Page 1: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

EDUS331608C-D202002

Engineering Data

Heat Pump, 1 phase, 208 / 230 V, 60 Hz

Design ManualRXTQ-TAVJ9A / TAVJUA

EDU

S331608C-D

ENG

INEER

ING

DA

TA VR

V IV-S RXTQ

-TAVJ9A

/ TAVJU

A H

EAT PU

MP 60 H

z DESIG

N M

AN

UA

L

Page 2: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU
Page 3: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

1

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Table of Contents

1. FeaturesandBenefits ................................................................................32. Nomenclature .............................................................................................43. Model Names .............................................................................................7

3.1 Outdoor Units ....................................................................................73.2 Indoor Units .......................................................................................83.3 Air Treatment Equipment ..................................................................9

4. External Appearance ................................................................................104.1 Outdoor Units ..................................................................................104.2 Indoor Units .....................................................................................114.3 Air Treatment Equipment ................................................................12

5. Capacity Range ........................................................................................135.1 Connection Ratio ............................................................................135.2 Outdoor Unit Combination ..............................................................13

6. Specifications ...........................................................................................147. Dimensions ...............................................................................................178. Service Space ..........................................................................................209. Center of Gravity ......................................................................................2410. Piping Diagrams .......................................................................................2611. Wiring Diagrams .......................................................................................2912. Field Wiring ..............................................................................................3213. Electrical Characteristics ..........................................................................3414. Operation Limits .......................................................................................3515. Sound Levels (Reference Data) ...............................................................3616. Accessories ..............................................................................................42

16.1 Optional Accessories ......................................................................4217. Selection Procedure .................................................................................43

17.1 Selection Procedure ........................................................................4318. Caution Label ...........................................................................................49

18.1 RXTQ36TAVJ9A .............................................................................4918.2 RXTQ48TAVJUA ............................................................................5318.3 RXTQ60TAVJUA ............................................................................57

19. Caution for Refrigerant Leaks ..................................................................6119.1 Introduction .....................................................................................6119.2 Procedure for Checking Maximum Concentration ..........................62

20. Safety Devices Setting .............................................................................6420.1 FXFQ-T ...........................................................................................6420.2 FXZQ-TA .........................................................................................64

Page 4: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

2

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

20.3 FXUQ-P ..........................................................................................6420.4 FXEQ-P ...........................................................................................6420.5 FXDQ-M ..........................................................................................6520.6 FXSQ-TA ........................................................................................6520.7 FXMQ-PB ........................................................................................6520.8 FXHQ-M ..........................................................................................6520.9 FXAQ-P ...........................................................................................6620.10 FXLQ-M, FXNQ-M .........................................................................6620.11 FXTQ-TA .......................................................................................66

Appendix........................................................................................................671. Introduction ...............................................................................................68

1.1 ED Book List ...................................................................................681.2 Publication List of Engineering Data for VRV Products ..................69

Page 5: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

3

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

1. Features and Benefits

The new -series completes the familybyintroducingtheenhancedfeaturesandbenefitsoffered in Daikin’s 3-phase VRV products in to the single phase offering.• Available in 3, 4 and 5 ton models• Year round comfort and energy savings delivered by combining VRV and Variable Refrigerant

Temperature (VRT) technologies• Broader diversity with ability to provide cooling and heating in up to 9 zones• Compatible with all Daikin ducted and ductless indoor fan coils• Space saving design with under 39” (991 mm)* in height and over 25% smaller as compared to • Easier to install with over 39% weight reduction compared to • Low sound levels for comfort in sound sensitive applications• EngineeredwithDaikin’sswingcompressortechnologytoincreaseefficiencyandreliability• Dependableoperationinextremeambientconditionsdownto−4°F(−20°C)inheatingandupto122°F(50°C)incooling

• Added safety and peace of mind with optional auto changeover to auxiliary heat• Backed by best in class 10 year parts limited warranty and 10 years replacement compressor limited

warranty **

*-maxnumberofindoorunitsvariesbymodel,refermodelspecificationfordetails**- Complete warranty details available from local distributor or manufacturer's rep

Page 6: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

4

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2. Nomenclature

Outdoor Unit

Minor revision

Standard symbolU: United States of America9: Minor model change

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Capacity indication in cooling36: 36,000 Btu/h48: 48,000 Btu/h60: 57,500 Btu/h

RefrigerantQ: R410A

TypeT:

Series categoryX: Inverter

Unit categoryR: Outdoor unit for air cooled type

T VJ U A48 TAQXR

Page 7: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

5

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Indoor Unit

M 54 VJPB UX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Capacity indication in cooling05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h09: 9,500 Btu/h 30: 30,000 Btu/h 60: 60,000 Btu/h12: 12,000 Btu/h 36: 36,000 Btu/h 15: 15,000 Btu/h 42: 42,000 Btu/h

RefrigerantQ: R410A

ShapeF: Ceiling mounted cassette (Round flow with sensing)Z: VISTA™ 2 × 2 cassette unitU: 4-way blow ceiling-suspendedE: One way blow cassetteD: Slim ceiling mounted ductS: MSP concealed ducted unitM: Ceiling mounted ductH: Ceiling suspendedA: Wall mountedL: Floor standingN: Concealed floor standingT: Air handling unit (FXTQ)

Series categoryX: Inverter

Unit categoryF: Indoor unit for air cooled type

Page 8: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

6

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Air Treatment Equipment

M 48 VJ UM FX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Outdoor air processing unit

Indicates major design category

Capacity indication in cooling48: 48,000 Btu/h

RefrigerantQ: R410A

ShapeM: Ceiling mounted duct

Series categoryX: Inverter

Unit categoryF: Indoor unit for air cooled type

Outdoor Air Processing Unit

UG300V A M VJ

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Airflow rate (H)300: 300 cfm 470: 470 cfm 600: 600 cfm1200: 1,200 cfm

Mounted type

Air

Ventilation

Energy Recovery Ventilator (VAM series)

Page 9: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

7

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

3. Model Names3.1 Outdoor Units

Capacity range 3 ton 4 ton 5 ton Power supply, StandardCapacity index 36 48 57

Heat pump 208/230 V RXTQ36TA — — VJ9A

— 48TA 60TA VJUA

Note:VJ: 1 phase, 208/230 V, 60 HzU(VJU): Standard symbolA: Minor revision

Page 10: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

8

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

3.2 Indoor Units

Capacity range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton Power supply, StandardCapacity index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60

Ceiling mounted cassette (Roundflowwithsensing)type

FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T — —

VJU

VISTA™ 2 × 2 cassette unit FXZQ 05TA 07TA 09TA 12TA 15TA 18TA — — — — — — — —4-way blow ceiling-suspended type FXUQ — — — — — — 18P 24P 30P 36P — — — —

One way blow cassette type FXEQ — 07P 09P 12P 15P 18P — 24P — — — — — —Slim ceiling mounted duct type FXDQ — 07M 09M 12M — 18M — 24M — — — — — —

MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA —Ceiling mounted duct type (Middle and high static pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB —

Ceiling suspended type FXHQ — — — 12M — — — 24M — 36M — — — —Wall mounted type FXAQ — 07P 09P 12P — 18P — 24P — — — — — —Floor standing type FXLQ — 07M 09M 12M — 18M — 24M — — — — — —Concealedfloorstandingtype FXNQ — 07M 09M 12M — 18M — 24M — — — — — —

Air handling unit FXTQ— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA VJUA— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA VJUD

Page 11: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

9

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

3.3 Air Treatment EquipmentOutdoor Air Processing Unit

Series Model name Power supply, StandardFXMQ 48MF VJU

Energy Recovery Ventilator (VAM series)

Series Model name Power supply, StandardVAM 300G 470G 600G 1200G VJU

Page 12: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

10

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

4. External Appearance4.1 Outdoor Units

RXTQ60TAVJUARXTQ36TAVJ9ARXTQ48TAVJUA

3, 4 ton 5 ton

Page 13: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

11

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

4.2 Indoor Units

Ceilingmountedcassette(Roundflowwithsensing)type

FXFQ-T

Shown with BYCQ125B-W1

Ceiling mounted duct type (Middle and high static pressure)

FXMQ-PB

VISTA™ 2 × 2 cassette unit

FXZQ-TA

Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S

Ceiling suspended type

FXHQ-M

4-way blow ceiling-suspended type

FXUQ-P

Wall mounted type

FXAQ-P

One way blow cassette type

FXEQ-P

Floor standing type

FXLQ-M

Slim ceiling mounted duct type

FXDQ-M

Concealedfloorstandingtype

FXNQ-M

MSP concealed ducted unit

FXSQ-TA

Air handling unit

FXTQ-TA

Page 14: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

12

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

4.3 Air Treatment Equipment

Outdoor air processing unit

FXMQ-MF

Energy recovery ventilator (VAM series)

VAM-G

Page 15: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

13

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

5. Capacity Range5.1 Connection Ratio

Connection ratio =Total capacity index of the indoor units

Capacity index of the outdoor units

Type Min. connection ratioMax. connection ratio

Types of connected indoor unitsVRV indoor units

Single outdoor units 50% 130%

5.2 Outdoor Unit Combination

Model name RXTQ36TAVJ9A RXTQ48TAVJUA RXTQ60TAVJUACapacity range 3 ton 4 ton 5 tonCapacity index 36 48 57Max. number of connectable indoor units 6 8 9

Total capacity index of indoor units to be connected 18.0 ~ 46.8 24.0 ~ 62.4 28.5 ~ 74.1

Page 16: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

14

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

6. Specifications

Model RXTQ36TAVJ9APower supply 1 phase, 208/230 V, 60 Hz

1 Cooling capacityNominal Btu/h

(kW)36,000 (10.6)

Rated 34,200 (10.0)

2 Heating capacityNominal Btu/h

(kW)40,000 (11.7)

Rated 37,000 (10.8)Casing color Ivory whiteDimensions: (H × W × D) in. (mm) 39 × 37 × 12-5/8 (990 × 940 × 320)Heat exchanger Crossfincoil

CompressorType Hermetically sealed swing typeMotor output kW 1.9Starting method Soft start

Fan

Type Propeller fanMotor output kW 0.200

Airflowrate cfm (m3/min) 2,682 (76)

Drive Direct drive

Sound pressure level (reference data)

Cooling dBA 58Heating dBA 61

Sound power level (reference data)

Cooling dB 75Heating dB 79

Connecting pipes

Liquid pipe in. (mm) f3/8(9.5)C1220T(flareconnection)Gas pipe in. (mm) f5/8(15.9)C1220T(flareconnection)

Weight lbs (kg) 172 (78)Safety devices High pressure switch, Fan driver overload protector, Inverter overload protector, Fusible plug, FuseDefrost method Reverse cycle defrostingCapacity control % 14-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 6.4 (2.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Drain socket, Clamps

Note:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft(7.6m),level

difference: 0 ft. (0 m).2. Indoortemp.:70°FDB(21.1°CDB)/outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft(7.6m),level

difference: 0 ft. (0 m).

C: 4D126371

Page 17: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

15

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Model RXTQ48TAVJUAPower supply 1 phase, 208/230 V, 60 Hz

1 Cooling capacityNominal Btu/h

(kW)48,000 (14.1)

Rated 45,500 (13.3)

2 Heating capacityNominal Btu/h

(kW)52,000 (15.2)

Rated 49,500 (14.5)Casing color Ivory whiteDimensions: (H × W × D) in. (mm) 39 × 37 × 12-5/8 (990 × 940 × 320)Heat exchanger Crossfincoil

CompressorType Hermetically sealed swing typeMotor output kW 3.0Starting method Soft start

Fan

Type Propeller fanMotor output kW 0.200

Airflowrate cfm (m3/min) 2,682 (76)

Drive Direct drive

Sound pressure level (reference data)

Cooling dBA 58Heating dBA 61

Sound power level (reference data)

Cooling dB 76Heating dB 78

Connecting pipes

Liquid pipe in. (mm) f3/8(9.5)C1220T(flareconnection)Gas pipe in. (mm) f5/8(15.9)C1220T(flareconnection)

Weight lbs (kg) 176 (80)Safety devices High pressure switch, Fan driver overload protector, Inverter overload protector, Fusible plug, FuseDefrost method Reverse cycle defrostingCapacity control % 14-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 7.5 (3.4)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Drain socket, Clamps

Note:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft(7.6m),level

difference: 0 ft. (0 m).2. Indoortemp.:70°FDB(21.1°CDB)/outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft(7.6m),level

difference: 0 ft. (0 m).

C: 4D126373

Page 18: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

16

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Model RXTQ60TAVJUAPower supply 1 phase, 208/230 V, 60 Hz

1 Cooling capacityNominal Btu/h

(kW)57,500 (16.9)

Rated 57,500 (16.9)

2 Heating capacityNominal Btu/h

(kW)57,000 (16.7)

Rated 57,000 (16.7)Casing color Ivory whiteDimensions: (H × W × D) in. (mm) 52-15/16 × 35-7/16 × 12-5/8 (1,345 × 900 × 320)Heat exchanger Crossfincoil

CompressorType Hermetically sealed swing typeMotor output kW 3.5Starting method Soft start

Fan

Type Propeller fanMotor output kW 0.070 × 2

Airflowrate cfm (m3/min) 3,741 (106)

Drive Direct drive

Sound pressure level (reference data)

Cooling dBA 57Heating dBA 59

Sound power level (reference data)

Cooling dB 74Heating dB 77

Connecting pipes

Liquid pipe in. (mm) f3/8(9.5)C1220T(flareconnection)Gas pipe in. (mm) f3/4(19.1)C1220T(flareconnection)

Weight lbs (kg) 225 (102)Safety devices High pressure switch, Fan driver overload protector, Inverter overload protector, Fusible plug, FuseDefrost method Reverse cycle defrostingCapacity control % 14-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 7.9 (3.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Drain socket, Clamps, Auxiliary piping

Note:1. Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft(7.6m),level

difference: 0 ft. (0 m).2. Indoortemp.:70°FDB(21.1°CDB)/outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft(7.6m),level

difference: 0 ft. (0 m).

C: 4D126375

Page 19: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

17

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

7. Dimensions

RXTQ36TAVJ9A

3D12

6496

Page 20: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

18

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ48TAVJUA

3D12

6497

Page 21: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

19

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

3D12

6498

Page 22: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

20

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

8. Service Space

RXTQ36TAVJ9A / RXTQ48TAVJUA

2D102479B

Page 23: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

21

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ36TAVJ9A / RXTQ48TAVJUA

2D102479B

Page 24: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

22

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

2D102480B

Page 25: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

23

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

2D102480B

Page 26: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

24

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

9. Center of Gravity

RXTQ36TAVJ9A

RXTQ48TAVJUA4D101439A

Unit : in. (mm)

4D101440A

Unit : in. (mm)

Page 27: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

25

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

4D101441A

Unit : in. (mm)

Page 28: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

26

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

10. Piping Diagrams

RXTQ36TAVJ9A

3D08

2498

F

Page 29: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

27

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ48TAVJUA

3D08

8594

A

Page 30: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

28

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

3D08

8595

A

Page 31: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

29

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

11. Wiring Diagrams

RXTQ36TAVJ9A

3D12

4497

Page 32: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

30

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ48TAVJUA

3D12

4499

Page 33: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

31

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

3D12

4502

Page 34: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

32

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

12. Field Wiring

RXTQ36TAVJ9A / RXTQ48TAVJUA

3D12

7111

Page 35: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

33

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA

3D12

7113

Page 36: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

34

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

13. Electrical Characteristics

RXTQ36TAVJ9A / RXTQ48 - 60TAVJUA

3D126394

Page 37: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

35

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

14. Operation Limits

RXTQ36TAVJ9A / RXTQ48 - 60TAVJUA

3D115457

Page 38: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

36

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

15. Sound Levels (Reference Data)

RXTQ36TAVJ9A (Cooling)

4D101947D

Page 39: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

37

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ36TAVJ9A (Heating)

4D101948E

Page 40: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

38

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ48TAVJUA (Cooling)

4D102719C

Page 41: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

39

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ48TAVJUA (Heating)

4D102720D

Page 42: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

40

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA (Cooling)

4D101949D

Page 43: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

41

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

RXTQ60TAVJUA (Heating)

4D101950E

Page 44: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

42

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

16. Accessories16.1 Optional AccessoriesRXTQ36TAVJ9A / RXTQ48 - 60TAVJUA

Optional accessories RXTQ36TAVJ9A RXTQ48TAVJUA RXTQ60TAVJUAABC I/P printed circuit board kit — BRP2A82

Distributive pipingREFNET header KHRP26M22H9 (Max. 4 branch)

KHRP26M33H9 (Max. 8 branch)REFNET joint KHRP26A22T9

4D102596E

Page 45: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

43

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

17. Selection Procedure17.1 Selection Procedure17.1.1 Flowchart

Provisionally select outdoor unit type and size based on limitation of connection ratio

Correct for cooling & heating capacity of the outdoor unit by the following items

VRV system selection is complete.

Confirm that the number of indoor units connected to the outdoor unit is within limitation.

Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit

2) Use the system peak load1) Use the sum of the peak load of each room

Define required total heat load to outdoor unit

Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units

Yes

No

-Piping length, level difference-Piping heat loss-Safety factor for the outdoor unit-Defrost (only for heating capacity)

-Outdoor air temperature-Indoor air temperature-Connection ratio

Given conditions:· Design temperature and humidity (indoor & outdoor)· Required heat load of each room· System peak load (if necessary)· Piping length, level difference· Specifications of indoor units (type and number)

Define safety factor for the indoor units and outdoor unit

[1] Given conditions

[2] Selection of indoor units

[3] Selection of outdoor unit

Page 46: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

44

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

17.1.2 Selection ExampleThe following is a selection example based on total heat load for cooling.

Room ARoom F

Room E

Room B Room DRoom C

Floor plan

[1] Given conditions-Design conditionsIndoorairtemperature:67°FWB/80°FDB,Outdoorairtemperature:93°FDB

-Determine peak load of each room (and system peak load if necessary)

-Required heat load of each roomTime Room A Room B Room C Room D Room E Room F Total9:00 8.0 8.0 6.0 6.0 10.5 10.5 49.0

12:00 10.0 10.0 6.0 5.8 8.0 8.0 47.814:00 11.0 11.0 6.8 6.8 6.2 8.0 49.816:00 12.1 12.2 5.4 5.0 7.0 8.0 49.7

Total heat load (MBH)

From the above heat load calculation, the maximum heat load for the system (system peak load) is 49.8 MBH.

Level difference10 ft.

Select VRV indoor units FXMQ-PB series for each room.

Equivalent pipe length 100 ft.

-Safety factorIn this example, safety factor is not used. (i. e., safety factor = 1.0)

[2] Selection of indoor unitsCalculate total heat capacity of indoor units corrected for indoor air temperature.In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.

Page 47: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

45

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Capacity table of indoor unitCooling capacity

Model

Indoorairtemp.°FWB(Te:43°F(6°C))61 64 67 70 72 75

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH

FXMQ07PBVJU 5.7 5.5 6.4 5.9 7.2 6.1 7.3 6.5 7.4 5.8 7.6 5.8 FXMQ09PBVJU 7.5 6.9 8.5 7.3 9.5 7.8 9.7 8.1 9.8 7.1 10.0 7.2FXMQ12PBVJU 9.5 8.5 10.7 9.1 12.0 9.7 12.2 10.0 12.4 9.2 12.6 9.2FXMQ15PBVJU 11.2 10.2 12.7 10.7 14.2 11.4 14.5 11.6 14.7 11.5 14.9 9.6 FXMQ18PBVJU 14.2 13.9 16.1 14.7 18.0 15.6 18.4 16.1 18.6 14.6 18.9 12.1FXMQ24PBVJU 19.0 16.5 21.5 17.7 24.0 18.8 24.5 19.2 24.8 17.9 25.3 20.1FXMQ30PBVJU 23.7 20.8 26.8 22.3 30.0 23.8 30.6 24.4 31.0 22.5 31.6 22.5FXMQ36PBVJU 28.4 25.0 32.2 26.9 36.0 28.8 36.7 30.0 37.2 27.7 37.9 27.7FXMQ48PBVJU 37.9 31.3 43.0 33.6 48.0 35.8 49.0 36.9 49.6 34.7 50.5 33.2FXMQ54PBVJU 42.6 35.2 48.3 37.8 54.0 40.3 55.1 41.5 55.8 39.0 56.8 37.4

TC : Total capacity: MBHSHC : Sensible heat capacity: MBH

Selection results of indoor units

Room A Room B Room C Room D Room E Room FMax. heat load (MBH) 12.1 12.2 6.8 6.8 10.5 10.5

Selected IDU FXMQ15PBVJU FXMQ15PBVJU FXMQ07PBVJU FXMQ07PBVJU FXMQ12PBVJU FXMQ12PBVJUCorrected TC (MBH) 14.2 14.2 7.2 7.2 12.0 12.0

∗In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.

[3] Selection of outdoor unit[3] –1 Define the required total heat load from the indoor units to the outdoor unitDefinetherequiredtotalheatload(A)basedon(1)thesumofthepeakloadofeachroomor(2)thesystempeakload.In this example, select an outdoor unit by (2).Therefore, (A) = 49.8 MBH

Page 48: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

46

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

[3] –2 Provisionally select outdoor unit(1) Calculate CI (Capacity Index) of the selected indoor units. CI of VRV indoor units CI of FXMQ07PBVJU = 7.5 CI of FXMQ12PBVJU = 12 CI of FXMQ15PBVJU = 15

Calculate the total CI of the indoor units. Total CI = 7.5 × 2 + 12 × 2 + 15 × 2 = 69

(2) Provisionally select an outdoor unit based on the total CI of the indoor units The connection ratio of RXTQ-TA shall be between 50% and 130%.

As the total CI of the indoor units is 69, outdoor units 5 ton are connectable.

(3) Confirm that the number of the connected indoor units is within the limitation. The number of the connected indoor units = 6

The max. number of connectable indoor units of 5 ton outdoor unit = 9

Page 49: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

47

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

[3] –3 Calculate the corrected capacity of the outdoor unit.- Calculate the connection ratio of the system. Total CI = 69, CI of RXTQ60TAVJUA = 57 Connection ratio = 69 / 57 = 121%

- Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air temperature, and connection ratio.

*In case the outdoor air temperature, the indoor air temperature, or the connection ratio falls between temperatures listed in the table, calculate the capacity by interpolation.RXTQ60TAVJUA Cooling Capacity for Standard Condition (Te: 43°F)

Connection ratio 120% 121% 130%

Cooling capacity 62.6 (B) 63.7

(B) = 62.6 + (63.7 – 62.6) × (121 – 120) / (130 – 120) = 62.7

Page 50: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

48

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

-Confirm capacity correction factor by piping length and level difference (K1)

-Calculate capacity correction factor by piping heat loss (K2)(K2) = 1 + (heat loss factor per feet of piping × (equivalent piping length – 25 ft.)) / 100

In cooling mode, heat loss factor per feet at 93°F is calculated as below.(R) Heat loss factor per feet = 0.072*2 + (0.098*1 – 0.072*2) × (93*3 – 86*4) / (95*5 – 86*4) = 0.0922

Using “Equivalent piping length = 100 ft.” and “Heat loss factor per feet = 0.0922”,(K2) = 1 + (0.0922 × (100 – 25)) / 100 = 1.07

-Calculate the corrected capacity of RXTQ60TAVJUA (C) by using (K1) and (K2).Corrected capacity of RXTQ60TAVJUA (C) = (B) × (K1) / (K2) (add defrost correction factor for heating capacity) Therefore (C) = 62.7 × 0.94 / 1.07 = 55.1 MBH

If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outdoor unit.In this example, 55.1 MBH (C) > 49.8 MBH (A), so there is no need to select a larger outdoor unit.

Cooling Ambient temperature

Heat loss factor per feet of piping (%)

Heating Ambient temperature

Heat loss factor per feet of piping (%)

5°F 14°F 23°F 32°F 41°F 50°F 59°F 68°F0.328 0.305 0.282 0.256 0.233 0.210 0.187 0.161

(K1) = 0.94

41°F

0.000

50°F

0.000

59°F

0.013

68°F

0.030

77°F

0.046

86°F*4

0.072*2

93°F*3

(R)

95°F*5

0.098*1

104°F

0.125

100

10

Page 51: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

49

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

18. Caution Label18.1 RXTQ36TAVJ9A

2P435101-1C

Page 52: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

50

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435101-1C

Page 53: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

51

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435101-1C

Page 54: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

52

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435101-1C

Page 55: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

53

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

18.2 RXTQ48TAVJUA

2P435103-1B

Page 56: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

54

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435103-1B

Page 57: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

55

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435103-1B

Page 58: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

56

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435103-1B

Page 59: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

57

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

18.3 RXTQ60TAVJUA

2P435104-1A

Page 60: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

58

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435104-1A

Page 61: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

59

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435104-1A

Page 62: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

60

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

2P435104-1A

Page 63: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

61

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

19. Caution for Refrigerant Leaks19.1 Introduction

Points to note in connection with refrigerant leaks

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant.Neverthelesscaremustbetakentoensurethatairconditioningfacilitiesareinstalledinaroomwhichissufficientlylarge.Thisassuresthat the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.

Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lb./1000 ft.3 (the weight in Ibs. of the refrigerant gas in 1 ft.3 volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

Direction of therefrigerant flow

Room where refrigerant leak has occurred(outflow of all the refrigerant from the system)

Pay special attention to places, such as basements, etc. where refrigerant can stay, since refrigerant is heavier than air.

Page 64: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

62

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

19.2 Procedure for Checking Maximum Concentration

Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.Step1: Calculate the amount of refrigerant (lbs.) charged to each system separately.

Amount of refrigerant in a single unitsystem (amount of refrigerant withwhich the system is charged beforeleaving the factory)

+

Additional charging amount (amountof refrigerant added locally inaccordance with the length or diameterof the refrigerant piping)

= Total amount of refrigerant (lbs.)in the system

Note:Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged.

Step 2: Calculate the smallest room volume (ft.3) In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room. (a) Where there are no smaller room divisions.

(b)Wherethereisaroomdivisionbutthereisanopeningbetweentheroomssufficientlylargetopermitafreeflowofairbackandforth.

Opening betweenrooms

Partition

(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% ormoreofthefloorarea.)

(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target.

Page 65: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

63

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Step 3: Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.

Total volume of refrigerant in therefrigerant system

≤ Maximum concentration level (lbs./ft.3)Size (ft.3) of the smallest room in whichthere is an indoor unit installed

If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration.

Step 4: Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise

the system. Please consult your Daikin supplier.

Page 66: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

64

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

20. Safety Devices Setting20.1 FXFQ-T

Model FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – – –Fan motor thermal protector °F(°C) – – – – –Fan motor thermal fuse °F(°C) – – – – –

Model FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –

C: 3D086932C

20.2 FXZQ-TA

Model FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F(°C) – – – – – –Fan motor thermal protector °F(°C) – – – – – –Drain pump fuse °F(°C) – – – – – –

C: 4D110603

20.3 FXUQ-P

Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –

C: 3D090213

20.4 FXEQ-P

Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJUPrinted circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A

Fan motor thermal protector °F(°C)OFF: 223±9

(106±5)ON: 205±27

(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9 (106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

C: 4D098709

Page 67: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

65

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

20.5 FXDQ-M

Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrinted circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

C: 3D051758

20.6 FXSQ-TA

Model FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — —

Model FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — — —

3D112398

20.7 FXMQ-PB

Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

Model FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

C: 3D086916B

20.8 FXHQ-M

Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – – –

Fan motor thermal protector °F OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

C: 3D049334A

Page 68: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

66

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

20.9 FXAQ-P

Model FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F – – – – –Fan motor thermal protector °F – – – – –

C: 4D047085D

20.10 FXLQ-M, FXNQ-M

Model FXLQ07MVJUFXNQ07MVJU

FXLQ09MVJUFXNQ09MVJU

FXLQ12MVJUFXNQ12MVJU

FXLQ18MVJUFXNQ18MVJU

FXLQ24MVJUFXNQ24MVJU

Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F(°C)OFF: 275±18

(135±10)ON: 248 (120)

or less

OFF: 275±18(135±10)

ON: 248 (120)or less

OFF: 275±18(135±10)

ON: 248 (120)or less

OFF: 275±18(135±10)

ON: 248 (120)or less

OFF: 275±18(135±10)

ON: 248 (120)or less

C: 3D045646B

20.11 FXTQ-TA

Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUAModel (with factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUD

Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Model FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUAModel (with factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUD

Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Page 69: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

67

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Appendix

1. Introduction ...............................................................................................681.1 ED Book List ...................................................................................681.2 Publication List of Engineering Data for VRV Products ..................69

Page 70: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

68

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

1. Introduction1.1 ED Book List

Design Manual ..................................................... RXTQ-TAVJ9ARXTQ-TAVJUA ...... EDUS331608C-D

(This booklet)

Capacity Table Book

Heat Pump ......................................................... RXTQ-TAVJ9ARXTQ-TAVJUA ..........EDUS331608C-C

Installation

Heat Pump, Heat Recovery .................................... RXYQREYQ ............EDUS371848-N

Indoor Units

Ceiling Mounted Cassette Type (Round Flow with Sensing) ....... FXFQ-T ..... EDUS391400A-F14

VISTA™ 2 × 2 Cassette Unit .................................. FXZQ-TA .......... EDUS391776-F9

4-Way Blow Ceiling-Suspended Type ...................... FXUQ-P ........ EDUS391437-F15

One Way Blow Cassette Type ................................ FXEQ-P ........ EDUS391533-F16

Slim Ceiling Mounted Duct Type ............................. FXDQ-M ........... EDUS39-600-F2

MSP Concealed Duct Unit ..................................... FXSQ-TA ........ EDUS391777-F17

Ceiling Mounted Duct Type .................................... FXMQ-PB ........ EDUS391503A-F4

Ceiling Suspended Type ....................................... FXHQ-M ........... EDUS39-600-F5

Wall Mounted Type .............................................. FXAQ-P .......... EDUS391100-F6

Floor Standing Type / Concealed Floor Standing Type ........ FXLQ-MFXNQ-M .......... EDUS391502-F7

Air Handling Unit .................................................. FXTQ-TA ....Engineering Data FXTQ-TA

Air Treatment Equipment

Outdoor Air Processing Unit ................................... FXMQ-MF ....... EDUS39-900A-F10

Energy Recovery Ventilator .................................... VAM-G ............. EDUS711116A

Controls ...................................................................................................... EDUS721909-T

Remote Controller

Navigation Remote Controller ................................. BRC1E73 ............... EDUS721438

Page 71: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

69

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

1.2 Publication List of Engineering Data for VRV Products

Shaded sections indicate Engineering Data Book/s published for this series.Timing of publication is subject to change without notice.

Outdoor Unit

Refrigerant Category Product series Type Volts Model name Area Book category Book No. Published in

R410A

Air cooled

VRV IV-X

H/R208/230 V460 V575 V

REYQ-XATJA, XAYDA, XAYCA USA Canada

Design manual EDUS371848A-DJan.2020

Capacity table EDUS371848A-C

H/P

208/230 V460 V RXYQ-XATJA, XAYDA USA

CanadaDesign manual EDUS341923-D

Nov.2019Capacity table EDUS341923-C

575 V RXYQ-XAYCA CanadaDesign manual EDUS341928-DCapacity table EDUS341928-C

VRV IV

H/R

208/230 V460 V REYQ-TATJA, TAYDA USA

CanadaDesign manual EDUS371704C-D

Feb.2020Capacity table EDUS371704C-C

575 V REYQ-TAYCA CanadaDesign manual EDUS371706C-DCapacity table EDUS371706C-C

H/P

208/230 V 460 V RXYQ-TATJA, TAYDA USA

CanadaDesign manual EDUS341703B-D

Jan.2020Capacity table EDUS341703B-C

575 V RXYQ-TAYCA CanadaDesign manual EDUS341824A-DCapacity table EDUS341824A-C

VRV Aurora

H/R208/230 V460 V575 V

RELQ-TATJA, TAYDA, TAYCA USACanada

Design manual EDUS371705C-DFeb.2020

Capacity table EDUS371705C-C

H/P208/230 V460 V575 V

RXLQ-TATJA, TAYDA, TAYCA USACanada

Design manual EDUS341819A-DJan.2020

Capacity table EDUS341819A-C

VRV IV-S H/P 208/230 V RXTQ36TAVJ9ARXTQ48/60TAVJUA

USA Canada

Design manual EDUS331608C-DFeb.2020

Capacity table EDUS331608C-C

H/P 208/230 V RXSQ24-60TAVJUA USA Canada

Design manual EDUS331721A-DFeb.2020

Capacity table EDUS331721A-CInstallation for all VRV air cooled type Installation EDUS371848-N Aug.2019

Water cooled

VRV-W H/P H/R

208/230 V460 V575 V

RWEQ-TATJU, TAYDU, TAYCU RWEQ-TATJA, TAYDA

USA Canada

Design manual EDUS301864A-DJan.2020

Capacity table EDUS301864A-C

Installation for all VRV water cooled type Installation EDUS301864-N Aug.2019

Note:C/O: Cooling only, H/P: Heat pump, H/R: Heat recovery

Page 72: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

70

RXTQ-TAVJ9A / TAVJUA EDUS331608C-D

Indoor Unit and Other Products

Refrigerant Product category Product type Model name Area Book No. Published in

R410A

VRV Indoor units

Ceiling Mounted Cassette Type (Round Flow with Sensing) FXFQ07-48TVJU USA EDUS391400A-F14 May 2018

VISTA™ 2 x 2 Cassette Unit FXZQ05-18TAVJU USA EDUS391776-F9 Mar.2018

4-Way Blow Ceiling- Suspended Type FXUQ18-36PVJU USA EDUS391437-F15 May 2015

One Way Blow Cassette Type FXEQ07-24PVJU USA EDUS391533-F16 Oct.2015Slim Ceiling Mounted Duct Type FXDQ07-24MVJU USA EDUS39-600-F2 Sep.2006MSP Concealed Ducted Unit FXSQ05-54TAVJU USA EDUS391777-F17 Mar.2018

Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018

Ceiling Mounted Duct Type FXMQ72/96MVJU USA EDUS39-900A-F11 May 2010Ceiling Suspended Type FXHQ12-36MVJU USA EDUS39-600-F5 Sep.2006Wall Mounted Type FXAQ07-24PVJU USA EDUS391100-F6 Jan.2012Floor Standing Type Concealed Floor Standing Type

FXLQ07-24MVJU FXNQ07-24MVJU USA EDUS391502-F7 Jul.2015

Air Handling Unit FXTQ09-60TAVJUA FXTQ09-60TAVJUD USA Engineering Data

FXTQ-TA Sep.2016

Cased Coil Unit CXTQ24-60TASBLU USA Engineering Data CXTQ-TA —

Outdoor Air Processing Unit FXMQ48-96MFVJU USA EDUS39-900A-F10 May 2010Single Branch Selector Unit BSQ36-96TVJ USA EDUS391434-B Aug.2015Multi Branch Selector Unit BS4-12Q54TVJ USA EDUS391434-B Aug.2015

Controls and

networks

Remote controllers Control devices Adaptors

BRC1E73, BRC4C/7E/082A, BRC2A71 DCS302C71, DST301BA61, DCS601C71KRP1C74/75

USA EDUS721909-T Dec.2019

Navigation remote controller BRC1E73 USA EDUS721438 Apr.2015intelligent Touch Manager DCM601A71, DCM601A72 USA EDUS721212 Oct.2012intelligent Touch Controller DCS601C71 USA EDUS72-608 Dec.2006Interface for use in BACnet® DMS502B71 USA EDUS72-749 Oct.2007

Option for all type For indoor and outdoor units USA OHUS07-1 Nov.2007Energy Recovery Ventilator (VAM) VAM300-1200GVJU USA EDUS711116A Jun.2017

Page 73: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU
Page 74: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU
Page 75: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU
Page 76: EDUS331608C-D Engineering Data€¦ · Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018 Ceiling Mounted Duct Type FXMQ72/96MVJU

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

©All rights reserved 02/20 FS

●Specifications, designs and other content appearing in this brochure are current as of February 2020 but subject to change without notice.

EDU

S331608C-D

ENG

INEER

ING

DA

TA VR

V IV-S RXTQ

-TAVJ9A

/ TAVJU

A H

EAT PU

MP 60 H

z DESIG

N M

AN

UA

L