engİn Çetİn maintenance and fault detection in the photovoltaic power
TRANSCRIPT
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 1/73
Maintenance and Fault Detection in
the Photovoltaic Power Plants
Engin CETIN, Ph.D.
Electrical&Electronics Eng. Dept.
Pamukkale University, Denizli-TR
1Engin CETIN, Ph.D., Renewable Energy Systems Winter School15-18 January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 2/73
Please take notes during the seminar
2Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 3/73
Traditional Energy Sources Alternative Energy Sources
3Engin CETIN, Ph.D., Renewable EnergySystems Winter School 15-18 January 2015,
Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 4/73
Solar Energy Systems
4Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 5/73
Off-Grid PV Systems
5Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 6/73
Off-Grid PV Systems
6Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
PAU Clean Energy House, TR – 5 kWp
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 7/73
Off-Grid PV Systems
7Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Water Pumping System, Proton Automation – TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 8/73
On-Grid PV Systems
8Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 9/73
On-Grid PV Systems
9Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
61.2 kWp, Proton Automation – TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 10/73
On-Grid PV Systems
10Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
120 kWp, Seval Cable – TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 11/73
Inspection Procedures in the PV
Systems
11Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
• with eyes
• with measurement tools
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 12/73
Monitoring Systems
12Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 13/73
Inspection Procedures in the PV
Systems
13Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Please check the electrical schemas andsystem components before installation and
commissioning !
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 14/73
Safety Working in the PV Systems
14Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
• Wear proper PPE (Personel
Protective Equipment),• Shut the system off at the inverter,
• Stand to the right of the switch,
• Grab the handle with the left hand,
• Turn body and face away from the
switch,
• Close eyes,
• Take a deep breath and hold it (to
avoid breathing in flames if an arc
flash occurs),
• Throw (operate) the disconnect
lever,
• Use a properly rated voltmeter to
confirm that no voltage is present on
the disconnected circuit, and
• Ensure the switch remains off.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 15/73
Safety Working in the PV Systems
15Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Before operating the PV system, read all instructions for each product.
• All system components must be assumed to be energized with
maximum dc voltages (up to 1,000 V) until personnel verify that the
voltage has been removed.
• All enclosure doors should remain closed with latches tightened,except when they must be open for maintenance or testing.
• Only qualified personnel who meet all local and governmental code
requirements for licensing and training for the installation of electrical
power systems with alternating current (ac) and dc voltages up to 1,000
V (or 600 V, when applicable) should perform PV system servicing.
• To reduce the risk of electric shock, only qualified persons should
perform ser vicing other than that specified in the installation
instructions.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 16/73
Safety Working in the PV Systems
16Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
• In order to remove all sources of voltage from the inverter, the incoming
power must be de-energized at the source. This may be done by opening the acdisconnect and the dc disconnect. Follow manufacturer guidelines for specifics
of how to de-energize the inverter. In addition, allow a minimum of five minutes
for the dc bus capacitors to discharge after disconnecting the power, always
testing that voltage is reduced to touch-safe levels (30 Vdc) before working on
the system.
• Always follow LOTO procedures (lockout/tagout).• Always check for ground faults. If there is a ground fault, there may be a
voltage potential between the inverter and ground. Further, check that the
normally grounded pole is properly grounded and has not been energized by a
fault.
• Do not work alone when servicing PV equipment. A team of two is required
until the equipment is properly de-energized, locked-out, and tagged-out. Verifywith a meter that the equipment is de-energized.
• Do not open a string (also known as a source circuit) combiner fuse holder
without first confirming that there is no current flowing on the circuit.
• Do not disconnect (unplug) module leads, jumpers, or homerun wires under
load.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 17/73
General Site Annual Inspection
17Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
At least once a year, O&M personnel should conduct a general inspection of
the PV installation site. During this inspection, technicians should:
• ensure roof penetrations are watertight, if applicable;
• ensure roof drainage is adequate, roof drains are not clogged, and confirm
that there are no signs of water pooling in the vicinity of the array;
• check for vegetation growth or other new shade items such as a satellite dish;
• check for ground erosion near the footings of a ground mount system;• confirm proper system signage is in place;
• confirm appropriate expansion joints are used where needed in long conduit
runs;
• confirm electrical enclosures are only accessible to authorized personnel, are
secured with padlocks or combination locks, and have restricted access signage;
• check for corrosion on the outside of enclosures and the racking system;• check for cleanliness throughout the site—there should be no debris in the
inverter pad area or elsewhere;
• check for loose hanging wires in the array; and
• check for signs of animal infestation under the array.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 18/73
Detailed Visual Inspection
18Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
The installation should be inspected regularly for issues that impact the physicalintegrity or performance of the PV system. A visual inspection should include
the following actions:
• Inspect the inverter/electrical pad to make sure it does not show excessive
cracking or signs of wear. The inverter should be bolted to the pad at all
mounting points per the manufacturer installation requirements. Depending onthe size, location, and accessibility of the system to unqualified personnel, the
inverters, combiner boxes, and disconnect switches should require tools or have
locks to prevent unauthorized access to the equipment.
• Look for warning placards including arc flash or PPE requirements for
accessing equipment. Be sure to comply with all warning placards. If no placards
are present, or if some placards are missing, make a note of it and install themissing placards during the maintenance visit. Consult the NEC and
Underwriters Laboratories (UL) standards as well as the site host to determine
signage requirements.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 19/73
19Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Inspect PV modules for defects that can appear in the form of burn marks,
discoloration, delamination, or broken glass.
• Check modules for excessive soiling from dirt buildup or animal droppings.
(See Array Washing Procedure for proper procedures for cleaning an array.)
• Ensure that the module wiring is secure and not resting on the roof, hanging
loose and exposed to potential damage, bent to an unapproved radius, or
stretched across sharp or abrasive surfaces.• Inspect racking system for defects including rust, corrosion, sagging, and
missing or broken clips or bolts.
• If sprinklers are used to spray the array, check that the water is free of
minerals (demineralized) as these minerals can cause gradual performance
degradation.
• Inspect conduits for proper support, bushings, and expansion joints, whereneeded.
• In roof-mounted systems, check the integrity of the penetrations.
• In ground-mounted systems, look for signs of corrosion near the supports
Detailed Visual Inspection
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 20/73
20Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
• Open combiner boxes and check for torque marks on the connections. Torque marks
are made when lugs have been tightened to the proper torque value. Ideally they are
applied during initial installation, but if not, the technician can mark the lug after
torquing during a maintenance visit. A proper torque mark is made with a specialized
torque marking pen. The mark is a straight line through the lug and the housing. Over
time, if the line separates between the lug and the housing, it shows that the lug has
moved and needs to be re-torqued. Look for debris inside the boxes and any evidence
of damaging water intrusion. Look for discoloration on the terminals, boards, and fuse
holders.
• Open the door to the disconnect(s) and look for signs of corrosion or damage.
Check to make sure the cabinet penetrations are properly sealed and there is no
evidence of water ingress. Check for torque marks on the terminals.
• Perform a visual inspection of the interior and exterior of the inverter. Look for signs
of water, rodent, or dust intrusion into the inverter. Check for torque marks on the fieldterminations.
• If a weather station is present, ensure that the sensors are in the correct location and
at the correct tilt and azimuth. A global horizontal irradiance sensor should be flat, and
a plane of array irradiance sensor should be installed to the same pitch and orientation
as the array. Irradiance sensors should be cleaned to remove dirt and bird droppings.
Detailed Visual Inspection
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 21/73
Manufacturer Specific Inverter Inspection
21Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Each inverter manufacturer will have specific requirements for inspection,
testing, services, and documentation to meet its warranty obligations. Typicalrequirements for inverter inspections include:
• Record and validate all voltages and production values from the
humanmachine interface (HMI) display.
• Record last logged system error.
• Clean filters.• Clean the inside of the cabinet.
• Test fans for proper operation.
• Check fuses.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 22/73
Manufacturer Specific Inverter Inspection
22Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
• Check torque on terminations.
• Check gasket seal.• Confirm warning labels are in place. • Look for discoloration from excessive heat buildup. • Check integrity of lightning arrestors. • Check continuity of system ground and equipment grounding. • Check mechanical connection of the inverter to the wall or ground.
• Check internal disconnect operation.• Verify that current software is installed. • Contact installer and/or manufacturer about any issues found. • Document findings for all work performed.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 23/73
Manufacturer Specific Tracker Inspection
23Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Tracker manufacturers will have specific requirements for inspections, testing,
service, and documentation to meet their warranty obligations. Typicalmaintenance or startup requirements for tracker systems include:
• Lubricate tracker by inserting grease with grease gun into appropriate grease
caps per manufacturer maintenance recommendation.
• Check voltages inside the controller box.
• Use a digital level to check the calibration and positioning of the
inclinometers.
• Check array for signs of parts hitting or rubbing other parts.
• Remove vegetation that is near the drive shaft or moving components.
• Check wind-stow operation.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 24/73
Manufacturer Specific Tracker Inspection
24Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Additional testing (used when problems are identified or required by contract
terms) may include:
• thermal images of combiner boxes (opened and closed), disconnects, inverters (external and internal at a specified operating point for a specified
period of time), and modules;
• short circuit (Isc) testing of strings;
• current-voltage (IV) curve testing of strings;• insulation resistance tests (also known as “megger” tests) of conductors at
specified voltage; and
• comparison of a weather-corrected performance calculation of expected
output to actual output of the system.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 25/73
Manufacturer Specific Tracker Inspection
25Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Use appropriate (volt, ohm, dc clamp-on) meters to test:
• continuity of the equipment grounding at the inverter, combiner boxes, and
disconnects;
• continuity of all system fuses at the combiner boxes, disconnects, and inside
the inverter(s);
• open-circuit voltage (Voc) of all strings with the inverter off;
• maximum power current (Imp) of all strings with the inverter on and atspecified or recorded levels of power.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 26/73
Manufacturer Specific Data Acquisition
System Inspection
26Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Data acquisition system (DAS) manufacturers will have specific requirements for
inspections, testing, service, and documentation to meet their warrantyobligations. Typical maintenance or startup requirements for DASs include:
• taking voltage readings of power supplies,
• validating current transducer readings by comparing to calibrated
equipment, and
• validating sensor reading by comparing to calibrated equipment.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 27/73
Some Fault Types in the PV Systems
27Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
• Short circuit
• Insulation faults and electric arc
• Grounding faults and ligtning strikes
• Shaded PV module surface
• Mechanical mounting faults
• Other faults…
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 28/73
Short Circuit
28Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
A short circuit (sometimes
abbreviated to short or s/c) is
an electrical circuit that
allows a current to travel
along an unintended path,
often where essentially no
(or a very low) electrical
impedance is encountered*.
*http://en.wikipedia.org/wiki/Short_circuit
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 29/73
Short Circuit
29Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 30/73
Damages by Short Circuit Current
30Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 31/73
Protection Devices
31Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Miniature Circuit Breaker (MCB)
NH-Fuse
Molded Case Circuit Breaker
(MCCB)
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 32/73
Detection of Short Circuit
32Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Phase Pencil
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 33/73
Insulation Faults
33Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Between;
• One phase-ground
(AC side)
• Neutral-ground (AC side)
• Positive line-gorund (DC side)
• Negative line ground (DC side)
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 34/73
Insulation Faults
34Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 35/73
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 36/73
Insulation Faults
36Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 37/73
Insulation Faults
37Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 38/73
Verification of Ground Leakage
38Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
In the presence of anomalies or report of ground fault (where provided), theremay be a ground leakage from the PV generator (DC side).
To check this, measure the voltage between the positive pole and ground and
between the negative pole (of the PV generator) and ground using a voltmeter
whose input accepts a voltage of at least 1000 Volts.
Due to the capacitive effect of the PV generator, during the first moments
that the voltmeter is connected between one of the two poles and ground, it
will measure a voltage of about Voc/2, which will tend to stabilize to around
0V if there is no ground leakage, as shown in the graph below:
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 39/73
Verification of Ground Leakage
39Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 40/73
Verification of Ground Leakage
40Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 41/73
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 42/73
Verification of Ground Leakage
42Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
This means that if the system is made up of 10 modules in series and each one supplies
50V, the leakage can be located between the 4th and 5th PV module.
M i th I l ti R i t f PV
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 43/73
Measuring the Insulation Resistance of PV
Generator
43Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
M i th I l ti R i t f PV
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 44/73
Measuring the Insulation Resistance of PV
Generator
44Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 45/73
Detection of Insulation Faults
45Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
TL MODELS (Transformerless)
If the measured insulation resistance (Riso) is less than 1 MOhm
the inverter does not connect to the grid due to a low insulation
of photovoltaic generator respect to ground.
I MODELS (with high frequency transformer)
If the measured insulation resistance ( Riso in case of input
poles floating respect to ground or QF=1 if the one of input
poles is grounded) is less than 0.2 MOhm the inverter does notconnect to the grid due to a low insulation of photovoltaic
generator respect to ground.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 46/73
RCD for Leakage Currents (AC Side)
46Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 47/73
RCD for Leakage Currents (AC Side)
47Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Manuel Test/ 1 month
Withelectrical
installation
tool / every
6 months
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 48/73
Detection of Insulation Fault
48Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Electrical insulation test devices/multimeters
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 49/73
Lightning Strikes
49Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Surge Arrester
Please check thewindow. To geton work
position, it mustbe green.
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 50/73
Lightning Strikes
50Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 51/73
Lightning Strikes
51Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 52/73
Lightning Strikes
52Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 53/73
Lightning Strikes
53Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 54/73
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 55/73
Shaded PV Modules
55Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 56/73
Hot Spot Effect
56Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 57/73
Termal Detection
57Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 58/73
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 59/73
59Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
Cleaning of PV Modules
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 60/73
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 61/73
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 62/73
System Sample Proton Automation,
Denizli-TR
62Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 63/73
System Sample Proton Automation,
Denizli-TR
63Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 64/73
System Sample Proton Automation,
Denizli-TR
64Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 65/73
System Sample Proton Automation,
Denizli-TR
65Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 66/73
System Sample Proton Automation,
Denizli-TR
66Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 67/73
System Sample Proton Automation,
Denizli-TR
67Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 68/73
y p ,
Denizli-TR
68Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 69/73
y p ,
Denizli-TR
69Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 70/73
y p ,
Denizli-TR
70Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18
January 2015, Afyonkarahisar-TR
System Sample – Proton Automation,
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 71/73
y p ,
Denizli-TR
71Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18
January 2015, Afyonkarahisar-TR
References
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 72/73
References
72Engin CETIN, Ph.D., Renewable Energy Systems Winter School 15-18
January 2015, Afyonkarahisar-TR
• ABB Instruction Manuel, 2014, pdf version,p.111.
• Addressing Solar Photovoltaic Operations andMaintenance Challenges A Survey of CurrentKnowledge and Practices, July 2010.
• Haney J., Burstein A., 2013, PV SystemOperations and Maintenance Fundamentals,Solar America Board for Codes and Standards, pdf
version, p. 46.• McCallmont S., 2013, Low Cost Arc FaultDetection and Protection for PV Systems, NREL ,pdf version, p. 28.
• SunBrush Product Catalog, 2014, pdf verison,p.8.
• Şimşek B., 2013, Güneş-Elektrik Dönüşüm Sistemlerinde Yasa, Yönetmelik ve Standartlar"Güneş Enerji Sistemlerinin Şebeke Bağlantıları“, Fotovoltaik Çalıştayı, Hacettepe Üniversitesi.• www.wikipedia.org
E i CETIN Ph D
8/18/2019 ENGİN ÇETİN Maintenance and Fault Detection in the Photovoltaic Power
http://slidepdf.com/reader/full/engin-cetin-maintenance-and-fault-detection-in-the-photovoltaic-power 73/73
Engin CETIN, Ph.D.
Pamukkale University