Page 1: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 1

Energise to trip?De-energise to trip?

Simple Choice?

Tony Foord & Colin Howardwww.4-sightConsulting.co.uk

+44 (0)1 582 462 324

Page 2: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 2

Examples

Page 3: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 3

Overview

• Available guidance• Why do trip systems fail?• Trip system issues• System failure modes• 3 examples• Architecture and Spurious trip frequency• Diagnostics and Reverse acting transmitters• References• Conclusions

Page 4: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 4

Traditional Choices

Operation

Safety Availability

De-energise to Trip (DT)

Energise to Trip (ET)

Page 5: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 5

Available Guidance

• Very little specific guidance publishedOne or two paragraphs only

Concentrate on “fail safe”WHY?

Custom and practice?Taken for granted?Principles assumed?

Page 6: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 6

Overpressure protection for a turbine driven compressor

Page 7: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 7

Why do trip systems fail?Inadequatespecification

Inadequate designandimplementationInadequateinstallation andcommissioningInadequateoperation andmaintenanceInadequatemodification

Source: Out of Control 2003

Page 8: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 8

Trip system issues

• SIF Requirements• Passive / active systems• Utility Requirements• Effect on Fail to Danger and Spurious Trips

– Design policy / Architecture / Overrides (defeats)– People issues– Operate / Test / Repair policies– Component reliability– Diagnostics

Page 9: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 9

System failure modes

Source: Sintef PDS Method Handbook 2006

Page 10: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 10

SIF

Energise or De-energise to Trip?

Process unit

consumers

Emergency Feed

Surge Drum

OAF

LSZ

Page 11: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 11

Addition of Reactor Inhibitor Options

BD1

CW In

HW In

CW Out

HW Out

Feed B

Feed ATT 1

PT 1

Product Out

Vent

N2 In

Dump tank

HP N2

Inhibitor

Inhibitor

Energise to Trip

De-energise to Trip

Page 12: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 12

Architecture and Spurious Trip Frequency

0.0000001

0.000001

0.00001

0.0001

0.001

0.01

0.1

11oo1 1oo2 1oo3 2oo3

Freq

uenc

y

Page 13: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 13

Valve failure modes ~ 80% open

Failure mode %

Blocking 5

External leak 15

Passing 60

Sticking 20

Data source: Smith: Reliability, Maintainability and Risk

Page 14: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 14

Relay failure modes ~ 90% open

Failure mode %Contacts short circuit

10

Contacts open circuit

80

Coil 10

Data source: Smith: Reliability, Maintainability and Risk

Page 15: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 15

Overpressure protection for a turbine driven compressor

Page 16: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 16

DT fails to danger

Page 17: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 17

ET fails to danger

Logic solver fails

Logic solverhardware fails

Logic solver fails

Logic solverhardware fails

Sensor 1 fails

Sensor 1 fails

Sensor 1 fails

Sensor 1 fails

Sensor 2 fails

Sensor 2 fails

Sensor 2 fails

Sensor 2 fails

Sensor 3 fails

Sensor 3 fails

Sensor 3 fails

Sensor 3 fails

2

Sensors fail

2oo3 sensorsfail

2

Sensors fail

2oo3 sensorsfail

FE 1 fails

Final element1 fails

FE 1 fails

Final element1 fails

FE 2 fails

Final element2 fails

FE 2 fails

Final element2 fails

Both FEs fail

Both finalelement

Both FEs fail

Sensors Logicsolver

Finalelements

Key toFaultTrees

Both FEs fail

Page 18: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 18

DT (left) and ET fails to danger

Logic solver fails

Logic solverhardware fails

Logic solver fails

Logic solverhardware fails

Sensor 1 fails

Sensor 1 fails

Sensor 1 fails

Sensor 1 fails

Sensor 2 fails

Sensor 2 fails

Sensor 2 fails

Sensor 2 fails

Sensor 3 fails

Sensor 3 fails

Sensor 3 fails

Sensor 3 fails

2

Sensors fail

2oo3 sensorsfail

2

Sensors fail

2oo3 sensorsfail

FE 1 fails

Final element1 fails

FE 1 fails

Final element1 fails

FE 2 fails

Final element2 fails

FE 2 fails

Final element2 fails

Both FEs fail

Both finalelement

Both FEs fail

Sensors Logicsolver

Finalelements

Key toFaultTrees

Both FEs fail

Page 19: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 19

DT spurious trips

Page 20: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 20

ET spurious trips

Page 21: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 21

DT (left) and ET spurious trips

Logic solver fails

Logic solverhardware fails

Logic solver fails

Logic solverhardware fails

Sensor 1 fails

Sensor 1 fails

Sensor 1 fails

Sensor 1 fails

Sensor 2 fails

Sensor 2 fails

Sensor 2 fails

Sensor 2 fails

Sensor 3 fails

Sensor 3 fails

Sensor 3 fails

Sensor 3 fails

2

Sensors fail

2oo3 sensorsfail

2

Sensors fail

2oo3 sensorsfail

FE 1 fails

Final element1 fails

FE 1 fails

Final element1 fails

FE 2 fails

Final element2 fails

FE 2 fails

Final element2 fails

Both FEs fail

Both finalelement

Both FEs fail

Sensors Logicsolver

Finalelements

Key toFaultTrees

Both FEs fail

Page 22: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 22

Diagnostics and Reverse Acting Transmitters

• Safety Function operates on “high” signals• Transmitter failure leads to low signal

Diagnostics require separate inputReverse acting transmitter provides automatic protection– Avoids technical complexity BUT introduces

human factors and management complexity

Page 23: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 23

References - 1• http://www.hse.gov.uk/comah/sragtech/index.htm

which includes links to Case Studies illustrating the importance of Control and Protection Systems, for example– Texaco Refinery - Milford Haven - Explosion and Fires (24/7/1994)– International Biosynthetics Ltd (7/12/1991) – BP Oil (Grangemouth) Refinery Ltd (22/3/1987)– Seveso - Icmesa Chemical Company (9/7/1976)

• Out of Control (2003), Second edition, HSE Books, ISBN 0-7176-2192-8

• IEC 61508 (1998 & 2000), Functional safety of electrical/electronic/programmable electronic safety-related systems Parts 1-7

Page 24: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 24

References - 2• Reliability Prediction Method For Safety Instrumented

Systems. PDS Method Handbook (2006) SINTEF• ISA-TR84.00.02 (2002) - Safety Instrumented Function

(SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction – page 57

• Reliability Maintainability and Risk (2001) David J Smith ISBN 0-7506-5168-7

• Safety Shutdown Systems Design, Analysis and Justification (1998) Paul Gruhn and Harry Cheddie ISBN1-55617-665-1

• Safety-Critical Computer Systems (1996), Neil Storey, ISBN 0-201-42787-7

• Safeware: system safety and computers (1995), Nancy Leveson, ISBN 0-201-11972-2

Page 25: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 25

Available Guidance on ET

Is there anything else out there?

Page 26: Energise to Trip - Institution of Engineering and …• ISA-TR84.00.02 (2002) - Safety Instrumented Function (SIF) - Safety Integrity Level (SIL) Evaluation Techniques Part 1: Introduction

Slide DT/ET - 26

Conclusions

• Choice less clear-cut than at first sight– Need to look holistically– Wider than simply the core SIF

• ET can be made to work – possibilities of getting it wrong are greater

• ET inherently more complex– Does everyone understand the

complexity?• Some DT systems have ET elements