Project name: Drawing No. Ductwork installer name : Damper reference No. Damper Location Damper make / model. Damper manufacturers installation ref: Question Action Initial 1 Are the dampers the correct type? Confirm if Fire or Smoke. 2 Are the dampers located correctly? Damper location to be checked against drawing. 3 Have the dampers been supported correctly? 4 Are the dampers fitted in the correct orientation? 5 Have suitable access doors been fitted? 6 Has the damper blades catch been released to simulate failure of the thermal release? Perform a drop test. 7 Has the damper been checked for internal cleanliness and absence of damage? Check for damage with the damper in the closed position. 8 Have the damper blades been re-set following the drop testing & access panel replaced? 9 At the time of drop test is the fire barrier and penetration seal correct & complete? Checked by: Signature Date Checked by: Signature Date Checked by: Signature Date COMMERCIAL DUCTING LTD is an official registered company in England and Wales. Company registration no. 9964205 Registered Office address: Bankview Cottage 32 Robin Hood Lane, Chatham, Kent, ME5 9LD VAT Registration no. 258 2022 20 DW145 FIRE/SMOKE DAMPER HANDOVER CERTIFICATE

Upload: others

Post on 19-Feb-2021

59 views

Category:

Documents


23 download

TRANSCRIPT

  • Project name:

    Drawing No.

    Ductwork installer name : Damper reference No.

    Damper Location

    Damper make / model.

    Damper manufacturers installation ref: Question Action Initial

    1 Are the dampers the correct type? Confirm if Fire or Smoke.

    2 Are the dampers located correctly? Damper location to be checked against drawing.

    3 Have the dampers been supported correctly?

    4 Are the dampers fitted in the correct orientation?

    5 Have suitable access doors been fitted?

    6 Has the damper blades catch been released to simulate failure of the thermal release?

    Perform a drop test.

    7 Has the damper been checked for internal cleanliness and absence of damage?

    Check for damage with the damper in the closed position.

    8 Have the damper blades been re-set following the drop testing & access panel replaced?

    9 At the time of drop test is the fire barrier and penetration seal correct & complete?

    Checked by: Signature Date

    Checked by: Signature Date

    Checked by: Signature Date