di electrics
DESCRIPTION
JLHVDDSHLVTRANSCRIPT
-
ENGRAM Engineering Ltd.
-
Insulation distances arround the active part in the tank
End-Distances in the core window
Main insulation distances between the windings
Phase to phase distances in core window
Spacer thicknesses in the winding
-
The insulation distances between the outer winding and the tank wall on the non regulated low voltage side
Insulation level Minimum distance
up to 12 kV 80 mm
up to 24 kV 90 mm
up to 36 kV 100 mm
up to 45 kV 110 mm
over 45 kV 120 mm
The above distances are to be increased by 40 mm if the HV insulation level is over 120 kV
-
The insulation distances between the outer winding and the flux collector covered tank wall on the regulated high voltage side
Insulation level Minimum distance
up to 36 kV 120 mm
up to 52 kV 160 mm
up to 72.5 kV 180 mm
up to 100 kV 200 mm
up to 123 kV 220 mm
up to 145 kV 240 mm
up to 170 kV 270 mm
up to 245 kV 300 mm
up to 362 kV 320 mm
up to 420 kV 340 mm
up to 525 kV 390 mm
-
The HV side distances shall be used for distance between the tank wall and OLTC and for the OLTC and outer winding.
The LV side distances shall be used for the distance between the outer winding and the short side of the tank.
The given distances can be modified by the followings.
the non usual arrangement of the leads
LV side regulation
high currents on LV side
booster, auxiliary transformer or reactor inside the tank
more tap changer in the tank
etc
-
Under the core to the bottom of the tank:
65 mm
Above the core to the tank cover:
80 100 mm
-
The given distances are with the consideration of 30 40 mm pressure ring
In case of ODAF cooling the end distances are changed
-
LI AC UD + LD X Y
325 140 200 60 90
350 140 200 60 90
380 152 210 65 95
450 185 220 70 100
550 230 240 75 105
650 275 260 80 115
750 325 280 115 150
850 360 300 125 165
900 395 320 140 175
950 395 340 150 185
1050 460 360 195 240
-
Radial clearances in the same phase
Oil duct at the winding is 6 mm maximumEF EndFed, CF CenterFed, CR CourseRegulation, FR - FineRegulation
BIL 75 95 125 170 250 325 380 450
AC kV 30 38 50 70 100 140 152 185
Main gapEF 16 16 16 16 17 24 25 32
CF 16 16 16 16 17 22 24 29
HV CR/FREF 16 16 16 16 17 25 27 32
CF 16 16 16 16 17 22 24 29
CR
-FR
no ZnO
20% 16 16 16 16 16 16 16 20
10% 16 16 16 16 16 16 16 16
with ZnO
20% 16 16 16 16 16 16 16 16
10% 16 16 16 16 16 16 16 16
-
BIL 550 650 750 850 900 950 1050 1300 1425
AC kV 230 275 325 360 395 395 460 570 630
Main gapEF 38 46 54 60 66 66 76 96 106
CF 36 44 50 56 62 62 72 90 100
HV CR/FR
EF 38 46 54 60 66 66 76 96 106
CF 36 44 50 56 62 62 72 90 100
CR
-FR
no ZnO
20% 22 26 31 34 38 38 42 52 58
10% 16 16 16 17 20 20 22 26 29
with ZnO
20% 16 17 20 24 25 25 29 36 38
10% 16 16 16 16 16 16 16 17 20
-
No switching impulse test
BIL 75 95 125 170 250 325 380 450
AC kV 30 38 50 70 100 140 152 185
FR
-F
R
Y connected
20% 20 20 20 20 20 20 20 20
10% 20 20 20 20 20 20 20 20
Delta connected
20 20 20 20 20 26 28 33
HV - HV 20 20 20 20 20 26 28 33
-
No switching impulse test
BIL 550 650 750 850 900 950 1050 1300 1425
AC kV 230 275 325 360 395 395 460 570 630
FR
-F
R
Y connect.
20% 24 29 33 38 40 42 47 58 63
10% 20 20 20 20 20 21 23 29 32
Delta connected
41 48 56 63 67 70 78 96 106
HV - HV 41 48 56 63 67 70 78 96 106
-
The given minimum values are for the average spacer thickness in the winding.
At internal directed oil flow the minimum spacer thickness is 3 mm.
For position changing of parallel conductors the appropriate place should be ensured. This is the sum of conductor height and the spacer thickness.
BIL of the winding end Minimum thickness of the spacers
BIL 450 kV 3 mm
450 kV < BIL 550 kV 4 mm
550 kV < BIL 750 kV 4.5 mm
750 kV < BIL 950 kV 5 mm
950 kV < BIL 6 mm
-
DIL factors
Weidmann curve safety margin
T50
Spacer thickness
Combined stress
Point stress
Turn to turn
-
The reference voltage kVAC is calculated by dividing the actual occurring voltage by the corresponding DIL factor
DIL factor
BIL Chopped wave 2.75
BIL full wave 1.2/50 s 2.50
Switching impulse 1.90
1 hour voltage 0.80
AC test voltage 1.00
Nominal voltage 0.59
-
Maximum allowed electrical stress in the oil ducts is given by the Weidmann curves (degassed oil):
Adjacent to a winding:
Between cylinders:
Safety margin with respect to the curves of degassed oil: 10%
Safety margin defined by
Safety margin values (minimum):
Regular transformer: 10 % (Limit = curve * 0.9)
Large Power, Special, Critical, : 20 % (Limit = curve * 0.8)
37.0
max *5.17 dE
37.0
max *5.21 dE
With d: width of the oil duct
strength
stressSF 1
-
Weidmann curves
Bare electrodes + cooling ducts adjacent to windings
1: degassed oil -> E = 17.539 * d-0.3581
2: gas saturated oil -> E = 14.196 * d-0.3690
Insulated electrodes
1: degassed oil -> E = 21.407 * d-0.3684
2: gas saturated oil -> E = 18.557 * d-0.3769
-
Use only T50 factor for situation between discs where:Safety margin is not metSafety margin can not easily be increased by standard measures.Well defined half-value time. Well defined peak.
Increase withstand by multiplying with adequate factor in function of the half-value time.
-
T50 FACTOR
Time, microsecondUnshrunk paper covering, mm
0,65 0,75 0,80 0,85 1,00 1,15 1,25 1,50 2,00 2,50 3,00
1 1,514 1,507 1,503 1,500 1,489 1,478 1,471 1,454 1,419 1,385 1,351
2 1,343 1,341 1,340 1,340 1,332 1,323 1,319 1,309 1,289 1,269 1,249
3 1,266 1,264 1,262 1,261 1,257 1,253 1,250 1,243 1,228 1,213 1,198
4 1,220 1,218 1,217 1,216 1,213 1,210 1,208 1,202 1,191 1,180 1,167
5 1,188 1,186 1,186 1,185 1,182 1,180 1,179 1,174 1,165 1,156 1,146
7 1,146 1,145 1,145 1,144 1,142 1,141 1,140 1,137 1,130 1,123 1,116
10 1,109 1,108 1,108 1,107 1,107 1,106 1,105 1,103 1,098 1,093 1,088
15 1,073 1,073 1,072 1,072 1,072 1,071 1,070 1,069 1,067 1,064 1,061
20 1,052 1,052 1,051 1,051 1,051 1,051 1,050 1,049 1,048 1,046 1,044
25 1,037 1,037 1,037 1,037 1,037 1,036 1,036 1,035 1,034 1,033 1,032
30 1,026 1,026 1,026 1,026 1,026 1,026 1,025 1,025 1,024 1,024 1,022
35 1,017 1,017 1,017 1,017 1,017 1,014 1,006 1,000 1,017 1,016 1,016
40 1,011 1,011 1,011 1,011 1,010 1,010 1,010 1,010 1,010 1,010 1,009
45 1,005 1,005 1,005 1,005 1,005 1,005 1,005 1,005 1,005 1,005 1,004
50 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
55 0,996 0,996 0,996 0,996 0,996 0,996 0,996 0,996 0,996 0,998 0,996
60 0,992 0,992 0,992 0,992 0,992 0,992 0,992 0,992 0,992 0,993 0,993
65 0,989 0,989 0,989 0,989 0,989 0,989 0,989 0,989 0,989 0,990 0,990
70 0,986 0,986 0,986 0,986 0,986 0,986 0,986 0,986 0,986 0,987 0,987
75 0,983 0,983 0,983 0,983 0,984 0,984 0,984 0,984 0,984 0,984 0,985
-
The target is the partial discharge free arrangement
Partial discharge free curve as formula:
Umax=(0.375*sp+15.75)*wire+9.5*sp+57
-
The minimum paper insulation on normal rectangular conductor is 0.45 mm.
For Continously Transposed Cable this is 0.6 mm.
The thickness of enamel on CTC individual strands depends on the CTC manufacturer. Typical value is arround 0.1 mm.
In windings without key spacers the allowable maximum impulse voltage between wire:
Umax=84.5* wire+10 [kV]
-
In case of a winding with internal directed oil flow the following minimum spacer thicknesses should be used.
3 mm up to 60 mm winding radial dimension
4 mm up to 100 mm winding radial dimension
6 mm up to 140 mm winding radial dimension
7.5 mm winding radial dimension over 140 mm
4 mm is the minimum spacer thickness in case of CTC winding
The above thicknesses must be increased for electrical reasons
-
AVERAGE COMBINED STRESS
The equivalent radial gap clearence:
t = oil clearance + pressboard clearance/2 + paper clearance/1.5 [mm]
The equivalent axial gap clearance
uncompressed thickness of key spacers + (thickness of paper insulation * (2.2/3.5)) [mm]
Axial stress calculated maximum lghtning impulse voltage between discs
Radial stress calculated maximum radial lightning impulse voltage to neighbouring winding
Max. allowed value:
BIL full wave: < 25 kV / mm
BIL chopped wave: < 27.5 kV / mm
22 ) . .
()
. .
(..
gapaxeq
stressax
gapradeq
stressradStressCombAv
-
POINT STRESS
On critical points (if the average combined stress seems to be critical), electric field calculation should be made for checking the critical regions.
The field calculation practical boundary conditions:Axi-symmetric
Max voltage in time to be used, in axial and radial direction, independent from each other.
Max radial voltage at same position of considered discs.
Max allowed Point stress < 35 kV / mm (max. 6 mm duct at the winding)
-
TURN TO TURN IN DISC
Strength is the 70% of the curve on page 303 (fig.5.79) from Large Power Transformers, Karsai-Kernyi-Kiss
Continuous service
Turn-to-turn voltage at nominal voltage < 2.5 kV / mm
-
Have a good job!