fxmq-m ceiling mounted duct unit - · pdf fileedus39-900a-f11_a fxmq-m 1 fxmq-m ceiling...

Download FXMQ-M Ceiling Mounted Duct Unit -  · PDF fileEDUS39-900A-F11_a FXMQ-M 1 FXMQ-M Ceiling Mounted Duct Unit 1. External Appearance

If you can't read please download the document

Upload: lethuan

Post on 07-Feb-2018

227 views

Category:

Documents


3 download

TRANSCRIPT

  • EDUS 39 - 900A - F11_a

    AMERICAS

    FXMQ-MCeiling Mounted Duct Unit

  • EDUS39-900A-F11_a

    FXMQ-M 1

    FXMQ-MCeiling Mounted Duct Unit

    1. External Appearance...................................................................................22. Specifications ..............................................................................................33. Dimensions .................................................................................................44. Piping Diagrams..........................................................................................55. Wiring Diagrams..........................................................................................66. Electric Characteristics................................................................................77. Capacity Tables ..........................................................................................8

    7.1 Cooling Capacity .......................................................................................... 87.2 Heating Capacity .......................................................................................... 9

    8. Fan Performances.....................................................................................109. Sound Levels ............................................................................................1210.Center of Gravity .......................................................................................1311.Installation .................................................................................................1412.Accessories...............................................................................................25

  • External Appearance EDUS39-900A-F11_a

    1. External Appearance

    FXMQ7296MVJU

    2 FXMQ-M

  • EDUS39-900A-F11_a Specifications

    2. Specifications

    Ceiling Mounted Duct Unit

    Notes: 1 Nominal cooling capacities are based on the following conditions:

    Return air temperature: 80FDB, 67FWBOutdoor temperature: 95FDB Equivalent ref. piping: 25ft (Horizontal)

    2 Nominal heating capacities are based on the following conditions:Return air temperature: 70FDB. Outdoor temperature: 47FDB, 43FWBEquivalent ref. piping: 25ft (Horizontal)

    3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure means High static pressure-

    Standard. 5 Air filter is not standard accessory, but please mount it in the duct system of the suction side.

    Select its dust collection efficiency (gravity method) 50% or more.

    Model FXMQ72MVJU FXMQ96MVJU

    1 Cooling Capacity Btu/h 72,000 96,000

    2 Heating Capacity Btu/h 81,000 108,000

    Casing / Color Galvanized Steel Plate Galvanized Steel Plate

    Dimensions: (HWD) in. 18-1/854-3/843-5/16 18-1/854-3/843-5/16

    Coil (Cross Fin Coil)

    RowsStagesFPI 32613 32613

    Face Area ft 7.32 7.32

    Fan

    Model D13/4G2DA12 D13/4G2DA12

    Type Sirocco Fan Sirocco Fan

    Motor Output (High) W 3802 3802

    Air Flow Rate (H/L) cfm 2,047/1,764 (H/L) 2,541/2,188 (H/L)

    Drive Direct Drive Direct Drive

    Temperature Control Microprocessor Thermostatfor Cooling and HeatingMicroprocessor Thermostat

    for Cooling and Heating

    Air Filter 5 5

    Piping Connections

    Liquid Pipes in. 3/8 (Flare Connection) 3/8 (Flare Connection)Gas Pipes in. 3/4 (Flare Connection) 7/8 (Flare Connection)

    Drain Pipe in. PS1B PS1B

    Machine Weight (Mass) Lbs 302 302

    Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor

    Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve

    Connectable outdoor unit R-410A P Series R-410A P Series

    Standard Accessories Operation manual, Installation manual, Sealing pads, Connection pipes, Screws, ClampsOperation manual, Installation manual, Sealing pads, Connection pipes, Screws, Clamps

    Drawing No. C:3D065683

    FXMQ-M 3

  • Dimensions EDUS39-900A-F11_a

    3. Dimensions

    FXMQ72MVJUFXMQ96MVJU

    C :

    3D06

    5655

    4 FXMQ-M

  • EDUS39-900A-F11_a Piping Diagrams

    4. Piping Diagrams

    R1T : Thermistor for suction air temperatureR2T : Thermistor for liquid line temperatureR3T : Thermistor for gas line temperature

    Capacity GAS Liquid

    72M 3/4 3/896M 7/8 3/8

    C:4D040157

    Heat exchangerGas piping connection port

    Liquid piping connection port

    Fan

    R3T

    R1T

    Electronicexpansion valve

    Filter Filter

    R2T

    FXMQ-M 5

  • Wiring Diagrams EDUS39-900A-F11_a

    5. Wiring Diagrams

    FXMQ72/96MVJU

    3D06

    5414

    C

    6 FXMQ-M

  • EDUS39-900A-F11_a Electric Characteristics

    6. Electric Characteristics

    NOTES:

    1. Voltage range: Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.

    2. Maximum allowable voltage imbalance between phases is 2%.

    3. MCA/MOP

    MCA = 1.25 X FLA

    MOP < 4 x FLA

    (next lower standard fuse rating: Min. 15A)

    4. Select wire based on the MCA.

    5. Instead of a fuse, use a circuit breaker.

    SYMBOLS:

    MCA: Minimum Circuit Amps (A)

    MOP: Maximum Overcurrent Protection (A)

    kW: Fan Motor Rate Output (kW)

    FLA: Full Load Amps (A)

    IFM: Indoor Fan Motor

    Units Power supply IFM Input (W)

    Model Hz Volts Voltage range MCA MOP kW FLA Cooling Heating

    FXMQ72MVJU60 208-230 MAX. 253MIN. 187

    9.5 15 0.380 x 2 7.6 1,490 1,490

    FXMQ96MVJU 10.7 15 0.380 x 2 8.6 1,684 1,684

    FXMQ-M 7

  • Capacity Tables EDUS39-900A-F11_a

    7. Capacity Tables7.1 Cooling Capacity

    FXMQ72MVJU

    FXMQ96MVJU

    TC = Total capacity ; MBhSHC = Sensible heat capacity ; Btu/hr

    Cooling capacity

    OutdoorIndoor (FWB)

    61 64 67 70 72 75FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC75 56.9 50.8 64.4 53.9 72.0 56.9 79.5 60.1 81.0 58.7 82.5 55.679 56.9 50.8 64.4 53.9 72.0 56.9 78.8 60.1 79.5 58.0 81.0 54.983 56.9 50.8 64.4 53.9 72.0 56.9 77.3 60.1 78.0 57.3 79.5 54.687 56.9 50.8 64.4 53.9 72.0 56.9 75.8 60.1 77.3 56.6 78.8 53.991 56.9 50.8 64.4 53.9 72.0 56.9 74.7 60.1 75.8 56.0 77.3 53.295 56.9 50.8 64.4 53.9 72.0 56.9 73.4 60.1 74.4 54.9 75.8 52.899 56.9 50.8 64.4 53.9 70.7 56.9 72.2 59.0 73.1 54.3 74.5 52.2

    103 56.9 50.8 64.4 53.9 69.4 56.9 70.8 58.7 71.8 53.2 73.2 51.9

    Cooling capacity

    OutdoorIndoor (FWB)

    61 64 67 70 72 75FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC75 75.8 63.8 85.9 67.2 96.0 71.0 106.0 74.7 108.0 73.7 110.0 69.779 75.8 63.8 85.9 67.2 96.0 71.0 105.0 74.7 106.0 73.0 108.0 68.683 75.8 63.8 85.9 67.2 96.0 71.0 103.0 74.7 104.0 72.0 106.0 67.687 75.8 63.8 85.9 67.2 96.0 71.0 101.0 74.7 103.0 71.3 105.0 66.991 75.8 63.8 85.9 67.2 96.0 71.0 99.6 74.7 101.0 70.3 103.0 66.595 75.8 63.8 85.9 67.2 96.0 71.0 97.9 74.4 99.2 69.3 101.0 65.999 75.8 63.8 85.9 67.2 94.3 71.0 96.2 73.7 97.4 67.9 99.3 65.5

    103 75.8 63.8 85.9 67.2 92.5 71.7 94.4 73.0 95.7 66.5 97.6 64.8

    8 FXMQ-M

  • EDUS39-900A-F11_a Capacity Tables

    7.2 Heating Capacity

    FXMQ72MVJU

    FXMQ96MVJU

    TC = Total capacity ; MBh

    Heating capacity

    OutdoorIndoor (FDB)

    62 65 68 70 72 75FDB FWB TC TC TC TC TC TC22.0 20.0 72.2 72.1 71.9 71.9 71.8 71.626.0 24.0 76.5 76.5 75.8 75.8 75.8 73.530.0 28.0 81.0 81.0 80.3 80.3 78.0 73.535.0 32.0 85.5 85.5 84.0 81.0 78.0 73.539.0 36.0 90.8 88.5 84.0 81.0 78.0 73.544.0 40.0 94.5 88.5 84.0 81.0 78.0 73.547.0 43.0 94.5 88.5 84.0 81.0 78.0 73.551.0 47.0 94.5 88.5 84.0 81.0 78.0 73.554.0 50.0 94.5 88.5 84.0 81.0 78.0 73.557.0 53.0 94.5 88.5 84.0 81.0 78.0 73.560.0 56.0 94.5 88.5 84.0 81.0 78.0 73.5

    Heating capacity

    OutdoorIndoor (FDB)

    62 65 68 70 72 75FDB FWB TC TC TC TC TC TC22.0 20.0 96.3 96.1 95.9 95.8 95.7 95.526.0 24.0 102 102 101 101 101 98.030.0 28.0 108 108 107 107 104 98.035.0 32.0 114 114 112 108 104 98.039.0 36.0 121 118 112 108 104 98.044.0 40.0 126 118 112 108 104 98.047.0 43.0 126 118 112 108 104 98.051.0 47.0 126 118 112 108 104 98.054.0 50.0 126 118 112 108 104 98.057.0 53.0 126 118 112 108 104 98.060.0 56.0 126 118 112 108 104 98.0

    FXMQ-M 9

  • Fan Performances EDUS39-900A-F11_a

    8. Fan Performances

    FXMQ72MVJU

    Notes:1. The remote controller can be used to switch between high and low.2. The air flow is set to standard before leaving the factory.

    It is possible to switch between standard ESP and high ESP by changing the switch in the indoor unit electrical box.

    3D065628A

    10 FXMQ-M

  • EDUS39-900A-F11_a Fan Performances

    FXMQ96MVJU

    Notes:1. The remote controller can be used to switch between high and low.2. The air flow is set to standard before leaving the factory.

    It is possible to switch between standard ESP and high ESP by changing the switch in the indoor unit electrical box.

    3D065629A

    FXMQ-M 11

  • Sound Levels (Reference) EDUS39-900A-F11_a

    9. Sound Levels (Reference)9.1 Overall

    9.2 Octave Band Level208V-230V, 60Hz

    Location of microphone Notes:1. The operating conditions are assumed to be standard

    (JIS conditions). Power source 208-230V, 60hz. 2. The operating values were obtained in an anechoic

    chamber (conversion values).3. Sound levels will vary depending on a range of factors

    such as the construction (acoustic absorption coefficient) of the particular room in which the equipment is installed.

    dBA