    Installation, Operation and Maintenance Instructions

    Read and Save These Instructions

    This manual is provided to acquaint you withthe dehumidier so that installation, operationand maintenance can proceed successfully.Ultimate satisfaction depends on the qualityof installation and a thorough understandingof this equipment. The dehumidier is built

    around tested engineering principles and haspassed a thorough inspection for quality ofworkmanship and function.

    QuestDRY 150

    Installation, Operation and Maintenance Instructions

    P. O. Box 8680 Phone 608-222-5301

    Madison, WI 53708 Toll-Free 1-800-533-7533

    www.thermastor.com [email protected]

    Read and Save These Instructions

    Specifcations subject to change without notice.

    TS-472

    Revised 2/08

    QuestDRY50

    Water Removal Rates (Pints/Day)

    150 pints 80F, 60% (AHAM)

    Quest DRY50:

    Patentpending,optimizedair-to-airheatexchanger.

    Requiresonly6.9amps/115Vhalftheamountofcompetitors!

    Environmentally-friendlyR410Arefrigerant.

    High-efciency,long-lifeimpellerfan.

    Quietoperationandsuperiorhighstaticpressureperformance.

    Pre-conguredforfreshairventilation.

    Industry-leading7.9pintsperkWh.

    questAsset Protection and IAQ Solutions

    quest

  • 8/14/2019 Dry150 Manual

    2/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    Table of ContentsSafetyPrecautions.....................................................3

    1. IntendedApplication............................................4

    2.Specications......................................................4

    3.Installation4 3.1 Location........................................................4

    3.2ElectricalRequirements................................. 5

    3.3CondensateWaterRemoval...........................5

    3.4Ducting......................................................... 6

    3.4AInstallingDuctCollars..........................6

    3.4BDuctingforDehumidication................6

    3.4CDuctingforFreshAir............................. 6

    3.4DInstallationinaBasement....................7

    3.4EInstallationinaattic.............................. 8

    3.4FInstallationwith(2)HVACsystems......... 8

    3.4GInstallationwithoutanHVACsystem....8 3.5QuietInstallation...........................................8

    3.6NoiseAbatement...........................................9

    4.Controls ...........................................................9

    4.1A Humidity/FanControlPanel WITHOUTFreshAirVentilationor...... Damper..............................................9

    4.1B Humidity/FanControlPanelWITH...... FreshAirVentilationandWITHOUT

    Damper..............................................9

    4.1C Humidity/FanControlPanelWITH

    FreshAirVentilationANDDamper...10 4.1DVentilationTimerandHumidity ControlWITHFreshAirAND MotorizedDamper...........................10

    4.1E DEH3000DigitialControl

    WITHFreshAirANDDamper.......... 10

    4.1F DEH3000DigitalControlWITHOUT FreshAir...........................................10

    4.2HumidityControlAdjustment...................... 10

    4.3Fan/FilterSwitch.......................................... 10

    4.4VentilationTimer......................................... 11

    4.4ASettingtheTime................................... 11

    4.4BVentilationSchedule............................11 4.4CAutomaticorManualMode................11 ControlsWiringDiagram............................. 12

    5.DEH3000DigitalControl

    InstallationInstructions.......................................13

    5.1.Specications.............................................. 13

    5.2.Installation...................................................13

    5.2A InstallInstructions............................. 13

    5.2B Wiring..............................................13

    5.2C AuxillaryRelayOperation................14 5.2D DehumidierLockout....................... 15 5.2E Location........................................... 15 5.2F Testing..............................................15

    5.3.Operation....................................................17 5.3A Display............................................. 17

    5.3B Setting..............................................17

    5.3C On/OffSetting..................................17

    5.3D SettingClockTime............................17

    5.3E SettingRelativeHumiditySetpoint.... 17

    5.3F Operation......................................... 18

    5.3G FanSetting&Operation................... 18

    5.3H DamperOperationandSetting (Ventilation)......................................19

    5.3I Intermittent/ProgrammedVentilation19

    5.3J TemperatureCutoutProgramming....20

    5.3K DefaultSettings................................21

    6.Maintenance....................................................... 22

    6.1StandardAirFilter........................................22

    6.2HighEfciencyAirFilter.............................. 22

    6.3 ImpellerFanOiling...................................... 22

    6.4FreshAirReturn.......................................... 22

    7.Service ......................................................... 22

    7.1Warranty....................................................22

    7.2Technicaldescription...................................23

    7.3Troubleshooting...........................................23

    7.4RefrigerantCharging...................................25

    7.5ImpellerFanReplacement.......................... 25

    7.6Compressor/CapacitorReplacement............25

    7.6ACheckingCompressorMotorCircuits. 26

    7.6BReplacingBurnedOutCompressor..... 26

    7.6CReplacingCompressor-NonburnOut..27

    7.7RemoteControls.......................................... 27

    7.7AHumidityControl................................27

    7.7BVentilationTimer..................................27

    7.8DefrostThermostat.......................................28

    7.9ElectricVentilationDamper.......................... 28 7.10CondensatePumpKit................................. 28

    ElectricalSchematic...............................................29

    PictorialElectricalDiagram..................................... 30

    ServicePartsList..................................................... 31

    OptionalPartsList.................................................. 32

    DoorandCollarAssembly......................................33

    Warranty ............................................................. 34

  • 8/14/2019 Dry150 Manual

    3/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    Safety Precautions

    Readtheinstallation,operationandmaintenanceinstructionscarefullybeforeinstallingandoperatingthisdevice.ProperadherencetotheseinstructionsisessentialtoobtainmaximumbenetfromyourQuestDRY150indoorairqualitysystem.

    FOR HVAC INSTALLER AND OWNER ONLY

    READ AND SAVE THESE INSTRUCTIONS

    ThedeviceisdesignedtobeinstalledINDOORSINASPACETHATISPROTECTEDFROMRAINANDFLOODING.

    Installtheunitwithspacetoaccessthebackorsidepanels

    formaintenanceandservice.DONOTINSTALLUNITWITHTHESERVICEPANELSINACCESSIBLE.

    Avoiddirectingthedischargeairatpeople,oroverthewaterinpoolareas.

    Ifusednearapoolorspa;becertainthereisNOchancetheunitcouldfallintothewater,besplashedandthatitispluggedintoaGFIGROUNDFAULTINTERRUPTOUTLET.

    DO NOT use the device as a bench or table.

    DONOTplacethedevicedirectlyonstructuralmembers.Providevibrationisolationinordertominimizeoperational

    vibrationand/ornoise. AdrainpanMUSTbeplacedundertheunitifinstalledabovealivingareaoraboveanareawherewaterleakagecouldcausedamage

  • 8/14/2019 Dry150 Manual

    4/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    1. Intended Application for Quest DRY150

    Fortheidealinstallation,drawairfromthecentralpartofthestructureandreturnittoisolatedareasofthestructureliketherestrooms,utilityormechanicalroom,orcookingarea.Theductworkoftheexistingheatingsystemcanbeusedtosupplyairtothestructure.

    2. Specications

    Model: QuestDRY150IndoorAirQualitySystem

    Electrical: 110-120VAC,6.9Amps,60Hz,grounded

    WaterRemovalCapacity: 150pints/day@80F,60%RH

    OperatingTemp.Range: 56Fmin.,100Fmax.

    AirFlow: [email protected]"WG

    [email protected]"WG

    RefrigerantCharge: 2lb.,R-410.A

    Ductconnections: Round10"&6"inlets,10"outlet(ovaled)

    FilterSize: 2"X16"X16"

    Size(w/oductcollars): 37"wideX22"highX205/8"deep

    UnitWeight: 134lbs.

    3. Installation

    3.1 LocationTheQuestDRY150canbeinstalledinavarietyoflocationstomeettheowner'sneedsaslistedbelow.Inallcaseskeepthefollowingcautionsinmind:

    ItisdesignedtobeinstalledINDOORSINASPACETHATISPROTECTEDFROMRAINANDFLOODING.

    Installtheunitwithspacetoaccessthebackandsidepanelsformaintenanceandserviceandalsotoalloweasyaccesstotheltercoverpanel.DONOTINSTALLUNITWITHTHEFRONTPANELORFILTERCOVERPANELINACCESSIBLE.

    Avoiddischargingtheairdirectlyatpeople,oroverthewaterinpoolareas.

    Ifusednearapoolorspa,becertainthereisNOchancetheunitcouldfallintothewaterorbesplashed

    andthatitispluggedintoaGROUNDFAULTINTERRUPTER.

    DONOTusetheQuestDRY150asabenchortable.

    DONOTplacetheQuestDRY150directlyonstructuralmembers.Providevibrationisolationinordertominimizeoperationalvibrationand/ornoise.

    AdrainpanMUSTbeplacedundertheunitifinstalledabovealivingareaoraboveanareawherewaterleakagecouldcausedamage.

    FOR HVAC INSTALLER AND OWNER ONLY

  • 8/14/2019 Dry150 Manual

    5/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    5

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    PlacetheQuestDRY150onsupportsthatraisethebaseoftheunitabovethetopoftheangesonthedrainpanbeneathit.RaisingtheQuestDRY150willhelptheunitdrainwithgravityow.DonotplacetheQuestDRY150directlyonstructuralbuildingmemberswithoutvibrationabsorbersorunwantednoisemayresult.

    TheQuestDRY150maybesuspendedwithsteelhangerstraps(plumberstape)orasuitablealternativefrom

    structuralmembers,unitmustbesupportedfromunderneath.Don'thangfromsidesorends.Remembertoplaceadrainpanundertheunitifitissuspendedaboveanishedareaoraboveanareawherewaterleakagecouldcausedamage.

    TheQuestDRY150shouldbelocatedneartheexistingairhandlingsystemtominimizetherequiredductworkforconnectingtheQuestDRY150totheexistingairhandlingsystem.ThecontrolsfortheQuestDRY150areremotefromtheunitandmustbelocatedinthespacethatistobeconditioned.Thecontrolsarelowvoltage(24volt)andshouldbeconnectedtotheQuestDRY150withlowvoltagethermostatcable.

    Iffreshairventilationisdesired,thoughtshouldbegiventothelocationforthefreshairducting.A6"roundinsulatedductwillhavetobeinstalledontheQuestDRY150andruntotheoutsideofthestructuretobringinfreshair.Usean8"insulatedroundductforlengthsofmorethan50feetorifmorethan100CFMisneeded.Consultlocalcodesfornecessarydistancesfromexhaustportswheninstallingfreshairreturn.

    3.2 Electrical Requirements

    WARNING: DO NOT ALLOW THE YELLOW LEAD FROM THE QUEST DRY150 TO CONTACT THE REDLEAD OR WHITE LEAD FROM THE Quest DRY150 OR DAMAGE TO THE TRANSFORMER WILL RESULT.

    TheQuestDRY150plugsintoacommongroundedoutlet.Itdrawsaround6.9Ampsundernormaloperatingconditions.Ifusedinawetarea(pool,sparoom,orbasementpronetoooding),agroundfaultinterrupterprotectedcircuitisrequired.

    Installtheremotecontrolpanelinacentralareaofthestructurewhereitwillsensetherelativehumidityofthestructureaccurately.DonotinstallthecontrolpanelwhereitmaynotaccuratelysensetherelativehumiditysuchasnearHVACsupplyregisters,nearexteriordoors,ornearapoolorspa.TheinstallermustsupplythewiringbetweentheQuestDRY150andthecontrolpanel.Besuretosafelyroutethecontrol

    wiringtopreventdamageduringinstallation.BecarefulnottocrossthewireswhenconnectingtheQuestDRY150andtheremotecontrolpanelordamagetothetransformermayresult.

    TheremotecontrolsoftheQuestDRY150arepoweredbyalowvoltagecircuit(24Vac)andmustNEVERcontactorbeconnectedtoahighvoltagecircuit.ThecontrolwiresleavingtheQuestDRY150andtheremotecontrolpanelsarenumberedandcolor-codedtopreventconfusion.SomeofthecontrolwiresleavingtheQuestDRY150maynotbeusedwithcertaincontrolpanelsandshouldbeleftsafelydisconnectedwithwirenutstapedontothestrippedends.BesuretoconsulttheelectricalschematicinthismanualorinsidetheaccesspaneloftheQuestDRY150beforemakingthecontrolconnections.

    3.3 Condensate Water RemovalCondensatedrainsbygravityviathedrainport.Use3/4"maleNPTPVCpipe.Routedrainpipetodrain.Installatrap

    ifpossible.Takecarewheninstallingdrainpipetodrainport.Useanadjustablewrenchtosecurethedrainport.Anoptionalcondensatepumpkitmaybeinstalledifaliftisrequiredtodisposeofthecondensate.Thecondensatepumpkitcanbeordereddirectlyfromthefactory.Seetheoptionalpartslistforinformationonthekit.

    1.00"

    External drain trap on unit

    is recommended

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    6/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    3.4 Ducting3.4A Installing Duct Collars

    TheQuestDRY150isequippedwith10"and6"roundinletcollarsanda10"round(ovaled)exhaustcollar.Followinstructionsincludedwithcollars.

    3.4B Ducting for Dehumidication

    Fortheidealinstallation,drawairfromthecentralpartofthestructureandreturnittotheisolatedareasofstructure.Theductworkoftheexistingheatingsystemcanbeusedtosupplyairtothestructure.Iftheexistingsupplygoestoisolatedareasofthestructure,dischargethesupplyoftheQuestDRY150intothesupplyoftheexistingheatingsystem.Iftheexistingheatingsystemincorporatesacentralsupply,installationofaseparatesupplyductfromtheQuestDRY150toeachisolatedareaisrecommended.DONOTdrawairdirectlyfromtheisolatedareas.Youmaydrawairfromareasthatareopentothestructure.AllexibleductingconnectedtotheQuestDRY150shouldbeULlisted.

    TheinletoftheQuestDRY150isthe10"diameterholeinthelterenclosureoftheunit.A10"roundcollarissuppliedwiththeunittoattachtoroundduct.Theductmaybepermanentlyattachedtothecollar.A6"roundcollarisprovidedwiththeunittoattachtothe6"holeinthelterenclosure.The6"collarshouldbe

    cappediffreshmake-upairisnotdesired.Iffreshmake-upairisdesired,seeSection3.4C.A10"round(ovaled)collarissuppliedwiththeunitfortheoutletoftheQuestDRY150.

    AlengthofexibleductingonallQuestDRY150ductconnectionsisrecommendedtoreducenoiseandvibrationtransmittedtorigidductworkinthestructure.

    DuctingtheQuestDRY150asmentionedinSections3.4A-3.4Grequiresconsiderationofthefollowingpoints:

    Duct Sizing: Fortotalductlengthsupto25',useaminimum10"diameterroundorequivalentrectangular.Forlongerlengths,useaminimum12"diameterorequivalent.Grillsordiffusersontheductendsmustnotexcessivelyrestrictairow.

    Isolated Areas:Effectivedehumidicationmayrequirethatductingbebranchedtoisolated,stagnantareas.

    Use8"orlargerdiameterbranchductingtoeachoftwoorthreeareas,use6"orlargertoeachoffourormoreareas.

    Connecting to existing HVAC systems: Anoptional10"checkdamperisavailablefromthefactorytopreventreverseowthroughtheQuestDRY150.IftheQuestDRY150isductedtothesupplyductingairhandler,itisrecommendedthatthecheckdamperbeplacedintheQuestDRY150supplyduct.Contactthefactorywhenconnectingtoastaticpressureofgreaterthanorequalto+.5"WG.

    3.4C Ducting for Fresh Air

    Freshaircanbebroughtintothestructurebyconnectinganinsulatedductfromoutsidetothe6"QuestDRY150inletandbyturningonthefanswitchoractivatingthehumiditycontrol(onunitswiththehumiditycontrolpanel).Activatetheventilationtimeronunitswiththeventilatingandhumiditycontrolpaneltobringinfreshair.RefertoSection4.5forprogramminginstructionsfortheventilationtimer.Advantagesofthisformofventilationinclude:

    1.Outsideairislteredbeforeenteringthebuilding.

    2.OutsideairwillbedehumidiedbeforeenteringiftheQuestDRY150isrunningindehumidicationmode.

    3.Drawingairfromoutsideandblowinginsideaidsinslightlypressurizingthestructure.Thishelpspreventdirtyandhumidairfromenteringelsewhere.Italsoreducesthepotentialforcarcinogenicradongastoenterandprovidesmake-upairforopencombustionandexhaustdevicesliketheclothesdrier,replace,andwaterheater.

    4.Adequateexhaustfansarerecommendedthroughoutthestructure(e.g.,restrooms).

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    7/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    Incoldclimatesorareaswheretheoutdoordewpointislowattimes,ventilationcanbeusedtodehumidifythestructure.Thisisaccomplishedbybringingthedry,lowdewpointairintothestructureduringthesetimes.Thisapproachisoftenmoreeconomicalthanrunningthedehumidiertoremoveexcessmoisturefromthestructure.Incoldclimates,itiscriticaltoadequatelyventilatetoreducetheinsidemoisture

    contenttoavoidmoistureaccumulatinginthewallcavities.Forexample;inastructurethatexperiencescondensationontheinteriorsurfaceofthewindowsduringthewinter,increasingtheamountofventilationwilloftencuretheproblem.

    Aninsulated6"diameterductisgenerallysufcienttoprovideupto125CFMofoutsideair.LargequantitiesofoutsideairwilleitherpositivelyornegativelyimpacttheperformanceoftheQuestDRY150,dependinguponinsideandoutsideairconditions.Consultthefactorybycalling1-800-533-7533forrecommendationsregardingtheuseofhigherowswithyourspecicapplication.

    Theoutsideairductshouldbeconnectedtothe6"roundcollaronthelterenclosureoftheunit.The6"roundcollarincludesamanualdamper.Adjustthemanualdampertoprovidethedesiredamountoffreshairforventilation.Theamountoffreshairshouldbebasedonthesizeandoccupancyoftheresidence.Ifyouareunsureofyourventilationairrequirements,consultthefactorybycalling1-800-533-7533forassistance.

    3.4D Installation in a Basement or Crawlspace with an Existing Forced Air HVAC System

    Itisrecommendedthatanew,separatereturnductbeinstalledfortheQuestDRY150fromacentralareaofthestructure.Ifthisisnotpossible,andiftheexistingsystemhasmultiplereturns,selectonetodisconnectfromtheexistingforcedairsystemanduseitforthededicatedQuestDRY150return.Alwaysselectareturnfromacentrallocationinthestructureinanareathatisalwaysopentotherestofthestructure.Donotuseareturnfromaroomthatmayhaveitsdoorclosedmuchofthetime.

    IfthestructureinwhichtheQuestDRY150istobeinstalledhasanexistingforcedairHVACsystem,utilizetheHVACsystemtomaketheQuestDRY150installationeasier.

    Basement Installation:Installaseparate10"returnfortheQuestDRY150inacentralareaofthestructure.DuctthesupplyoftheQuestDRY150toanoptional10"x10"x10"tee/damperthatis20%opentothebasement.Thisallowstheabilitytodischargeavariableamountofdehumidiedairintoabasementthat

    maynotbewellservedbytheexistingductsystem.DucttheothersideoftheteetotheairsupplyoftheexistingHVACsystem.Abackdraftdamperisrequiredintheductbetweenthe10"teeandthecentralsupplyducttopreventairfrombeingdischargedintothebasementduringcentralfanoperation.Connectaductfromoutsidetothe6"collaroftheQuestDRY150ifyouwishtoprovidefreshairventilation.

    Crawl Space Installation:InstallaseparatereturnfortheQuestDRY150inacentralareaofthestructure.DuctthesupplyoftheQuestDRY150toa10"x10"x10"tee/damperthatis20%opentothecrawlspaceifdesired.Ducttheothersideoftheteetotheairsupplyof

    theexistingHVACsystemventilation.Connectaninsulatedductfromoutsidetothe6"collaroftheQuestDRY150ifyouwishtoprovideoptionalfreshair.

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    8/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    3.4E Installation in a Ceiling Cavity with an Existing Forced Air HVAC System

    ALWAYSinstallacatchpanwithadrainand/oroatinterruptswitchforcondensateundertheQuestDRY150inanattictoreducelikelihoodofwaterdamage.

    LocateaseparatereturnfortheQuestDRY150inacentralareaofthestructure.DuctthesupplyoftheQuestDRY150totheairsupplyoftheexistingHVACsystem.Connectaninsulatedductfromoutsidetothe6"collaroftheQuestDRY150ifyouwishtoprovidefreshairventilation.Adjustdamperinthecollartoprovidethedesiredamountoffreshair.Usingaremotecontrol,programtheunittobringinthedesiredamountoffreshair.

    3.4F Installation in a Structure with Two ForcedAir HVAC Systems

    TheQuestDRY150canbeinstalledintotwotypicalHVACductingsystems.InstallaseparatereturnfortheQuestDRY150asdirectedabove.Dischargeairfromthedehumidiershouldbe

    splitandroutedtoeachsupplyductingsystem.AbalancingdamperandabackdraftdamperisrequiredineachductbetweentheQuestDRY150andtheHVACductingsystem.Thisallowsairowtobeadjustedandpreventsowofairbetweentheductingsystems.Contactthefactoryforassistance,ifnecessary.

    3.4G Installation in a Structure with No Existing Forced Air HVAC System

    WheninstallingtheQuestDRY150inastructurethatdoesnothaveaforcedairHVACsystem,asinglereturnfortheQuestDRY150shouldbeinstalledincentralopenareaofthestructure.DONOTlocatethereturninarestroomorakitchenorcookingarea.ThesupplyoftheQuestDRY150shouldbelocatedintheremoteareasofthestructure(suchasbedrooms,den,etc.).Byductingthisway,theairinsidethestructurewillcirculatethroughtheQuestDRY150tobelteredanddehumidied.Avoiddischargingalltheairfrom

    thedehumidierinonelocationtopreventheatbuildupinthatarea.4"diameterductisrecommendedforbranchestothesmallerareas,6"diameterductisrecommendedforbranchestolargerareas.Refertosection3.4Bforbranchductsizing.Connectaninsulatedductfromoutsidetothe6"collaroftheQuestDRY150ifyouwishtoprovidefreshairventilation.

    3.5 Quiet InstallationConsidercompressionvibrationandairownoiseduringinstallation.Useofexductand/orvibrationisolationmaterialsduringmountingandductingwillresultinquieteroperation.

    3.6 Noise AbatementAlengthofexibleductingonallQuestDRY150ductconnectionsisrecommendedtoreducenoiseandvibrationtransmittedtorigidductworkinthestructure.

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    9/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    4. Controls

    Allcontrolpanelsshouldbemountedinacentralareaofthestructurewhereitcanaccuratelysensethehumidityoftheairinthelivingspaceandbeaccessed.Allcontrolsrequireeldwiringfromtheunitlocationtothepanelmountlocation.

    To determine how each control operates the Quest DRY150, it must rst be determined which control isbeing used and whether or not the Quest DRY150 is ducted for fresh air ventilation. Refer to appropriatesection.

    Humidity/Fan Control Panel (P/N 4024155) (Figure 1)

    4.1A Humidity/FanControlPanelWITHOUTFreshAirVentilationorDamper

    4.1B Humidity/FanControlPanelWITHFreshAirVentilationandWITHOUTDamper

    4.1C Humidity/FanControlPanelWITHFreshAir

    VentilationANDDamper

    Ventilation Timer/Humidity Control Panel (P/N 4024125)(Figure 2)

    4.1D VentilationTimerandHumidityControlWITHFreshAirANDMotorizedDamper

    DEH 3000 Digital Control (P/N 4024539) (Figure 3)

    4.1E DigitalControllerWITHFreshAirANDDamper

    4.1F DigitalControllerWITHOUTFreshAir

    4.1A Humidity/Fan Control Panel WITHOUT Fresh Air Ventilation or Damper

    Thehumidity/fancontrolpanelautomaticallycontrolsthehumidityofthespace.Thehumidity/fancontrolpanelcontainsanadjustablehumiditycontrolandafanswitch.Thepanelhasacoverthatmustremainopentotheairwithinthelivingspaceforaccuratehumiditysensing.WhenthefanswitchisintheONposition,airwillbecontinuallylteredandcirculatedthroughoutthestructure.Forhumiditycontroloperationrefertosection4.2.

    4.1B Humidity/Fan Control Panel WITH Fresh Air Ventilation and WITHOUT Damper

    Thehumidity/fancontrolpanelautomaticallycontrolsthehumidityofthespace.Thehumidity/fancontrolpanelcontainsanadjustablehumiditycontrolandafanswitch.Thepanelhasacoverthatmustremainopentotheairwithinthelivingspaceforaccuratehumiditysensing.Outsideairiscontinuallyintroducedwhenever

    fanisON.Manualoperationoffanlterswitchcontrolsoutsideairventilation.SincethefanoperateswhenevertheQuestDRY150isdehumidifyingoutsideairwillalsobeintroduced.Forhumiditycontroloperationrefertosection4.2.

    4.1C Humidity/Fan Control Panel WITH Fresh Air Ventilation AND Damper

    Inthisconguration,amotorizeddamperhasbeeninstalledinthefreshairduct.Whenthefan/lterswitchisintheOFFposition,thedamperisclosed.TheQuestDRY150willthencirculateanddehumidifyairtoprovidehumiditycontrol.

    Figure 1: Humidity/Fan

    Control PanelPart No. 4024155

    Figure 2: Ventilation Timer

    and Humidity Control PanelPart No. 4024125

    Figure 3: DEH 3000 DigitalControl (P/N 4024539)

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    10/34

  • 8/14/2019 Dry150 Manual

    11/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    resetbuttonisthesmallrecessedbuttonwithanRbeneathitlocatedbelowthe1-7andhbuttons.Depresstheresetbuttonuntilthedisplayclears.Releasetheresetbutton.Thedisplaywillreappearas00:00.Resettingthetimerwillclearthetimeandallprogramsettings.Afterresettingthetimerfollowtheinstructionsbelowtosetthecorrecttimeandventilation

    programs.4.4A Setting the Time

    Setthecorrecttimeonthetimerbyslidingtheswitchintheupperrighthandcornerofthetimertotheclocksymbol.andpressingthe1-7(DAY),h(HOUR),andm(MINUTE)buttons.Rememberthistimeroperatesona24-hour(militarytime)clock.

    4.4B Ventilation Schedule

    SlidetheswitchintheupperrighthandcornertotheprogramsymbolP.ONwillappeartotherightofthetimeandthenumber1willappearinthelowerrighthandcornerofthedisplay.The1andONsignifytheturnontimefortherstprogram.Pressthe1-7,handmbuttontochoosethedaysoftheweekforthisprogram.YoucanchooseMon.-Sun.,Mon.-Fri.,Sat.-Sun.,oranysingledayoftheweek.Thedayschosenareshownalongthetop

    ofthedisplayontheventilationtimer.Nextpressthehbuttontosetthehourforthestartoftheventilationperiod.Rememberthistimeroperatesona24-hourclock(militarytime).Thenpressthembuttontosettheminutespastthehourtostarttheventilation.

    Now,withtheventilationstarttimeset;presstheI/Obutton.ThewordOFFshouldappeartotherightofthetimeandthenumber1shouldremaininthelowerrighthandcornerofthedisplay.The1andOFFsignifytheturnofftimefortherstprogram.Settheturnofftimeusingthe1-7,handmbuttonsinthesamewayasdescribedaboveandcontinueontothesecondthroughsixthprograms.Whensettingtheventilationprograms,youcanreturntothecurrenttimedisplaybyslidingtheswitchintheupperrightcornerofthetimertoRUN.TheslideswitchmustbesettoRUNforthetimertooperateitsscheduledprograms.

    4.4C Automatic or Manual Mode

    Theslideswitchintheupperleftofthetimerisusedtochoosebetweenautomaticandmanualoperation.WhentheslideswitchissettoAUTOmode,theQuestDRY150willventilatewhenthescheduledprogramscallforventilation.When

    theslideswitchissettomanual(settohandsymbolontheright),theoperationofthetimeriscontrolledbytheI/Obuttononly.PressingtheI/ObuttonwillswitchtheventilationtimerbetweenON(detent)andOFF(detent).AsyoupresstheI/Obutton,ONorOFFwillbedisplayedtotherightofthetime.The ONorOFFindicatesiftheventilationtimerisonoroff.TheI/ObuttonwillmanuallyoverridescheduledprogramsifthetimerisinAUTOmode.

    Figure 6: Humidity/FanControl Panel Part No.055

    Figure 7: Ventilation Timerand Humidity ControlPanel Part No. 4024125

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    12/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    WIRE THE UNIT AND CONTROL PACKAGE AS SHOWN IN THE DIAGRAM BELOW

    WARNING: DO NOT allow the yellow lead from the unit to contact the red lead or the white lead from the unit ordamage to the transformers will result. Do not direct connect the white lead on the unit to the violet lead on theventilation control or damage to the transformer will result.

    ControlPartNo.4026570

    UA Base Unit

    Yello

    w

    Re

    d

    Blue

    Green

    White

    DAMPER

    24VAC

    DMP COMP FAN

    optional

    Humidity/Fan Control Panel

    Ventilation Timer/HumidityControl Panel

    DEH 3000 Digital Control

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    13/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    5. DEH 3000 Digital Control Installation Instructions

    5.1 SpecicationsPartNumber: 4026570

    Model: DEH3000DigitalControl

    Electrical: 24VAC

    HumidityRange: 1095%RH

    HumidityAccuracy: +/-5%

    Output: 3Amps24VAC

    RelayCapacity: 5Amps

    TempRange/Accuracy: 2%

    Size: 4.95"widex4.19"high

    5.2 InstallationThiscontrolpanelmustbeinstalledintheconditionedspaceandinaccordancewithallapplicablecodesandstandards.Followtheinstructionsbelowwheninstallingandsettingthiscontrol.

    5.2A Install Instructions

    1. Separatethefrontpanelfromthebackpanelbydepressingthemiddlesectionsofthetopandbottomofthefrontpanel.

    2. Linethebackpanelupagainstthewalloratsurfaceontowhichitistobemountedanddrillintheappropriatemountingholes.

    3. Insertthescrewsandtightendownsotheyextendapproximately1/8fromthebackplate.

    4. Alignthebackpanelsothatthecontrolislevel.

    5. Tightenthescrewstolockintoposition.

    6. Maketheelectricalconnectionstotheterminalsonthebackpanelasshowninthewiringdiagram.

    7. Reassemblethefronttothebackpanel.Connectatthetoprst,thenatthebottom.

    8. Testconnections(seeSection2.6)

    5.2B Wiring

    WARNING: DO NOT ALLOW THE YELLOW LEAD FROMTHE Quest DRY150 TO CONTACT THE RED OR WHITELEADS FROM THE Quest DRY150 OR DAMAGE TO THETRANSFORMER WILL RESULT. UNPLUG Quest DRY150BASE UNIT BEFORE WIRING CONTROL.

    TheinstallermustsupplythewiringbetweentheQuestDRY150andthecontrolpanel.Besuretosafelyroutethecontrolwirestopreventdamageduringinstallation.BecarefulnottocrossthewireswhenconnectingtheQuestDRY150andtheremotecontrolpanelordamagetothetransformermayresult.

    TheremotecontroloftheQuestDRY150ispoweredbyalowvoltagecircuit(24VAC)andmust NEVERcontactorbeconnectedtoahighvoltagecircuit.SomeofthecontrolwiresleavingtheQuestDRY150maynotbeusedwithcertaincontrolpanelsandshouldbeleftsafelydisconnectedwithwirenutstapedontothestrippedends.BesuretoconsulttheelectricalschematicinthismanualoronthefrontpaneloftheQuestDRY150beforemakingthecontrolconnections.

    Control Part No. 4026570

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    14/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    WARNING: TO AVOID TRANSFORMER DAMAGEONLY CONNECT THE WHITE WIRE TO THE

    CONTROL IF A DAMPER IS USED.

    Thewhitewirecontrolstheoptionalmotorizeddamperthatcanbeinstalledintoafreshairduct.ThisprovidestheabilitytocontrolwhenfreshairisintroducedintothebuildingbyusingtheventilationtimerfunctionlabeledDMPonthecontrol(SeeSection3.7).IF THE MOTORIZED DAMPER ISNOT USED, DO NOT CONNECT THE WHITEWIRE TO THE CONTROL OR DAMAGE TO THETRANSFORMER MAY RESULT.Simplyleavethe(DMP)terminalunusedifthedamperisnotused,andcapoffthewhiteleadfromtheQuestDRY150

    dehumidier.

    5.2C Auxiliary relay operationAttimesitmaybedesirabletocoordinatefanoperationofthecentralheating/coolingsystemwithdehumidieroperation.TheDEH3000featuresarelaythatprovidesthisability.TherelayterminalslabeledNC,COMandNOoperateaccordingtothefollowingchart:

    DehumidicationOperation COM/NO COM/NC

    ON CLOSED OPEN

    OFF OPEN CLOSED

    Commonuses(assumingstandardthermostatwiringcolorschemesasnoted):

    Disengage A/C during dehumidication

    RedirecttheyellowthermostatwiretotheNCterminal.WiretheyellowwirefromtheA/CtotheCOMterminal.

    Engage the A/C central fan during dehumidication

    1.Disconnectthegreenwirethatrunstothefanrelayfromthescrewonthethermostat.

    2.ConnectthegreenwirethatrunstothefanrelaytotheCOMscrewontheDEH3000board.

    3.RunawirefromtheredwirescrewonthethermostattotheNO(NormallyOpen)screwontheDEH3000board.

    4.RunawirefromthegreenwirescrewonthethermostattotheNC(NormallyClosed)screwontheDEH3000board.

    ThecentralfanshouldrunwhentheThermostatfanswitchisturnedtoONandwhenthedehumidierisoperating.

    FOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    15/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    5

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    5.2D Dehumidier lockout/activation:AC sensor featureThecontrolhastheabilitytoactivatethedehumidierordeactivatethedehumidierwhentheairconditionerisrunning.

    Standard wire colors for thermostats are as follows:

    Description Color Terminal code

    24VACReturn Red R

    CallforHeat White WorW1

    ForceFanOn Green G

    CompressorCallforCooling Yellow YorY1

    DEHUMIDIFIER DEACTIVATES WHEN THEAIR-CONDITIONER IS RUNNING

    Thecommonwireonthethermostattransformer(black)needstobewiredwiththeyellowwirefromthedehumidier.

    TheYellowwirefromthethermostatmustbewiredtotheACoffsensorterminal.

    DEHUMIDIFIER ACTIVATES WHEN THEAIR-CONDITIONER IS RUNNING

    Thecommonwireonthethermostattransformer(black)needstobewiredwiththeyellowwirefromthedehumidier.

    TheYellowwirefromthethermostatmustbewiredtotheAConsensorterminal.

    5.2E LocationInstalltheremotecontrolpanelinacentralareaofthestructurewhereitwillsensetherelativehumidityofthestructureaccurately.DonotinstallthecontrolpanelwhereitmaynotaccuratelysensetherelativehumiditysuchasnearHVACsupplyregisters,nearexteriordoorsandwindows,ornearapoolorspa.

    5.2F TestingAfterwiringconnectionshavebeenmade,verifyconnections.First,makesurethewhitewirefromthebaseunitisnotwireddirectlytotheDEH3000control.Theremustbeamotorizeddamperinserieswiththeseconnections,orthewhitewiremustnotbeconnectedtothecontrol.Mis-wiringmayresultintransformerdamage.

    FOR HVAC INSTALLER AND HOMEOWNERFOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    16/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    After connections have been veried, this short test will conrm proper wiring.

    1.Installfrontcoverofcontrol;insertattoprst,thenbottom.

    2.PluginQuestDRY150baseunit.Thecontrolshouldpowerup.

    3.TurncontrolonbypressingtheON/OFFbutton.

    4.EngagedehumidicationoperationbyadjustingRHsetpointbelowambientconditions.

    a.PressRHuntilRHsetpointis20%.

    b.VerifyQuestDRY150fanandcompressoroperation.

    c.Verifyventilationdamper(ifused)isclosed.

    5.Verifyfanonlyoperationbydisengagingdehumidicationandoperatingfan:

    a.AdjustRHsetpointaboveambientconditionsbypressingandholdingRHuntilsetpointis80%.

    b.Pressfanbutton,thenpressagaintotogglefantoONsetting.

    c.Releasefanbutton,thenpressagaintotogglefantoONsettinguntilFANashesondisplay.

    d.VerifyfanoperationofQuestDRY150.Nocompressoroperationshouldbenoted,andventilationdamper(ifused)shouldbeclosed.

    6.Verifyventilationdamperoperation(ifinstalled)bydisengagingfromoperationandengagingventilatingoperation.

    a.PressandholdfanbuttonuntilFANashesondisplay.

    b.ReleaseFANbutton,thenpressagaintotogglefanoperationoff.

    c.PressandholdVENTbuttonuntilVENTashesondisplay.

    d.ReleaseVENTbutton,thenpressagainuntilOPENisdisplayed.

    e.VerifyQuestDRY150fanoperationandventilationdamperisopen,withnocompressoroperation.

    7.Ifanyfunctionsarenotworkingproperly,verifywiringandconnections.Metersmaybeusedacrossterminalstoverifyvoltage.Ifthereisaconcernaboutthebaseunitnotoperatingproperly,theleadsexitingthebaseunitmaybeconnectedandoperationveriedaccordingtothefollowingmatrix:

    Wire connections Operation Yellow&Blue Fan&Compressor

    Yellow&Green FanOnly

    Donottestanyotherconnectionsortransformerdamagemayresult.RefertotheappropriateQuestDRY150baseunitmanualforadditionalinformation.

    8.Verifyadditionaloptionalcontroloperationssuchasfaninterlockorlockout.

    9.Proceedtooperation/settingsection.

    FOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    17/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    5.3 Operation

    5.3A Display

    Whenthereispowertothecontrol,thecontroldisplaywillshowthe

    time,day,humidity,andtemperature. Whenthecontrolisturnedon,thesetpoint,fanstatus,auto/holdmode,andfreshairventstatusisdisplayed.

    Whenakeyispressedthedisplaywilllight.

    TheTIMEandDAYisdisplayedatthetopofthescreen.

    RHandTemperaturearedisplayedinrealtime.

    AnObeforethesetpoint,vent,orfanindicatestheunitisoperatingthedevice.

    AashingObeforethesetpoint,vent,orfanindicatestheunitisinadelaypriortooperatingthedevice.

    Note: Delay is an intentional factory installed time delay cycle that ismeant to prevent short cycles, extending the life of the Quest DRY150. Ifa delay is encountered, WAIT 10 MINUTES BEFORE EXPECTING NORMALOPERATION.

    5.3B Setting

    Duringtheset-upprocess,ifyoumakeamistake,simplycontinue.Youcanalwaysgobacktoadjustthesettings.Ifyouleavethecontrolaloneanddonttouchanybuttonsfor10seconds,thecontrolwillrememberanychangesmadeandreturntohome.

    5.3C On/Off Setting

    PresstheON/OFFbuttontoturnthesystemonoroff.Whenthesystemison,thesetpoint,fanstatus,auto/holdmode,andfreshairventstatusisdisplayed.Intheoffmode,thecontrolwillshowthetime,day,humidity,andtemperature.Whentheunitisshipped,itisinmanualmode.

    5.3D Setting Clock Time

    1. PressandholdtheCLOCKbutton.Thehourdisplaywillash.Releasethebutton.

    2. UsetheUP/DOWN RHbuttonstochangethevalue.

    3. PresstheCLOCKbuttonagainandtheminutedisplaywillash.UsetheRHbuttonstochangethevalue.

    4. PresstheCLOCKbuttonagainandtheAM/PMdisplaywillash.UsetheRHbuttonstotogglethevalue.

    5. PresstheCLOCKbuttonagainandthedaydisplaywillash.UsetheRHbuttonstochangethevalue.

    IftheCLOCKbuttonispressedagainornobuttonispressedfor5seconds,thedisplaywillautomaticallyreturntoHOME.

    5.3E Setting Relative Humidity Setpoint

    Therelativehumiditysetpoint(theaverageRHthatismaintained)operatesthedehumidierfunctionoftheQuestDRY150.Ithasnoeffectonanyotherfunctionoftheunit.Thecontrolsensestheambientrelativehumidityofthespaceinwhichitislocated.

    FOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    18/34

  • 8/14/2019 Dry150 Manual

    19/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    WiththefanintheAUTOmode,thefanwilloperateonlywhenneededbyotherfunctionsofthesystem.Thefanwillremainoffunlessthesystemisdehumidifyingand/orventilating.ThefanalwaysrunsduringdehumidicationandventilationandthefanOiconwillbelit.Tocompletelyturnthesystemoff,usetheON/OFFbuttonasdescribedearlier.ToadjusttheventilationmodeseeSection3.7.

    5.3H Damper Operation and Setting (Ventilation) Manual/Hold ModeQuestDRY150unitscanbeinstalledtoincorporateoptionalventilation.Thedampersettingcontrolstheventilationfunctionofthesystem.Ithasnocontroloverthedehumidicationfunction,althoughtheventilationfunctioncanandshouldbeusedtodrythespacedependingontheclimateandtheoutsideairconditions.RefertotheappropriateQuestDRY150manualformoreinformation.

    Inordertoprovideventilation,thedampermustbeopen(ON)andthefanmustberunning.Thecontrollertakescareofthesetwofunctionsautomatically,sothatwheneverthedamperisopen(ON),thefanisrunning.

    TheventilationindicatorOwillbedisplayedwhenevertheunitisventilating.ThefanoperationindicatorOwillalsobelit.

    Therearethreedamperoperationmodes,OPEN HOLD,CLOSED HOLDandPROGRAM

    (denotedbyON TIME OFF TIME.Refertosection3.8).WiththedamperintheOPEN HOLDmode,thedamperwillbeopenandthefanofthesystemwillbeoperatinginordertointroducefreshairintothespace.Usethismodeforcontinuousfreshairventilation.Thefanisalwaysonwhenthedamperisopen.WheninCLOSED HOLDmode,thedamperwillnotopenandthesystemwillnotventilate.

    WheninthePROGRAMmode,thecontrolwilloperatethedamperandfan(ventilate)accordingtotheprogrammedventilationschedule(SeeSection3.8).

    To set the damper operation:

    1. PresstheVENTbutton.Thecurrentsettingwillbegintoashonthedisplay.Releasethebutton.

    2. PresstheVENTbuttonagaintotogglebetween

    open,closedandprogram.3. Leavethecontrolalonefor10secondstoselecttheindicateddampermodeandreturntoHOME.

    5.3I Intermittent or Programmed Ventilation

    Thesystemwilloperatetheventilationfunctionaccordingtothecurrentventilationprogram.Thecontrolneedstobeprogrammedtoturntheventilationfunctiononandoffatthedesiredintervals.Thisisdonebyprogrammingtheventilationtimer.

    TherearetwoprogramsavailableforventilationMondaythroughFriday.TherearealsotwoprogramsforSaturdayandSunday.Nootherchoiceofdaysisavailable.

    Eachprogramhas:

    ASTARTtimeofdaywhentheventilationschedulebegins.

    AnOPEN FORdurationfortheamountoftimethedamperstaysopenin5minuteintervals,from0to60.

    ACLOSED FORdurationwhichclosestheventforaspeciedtimein5minuteintervalsfrom0to60.

    FOR HVAC INSTALLER AND HOMEOWNERFOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    20/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    0

    www.thermastor.com

    [email protected]

    Example:

    1. PressPROGRAM ENTERbutton.Thefollowingmenuappears:

    2. Usingtheup/downRHbuttons,selectPROGRAM.Thefollowingmenuappears:

    You can select from:

    MON-FRIorSAT-SUNforseparateweekday/weekendschedulesorMON-SUNwhichgivesyouequalweekday/weekendschedules.

    MenuwhenyouselectMON-FRIorSAT-SUN:

    1. Enterthestartingtimeforweekdaysusingtheup/downRHkeystochangethetime.

    2.PresstheprogramenterkeytotoggletotheOPEN FORsetting.Usingtheup/downRHkeys,changethedurationthatthedamperwillventilatefreshair.

    3.Presstheprogramenterkeytotoggletotheclosedforsetting.Usingtheup/downRHkeys,changethedurationthatthedamperwillremainclosedbetweenventilation.

    Fortheexamplegiven,startingat8:00AMinthemorning,thecontrolwillventilatefreshairfor15minutesthenstopfor15minutes.Thisscheduleof15minutesopen;15minutesclosedwillcontinueuntilthestarttimeofthenightschedule.

    PressPROGRAM ENTERagaintogototheMON-FRInightschedule.RepeatthestepslistedaboveforthisandtheSAT-SUNdayandnightschedules.

    Whenyoureturntothemainprogrammenu,usetheup/downRHbuttonstoselectRUN PROGRAM.

    PressPROGRAM ENTERtoruntheprogram.Thedisplaywillappearasfollows:

    5.3J Temperature Cutout ProgrammingQuestDRY150unitsproduceheatwhendehumidifying.Dependingonoutsideconditions,theventilationfunctionmayintroducewarmairintothespace.Occasionally,theoperationoftheQuestDRY150mayproduceenoughheattodrivetemperaturesup.ThetemperaturecutoutfeaturedisablesallQuestDRY150operationsiftemperaturesreachcutoutsetpoint.Inmostinstallationsthisfeaturewillnotneedtobeused.Iftemperaturecutoutisdesired,programthesetpointbypressingthePROGRAM ENTERbutton.PressRHuntilTEMP CUTOUTisashing.UseRHuporRHdowntoadjustsetpoints.

    FOR HVAC INSTALLER AND HOMEOWNERFOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    21/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    5.3K Default SettingsUponinitialpower-uporafterprolongedpoweroutages(morethan30minutes),theDEH3000isprogrammedwiththefollowingdefaults.Aspaceisprovidedtomakenoteofuserinputs.

    Setting Default My SettingRHsetpoint 50% __________

    VentilationOperation Closed __________

    FanSetting Auto __________

    TempCutout 80% __________

    If you have questions about the DEH 3000, please call Therma-Stor LLC at1-800-533-7533 or email us at [email protected] or [email protected]

    FOR HVAC INSTALLER AND HOMEOWNERFOR INSTALLER AND HOMEOWNERFOR HVAC INSTALLER AND OWNER

  • 8/14/2019 Dry150 Manual

    22/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    6. Maintenance

    6.1 Standard Air FilterTheQuestDRY150isequippedwithapleatedclothairlter.Thisltershouldbecheckedeverysixmonths.Operatingtheunitwithadirtylterwillreducedehumidiercapacityandefciencyandmaycausethecompressortocycleoffandonunnecessarilyonthedefrostcontrol.

    Toaccesstheairlter,removethelteraccesspanelfromtheendoftheQuestDRY150.TheltershouldbereadilyvisibleandcanberemovedbypullingthemstraightoutoftheQuestDRY150.

    Thepleatedclothltercangenerallybevacuumedcleanseveraltimesbeforeneedingreplacement.Replacementlterscanbeorderedfromthefactoryorpurchasedlocallyifavailable.DO NOToperatetheunitwithoutthestandardlterorwithalesseffectivelterthanthestandardlter.Theheatexchangecoilsinsidetheunitcouldbecomecloggedandrequiredisassemblytoclean.Filternon-complianceinvalidatestheproductwarranty.

    6.2 High Efciency Air FilterAnoptionalhighefciencypleatedmicroglasspaperlterisavailablefortheQuestDRY150.Thislterisratedas90%-95%efcientbytheASHRAEDustSpottestmethod52-76.Thehighefciencypleatedmicroglasspaperltershouldbeusedinconjunctionwiththestandardlter,andplaceddirectlybeneaththestandardlter.

    Thislterisabletoremoveallergycausingparticlesfromtheairstream.Thehighefciencylterhasamuchlargersurfaceareathanthestandardlter,thusthestandardltermayneedtobecleanedorreplacedseveraltimesbeforethehighefciencylterrequiresreplacement.Becarefulnottodamagethefabricmediawhenhandlingthehighefciencypleatedpaperlter.Donotattempttocleanthehighefciencypleatedpaperlter.Itshouldbereplacedwhenitbecomesrestrictive.

    6.3 Impeller Fan Oiling

    Theimpellerfanmotorisfactorylubricatedformanyyearsofnormaloperation,andnofurtheroilingisrequired.

    6.4 Optional Fresh Air ReturnCheckandcleanthescreenontheoutdoorfreshairreturnseasonally.Thescreenmaybecomepluggedduringtheseasonswhentherearemanyparticlesintheoutdoorair.

    7. Service

    7.1 WarrantyAwarrantycerticatehasbeenenclosedwiththisunit;readitbeforeanyrepairisinitiated.Ifawarrantyrepairisrequired,callthefactoryrstat1-800-533-7533forwarrantyclaimauthorizationandtechnicalassistance.

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    23/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    7.2 Technical DescriptionTheQuestDRY150usesarefrigerationsystemsimilartoanairconditioner'storemoveheatandmoisturefromincomingair,andaddheattotheairthatis

    discharged.

    Hot,high-pressurerefrigerantgasisroutedfromthecompressortothecondensercoil(SeeFigure3).Therefrigerantiscooledandcondensedbygivingupitsheattotheairthatisabouttobedischargedfromtheunit.Therefrigerantliquidthenpassesthroughalter/drierandcapillarytubingwhichcausestherefrigerantpressureandtemperaturetodrop.Itnextenterstheevaporatorcoilwhereitabsorbsheatfromtheincomingairandevaporates.Theevaporatoroperatesinaoodedcondition,whichmeansthatalltheevaporatortubescontainliquidrefrigerantduringnormal

    operation.Aoodedevaporatorshouldmaintainnearlyconstantpressureandtemperatureacrosstheentirecoil,frominlettooutlet.

    Themixtureofgasandliquidrefrigerantentertheaccumulatorafterleavingtheevaporatorcoil.Theaccumulatorpreventsanyliquidrefrigerantfromreachingthecompressor.Thecompressorevacuatesthecoolrefrigerantgasfromtheaccumulatorandcompressesittoahighpressureandtemperaturetorepeattheprocess.

    7.3 Troubleshooting

    No dehumidication, neither impeller fan nor compressor run with fan switch and ventilation timer OFF.

    1. Unitunpluggedornopowertooutlet.

    2.Humiditycontrolsettoohighordefective(Sec.3.3&5.7A)

    3.Looseconnectionininternalorcontrolwiring.

    4.DefectiveCompressorrelay.

    5.Defectivecontroltransformer.

    6.LowpressureControlopen(Sec3.7&5.10).

    7.OptionalCondensatePumpSafetySwitchopen(Sec5.11).

    No dehumidication, compressor does not run but impeller fan runs with fan switch and ventilation timerOFF and humidity control turned to ON.

    1.Defectivecompressorruncapacitor(Sec.5.6).2.Badconnectionincompressorcircuit(SeeFig.4).

    3.Defectivecompressoroverload(Sec.5.6A).

    4.Defectivecompressor(Sec.5.6).

    5.Defrostthermostatopen(Sec.5.8).

    Refrigeration System of Quest DRY150

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    24/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    Impeller fan runs with fan switch and ventilation timer OFF, but compressor cycles on & off.

    1.Lowambienttemperatureand/orhumiditycausingunittocyclethroughdefrostmode.

    2.Defectivecompressoroverload(Sec.5.6A).

    3.Defectivecompressor(Sec.5.6).

    4.Defrostthermostatdefective(Sec.5.8).

    5.Dirtyairlter(s)orairowrestricted.

    6.Lowrefrigerantcharge,causingdefrostcontroltocycle.

    7.Badconnectionincompressorcircuit.

    Impeller fan does not run with fan switch in either position. Impeller fan does not run with ventilationtimer activated. Compressor runs briey but cycles on & off with humidity control turned to ON.

    1.Looseconnectioninimpellerfancircuit(SeeFig.4).

    2.Obstructionpreventsimpellerfanrotation.

    3.Defectiveimpellerfan.

    4.Defectiveimpellerfanrelay.5.Defectiveimpellerfancapacitor.

    Impeller fan runs with fan switch ON. Impeller fan does not run with ventilation timer activated.

    1.Defectiveventilationtimer.

    2.Timenotcorrectonventilationtimer.

    3.Ventilationtimersettomanual&switchedOFF.

    4.Defectivefanswitch.

    Evaporator coil frosted continuously, low dehumidifying capacity.

    1.Defrostthermostatlooseordefective(Sec.5.8).

    2.Lowrefrigerantcharge3.Dirtyairlter(s)orairowrestricted.

    4.Excessivelyrestrictiveductingconnectedtounit.

    Unit not providing ventilation. Ventilation timer not operating correctly.

    1. Iftimerisnotfunctioningcorrectlyresettimerandreprogram(Sec.3.5).

    2.Checkcontrolwireconnections(checkconnectionsatfreshairdamperalso).

    3.Defectivefreshairdamper(Sec.5.9).

    4.Defectivefanswitch.

    Unit removes some water, but not as much as expected.

    1.Airtemperatureand/orhumidityhavedropped.2.Humiditymeterandorthermometerusedareoutofcalibration.

    3.Unithasentereddefrostcycle(Sec.5.8).

    4.Airlterdirty(Sec.4.1&4.2).

    5.Defectivedefrostthermostat(Sec5.8).

    6.Lowrefrigerantcharge(Sec.5.4).

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    25/34

  • 8/14/2019 Dry150 Manual

    26/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    7.6A Checking Compressor Motor Circuits

    PerformthefollowingtestsiftheimpellerfanrunsbutthecompressordoesnotwiththefanswitchandventilationtimerOFFandthehumiditycontrolON.

    1.Unplugtheunit;removethecabinetsideandtheelectricalconnectioncoveronthecompressortop.

    2.PlugintheunitandturnthehumiditycontroltoON.Checkfor110voltsfromcompressorterminalRtooverloadterminal3usinganACvoltmeter.Ifvoltageispresent,gotostep3.Ifnovoltage,theremaybealooseconnectioninthecompressorcircuit.Testeachcomponentforcontinuity.Seetheappropriatesectionifadefectissuspected.

    3.Unplugtheunit,andthendisconnecttheredandyellowwiresfromcompressorterminalsR&S.Usinganohmmetercheckcontinuitybetweenthepointslistedbelow.

    4.CompressorterminalsCandS:Nocontinuityindicatesanopenstartwinding.Thecompressormustbereplaced.Normalstartwindingresistanceis3to7ohms.

    5.CompressorterminalsCandR:Nocontinuityindicatesanopenrunwinding.Thecompressormustbereplaced.Normalrunwindingresistanceis.5to2ohms.

    6.CompressorterminalCandoverloadterminal1:Nocontinuityindicatesadefectiveoverloadlead.

    7.Overloadterminals1and3:Ifthereisnocontinuity,theoverloadmaybetripped.Wait10minutesandtryagain.Ifthereisstillnocontinuity,itisdefectiveandmustbereplaced.

    8.CompressorterminalCandcompressorcase:Continuityindicatesagroundedmotor.Thecompressormustbereplaced.

    9.Disconnectthewiresfromtheruncapacitor.SettheohmmetertotheRx1scale.Thecapacitorisshortedandmustbereplacedifcontinuityexistsacrossitsterminals.IfthereisnoneedlemovementwiththemetersetontheRx100000scale,thecapacitorisopenandmustbereplaced.

    10.Reconnectthewirestothecompressorandcapacitor.Pluginandturnontheunit.Ifthecompressorfailstostart,replacetheruncapacitor.

    11.Iftheunitstilldoesnotstart,addingahard-startkit(relay&capacitor)willprovidegreaterstartingtorque.Ifthisdoesn'twork,thecompressorhasaninternalmechanicaldefectandmustbereplaced.

    7.6B Replacing a Burned Out Compressor

    Therefrigerantandoilmixtureinacompressorischemicallyverystableundernormaloperatingconditions.However,whenanelectricalshortoccursinthecompressormotor,theresultinghightemperaturearccausesaportionoftherefrigerantoilmixturetobreakdownintocarbonaceoussludge,averycorrosiveacid,andwater.Thesecontaminantsmustbecarefullyremovedotherwiseevensmallresidueswillattackreplacementcompressormotorsandcausefailures.

    Thefollowingprocedureiseffectiveonlyifthesystemismonitoredafterreplacingthecompressortoinsurethatthecleanupwascomplete.

    1.Thisprocedureassumesthatthepreviouslylistedcompressormotorcircuittestsrevealedashortedoropenwinding.

    2.Removeandproperlydisposeofthesystemcharge.DO NOTventtherefrigerantorallowittocontactyoureyesorskin.

    3.Removetheburnedoutcompressor.Userubberglovesifthereisanypossibilityofcontactingtheoilorsludge.

    4.Tofacilitatesubsequentsteps,determinethetypeofburnoutthatoccurred.Ifthedischargelineshowsnoevidenceofsludgeandthesuctionlineisalsocleanorperhapshassomelightcarbondeposits,theburnoutoccurredwhilethecompressorwasnotrotating.Contaminantsarethereforelargelyconnedtothecompressorhousing.Asingleinstallationofliquidandsuctionlinelter/drierswillprobablycleanupthesystem.

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    27/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    Ifsludgeisevidentinthedischargeline,itwilllikelybefoundinthesuctionline.Thisindicatesthecompressorburnedoutwillrunning.Sludgeandacidhavebeenpumpedthroughoutthesystem.Severalchangesoftheliquidandsuctionlter/drierswillprobablybenecessarytocleansethesystem.

    5.Correctthesystemfaultthatcausedtheburnout.Consultthefactoryforadvice.

    6.Installthereplacementcompressorwithanewcapacitorandanoversizedliquidlinelter.

    Inarunningburnout,installanoversizedsuctionlinelter/drierbetweentheaccumulatorandcompressor.Thoroughlyushtheaccumulatorwithrefrigeranttoremovealltrappedsludgeandtopreventtheoilholefrombecomingplugged.Astandingburnoutdoesnotrequireasuctionlinelter/drier.

    7.Evacuatethesystemwithagoodvacuumpumpandaccuratevacuumgauge.Leavethepumponthesystemforatleastanhour.

    8.Operatethesystemforashortperiodoftime,monitoringthesuctionpressuretodeterminethatthesuctionlterisnotbecomingplugged.Replacethesuctionlter/drierifpressuredropoccurs.Ifasevererunningburnouthasoccurred,severallter/driersmayhavetobereplacedtoremovealloftheacidandmoisture.

    NOTE: NEVER use the compressor to evacuate the system or any part of it.

    7.6C Replacing a Compressor, Nonburn Out

    Removetherefrigerantfromthesystem.Replacethecompressorandliquidlinelter/drier.Chargethesystemto50PSIGandcheckforleaks.Removethechargeandweighintherefrigerantquantitylistedonthenameplate.Operatethesystemtoverifyperformance.

    7.7 Remote Controls

    TheQuestDRY150iscontrolledbydevicesmountedonapanelthatisremotefromtheunit.Youmayormaynothavethedeviceslistedbelowdependingonthemodeloftheremotecontrolpanelyoupurchased.IftheQuestDRY150failstooperateasdesired,alwayscheckthesettingsofthecontrolstoinsurethattheyarecorrect.Checkthatthecontrolsarereceiving24VacfromtheQuestDRY150.ChecktheconnectionsbetweentheQuestDRY150,thecontrolpanel,andtheeldcontrolwiring.

    7.7A Humidity Control

    Thehumiditycontrolisanadjustableswitchthatcloseswhentherelativehumidityoftheairinwhichitislocatedrisestothedialsetpoint.ItopenswhentheRHdrops4to6%belowthesetpoint.IftheQuestDRY150doesnotrun,tryturningthehumiditycontrolclockwiseuntilitreachesthestopandtheknobpointerpointsatMaxDry(seebackofcontrolpanelcover).Ifitstilldoesnotrun,removethestopscrewfromthepanelandturntheknobfarther.Ifitthenruns,thehumiditycontrolisoutofcalibrationortheRHisbelow40%.

    TheQuestDRY150isequippedwithanautomaticdefrostmechanism.IftheQuestDRY150operatesinconditionsthatdevelopfrostontheevaporator,itwillsensethefrostbuild-upandautomaticallydefrosttheevaporator.TheQuestDRY150maynotappeartobeoperatingcorrectlyduringthedefrostsequence,butoncethedefrostsequenceiscompleted,theQuestDRY150willresumedehumidifying.

    7.7B Programmable Ventilation Timer

    Theventilationtimercontrolstheimpellerfanandthemotorizedfreshairdamper.Whentheventilationtimerisactivated,theQuestDRY150willcirculatetheindoorair,andbringinfreshairfromoutside.Theventilationtimershouldbesetfortherequiredventilationoftheresidence.Thestructureshouldbeventilatedwithfreshairassuggestedbyapplicablecodesandstandards.

    IftheQuestDRY150failstoventilateasexpected,checkthatthetimeonthetimeriscorrect.Forthetimertocarryouttheprogramschedule,theslideswitchintheupperleftcorneronthetimermustbesettoAUTO.TheslideswitchintheupperrightcorneroftheQuest DRY150mustbesettoRUN.Alsochecktheprogramsonthetimertobesurethatthetimeriscallingforventilationatthecorrecttimes.Ifthetimerfailstooperateoroperateserratically,resetthetimer;seesection4.5ofthismanual.

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    28/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    7.8 Defrost ThermostatThedefrostthermostatisattachedtotherefrigerantsuctiontubebetweentheaccumulatorandthecompressor.Itwillautomaticallyshutthecompressoroffifthelowsiderefrigeranttemperaturedropsduetoexcessivefrostformationontheevaporatorcoil.Theimpellerfanwillcontinuetorun,causingairtoow

    throughtheevaporatorcoilandmelttheice.Whentheicehasmelted,theevaporatortemperaturewillriseandthethermostatwillrestartthecompressor.

    7.9 Electric Ventilation DamperTheelectricventilationdamperiscontrolledbytheventilationtimer.Thedamperwillopenwhentheventilationtimerisactivatedtoallowfreshairintothestructurethroughthe6diameterfreshairinletduct.Theelectricventilationdamperwillremainclosedwhentheventilationtimerisnotactivatedtopreventover-ventilatingthestructurewhentheunitisdehumidifyingorrecirculatingtheindoorair.

    Theelectricventilationtimeroperateson24Vacfromthecontrolcircuit. DO NOTconnecthighvoltagetothedampermotorordamagetothemotormayresult.DO NOTforcethebladeofthedamperbyhandordamagetothedampermotormayresult.

    Thedamperopensinonedirectiononly.Thedamperrotatesveryslowly,allowsufcienttimeforthedampertocycle.Thedamperwilltakeapproximately1minutetocyclefromclosedtoopenorfromopentoclosed.

    Iftheelectricventilationdamperfailstooperate:

    1.Checkthatthewiringiscorrectandthatvoltageispresentatthedampermotor.

    2.Checkforanyobstructioninsidethedamper.Iftheelectricventilationdamperfailstooperateafterperformingthesechecks,itmustbereplaced.

    7.10 Condensate Pump KitAnoptionalcondensatepumpkitisavailablefromthefactoryforusewiththeQuestDRY150.Condensateisautomaticallypumpedtoaremotelocationwhenthewaterlevelinthepump'sreservoirrisestoclosetheoatswitch.

    Thepumpalsocontainsasafetyoatswitch.Thewhiteleadsfromthisswitchextendfrombeneaththepumpcover.Thisswitchshouldbeinstalledinserieswiththeeldwirethatconnectstheblue(#5)leadfromtheQuestDRY150totheblue(#5)leadonthecontrolpanel.

    Ifthepumpfails,thisswitchopensthecompressorcontrolcircuitandstopswaterproductionbeforethereservoiroverows.TheQuestDRY150willcontinuetoventilateorcirculateairasnormal,butwillnotdehumidifyuntilthisswitchcloses.

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    29/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    FOR HVAC INSTALLER ONLY

    Electric Schematics

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    30/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    0

    www.thermastor.com

    [email protected]

    Pictorial Electrical Diagrams

    FOR HVAC INSTALLER ONLY

  • 8/14/2019 Dry150 Manual

    31/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    Item Part No Qty Description

    1 4026477 1 HEATEXCHANGER

    2 4026672 1 EVAPORATOR

    3 4026934 2 CAPILLARYTUBES

    .050"X.124"X59.00" 4 4026670 1 COMPRESSOR-TOSHIBA,8.1

    KBTU,115V,60HZ

    5 4026655 1 ACCUMULATOR

    6 4025087 1 FILTER/DRIER

    7 4026674 1 TUBE-CONDTOFILTER

    8 4026472 1 TUBE-DISCHARGELINE

    9 4026673 1 CONDENSOR

    10 4026657 1 IMPELLER

    11 4020924 1 RELAY/BLOWER

    Item Part No Qty Description

    12 4026687 1 45mFdCAPACITOR-COMPRESSOR

    13 4022487 1 TRANSFORMER

    14 4022484 1 RELAY/COMPRESSOR

    15 4017021 1 15mFdCAPACITOR-IMPELLER16 4026932 1 COLLAR10INCH

    17 4026947 1 COLLAROVAL10INCH

    18 4026933 1 COLLARW/DAMPER6INCH

    (NOTSHOWN)

    19 4026221 4 LEVELINGFOOT

    20 4021470 1 DEFROSTTHERMOSTAT

    (NOTSHOWN)

    4021648 1 DEFROSTTHERMOSTATCLIP

    (NOTSHOWN)

    21 4026660 1 WIRINGDIAGRAM

    50

    The Quest DRY 150

    5

    notshown

    Service Parts List

  • 8/14/2019 Dry150 Manual

    32/34

    questAsset Protection and IAQ Solutions

    quest1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    ITEM PART NO. QTY. DESCRIPTION

    26 4024375 1 CheckDamper,10"Diameter(notshown)27 4022220 1 CondensatePumpKit,External

    28 4024155 1 ControlPanelAssembly,Humidity/Fan29 4024125 1 ControlPanelAssembly,VentilationTimer&Humidity30 4023660 1 Controller,Humidity31 4023672 1 DuctDamper,6"Diameter,ElectricallyActuated(notshown)32 4024153 1 CoverforItems28&29(notshown)33 4021495 1 Knob,Black,.25"shaft34 4024150 1 Instructions,Humidity/Fan(notshown)35 4024122 1 Instructions,VentilationTimer&Humidity(notshown)36 4025560 1 Switch,Black,SPDT,On/Off37 4022486 1 Timer,7-Day,24Vac,Programmablenotshown 4024369 1 Merv11StandardFilter20"x16"x2"notshown 4025287 1 FilterBox

    Optional Parts List

  • 8/14/2019 Dry150 Manual

    33/34

    1-800-533-7533

    Quest DRY150 Installation, Operation and Maintenance Instructions

    www.thermastor.com

    [email protected]

    questAsset Protection and IAQ Solutions

    quest

    Door And Collar Assembly

    Door InstallInserttabonthebottomofthedoor,inbetweenthefoaminstallationandthemetalside.

    Pushdownontheplasticdoorlatchandswingdoorshut.Oncethedoorisshutreleasethedoorlatch.

    Collar InstallRemovethe2roundducts,3sealsandsmallbagofmountinghardwarefrominsidetherectangleopening.

    Adheresealsontothebackofeachductandmounttheductstothefrontofthedehumidierusingscrewsprovided.

    Collars andhardware arelocated here.

  • 8/14/2019 Dry150 Manual

    34/34

    Quest DRY150 Installation, Operation and Maintenance InstructionsQuest DRY150 Installation, Operation and Maintenance Instructions

    Quest DRY150 Dehumidier Limited Warranty

    WARRANTOR:

    Therma-StorLLC

    POBox8680,Madison,WI53708Telephone:1-800-533-7533

    WHO IS COVERED: Thiswarrantyextendsonlytotheoriginalend-useroftheQuestDRY150dehumidier,andmaynotbeassignedortransferred.

    FIRSTYEARWARRANTY:Therma-StorLLCwarrantsthat,forone(1)yeartheQuest DRY150dehumidierwilloperatefreefromanydefectsinmaterialsandworkmanship,orTherma-StorLLCwill,atitsoption,repairorreplacethedefectivepart(s),freeofanycharge.

    SECOND THROUGH FIFTH YEAR WARRANTY:Therma-StorLLCfurtherwarrantsthatforaperiodofve(5)years,thecondenser,evaporator,andcompressoroftheQuest DRY150dehumidierwilloperatefreeofanydefectsinmaterialorworkmanship,orTherma-StorLLC,atitsoption,willrepairorreplacethedefectivepart(s),providedthatalllaborandtransportationchargesforthepart(s)shallbebornebytheend-user.

    END-USER RESPONSIBILITIES:WarrantyservicemustbeperformedbyaServicerauthorizedbyTherma-StorLLC.Iftheend-userisunabletolocateorobtainwarrantyservicefromanauthorizedServicer,heshouldcallTherma-StorLLCattheabovenumberandaskfortheTherma-StorLLCServiceDepartment,whichwillthenarrangeforcoveredwarrantyservice.Warrantyservicewillbeperformedduringnormalworkinghours.

    TheEnd-usermustpresentproofofpurchase(lease)uponrequest,byuseofthewarrantycardorotherreasonableandreliablemeans.Theend-userisresponsiblefornormalcare.Thiswarrantyonlyappliestoresidentialapplicationsanddoesnotcoveranydefect,malfunction,etc.resultingfrommisuse,abuse,lackofnormalcare,corrosion,freezing,tampering,modication,unauthorizedorimproperrepairorinstallation,accident,actsofnatureoranyothercausebeyondTherma-StorLLC'sreasonablecontrol.

    LIMITATIONS AND EXCLUSIONS: IfanyQuestDRY150Dehumidierpartisrepairedorreplaced,the

    newpartshallbewarrantedforonlytheremainderoftheoriginalwarrantyperiodapplicablethereto(butallwarrantyperiodswillbeextendedbytheperiodoftime,ifany,thattheQuestDRY150Dehumidierisoutofservicewhileawaitingcoveredwarrantyservice).

    UPONTHEEXPIRATIONOFTHEWRITTENWARRANTYAPPLICABLETOTHEQUESTDRY150DEHUMIDIFIERORANYPARTTHEREOF,ALLOTHERWARRANTIESIMPLIEDBYLAW,INCLUDINGMERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE,SHALLALSOEXPIRE.ALLWARRANTIESMADEBYTHERMA-STORLLCARESETFORTHHEREIN,ANDNOCLAIMMAYBEMADEAGAINSTTHERMA-STORLLCBASEDONANYORALWARRANTY.INNOEVENTSHALLTHERMA-STORLLC,INCONNECTIONWITHTHESALE,INSTALLATION,USE,REPAIRORREPLACEMENTOFANYQUESTDRY150DEHUMIDIFIERORPARTTHEREOFBELIABLEUNDERANYLEGALTHEORYFORANYSPECIAL,INDIRECTORCONSEQUENTIALDAMAGESINCLUDINGWITHOUTLIMITATIONWATERDAMAGE(THEEND-USERSHOULDTAKEPRECAUTIONSAGAINSTSAME),LOSTPROFITS,DELAY,OR

    LOSSOFUSEORDAMAGETOANYREALORPERSONALPROPERTY.Somestatesdonotallowlimitationsonhowlonganimpliedwarrantylasts,andsomedonotallowtheexclusionorlimitationofincidentalorconsequentialdamages,sooneorbothoftheselimitationmaynotapplytoyou.

    LEGAL RIGHTS:Thiswarrantygivesyouspeciclegalrights,andyoumayalsohaveotherrightswhichvaryfromstatetostate.