1/3/2008 1 Fire Safety of Wood Floor Assembly: Model and Full-Scale Test Hisa Takeda Fire Research Canada (LGS)

Upload: doanthu

Post on 22-Aug-2019

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

1/3/2008 1

Fire Safety of Wood Floor Assembly:

Model and Full-Scale Test

Hisa TakedaFire Research Canada (LGS)

Page 2: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Sub-floor

Joist

Ceiling

F I R E

Page 3: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Model employs two dimensional heat conduction equation to calculate the flow of heat through the ceiling, wood joist and sub-floor.

Cpρ(∂T/∂t) = ∂/∂x(k∂T/∂x)+∂/∂y(k∂T/∂y)

Page 4: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Sub-floor

Joist

Ceiling

Boundary condition at the surface of the ceiling which is exposed to fire can be described by this equation,

-ks(∂T/∂x) = hf(Tf - Tsf) + εffσ(Tf4 - Tsf

4)

Page 5: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

εff is the effective emissivity calculated from the

furnace gas emissivity εf and surface emissivity

of the ceiling(gypsum board) εs.

εff = 1 / ( 1 / εf + 1 / εs - 1 )

Page 6: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Sub-floor

Joist

Ceiling

Boundary condition at the sub-floor surface facing

the inside the room

k(∂ T/ ∂ x) = ha(Ta - Tga) + εffσ(Ta4 - Tsa

4)

Page 7: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Sub-floor

Joist

Ceiling

The boundary condition at the surface of the ceiling board facing cavity-k(∂T/∂x) = h(Tcf - Tc) + F12σ (Tcf

4 - Tcs4) + F13σ

(Tcf4 - Tcw

4)

Page 8: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

View factors F12 and F13 for radiation heat exchange in the ceiling cavity

YL

F12

Joist

F13 F13

Sub-floor

Ceiling

Page 9: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

0

10

20

30

40

50

60

70

80

0 50 100 150 200

Distance YL (mm)

%F1313

F12F12

F

Page 10: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Sub-floor

Joist

Ceiling

The boundary condition at the joist surface -k(∂T/∂y) = h(Tcf - Tcw) + F31σ (Tcf

4 - Tcw4) +

F32σ (Tcs4 - Tcw

4)

Page 11: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

View factors F21 and F31 for radiation heat exchange in the ceiling cavity

Sub-floor

XL F31

JoistF32

Ceiling

Page 12: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

0

10

20

30

40

50

60

0 50 100 150 200 250

Distance XL (mm)

%F32F32

F31F31

Page 13: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Boundary condition at the interface between

ceiling and wood joist, wood joist and sub-floor

can be described using continuity equation,

k(∂ T/ ∂ x) o = k(∂ T/ ∂ x) w

Page 14: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Initial condition can be described by using initial

temperature in the assembly,

T = Ta at any x and y

TF = Ta

Page 15: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

0

0.1

0.2

0.3

0.4

0.5

0 200 400 600 800 1000

Temperature (C)

Ther

mal

con

duct

ivity

(W/m

C)

Gypsum boardGypsum board

WoodWood

Page 16: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

0

5

10

15

20

25

30

0 200 400 600 800 1000Temperature (C)

Spec

ific

heat

(J/g

C) Gypsum boardGypsum board

WoodWood

Page 17: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Gypsum boardGypsum board

WoodWood

0

20

40

60

80

100

0 200 400 600 800 1000

Temperature (°C)

Mas

s(%

)

Gypsum boardGypsum board

WoodWood

Page 18: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Full-Scale Test

Test floor was 4.8m long and 3.9m wide.

The ceiling was exposed to heat in a propane

fired horizontal furnace, in accordance with

CAN/ULC-S191-M89(ASTM E119) standard.

Page 19: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model
Page 20: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Test specimen:

2 x 10 wood joist

½ inch type X gypsum board as a ceiling

5/8 inch plywood as a sub-floor.

Page 21: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Wood joist 235 x 38

3874

11 joists @ 406 O.C.

Page 22: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

[ FROM FULL-SCALE TEST]

Visual observations demonstrate that gypsum

filler-compound used to cover fasteners and

joints, loosens and begins to fall from the ceiling,

5 minutes after exposure to the fire, and after 15

minutes almost all filler compound fell from the

ceiling.

Page 23: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

CeilingFiller

Joist

Joist

Joint

Joist

Ceiling tends to separate

Page 24: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Once the joints open, the gypsum ceiling board

was seriously heated by convection and radiation.

Therefore the temperature of the board rapidly

increases and the ceiling tends to separate from

the assemblies.

Page 25: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

AA

BB CC

DD

A

B C

D

TEMP (C)

A

FIREJoint No Joint

B

CD

A

1000

0500 TIME (min)

Page 26: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

0

200

400

600

800

1000

0 10 20 30 40 50

TIME (min)

TEM

PER

ATU

RE

(C)

B

ASTM E119ASTM E119Furnace

ACBB

AA

CC

DDD

FIREJoint No Joint

B

CD

AE

CA

B

E

Page 27: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Char formation in joists

25 26 27 28 29 min

Page 28: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Char formation in joists

30 31 32 33 34 min

Page 29: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Yield Stress of Wood

0

20

40

60

80

100

0 100 200 300 400

TEMPERATURE (C)

% Compressive stress by BenichouTensile stress by Benichou

Kacikova

Page 30: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Modulus of Elasticity of Wood

0

20

40

60

80

100

0 100 200 300 400

Konig

Glos

Kacikova

Benichou

%

TEMPERATURE (C)

Page 31: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Resistive moment

Applied load

Deflection (model)

Deflection (test)

Page 32: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

The results show that the model prediction for the joist deflection agrees well with the test results.

The model predicted the mechanical failure occurred at 28min 49sec. Actual test was terminated at 30min, because the flame penetrated through the sub-floor

Page 33: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

Mechanical failure

0

20

40

60

80

100

120

0 10 20 30 40

Thickness of ceiling (mm)

Tim

e (m

in)

Page 34: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

0

20

40

60

80

100

0 2000 4000 6000 8000

Load (N/m2)

Tim

e of

mec

hani

cal f

ailu

re (m

in)

Page 35: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

1/3/2008 35

Concluding Remarks

1. A computer model to predict the fire resistance of load bearing wood-framed floor / ceiling assemblies has been developed.

Page 36: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

1/3/2008 36

2. The model includes the heat transfer model to calculate the flow of heat in the floor / ceiling assemblies and the mechanical model to calculate the strength of the assemblies.

Page 37: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

1/3/2008 37

3. The results from the heat transfer model had a good agreement with the results from the full-scale tests.

Char formation in wood joists predicted by the model were favourably consistent with the pictures of the actual char formation in wood obtained from the full-scale tests.

Page 38: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

1/3/2008 38

4. Structural model predicted the deflection and strength (resistive moment) of wood joists. The results were compared to the results from the full-scale tests and a good agreement was observed.

Page 39: Fire Safety of Wood Floor Assembly: Model and Full-Scale Testiufro-archive.boku.ac.at/iufro/D5-conference07/10.30tuesday/105/5.03...1/3/2008 1 Fire Safety of Wood Floor Assembly: Model

1/3/2008 39

5. Calculated results show that the thickness of ceiling would be rather important for fire resistance of floor / ceiling assemblies.