXIT SIGN W/ ARROWS AS INDICATED
FIXTURE WITH EMERGENCY BATTERY PACK)
CEILING MOUNTED WALL WASHER (" " - DESIGNATES
WITH EMERGENCY BATTERY PACK)
CEILING MOUNTED FIXTURE (" " - DESIGNATES FIXTURE
WITH EMERGENCY BATTERY PACK)
WALL MOUNTED FIXTURE (" " - DESIGNATES FIXTURE
WITH EMERGENCY BATTERY PACK)
POLE MOUNTED FIXTURE (" " - DESIGNATES FIXTURE
BATTERY PACK)
(" " - DESIGNATES FIXTURE WITH EMERGENCY
OF FIXTURES AS INDICATED ON PLAN.
LIGHTING TRACK - LENGTH OF TRACK AND NO.
DETAILS ON DRAWINGS E-350 AND E-351
LIGHTING CONTROL SCHEME INDICATOR - REFER TO
J J-HOOK PATHWAY
PEDESTAL-COUNTER MOUNTED DATA OUTLET ROUGH-IN
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
480V,3P,30A,10AF
NEMA 12
W/10A FUSE
30A SWITCH SIZE
3 POLE
480V
480V,3P,30A,10AF - DENOTES:
(NOTATION TYPICAL)
NEMA 12 - DENOTES ENCLOSURE
NOTE:
OFOI OWNER FURNISHED OWNER INSTALLED
TELECOMMUNICATIONS OUTLET ROUGH-IN
TV
FURNISHED, OWNER INSTALLED)
WALL MOUNTED SECURITY CAMERA (OWNER
INSTALLED)
CARD READER LOCATION (OWNER FURNISHED, OWNER
SPECIFIED FOR REUSE, STORAGE, OR RETAINED BY THE OWNER.
MATERIALS AND EQUIPMENT INDICATED FOR REMOVAL, WHICH ARE NOT
DESIGNATED BY THE OWNER. REMOVE PROMPTLY FROM SITE ALL
REMOVE ALL EQUIPMENT THE OWNER WISHES TO RETAIN TO A SITE AS
THE OWNER SHALL REVIEW EQUIPMENT ITEMS INDICATED FOR REMOVAL. 11.
COORDINATED WITH THE OWNER PRIOR TO REMOVAL OR RELOCATION.
PRESENTLY CONCEALED IN EXISTING CONSTRUCTION SHALL BE
THE REMOVAL OR RELOCATION OF EXISTING ELECTRICAL EQUIPMENT 10.
THIS PROJECT.
CONTRACTORS. REMOVE FIXTURES AND WIRING AT THE COMPLETION OF
FIXTURES AND WIRING SHALL REMAIN IN PLACE FOR USE BY
WATTAGE REQUIRED FOR ADEQUATE ILLUMINATION. TEMPORARY LIGHTING
PROVIDE TEMPORARY POWER AND LIGHTING FIXTURES WITH LAMPS OF 9.
APPLICABLE CODES.
SERVICE, IT SHALL BE RE-SUPPORTED IN ACCORDANCE WITH ALL
SUPPORT OF EXISTING ELECTRICAL EQUIPMENT THAT IS TO REMAIN IN
IN THE EVENT THAT DEMOLITION WORK AFFECTS THE STRUCTURAL 8.
WORK. HOLES IN FLOOR SLABS SHALL BE FILLED WITH FIRE SAFING.
PATCH HOLES AND REPLACE DAMAGED MATERIAL CAUSED BY DEMOLITION 7.
NO ADDITIONAL CHARGE TO THE OWNER.
SHALL BE REPLACED WITH SIMILAR TYPE AS APPROVED BY THE OWNER, AT
REMAIN OR TO BE RELOCATED THAT ARE DAMAGED DURING DEMOLITION
ELECTRICAL EQUIPMENT, FIXTURES, AND/OR DEVICES SCHEDULED TO 6.
DRAWINGS, SHALL BE MAINTAINED.
THE ALTERATION, EVEN THOUGH THEY MAY NOT BE INDICATED ON THE
THE CONTINUITY OF EXISTING CIRCUITS THAT MAY BE INTERRUPTED BY 5.
DIRECTED BY THE OWNER.
POWER OUTAGES SHALL BE FOR MINIMUM DURATION AT OFF-HOURS AS 4.
CABINET AND COORDINATE WORK WITH OTHER TRADES.
ASSOCIATED WIRE, CONDUIT AND JUNCTION BOXES BACK TO PHONE
COORDINATE TELEPHONE WIRE DISCONNECTION WITH OWNER. REMOVE 3.
NOT SHOWN ON PLAN.
JUNCTION BOXES, ETC. WITHIN DEMOLITION AREA EVEN THOUGH THEY ARE
AT THE DISCRETION OF THE OWNER, REMOVE ABANDONED CONDUIT, WIRE, 2.
AND ASSOCIATED WIRE, CONDUIT, AND/OR JUNCTION BOXES.
EQUIPMENT, LIGHTING FIXTURES, JUNCTION BOXES, ELECTRICAL DEVICES
IN DESIGNATED DEMOLITION AREAS, PERMANENTLY REMOVE ELECTRICAL 1.
E EQUIPMENT CONNECTION
TYPE E - NEMA 6-20R
TYPE D - NEMA L6-50R
TYPE C - NEMA L6-30R
TYPE B - NEMA L6-20R
TYPE A - NEMA L5-30R
& TYPE AS INDICATED:
SPECIAL PURPOSE RECEPTACLE - SIZE
SPS
PROJECTION SCREEN UP/DN SWITCH
J
PSJ
CLG
PROJ
CLG
POWER FEED TO CEILING-MOUNTED PROJECTOR
POWER FEED TO MOTORIZED PROJECTION SCREEN