demolition / relocation designations this is a...

1
Revisions No. Date Description A B C D E F G H 1 2 3 4 5 6 The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden. Copyright Reserved Drawing No. Scale 7 I 8 CONFIDENTIAL INFORMATION: The information set forth hereon constitutes confidential proprietary technology of PPG INDUSTRIES, Inc. In consideration of the opportunity to supply goods or services to or on behalf of PPG requiring the use of said information, the recipient of this document agrees: (1) not to copy or reproduce said document in whole or in part without prior written authorization by PPG; (2) to return said document upon demand by PPG; (3) to make no use of said information other than for supplying goods or services in connection with the installation shown in the title without prior written authorization by PPG; (4) not to disclose said document or the information it includes to any third party. DISCIPLINE ITEM NO. DO NOT SCALE THIS PRINT DRAWN BY CHECKED APPROVED FRAME NO. DATE DATE 1 2 3 4 5 6 0 THIS PRINT SUPERSEDES ALL PRINTS PRIOR TO REVISION WORKS NO. OPERABLE UNIT LINE NO. Seal: 1 2 3 4 5 6 7 8 J DATE Title: SUBJECT INDEX KEY PLAN 2820 FOX BURBANK, CA 91504 2890 WEST EMPIRE AVENUE PPG AEROSPACE (724) 285-4761 (724) 285-6815 400 Morgan Center 101 East Diamond Street Butler, PA 16001-5923 www.stantec.com Tel: Fax: Stantec Architecture Inc. 2017.08.04 1 PACKAGE 2 FOX PROPERTY - PHASE 2 E-001 NTS L1 S CR ELECTRICAL COVER SHEET ELECTRICAL SYMBOLS SCHEDULE PENDANT TUBE FIXTURE 1X1 FIXTURE 1X4 FIXTURE OF FIXTURES AS INDICATED ON PLAN. LIGHTING TRACK - LENGTH OF TRACK AND NO. 'a' - INDICATES REMOTE FIXTURES POWERED BATTERY PACK W/ NO. OF HEADS AS SHOWN. BATTERY PACK. REMOTE EMERGENCY HEAD - 'a' INDICATES BATTERY PACK. REMOTE EMERGENCY DNLT - 'a' INDICATES BRANCH CIRCUIT RUN CONCEALED HOME RUN TO PANEL 2A CKTS 1, 3, & 5 NORMAL & EMERGENCY BRANCH CIRCUIT EMERGENCY ONLY BRANCH CIRCUIT NIGHT LIGHT BRANCH CIRCUIT LOW VOLTAGE CIRCUIT THERMITE WELD OF GROUND CONDUCTORS GROUND CONDUCTOR RUN CONCEALED LIGHTNING PROTECTION CONNECTION TO AIR TERMINAL FOR THERMITE WELD TO GROUND ROD GROUND ROD TRIODE BRANCH CIRCUIT UP OR DOWN JUNCTION BOX OR PULL BOX KEY-LOCK SWITCH PILOT-LIGHT SWITCH LIGHTED-HANDLE SWITCH EXPLOSION-PROOF SWITCH TIMER SWITCH TIMECLOCK EXTERIOR PHOTOCELL DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE SAFETY TYPE DUPLEX RECEPTACLE ISOLATED GROUND TYPE DUPLEX RECEPTACLE SINGLE RECEPTACLE COORDINATE LOCATION WITH SUPPLIER DUPLEX FOR ELECTRIC WATER COOLER OUTLET ON WALL SWITCH DUPLEX SPLIT WIRED WITH BOTTOM RECEPTACLE WITH WEATHERPROOF COVER EXPLOSION-PROOF RECEPTACLE SURFACE MTD PANELBOARD FLUSH MTD PANELBOARD MOTOR CONNECTION DISCONNECT SWITCH MAGNETIC STARTER COMBINATION STARTER/DISCONNECT MANUAL PULL STATION FIRE ALARM SPEAKER - CEILING MTD PHOTOELECTRIC TYPE SMOKE DETECTOR THERMAL TYPE DETECTOR FLOW SWITCH TAMPER SWITCH ELECTROMAGNETIC SHUTTER HOLDER ELECTROMAGNETIC DOOR HOLDER PRESSURE SWITCH FOR DRY TYPE SYSTEM REMOTE TROUBLE BELL FIREMANS TELEPHONE JACK FIRE ALARM CONTROL PANEL FIRE ALARM COMMAND CENTER FIRE ALARM ANNUNCIATOR FIRE ALARM PUNCH TAPE RECORDER POWER COMPANY METER C. T. CABINET EMERGENCY POWER OFF SWITCH GENERAL SYMBOLS KEY NOTE INDICATOR DRAWING REVISION INDICATOR 6 2 E NL NE EM LV 2A-1,3,5 J G G G G G G G G G S S 2 S 3 S 4 S T S S S D S S S P S K L EXP T PC S EPO IG IG/SP EWC WP EXP FF FP M C T M TRANSFORMER FIRE ALARM BELL FS FS FS FS ID ID RI PD PD TD TD D D R FS TS PS SH TB DH DC FT FACC FAA FTR GROUNDING AND LIGHTNING PROTECTION FACP FDGP FIRE ALARM DATA GATHERING PANEL a a a DROP CORD D AUTOMATIC DOOR MD PP KS PR PS PUSH PLATE KEY SWITCH POWER RESET PRESENCE SENSOR OHJ H C FSCP FIRE SUPPRESSION CONTROL PANEL SI DOOR MOUNTED SAFETY INTERLOCK KEY OPERATED REMOTE CONTROL UNIT 2 SCHEDULED ITEM INDICATOR BRANCH CIRCUIT RUN UNDER FLOOR UP EX EXISTING BRANCH CIRCUIT INDICATES CONNECTION TO EXISTING PE EP PNEUMATIC TO ELECTRIC DEVICE ELECTRIC TO PNEUMATIC DEVICE 2A-2 KR RI REMOTE INDICATOR ES ELECTRIC STRIKE NO. OF CONDUCTORS TO BE INSTALLED SURFACE METAL RACEWAY SIZED FOR SMR CT CABLE TRAY FIRE, SMOKE OR FIRE/SMOKE DAMPER RA CONDUIT AND WIRING ELECTRICAL DEVICES COMMUNICATIONS FIRE ALARM SYSTEM LIGHTING SECURITY SYSTEM EMERGENCY BATTERY PACK M G FS TD PD PD D R FLUSH-FLOOR MOUNTED RECEPTACLE PEDESTAL-FLOOR MOUNTED RECEPTACLE FLUSH MOUNTED DISTRIBUTION PANEL SURFACE MOUNTED DISTRIBUTION PANELBOARD MANUAL MOTOR STARTER FUSED DISCONNECT SWITCH GROUNDING BUS BAR GROUND CONNECTION DUPLEX RECEPTACLE ON NORMAL/EMERGENCY OPERATOR HEAD JUNCTION POWER CONNECTION HORN (ONLY) HORN AND STROBE LIGHT CHIME AND STROBE LIGHT STROBE LIGHT FIRE ALARM SPEAKER FIRE ALARM SPEAKER WITH TRUMPET IONIZATION TYPE SMOKE DETECTOR E THERMAL TYPE DETECTOR FOR ELEVATOR SHUNT TRIP E THERMAL TYPE DETECTOR MOUNTED TO DUCT IONIZATION TYPE DETECTOR MOUNTED TO DUCT REMOTE ANNUNCIATOR FOR DETECTOR PHOTOELECTRIC TYPE SMOKE DETECTOR WITH RELAY REMOTE TEST SWITCH FOR DETECTOR FAEP FIRE ALARM EXTENDER PANEL BD BD T BEAM DETECTOR - RECEIVER BEAM DETECTOR - TRANSMITTER PS SINGLE-POLE DOUBLE-POLE 3-WAY & 4-WAY SWITCHES AC 1 MECHANICAL EQUIPMENT INDICATOR ISOLATED GROUND TYPE WITH SURGE SUPRESSION GROUND CONDUCTOR RUN UNDER FLOOR THERMITE WELD TO BLDG OR EQUIPMENT FIRE ALARM SYSTEM ACTIVATED DOOR CLOSER CLG RECEPTACLE MOUNTED ON CEILING DETAIL INDICATOR ELEVATION/SECTION INDICATOR V F D VARIABLE FREQUENCY DRIVE M MEDIUM VOLTAGE SWITCH MEDIUM VOLTAGE SWITCH AND FUSE 2 ST SHUNT TRIP CIRCUIT BREAKER LOW VOLTAGE DRY TYPE TRANSFORMER AUTOMATIC TRANSFER SWITCH G EMERGENCY GENERATOR DIGITAL METER CURRENT TRANSFORMER 600 4 DM ELECTRICAL SINGLE LINE CONTACT CLOSURE INTERFACE S S OS INTEGRAL WALL SWITCH/ OCCUPANCY SENSOR OS-2P WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR PD ???? ?? ???? ?? THIS LIST OF ABBREVIATIONS IS PROVIDED FOR CONVENIENCE ONLY. ITEMS LISTED HERE MAY OR MAY NOT BE USED ON THIS PROJECT. A/C AIR CONDITIONING UNIT AC ALTERNATING CURRENT ACT ABOVE CEILING TILE AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT ATS AUTOMATIC TRANSFER SWITCH ALT ALTERNATE AVG AVERAGE BKR BREAKER BLDG BUILDING BTM BOTTOM CAP CAPACITY CFM CUBIC FEET/MINUTE CIRC CIRCULATING CKT CIRCUIT CLG CEILING CONC CONCRETE CONN CONNECTION CONT CONTINUOUS DED DEDICATED DIAM DIAMETER DIM DIMENSION DISC DISCONNECT DPR DAMPER EC ELECTRICAL CONTRACTOR ELEC ELECTRICAL ELEV ELEVATOR EXH EXHAUST EXIST EXISTING FACP FIRE ALARM CONTROL PANEL FBO FURNISHED BY OTHERS FPC FIRE PROTECTION CONTRACTOR FAB FABRICATE FIXT FIXTURE FLR FLOOR HW HOT WATER HORIZ HORIZONTAL HTG HEATING MECH MECHANICAL RECEPT RECEPTACLE TEMP TEMPERATURE XFMR TRANSFORMER ABBREVIATIONS ELECTRICAL SECT SECTION SIM SIMILAR SQ FT SQUARE FOOT STAT THERMOSTAT STD STANDARD STL STEEL SUSP CLG SUSPENDED CEILING RM ROOM REQD REQUIRED REC RECESSED RA RETURN AIR SW SWITCH SUSP SUSPENDED SURF SURFACE STRUCT STRUCTURAL STOR STORAGE T-STAT THERMOSTAT TV TELEVISION TYP TYPICAL TERM TERMINAL UG UNDERGROUND UH UNIT HEATER UV UNIT VENTILATOR VT VAPOR TIGHT VERT VERTICAL VDT VISUAL DISPLAY TERMINAL WP WEATHERPROOF WT WEIGHT PTs POTENTIAL TRANSFORMERS PRESS SW PRESSURE SWITCH PNL PANEL PLBG PLUMBING PS PULL SWITCH PH PENTHOUSE PEND PENDANT PC PLUMBING CONTRACTOR PE PNEUMATIC-ELECTRIC OH OVERHEAD OC ON CENTER OPNG OPENING NTS NOT TO SCALE NO NUMBER NOM NOMINAL MTG MOUNTING MTD MOUNTED MLO MAIN LUG ONLY MISC MISCELLANEOUS MIN MINIMUM MFR MANUFACTURER MAX MAXIMUM MH MANHOLE MC MECHANICAL CONTRACTOR MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MER MECHANICAL EQUIPMENT ROOM LVR LOUVER LTS LIGHTS LTG LIGHTING LV LOW VOLTAGE JT JOINT JAN JANITOR JB JUNCTION BOX INSUL INSULATION INST INSTANTANEOUS INCL INCLUDE HZ HERTZ HP HORSEPOWER HGT HEIGHT HV HIGH VOLTAGE GA GAUGE GC GENERAL CONTRACTOR GFI GROUND FAULT INTERRUPTER FU FUSE FTN FOUNTAIN FLUOR FLUORESCENT FLASH FLASHING FIN FINISH FP FIRE PROTECTION F & I FURNISHED AND INSTALLED EXTER EXTERIOR EQUIP EQUIPMENT EP ELECTRIC-PNEUMATIC ENCL ENCLOSURE EM GEN EMERGENCY GENERATOR EM EMERGENCY ONLY EA EACH EWC ELECTRIC WATER COOLER DWG DRAWING DN DOWN DIV DIVISION DHW DOMESTIC WATER HEATER DF DRINKING FOUNTAIN DET DETAIL CU COPPER CRT CATHODE RAY TUBE CPU CENTRAL PROCESS UNIT CONTR CONTRACTOR CONST CONSTRUCTION CO COMPANY CL CENTERLINE CT CURRENT TRANSFORMERS C CONDUIT AUTO AUTOMATIC ARCH ARCHITECTURAL ADJ ADJUSTABLE AL ALUMINUM A AMPS 1/C SINGLE CONDUCTOR NIC NOT IN CONTRACT NE NORMAL/EMERGENCY "H" - HEAD MOUNTED; "C" - CEILING MOUNTED MOTION DETECTOR - CEILING MOUNTED COMBINATION SPEAKER/STROBE LIGHT COMBINATION SPEAKER/STROBE LIGHT PHOTOELECTRIC TYPE DETECTOR MOUNTED TO DUCT RECAPTURE PHOTOELECTRIC TYPE DETECTOR FOR ELEVATOR NOT BE USED ON THIS PROJECT. REFERENCE ONLY. SYMBOLS SHOWN HERE MAY OR MAY THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS FOR HEIGHT. TYPICAL UNLESS NOTED OTHERWISE INDICATES OUTLET TO BE MOUNTED 8" ABOVE COUNTER OTHERWISE NOTED OUTLETS MOUNTED ON 1'-0" CENTERS UNLESS SURFACE MOUNTED MULTI-OUTLET ASSEMBLY DUPLEX TO PIPING OR EQUIPMENT BONDING PLATE OR CLAMP CONNECTION MOTORIZED DAMPER CONTROL MODULE MONITOR MODULE DH SMOKE DETECTOR FOR DOOR HOLDS POWER DISTRIBUTION DRAW OUT MEDIUM VOLTAGE (15KV OR 5KV) CIRCUIT BREAKER DRAW OUT LOW VOLTAGE (480V OR 208) CIRCUIT BREAKER LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER STARTER SIZE COMBINATION MOTOR STARTER- NUMBER INDICATES MEDIUM VOLTAGE LIQUID FILLED TRANSFORMER CC TWO-POLE OCCUPANCY SENSOR WITH INTEGRAL SWITCH CM MM FEEDER SIZE INDICATOR DUPLEX RECEPTACLE FLOOR BOX DOUBLE DUPLEX RECEPTACLE FLOOR BOX EMERGENCY PUSH BUTTON EXISTING SURFACE MTD PANELBOARD EXISTING FLUSH MTD PANELBOARD GENERAL NOTES AFCI ARC FAULT CIRCUIT INTERRUPTER GAL GALLONS GRD GROUND DEMOLITION / RELOCATION DESIGNATIONS RELOCATED DEVICE. EXISTING DEVICE TO REMAIN. RR RR ER ER ETR ETR REMOVE EXISTING ELECTRICAL DEVICE. REMOVE & RELOCATE EXISTING ELECTRICAL DEVICE. SINGLE LINE DRAWING, AS APPLICABLE.) (SHOWN FOR CLARITY/COORDINATION WITH EXISTING ELECTRICAL PANEL REMOVED BY OWNER. RX/OD RX RX AND DEVICES SHOWN ON PLANS.) (NOTATIONS SHOWN ABOVE TO BE TYPICAL FOR ALL EQUIPMENT ETL EXISTING TO BE RELOCATED ETR EXISTING TO REMAIN ETD EMERGENCY TRANSFER DEVICE DT M MOTOR-RATED SWITCH/DISCONNECT CIRCUIT (GRAY RECEPTACLE) DUPLEX RECEPTACLE ON DEDICATED CIRCUIT NORMAL CIRCUIT & ONE DUPLEX (GRAY) ON DEDICATED DOUBLE DUPLEX RECEPTACLE WITH ONE DUPLEX ON TELE TELEPHONE THK THICK TRF TRANSFORMER VOL VOLUME VFD VARIABLE FREQUENCY DRIVE RX REMOVE J PF POWER FEED AT MOVEABLE PARTITION FH POWER FEED AT LABORATORY FUME HOOD (COORDINATE MTG. HT. W/ARCH.) RECEPTACLE FOR DISPLAY SCREEN/TV J PF PT POKE-THRU ASSEMBLY W/"PF" DESIGNATING POWER FEED PEDESTAL-COUNTER MOUNTED RECEPTACLE FVNR FULL VOLTAGE NON-REVERSING (MOTOR STARTER) RVNR REDUCED VOLTAGE NON-REVERSING (MOTOR STARTER) PP POWER POLE GENERAL DEMOLITION NOTES FB FLOOR BOX WITH POWER FEED AT MOVEABLE PARTITION CONTROLLED RECEPTACLE S S ONE UNCONTROLLED RECEPTACLE SPLITWIRED RECEPTACLE WITH ONE CONTROLLED AND DUPLEX AND ONE UNCONTROLLED DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE WITH ONE CONTROLLED GFI DEADFRONT GFCI DEVICE GFCI DUPLEX RECEPTACLE WP WEATHERPROOF HORN AND STROBE LIGHT HW HW HALLWAY COVERAGE PATTERN WALL MOUNTED PASSIVE INFRARED OCCUPANCY SENSOR, OCCUPANCY & DAYLIGHT SENSORS Fa S Sa 'a' SWITCH NO. 'S' SWITCH TYPE SWITCH DESIGNATIONS: (ON/OFF, RAISE, LOWER) LOW VOLTAGE WALL DIMMER SWITCH - 3 BUTTON LV2 (ON, OFF) LOW-VOLTAGE WALL SWITCH - 2 BUTTON S LV3 (FULL ON, PARTIAL ON, OFF) LOW-VOLTAGE WALL SWITCH - 3 BUTTON S TS S SC LIGHTING SCENE CONTROL STATION LIGHTING CONTROL SYSTEM TOUCHSCREEN INTERFACE DL 'DL' AUTOMATIC DAYLIGHTING CONTROLLED FIXTURE '2A-2' PANEL 2A CKT #2 'a' SWITCH NO. 'F' FIXTURE TYPE FIXTURE DESIGNATIONS: FB FLOOR BOX F RELOCATED BY THE OWNER. PROCESS EQUIPMENT WITH OWNER. EQUIPMENT IS EXISTING AND COORDINATE EXPLOSION-PROOF RECEPTACLE REQUIREMENTS FOR 30. LEAVING THE CLASSIFIED AREA. AREAS, PROVIDE RIGID CONDUIT AND CONDUIT SEALS ON CONDUIT AS REQUIRED BY CALIFORNIA ELECTRICAL CODE IN HAZARDOUS / LISTED 29. APPLICABLE. SPACES. INSTALL CONDUIT TIGHT TO CEILING OR BUILDING STEEL, AS GRID LINES, PARTICULLARLY IN OPEN CEILING OR LABORATORY CEILING INSTALL RACEWAYS PARALLEL AND/OR PERPENDICULAR TO BUILDING 28. SHOWN. AND THE SPECIFICATIONS, PROVIDE THE HIGHEST RATING SPECIFIED OR UPSTREAM DEVICE. IF THERE IS A CONFLICT BETWEEN THE DRAWINGS DEVICES OR EQUIPMENT SHALL BE RATED THE SAME AS THE NEAREST WHERE NO SHORT CIRCUIT INTERRUPT/WITHSTAND RATING IS INDICATED, 27. OPERATIONAL. BALANCE PANEL PHASES ONCE USER EQUIPMENT IS INSTALLED AND 26. EQUIPMENT. MAINTAIN ACCESSIBILITY TO CONTROLS. CONTRACTORS FOR LOCATION AND POWER REQUIREMENTS OF COORDINATE WITH HVAC, PLUMBING, AND FIRE PROTECTION 25. CEILINGS. MAINTAIN ACCESS TO ALL COMMUNICATIONS RACEWAYS ABOVE LAY-IN 24. CENTER OF THE CEILING TILES, UNLESS OTHERWISE NOTED. CEILING MOUNTED ELECTRICAL DEVICES SHALL BE MOUNTED IN THE 23. SEE ARCHITECTURAL FLOOR PLANS FOR WALL CONSTRUCTION TYPES. 22. ARCHITECTURAL REFLECTED CEILING PLANS. DRYWALL OR PLASTER CEILINGS. COORDINATE CEILING TYPES WITH PROVIDE PLASTER FLANGES FOR RECESSED LIGHTING FIXTURES IN 21. ARE NOT ACCEPTABLE. SMR SHALL BE ATTACHED TO WALL WITH PLUGS AND SCREWS. TAP CONS 20. STRUCTURE. FIXTURES. 2x4 PENDANT FIXTURES SHALL HAVE 4-POINT SUPPORT ON PROVIDE MINIMUM 2 POINT SUPPORT FROM STRUCTURE TO LIGHTING 19. WELL AS FACTORY ELBOWS AND MISCELLLANEOUS END PLATES. PROVIDE RISER DUCTS AS REQUIRED WHEN SMR ELEVATION CHANGES AS VERIFY SMR LOCATIONS IN REFERENCE TO CASEWORK LOCATIONS. 18. ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION. COORDINATE ELEVATION AND LOCATION OF ELECTRICAL DEVICES WITH 17. HAVE ITS OWN INDIVIDUAL FULL SIZE NEUTRAL BACK TO PANEL. EACH DESIGNATED CIRCUIT HOMERUN SERVING RECEPTACLES SHALL 16. ON ALL RACEWAYS WHICH CROSS ANY BUILDING EXPANSION JOINTS. THE USE OF APPROVED TYPE EXPANSION FITTINGS SHALL BE REQUIRED 15. OF USE. PROVIDE A GREEN GROUND WIRE FOR EACH COMMON NEUTRAL TO POINT HAVING EXISTING CIRCUITS SERVING AREAS BEYOND THIS PROJECT, CONDUITS DESIGNATED BY THE ELECTRICAL TRADE TO BE REUSED, AND AND ALL EXISTING CIRCUITS TO BE REUSED IN THIS PROJECT. IN EXISTING PROVIDE A GREEN GROUND WIRE FROM PANEL FOR ALL NEW CIRCUITS 14. EXACT LOCATIONS WITH THE MECHANICAL TRADE. MECHANICAL EQUIPMENT AND DUCTWORK IS INSTALLED. COORDINATE LOCATE JUNCTION BOXES AS REQUIRED TO ALLOW ACCESS AFTER 13. RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. FIXTURES, ETC. TO MEET THE CONSTRUCTION SCHEDULE SHALL BE THE ANY ADDITIONAL COST TO ENSURE DELIVERY OF PANELS, LIGHT 12. MOUNTED. INSTALLED IN GYPSUM BOARD CONSTRUCTION, THEY SHALL BE RECESS RACEWAY. WHERE DUPLEX RECEPTACLES ARE SHOWN AND CAN BE WALLS WITH SURFACE MOUNTED OUTLET BOX AND SURFACE METAL DUPLEX RECEPTACLES SHALL BE SURFACE MOUNTED ON MASONRY 11. OF EACH SHIFT. AREAS SHALL BE CLEANED AND LEFT IN ORIGINAL CONDITION AT THE END 10. END OF THAT SHIFT. BEING PERFORMED DURING THAT SHIFT AND SHALL BE REPLACED AT THE CEILING TILE SHALL ONLY BE REMOVED FROM AREAS WHERE WORK IS 9. PAINTING, CONCRETE, ETC. REQUIRED TO COMPLETE THIS PROJECT. ELECTRICAL TRADE SHALL BE RESPONSIBLE FOR CUTTING, PATCHING, 8. ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. EQUIPMENT SHALL BEAR U.L. LABELS AND BE GROUNDED AND BONDED IN 7. MINIMUM CONDUIT SIZE SHALL BE 3/4" 6. POWER CIRCUITS. WIRES SMALLER THAN #12 AWG SHALL NOT BE USED FOR LIGHTING OR 5. PAY ALL FEES. ELECTRICAL CONTRACTOR AND THE ELECTRICAL CONTRACTOR SHALL PERMITS NECESSARY FOR THIS WORK SHALL BE OBTAINED BY THE 4. WORK SHALL MEET THE APPROVAL OF THE OWNER'S REPRESENTATIVE. 3. RULES AND REGULATIONS OF THE LOCAL MUNICIPALITY. WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE N.E.C. AND ALL 2. TO THE PHASING AS OUTLINED BY THE OWNER. BEEN DIVIDED INTO SEVERAL PHASES AND ALL TRADES MUST CONFORM THE DEMOLITION AND CONSTRUCTION WORK FOR THIS PROJECT HAVE 1. DO J POWER FEED AT DOOR OPERATOR A SENSOR, HALLWAY COVERAGE PATTERN CEILING MOUNTED PASSIVE INFRARED OCCUPANCY DT/DS SENSOR WITH INTEGRAL DAYLIGHT SENSOR CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY DS CEILING MOUNTED DAYLIGHT SENSOR "x" INDICATES SWITCH LEG (TYPICAL) CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR DTx 2X4 FIXTURE CENTER DIFFUSER, IF PRESENT ON FIXTURE 2X2 FIXTURE - LINE INDICATES ORIENTATION OF EMERGENCY BATTERY PACK) 2X4 FIXTURE (" " - DESIGNATES FIXTURE WITH EMERGENCY BATTERY PACK) 2X2 FIXTURE (" " - DESIGNATES FIXTURE WITH WITH EMERGENCY BATTERY PACK) 1X1 FIXTURE (" " - DESIGNATES FIXTURE WITH EMERGENCY BATTERY PACK) 1X4 FIXTURE (" " - DESIGNATES FIXTURE WITH EMERGENCY BATTERY PACK) FLUORESCENT STRIPLIGHT (" " - DESIGNATES FIXTURE WITH EMERGENCY BATTERY PACK) PENDANT TUBE FIXTURE (" " - DESIGNATES FIXTURE LED STRIPLIGHT CEILING MOUNTED LIGHT FIXTURE CEILING MOUNTED WALL WASHER WALL MOUNTED FIXTURE POLE MOUNTED FIXTURE CEILING MOUNTED EXIT SIGN W/ ARROWS AS INDICATED WALL MOUNTED EXIT SIGN W/ ARROWS AS INDICATED FIXTURE WITH EMERGENCY BATTERY PACK) CEILING MOUNTED WALL WASHER (" " - DESIGNATES WITH EMERGENCY BATTERY PACK) CEILING MOUNTED FIXTURE (" " - DESIGNATES FIXTURE WITH EMERGENCY BATTERY PACK) WALL MOUNTED FIXTURE (" " - DESIGNATES FIXTURE WITH EMERGENCY BATTERY PACK) POLE MOUNTED FIXTURE (" " - DESIGNATES FIXTURE BATTERY PACK) (" " - DESIGNATES FIXTURE WITH EMERGENCY OF FIXTURES AS INDICATED ON PLAN. LIGHTING TRACK - LENGTH OF TRACK AND NO. DETAILS ON DRAWINGS E-350 AND E-351 LIGHTING CONTROL SCHEME INDICATOR - REFER TO J J-HOOK PATHWAY PEDESTAL-COUNTER MOUNTED DATA OUTLET ROUGH-IN EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT 480V,3P,30A,10AF NEMA 12 W/10A FUSE 30A SWITCH SIZE 3 POLE 480V 480V,3P,30A,10AF - DENOTES: (NOTATION TYPICAL) NEMA 12 - DENOTES ENCLOSURE NOTE: OFOI OWNER FURNISHED OWNER INSTALLED TELECOMMUNICATIONS OUTLET ROUGH-IN TV FURNISHED, OWNER INSTALLED) WALL MOUNTED SECURITY CAMERA (OWNER INSTALLED) CARD READER LOCATION (OWNER FURNISHED, OWNER SPECIFIED FOR REUSE, STORAGE, OR RETAINED BY THE OWNER. MATERIALS AND EQUIPMENT INDICATED FOR REMOVAL, WHICH ARE NOT DESIGNATED BY THE OWNER. REMOVE PROMPTLY FROM SITE ALL REMOVE ALL EQUIPMENT THE OWNER WISHES TO RETAIN TO A SITE AS THE OWNER SHALL REVIEW EQUIPMENT ITEMS INDICATED FOR REMOVAL. 11. COORDINATED WITH THE OWNER PRIOR TO REMOVAL OR RELOCATION. PRESENTLY CONCEALED IN EXISTING CONSTRUCTION SHALL BE THE REMOVAL OR RELOCATION OF EXISTING ELECTRICAL EQUIPMENT 10. THIS PROJECT. CONTRACTORS. REMOVE FIXTURES AND WIRING AT THE COMPLETION OF FIXTURES AND WIRING SHALL REMAIN IN PLACE FOR USE BY WATTAGE REQUIRED FOR ADEQUATE ILLUMINATION. TEMPORARY LIGHTING PROVIDE TEMPORARY POWER AND LIGHTING FIXTURES WITH LAMPS OF 9. APPLICABLE CODES. SERVICE, IT SHALL BE RE-SUPPORTED IN ACCORDANCE WITH ALL SUPPORT OF EXISTING ELECTRICAL EQUIPMENT THAT IS TO REMAIN IN IN THE EVENT THAT DEMOLITION WORK AFFECTS THE STRUCTURAL 8. WORK. HOLES IN FLOOR SLABS SHALL BE FILLED WITH FIRE SAFING. PATCH HOLES AND REPLACE DAMAGED MATERIAL CAUSED BY DEMOLITION 7. NO ADDITIONAL CHARGE TO THE OWNER. SHALL BE REPLACED WITH SIMILAR TYPE AS APPROVED BY THE OWNER, AT REMAIN OR TO BE RELOCATED THAT ARE DAMAGED DURING DEMOLITION ELECTRICAL EQUIPMENT, FIXTURES, AND/OR DEVICES SCHEDULED TO 6. DRAWINGS, SHALL BE MAINTAINED. THE ALTERATION, EVEN THOUGH THEY MAY NOT BE INDICATED ON THE THE CONTINUITY OF EXISTING CIRCUITS THAT MAY BE INTERRUPTED BY 5. DIRECTED BY THE OWNER. POWER OUTAGES SHALL BE FOR MINIMUM DURATION AT OFF-HOURS AS 4. CABINET AND COORDINATE WORK WITH OTHER TRADES. ASSOCIATED WIRE, CONDUIT AND JUNCTION BOXES BACK TO PHONE COORDINATE TELEPHONE WIRE DISCONNECTION WITH OWNER. REMOVE 3. NOT SHOWN ON PLAN. JUNCTION BOXES, ETC. WITHIN DEMOLITION AREA EVEN THOUGH THEY ARE AT THE DISCRETION OF THE OWNER, REMOVE ABANDONED CONDUIT, WIRE, 2. AND ASSOCIATED WIRE, CONDUIT, AND/OR JUNCTION BOXES. EQUIPMENT, LIGHTING FIXTURES, JUNCTION BOXES, ELECTRICAL DEVICES IN DESIGNATED DEMOLITION AREAS, PERMANENTLY REMOVE ELECTRICAL 1. E EQUIPMENT CONNECTION TYPE E - NEMA 6-20R TYPE D - NEMA L6-50R TYPE C - NEMA L6-30R TYPE B - NEMA L6-20R TYPE A - NEMA L5-30R & TYPE AS INDICATED: SPECIAL PURPOSE RECEPTACLE - SIZE S PS PROJECTION SCREEN UP/DN SWITCH J PS J CLG PROJ CLG POWER FEED TO CEILING-MOUNTED PROJECTOR POWER FEED TO MOTORIZED PROJECTION SCREEN

Upload: others

Post on 24-Jun-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DEMOLITION / RELOCATION DESIGNATIONS THIS IS A …chalmerscs.com/uploads/3/5/5/5/35559745/e-001... · 2017-09-01 · KEY PLAN 2820 FOX BURBANK, CA 91504 2890 WEST EMPIRE AVENUE PPG

Revisions

No. Date Description

A B C D E F G H

1

2

3

4

5

6

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors

or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any

purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Drawing

No.

Scale

7

I

8

CONFIDENTIAL INFORMATION: The information set forth hereon constitutes confidential proprietary technology of PPG INDUSTRIES, Inc. In

consideration of the opportunity to supply goods or services to or on behalf of PPG requiring the use of said information, the recipient of this document agrees: (1)

not to copy or reproduce said document in whole or in part without prior written authorization by PPG; (2) to return said document upon demand by PPG; (3) to

make no use of said information other than for supplying goods or services in connection with the installation shown in the title without prior written authorization by

PPG; (4) not to disclose said document or the information it includes to any third party.

DISCIPLINE ITEM NO.

DO NOT SCALE THIS PRINT

DRAWN BY

CHECKED

APPROVED

FRAME NO.

DATE

DATE

1 2 3 4 5 60

THIS PRINT SUPERSEDES ALL PRINTS

PRIOR TO REVISION

WORKS NO. OPERABLE UNITLINE NO.

Seal:

1

2

3

4

5

6

7

8

J

DATE

Title:

SUBJECT

INDEX

KEY PLAN

2820

FOX

BURBANK, CA 91504

2890 WEST EMPIRE AVENUE

PPG AEROSPACE

(724) 285-4761

(724) 285-6815

400 Morgan Center

101 East Diamond Street

Butler, PA 16001-5923

www.stantec.com

Tel:

Fax:

Stantec Architecture Inc.

2017.08.041 PACKAGE 2

FOX PROPERTY - PHASE 2

E-001NTS

L1

S

CR

ELECTRICAL COVER SHEET

ELECTRICAL SYMBOLS SCHEDULE

PENDANT TUBE FIXTURE

1X1 FIXTURE

1X4 FIXTURE

OF FIXTURES AS INDICATED ON PLAN.

LIGHTING TRACK - LENGTH OF TRACK AND NO.

'a' - INDICATES REMOTE FIXTURES POWERED

BATTERY PACK W/ NO. OF HEADS AS SHOWN.

BATTERY PACK.

REMOTE EMERGENCY HEAD - 'a' INDICATES

BATTERY PACK.

REMOTE EMERGENCY DNLT - 'a' INDICATES

BRANCH CIRCUIT RUN CONCEALED

HOME RUN TO PANEL 2A CKTS 1, 3, & 5

NORMAL & EMERGENCY BRANCH CIRCUIT

EMERGENCY ONLY BRANCH CIRCUIT

NIGHT LIGHT BRANCH CIRCUIT

LOW VOLTAGE CIRCUIT

THERMITE WELD OF GROUND CONDUCTORS

GROUND CONDUCTOR RUN CONCEALED

LIGHTNING PROTECTION

CONNECTION TO AIR TERMINAL FOR

THERMITE WELD TO GROUND ROD

GROUND ROD TRIODE

BRANCH CIRCUIT UP OR DOWN

JUNCTION BOX OR PULL BOX

KEY-LOCK SWITCH

PILOT-LIGHT SWITCH

LIGHTED-HANDLE SWITCH

EXPLOSION-PROOF SWITCH

TIMER SWITCH

TIMECLOCK

EXTERIOR PHOTOCELL

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

SAFETY TYPE DUPLEX RECEPTACLE

ISOLATED GROUND TYPE DUPLEX RECEPTACLE

SINGLE RECEPTACLE

COORDINATE LOCATION WITH SUPPLIER

DUPLEX FOR ELECTRIC WATER COOLER

OUTLET ON WALL SWITCH

DUPLEX SPLIT WIRED WITH BOTTOM

RECEPTACLE WITH WEATHERPROOF COVER

EXPLOSION-PROOF RECEPTACLE

SURFACE MTD PANELBOARD

FLUSH MTD PANELBOARD

MOTOR CONNECTION

DISCONNECT SWITCH

MAGNETIC STARTER

COMBINATION STARTER/DISCONNECT

MANUAL PULL STATION

FIRE ALARM SPEAKER - CEILING MTD

PHOTOELECTRIC TYPE SMOKE DETECTOR

THERMAL TYPE DETECTOR

FLOW SWITCH

TAMPER SWITCH

ELECTROMAGNETIC SHUTTER HOLDER

ELECTROMAGNETIC DOOR HOLDER

PRESSURE SWITCH FOR DRY TYPE SYSTEM

REMOTE TROUBLE BELL

FIREMANS TELEPHONE JACK

FIRE ALARM CONTROL PANEL

FIRE ALARM COMMAND CENTER

FIRE ALARM ANNUNCIATOR

FIRE ALARM PUNCH TAPE RECORDER

POWER COMPANY METER

C. T. CABINET

EMERGENCY POWER OFF SWITCH

GENERAL SYMBOLS

KEY NOTE INDICATOR

DRAWING REVISION INDICATOR

6

2

E

NL

NE

EM

LV

2A-1,3,5

J

G

G

G

G G

G

G

G

G

S S2

S3S4

S

T

S

S

SD

S

S

SP

SK

L

EXP

T

PC

S

EPO

IG

IG/SP

EWC

WP

EXP

FF

FP

M

C T

M

TRANSFORMER

FIRE ALARM BELL

FS

FS

FS

FS

ID

ID

RI

PD

PD

TD

TD

D

D

R

FS

TS

PS

SH

TB

DH

DC

FT

FACC

FAA

FTR

GROUNDING AND LIGHTNING PROTECTION

FACP

FDGP FIRE ALARM DATA GATHERING PANEL

a

a

a

DROP CORDD

AUTOMATIC DOOR

MD

PP

KS

PR

PS

PUSH PLATE

KEY SWITCH

POWER RESET

PRESENCE SENSOR

OHJ

H

C

FSCP FIRE SUPPRESSION CONTROL PANEL

SI DOOR MOUNTED SAFETY INTERLOCK

KEY OPERATED REMOTE CONTROL UNIT

2 SCHEDULED ITEM INDICATOR

BRANCH CIRCUIT RUN UNDER FLOOR

UP

EXEXISTING BRANCH CIRCUIT

INDICATES CONNECTION TO EXISTING

PE

EP

PNEUMATIC TO ELECTRIC DEVICE

ELECTRIC TO PNEUMATIC DEVICE

2A-2

KR

RI REMOTE INDICATOR

ES ELECTRIC STRIKE

NO. OF CONDUCTORS TO BE INSTALLED

SURFACE METAL RACEWAY SIZED FORSMR

CT CABLE TRAY

FIRE, SMOKE OR FIRE/SMOKE DAMPER

RA

CONDUIT AND WIRING

ELECTRICAL DEVICES

COMMUNICATIONS

FIRE ALARM SYSTEMLIGHTING

SECURITY SYSTEM

EMERGENCY BATTERY PACK

M

G

FS

TD

PD

PDD

R

FLUSH-FLOOR MOUNTED RECEPTACLE

PEDESTAL-FLOOR MOUNTED RECEPTACLE

FLUSH MOUNTED DISTRIBUTION PANEL

SURFACE MOUNTED DISTRIBUTION PANELBOARD

MANUAL MOTOR STARTER

FUSED DISCONNECT SWITCH

GROUNDING BUS BAR

GROUND CONNECTION

DUPLEX RECEPTACLE ON NORMAL/EMERGENCY

OPERATOR HEAD JUNCTION POWER CONNECTION

HORN (ONLY)

HORN AND STROBE LIGHT

CHIME AND STROBE LIGHT

STROBE LIGHT

FIRE ALARM SPEAKER

FIRE ALARM SPEAKER WITH TRUMPET

IONIZATION TYPE SMOKE DETECTOR

E THERMAL TYPE DETECTOR FOR ELEVATOR SHUNT TRIP

E

THERMAL TYPE DETECTOR MOUNTED TO DUCT

IONIZATION TYPE DETECTOR MOUNTED TO DUCT

REMOTE ANNUNCIATOR FOR DETECTOR

PHOTOELECTRIC TYPE SMOKE DETECTOR WITH RELAY

REMOTE TEST SWITCH FOR DETECTOR

FAEP FIRE ALARM EXTENDER PANEL

BD

BDT

BEAM DETECTOR - RECEIVER

BEAM DETECTOR - TRANSMITTER

PS

SINGLE-POLE DOUBLE-POLE 3-WAY & 4-WAY SWITCHES

AC

1 MECHANICAL EQUIPMENT INDICATOR

ISOLATED GROUND TYPE WITH SURGE SUPRESSION

GROUND CONDUCTOR RUN UNDER FLOOR

THERMITE WELD TO BLDG OR EQUIPMENT

FIRE ALARM SYSTEM ACTIVATED DOOR CLOSER

CLGRECEPTACLE MOUNTED ON CEILING

DETAIL INDICATOR

ELEVATION/SECTION INDICATOR

V F D VARIABLE FREQUENCY DRIVE

M

MEDIUM VOLTAGE SWITCH

MEDIUM VOLTAGE SWITCH AND FUSE

2

STSHUNT TRIP CIRCUIT BREAKER

LOW VOLTAGE DRY TYPE TRANSFORMER

AUTOMATIC TRANSFER SWITCH

G EMERGENCY GENERATOR

DIGITAL METER

CURRENT TRANSFORMER

600

4

DM

ELECTRICAL SINGLE LINE

CONTACT CLOSURE INTERFACE

S

SOS INTEGRAL WALL SWITCH/ OCCUPANCY SENSOR

OS-2P

WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR

PD

????

??

????

??

THIS LIST OF ABBREVIATIONS IS PROVIDED FOR

CONVENIENCE ONLY. ITEMS LISTED HERE MAY OR

MAY NOT BE USED ON THIS PROJECT.

A/C AIR CONDITIONING UNITAC ALTERNATING CURRENTACT ABOVE CEILING TILE

AFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNIT

ATS AUTOMATIC TRANSFER SWITCH

ALT ALTERNATE

AVG AVERAGE

BKR BREAKERBLDG BUILDINGBTM BOTTOM

CAP CAPACITYCFM CUBIC FEET/MINUTECIRC CIRCULATINGCKT CIRCUIT

CLG CEILING

CONC CONCRETECONN CONNECTION

CONT CONTINUOUS

DED DEDICATED

DIAM DIAMETERDIM DIMENSIONDISC DISCONNECT

DPR DAMPER

EC ELECTRICAL CONTRACTORELEC ELECTRICALELEV ELEVATOR

EXH EXHAUSTEXIST EXISTING

FACP FIRE ALARM CONTROL PANELFBO FURNISHED BY OTHERS

FPC FIRE PROTECTION CONTRACTOR

FAB FABRICATE

FIXT FIXTURE

FLR FLOOR

HW HOT WATER

HORIZ HORIZONTAL

HTG HEATING

MECH MECHANICAL

RECEPT RECEPTACLE

TEMP TEMPERATURE

XFMR TRANSFORMER

ABBREVIATIONS

ELECTRICAL

SECT SECTIONSIM SIMILARSQ FT SQUARE FOOTSTAT THERMOSTATSTD STANDARDSTL STEEL

SUSP CLG SUSPENDED CEILING

RM ROOMREQD REQUIRED

REC RECESSEDRA RETURN AIR

SW SWITCH

SUSP SUSPENDEDSURF SURFACESTRUCT STRUCTURALSTOR STORAGE

T-STAT THERMOSTATTV TELEVISION

TYP TYPICAL

TERM TERMINAL

UG UNDERGROUNDUH UNIT HEATERUV UNIT VENTILATOR

VT VAPOR TIGHT

VERT VERTICALVDT VISUAL DISPLAY TERMINAL

WP WEATHERPROOFWT WEIGHT

PTs POTENTIAL TRANSFORMERS

PRESS SW PRESSURE SWITCHPNL PANELPLBG PLUMBING

PS PULL SWITCH

PH PENTHOUSEPEND PENDANT

PC PLUMBING CONTRACTORPE PNEUMATIC-ELECTRIC

OH OVERHEAD

OC ON CENTER

OPNG OPENING

NTS NOT TO SCALE

NO NUMBERNOM NOMINAL

MTG MOUNTINGMTD MOUNTEDMLO MAIN LUG ONLYMISC MISCELLANEOUSMIN MINIMUM

MFR MANUFACTURER

MAX MAXIMUM

MH MANHOLE

MC MECHANICAL CONTRACTORMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTER

MER MECHANICAL EQUIPMENT ROOM

LVR LOUVER

LTS LIGHTSLTG LIGHTING

LV LOW VOLTAGE

JT JOINT

JAN JANITORJB JUNCTION BOX

INSUL INSULATIONINST INSTANTANEOUSINCL INCLUDE

HZ HERTZ

HP HORSEPOWER

HGT HEIGHT

HV HIGH VOLTAGE

GA GAUGE

GC GENERAL CONTRACTORGFI GROUND FAULT INTERRUPTER

FU FUSEFTN FOUNTAIN

FLUOR FLUORESCENT

FLASH FLASHING

FIN FINISH

FP FIRE PROTECTION

F & I FURNISHED AND INSTALLED

EXTER EXTERIOR

EQUIP EQUIPMENTEP ELECTRIC-PNEUMATICENCL ENCLOSUREEM GEN EMERGENCY GENERATOREM EMERGENCY ONLY

EA EACH

EWC ELECTRIC WATER COOLER

DWG DRAWING

DN DOWNDIV DIVISION

DHW DOMESTIC WATER HEATERDF DRINKING FOUNTAINDET DETAIL

CU COPPER

CRT CATHODE RAY TUBECPU CENTRAL PROCESS UNITCONTR CONTRACTOR

CONST CONSTRUCTION

CO COMPANY

CL CENTERLINE

CT CURRENT TRANSFORMERS

C CONDUIT

AUTO AUTOMATIC

ARCH ARCHITECTURAL

ADJ ADJUSTABLE

AL ALUMINUM

A AMPS

1/C SINGLE CONDUCTOR

NIC NOT IN CONTRACTNE NORMAL/EMERGENCY

"H" - HEAD MOUNTED; "C" - CEILING MOUNTED

MOTION DETECTOR

- CEILING MOUNTED

COMBINATION SPEAKER/STROBE LIGHT

COMBINATION SPEAKER/STROBE LIGHT

PHOTOELECTRIC TYPE DETECTOR MOUNTED TO DUCT

RECAPTURE

PHOTOELECTRIC TYPE DETECTOR FOR ELEVATOR

NOT BE USED ON THIS PROJECT.

REFERENCE ONLY. SYMBOLS SHOWN HERE MAY OR MAY

THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS FOR

HEIGHT. TYPICAL UNLESS NOTED OTHERWISE

INDICATES OUTLET TO BE MOUNTED 8" ABOVE COUNTER

OTHERWISE NOTED

OUTLETS MOUNTED ON 1'-0" CENTERS UNLESS

SURFACE MOUNTED MULTI-OUTLET ASSEMBLY DUPLEX

TO PIPING OR EQUIPMENT

BONDING PLATE OR CLAMP CONNECTION

MOTORIZED DAMPER

CONTROL MODULE

MONITOR MODULE

DHSMOKE DETECTOR FOR DOOR HOLDS

POWER DISTRIBUTION

DRAW OUT MEDIUM VOLTAGE (15KV OR 5KV) CIRCUIT BREAKER

DRAW OUT LOW VOLTAGE (480V OR 208) CIRCUIT BREAKER

LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER

STARTER SIZECOMBINATION MOTOR STARTER- NUMBER INDICATES

MEDIUM VOLTAGE LIQUID FILLED TRANSFORMER

CC

TWO-POLE OCCUPANCY SENSOR WITH INTEGRAL SWITCH

CM

MM

FEEDER SIZE INDICATOR

DUPLEX RECEPTACLE FLOOR BOX

DOUBLE DUPLEX RECEPTACLE FLOOR BOX

EMERGENCY PUSH BUTTON

EXISTING SURFACE MTD PANELBOARD

EXISTING FLUSH MTD PANELBOARD

GENERAL NOTES

AFCI ARC FAULT CIRCUIT INTERRUPTER

GAL GALLONS

GRD GROUND

DEMOLITION / RELOCATION DESIGNATIONS

RELOCATED DEVICE.

EXISTING DEVICE TO REMAIN.

RR

RR

ER

ER

ETR

ETR

REMOVE EXISTING ELECTRICAL DEVICE.

REMOVE & RELOCATE EXISTING ELECTRICAL DEVICE.

SINGLE LINE DRAWING, AS APPLICABLE.)

(SHOWN FOR CLARITY/COORDINATION WITH

EXISTING ELECTRICAL PANEL REMOVED BY OWNER. RX/OD

RX

RX

AND DEVICES SHOWN ON PLANS.)

(NOTATIONS SHOWN ABOVE TO BE TYPICAL FOR ALL EQUIPMENT

ETL EXISTING TO BE RELOCATEDETR EXISTING TO REMAIN

ETD EMERGENCY TRANSFER DEVICE

DT

MMOTOR-RATED SWITCH/DISCONNECT

CIRCUIT (GRAY RECEPTACLE)

DUPLEX RECEPTACLE ON DEDICATED

CIRCUIT

NORMAL CIRCUIT & ONE DUPLEX (GRAY) ON DEDICATED

DOUBLE DUPLEX RECEPTACLE WITH ONE DUPLEX ON

TELE TELEPHONE

THK THICKTRF TRANSFORMER

VOL VOLUMEVFD VARIABLE FREQUENCY DRIVE

RX REMOVE

JPF

POWER FEED AT MOVEABLE PARTITION

FHPOWER FEED AT LABORATORY FUME HOOD

(COORDINATE MTG. HT. W/ARCH.)

RECEPTACLE FOR DISPLAY SCREEN/TV

J

PFPT POKE-THRU ASSEMBLY W/"PF" DESIGNATING POWER FEED

PEDESTAL-COUNTER MOUNTED RECEPTACLE

FVNR FULL VOLTAGE NON-REVERSING (MOTOR STARTER)

RVNR REDUCED VOLTAGE NON-REVERSING (MOTOR STARTER)

PP POWER POLE

GENERAL DEMOLITION NOTES

FB FLOOR BOX WITH POWER FEED AT MOVEABLE PARTITION

CONTROLLED RECEPTACLE

S

S

ONE UNCONTROLLED RECEPTACLE

SPLITWIRED RECEPTACLE WITH ONE CONTROLLED AND

DUPLEX AND ONE UNCONTROLLED DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE WITH ONE CONTROLLED

GFI DEADFRONT GFCI DEVICE

GFCI DUPLEX RECEPTACLE

WPWEATHERPROOF HORN AND STROBE LIGHT

HW

HWHALLWAY COVERAGE PATTERN

WALL MOUNTED PASSIVE INFRARED OCCUPANCY SENSOR,

OCCUPANCY & DAYLIGHT SENSORS

FaS

Sa'a' SWITCH NO.

'S' SWITCH TYPE

SWITCH DESIGNATIONS:

(ON/OFF, RAISE, LOWER)

LOW VOLTAGE WALL DIMMER SWITCH - 3 BUTTON

LV2 (ON, OFF)

LOW-VOLTAGE WALL SWITCH - 2 BUTTON

SLV3

(FULL ON, PARTIAL ON, OFF)

LOW-VOLTAGE WALL SWITCH - 3 BUTTON

STS

SSC LIGHTING SCENE CONTROL STATION

LIGHTING CONTROL SYSTEM TOUCHSCREEN INTERFACE

DL

'DL' AUTOMATIC DAYLIGHTING CONTROLLED FIXTURE

'2A-2' PANEL 2A CKT #2

'a' SWITCH NO.

'F' FIXTURE TYPE

FIXTURE DESIGNATIONS:

FB FLOOR BOX

F

RELOCATED BY THE OWNER.

PROCESS EQUIPMENT WITH OWNER. EQUIPMENT IS EXISTING AND

COORDINATE EXPLOSION-PROOF RECEPTACLE REQUIREMENTS FOR 30.

LEAVING THE CLASSIFIED AREA.

AREAS, PROVIDE RIGID CONDUIT AND CONDUIT SEALS ON CONDUIT

AS REQUIRED BY CALIFORNIA ELECTRICAL CODE IN HAZARDOUS / LISTED 29.

APPLICABLE.

SPACES. INSTALL CONDUIT TIGHT TO CEILING OR BUILDING STEEL, AS

GRID LINES, PARTICULLARLY IN OPEN CEILING OR LABORATORY CEILING

INSTALL RACEWAYS PARALLEL AND/OR PERPENDICULAR TO BUILDING 28.

SHOWN.

AND THE SPECIFICATIONS, PROVIDE THE HIGHEST RATING SPECIFIED OR

UPSTREAM DEVICE. IF THERE IS A CONFLICT BETWEEN THE DRAWINGS

DEVICES OR EQUIPMENT SHALL BE RATED THE SAME AS THE NEAREST

WHERE NO SHORT CIRCUIT INTERRUPT/WITHSTAND RATING IS INDICATED, 27.

OPERATIONAL.

BALANCE PANEL PHASES ONCE USER EQUIPMENT IS INSTALLED AND 26.

EQUIPMENT. MAINTAIN ACCESSIBILITY TO CONTROLS.

CONTRACTORS FOR LOCATION AND POWER REQUIREMENTS OF

COORDINATE WITH HVAC, PLUMBING, AND FIRE PROTECTION 25.

CEILINGS.

MAINTAIN ACCESS TO ALL COMMUNICATIONS RACEWAYS ABOVE LAY-IN 24.

CENTER OF THE CEILING TILES, UNLESS OTHERWISE NOTED.

CEILING MOUNTED ELECTRICAL DEVICES SHALL BE MOUNTED IN THE 23.

SEE ARCHITECTURAL FLOOR PLANS FOR WALL CONSTRUCTION TYPES.22.

ARCHITECTURAL REFLECTED CEILING PLANS.

DRYWALL OR PLASTER CEILINGS. COORDINATE CEILING TYPES WITH

PROVIDE PLASTER FLANGES FOR RECESSED LIGHTING FIXTURES IN 21.

ARE NOT ACCEPTABLE.

SMR SHALL BE ATTACHED TO WALL WITH PLUGS AND SCREWS. TAP CONS 20.

STRUCTURE.

FIXTURES. 2x4 PENDANT FIXTURES SHALL HAVE 4-POINT SUPPORT ON

PROVIDE MINIMUM 2 POINT SUPPORT FROM STRUCTURE TO LIGHTING 19.

WELL AS FACTORY ELBOWS AND MISCELLLANEOUS END PLATES.

PROVIDE RISER DUCTS AS REQUIRED WHEN SMR ELEVATION CHANGES AS

VERIFY SMR LOCATIONS IN REFERENCE TO CASEWORK LOCATIONS. 18.

ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION.

COORDINATE ELEVATION AND LOCATION OF ELECTRICAL DEVICES WITH 17.

HAVE ITS OWN INDIVIDUAL FULL SIZE NEUTRAL BACK TO PANEL.

EACH DESIGNATED CIRCUIT HOMERUN SERVING RECEPTACLES SHALL 16.

ON ALL RACEWAYS WHICH CROSS ANY BUILDING EXPANSION JOINTS.

THE USE OF APPROVED TYPE EXPANSION FITTINGS SHALL BE REQUIRED 15.

OF USE.

PROVIDE A GREEN GROUND WIRE FOR EACH COMMON NEUTRAL TO POINT

HAVING EXISTING CIRCUITS SERVING AREAS BEYOND THIS PROJECT,

CONDUITS DESIGNATED BY THE ELECTRICAL TRADE TO BE REUSED, AND

AND ALL EXISTING CIRCUITS TO BE REUSED IN THIS PROJECT. IN EXISTING

PROVIDE A GREEN GROUND WIRE FROM PANEL FOR ALL NEW CIRCUITS 14.

EXACT LOCATIONS WITH THE MECHANICAL TRADE.

MECHANICAL EQUIPMENT AND DUCTWORK IS INSTALLED. COORDINATE

LOCATE JUNCTION BOXES AS REQUIRED TO ALLOW ACCESS AFTER 13.

RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

FIXTURES, ETC. TO MEET THE CONSTRUCTION SCHEDULE SHALL BE THE

ANY ADDITIONAL COST TO ENSURE DELIVERY OF PANELS, LIGHT 12.

MOUNTED.

INSTALLED IN GYPSUM BOARD CONSTRUCTION, THEY SHALL BE RECESS

RACEWAY. WHERE DUPLEX RECEPTACLES ARE SHOWN AND CAN BE

WALLS WITH SURFACE MOUNTED OUTLET BOX AND SURFACE METAL

DUPLEX RECEPTACLES SHALL BE SURFACE MOUNTED ON MASONRY 11.

OF EACH SHIFT.

AREAS SHALL BE CLEANED AND LEFT IN ORIGINAL CONDITION AT THE END 10.

END OF THAT SHIFT.

BEING PERFORMED DURING THAT SHIFT AND SHALL BE REPLACED AT THE

CEILING TILE SHALL ONLY BE REMOVED FROM AREAS WHERE WORK IS 9.

PAINTING, CONCRETE, ETC. REQUIRED TO COMPLETE THIS PROJECT.

ELECTRICAL TRADE SHALL BE RESPONSIBLE FOR CUTTING, PATCHING, 8.

ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE.

EQUIPMENT SHALL BEAR U.L. LABELS AND BE GROUNDED AND BONDED IN 7.

MINIMUM CONDUIT SIZE SHALL BE 3/4"6.

POWER CIRCUITS.

WIRES SMALLER THAN #12 AWG SHALL NOT BE USED FOR LIGHTING OR 5.

PAY ALL FEES.

ELECTRICAL CONTRACTOR AND THE ELECTRICAL CONTRACTOR SHALL

PERMITS NECESSARY FOR THIS WORK SHALL BE OBTAINED BY THE 4.

WORK SHALL MEET THE APPROVAL OF THE OWNER'S REPRESENTATIVE.3.

RULES AND REGULATIONS OF THE LOCAL MUNICIPALITY.

WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE N.E.C. AND ALL 2.

TO THE PHASING AS OUTLINED BY THE OWNER.

BEEN DIVIDED INTO SEVERAL PHASES AND ALL TRADES MUST CONFORM

THE DEMOLITION AND CONSTRUCTION WORK FOR THIS PROJECT HAVE 1.

DOJ POWER FEED AT DOOR OPERATOR

ASENSOR, HALLWAY COVERAGE PATTERN

CEILING MOUNTED PASSIVE INFRARED OCCUPANCY

DT/DS SENSOR WITH INTEGRAL DAYLIGHT SENSOR

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY

DS CEILING MOUNTED DAYLIGHT SENSOR

"x" INDICATES SWITCH LEG (TYPICAL)

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR

DTx

2X4 FIXTURE

CENTER DIFFUSER, IF PRESENT ON FIXTURE

2X2 FIXTURE - LINE INDICATES ORIENTATION OF

EMERGENCY BATTERY PACK)

2X4 FIXTURE (" " - DESIGNATES FIXTURE WITH

EMERGENCY BATTERY PACK)

2X2 FIXTURE (" " - DESIGNATES FIXTURE WITH

WITH EMERGENCY BATTERY PACK)

1X1 FIXTURE (" " - DESIGNATES FIXTURE

WITH EMERGENCY BATTERY PACK)

1X4 FIXTURE (" " - DESIGNATES FIXTURE

WITH EMERGENCY BATTERY PACK)

FLUORESCENT STRIPLIGHT (" " - DESIGNATES FIXTURE

WITH EMERGENCY BATTERY PACK)

PENDANT TUBE FIXTURE (" " - DESIGNATES FIXTURE

LED STRIPLIGHT

CEILING MOUNTED LIGHT FIXTURE

CEILING MOUNTED WALL WASHER

WALL MOUNTED FIXTURE

POLE MOUNTED FIXTURE

CEILING MOUNTED EXIT SIGN W/ ARROWS AS INDICATED

WALL MOUNTED EXIT SIGN W/ ARROWS AS INDICATED

FIXTURE WITH EMERGENCY BATTERY PACK)

CEILING MOUNTED WALL WASHER (" " - DESIGNATES

WITH EMERGENCY BATTERY PACK)

CEILING MOUNTED FIXTURE (" " - DESIGNATES FIXTURE

WITH EMERGENCY BATTERY PACK)

WALL MOUNTED FIXTURE (" " - DESIGNATES FIXTURE

WITH EMERGENCY BATTERY PACK)

POLE MOUNTED FIXTURE (" " - DESIGNATES FIXTURE

BATTERY PACK)

(" " - DESIGNATES FIXTURE WITH EMERGENCY

OF FIXTURES AS INDICATED ON PLAN.

LIGHTING TRACK - LENGTH OF TRACK AND NO.

DETAILS ON DRAWINGS E-350 AND E-351

LIGHTING CONTROL SCHEME INDICATOR - REFER TO

J J-HOOK PATHWAY

PEDESTAL-COUNTER MOUNTED DATA OUTLET ROUGH-IN

EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT

480V,3P,30A,10AF

NEMA 12

W/10A FUSE

30A SWITCH SIZE

3 POLE

480V

480V,3P,30A,10AF - DENOTES:

(NOTATION TYPICAL)

NEMA 12 - DENOTES ENCLOSURE

NOTE:

OFOI OWNER FURNISHED OWNER INSTALLED

TELECOMMUNICATIONS OUTLET ROUGH-IN

TV

FURNISHED, OWNER INSTALLED)

WALL MOUNTED SECURITY CAMERA (OWNER

INSTALLED)

CARD READER LOCATION (OWNER FURNISHED, OWNER

SPECIFIED FOR REUSE, STORAGE, OR RETAINED BY THE OWNER.

MATERIALS AND EQUIPMENT INDICATED FOR REMOVAL, WHICH ARE NOT

DESIGNATED BY THE OWNER. REMOVE PROMPTLY FROM SITE ALL

REMOVE ALL EQUIPMENT THE OWNER WISHES TO RETAIN TO A SITE AS

THE OWNER SHALL REVIEW EQUIPMENT ITEMS INDICATED FOR REMOVAL. 11.

COORDINATED WITH THE OWNER PRIOR TO REMOVAL OR RELOCATION.

PRESENTLY CONCEALED IN EXISTING CONSTRUCTION SHALL BE

THE REMOVAL OR RELOCATION OF EXISTING ELECTRICAL EQUIPMENT 10.

THIS PROJECT.

CONTRACTORS. REMOVE FIXTURES AND WIRING AT THE COMPLETION OF

FIXTURES AND WIRING SHALL REMAIN IN PLACE FOR USE BY

WATTAGE REQUIRED FOR ADEQUATE ILLUMINATION. TEMPORARY LIGHTING

PROVIDE TEMPORARY POWER AND LIGHTING FIXTURES WITH LAMPS OF 9.

APPLICABLE CODES.

SERVICE, IT SHALL BE RE-SUPPORTED IN ACCORDANCE WITH ALL

SUPPORT OF EXISTING ELECTRICAL EQUIPMENT THAT IS TO REMAIN IN

IN THE EVENT THAT DEMOLITION WORK AFFECTS THE STRUCTURAL 8.

WORK. HOLES IN FLOOR SLABS SHALL BE FILLED WITH FIRE SAFING.

PATCH HOLES AND REPLACE DAMAGED MATERIAL CAUSED BY DEMOLITION 7.

NO ADDITIONAL CHARGE TO THE OWNER.

SHALL BE REPLACED WITH SIMILAR TYPE AS APPROVED BY THE OWNER, AT

REMAIN OR TO BE RELOCATED THAT ARE DAMAGED DURING DEMOLITION

ELECTRICAL EQUIPMENT, FIXTURES, AND/OR DEVICES SCHEDULED TO 6.

DRAWINGS, SHALL BE MAINTAINED.

THE ALTERATION, EVEN THOUGH THEY MAY NOT BE INDICATED ON THE

THE CONTINUITY OF EXISTING CIRCUITS THAT MAY BE INTERRUPTED BY 5.

DIRECTED BY THE OWNER.

POWER OUTAGES SHALL BE FOR MINIMUM DURATION AT OFF-HOURS AS 4.

CABINET AND COORDINATE WORK WITH OTHER TRADES.

ASSOCIATED WIRE, CONDUIT AND JUNCTION BOXES BACK TO PHONE

COORDINATE TELEPHONE WIRE DISCONNECTION WITH OWNER. REMOVE 3.

NOT SHOWN ON PLAN.

JUNCTION BOXES, ETC. WITHIN DEMOLITION AREA EVEN THOUGH THEY ARE

AT THE DISCRETION OF THE OWNER, REMOVE ABANDONED CONDUIT, WIRE, 2.

AND ASSOCIATED WIRE, CONDUIT, AND/OR JUNCTION BOXES.

EQUIPMENT, LIGHTING FIXTURES, JUNCTION BOXES, ELECTRICAL DEVICES

IN DESIGNATED DEMOLITION AREAS, PERMANENTLY REMOVE ELECTRICAL 1.

E EQUIPMENT CONNECTION

TYPE E - NEMA 6-20R

TYPE D - NEMA L6-50R

TYPE C - NEMA L6-30R

TYPE B - NEMA L6-20R

TYPE A - NEMA L5-30R

& TYPE AS INDICATED:

SPECIAL PURPOSE RECEPTACLE - SIZE

SPS

PROJECTION SCREEN UP/DN SWITCH

J

PSJ

CLG

PROJ

CLG

POWER FEED TO CEILING-MOUNTED PROJECTOR