fire services at data centre. fm200 training course
TRANSCRIPT
FIRE SERVICES AT DATA CENTRE
FM200 TRAINING COURSE
INTRODUCTION OF FM 200
THE PROPERTIES OF FM-200®
WHAT IS FM-200® ?
C C C
F F F
F F
F FH
ASHRAE Designation = HFC227eaASHRAE Designation = HFC227ea
Fire TriangleFuel, oxygen, heat
What is fire?A series of highly exothermic chain-branching free radical reactions
Removal of any element of fire triangle results in suppression
THE PHYSICS OF FIRE
Removes heat, so fire can’t sustain itself
FAST & EFFICIENT PERFORMANCE
FM-200® CHEMICAL/PHYSICALEXTINGUISHING MECHANISM
Physical
Chemical
80%
Physical
Chemical 20%
80%
20%
Halon 1301 FM-200®®
Cup Burner Conc. [Heptane] - 5.8%
Use Concentration [Minimum] - 7.5% for ISO compliance
Maximum Discharge Time limited to 10 Seconds
HOW IS FM-200® APPLIED?
Compact storage space requirements
FAST & EFFICIENT PERFORMANCE
Halon 1301
CO
Inert Gas
FM-200® iscompletely safe for use in occupiedspaces.
HUMAN SAFETY
Reaches extinguishing concentration within 10 seconds
Provides ACTIVE Fire Protection
FM-200® IS FAST & EFFECTIVE
FM-200® ENGINEERED SYSTEMS
14
ENGINEERED CENTRAL STORAGE FM-200® SYSTEM
Raised Floor
Distribution PipeDischarge Nozzles
Smoke Detectors
Manual Station
Containers
Computer Rooms
PRIMARY APPLICATIONS
3M™ Novec™ 1230 Fire Protection Fluid
Novec 1230 fluid has distinct environmental benefits Ozone depletion potential (ODP) of
0
5 day atmospheric lifetime
Global Warming Potential (GWP) of 1
THE NEW CLEAN AGENT
FM200 CONTROL EQUIPMENT
Kentec Panel Kentec lock off
FM200 CONTROL EQUIPMENT
Kidde Panel Kidde Panel
FM200 CONTROL EQUIPMENT
Chubb Panel Viking & Notifier Panel
FM200 CONTROL EQUIPMENT
Thorn Panel
FM200 CONTROL EQUIPMENT
FM200 CYLINDER
Kidde FM200
FM200 CYLINDER
Chemetron FM200
FM200 CYLINDER
ThornFM200
FM200 CYLINDER
Fike FM200
FM200 CYLINDER
Siemens FM200
FM200 CYLINDER
SIGNAGE BOX AND PRESSURE SWITCH
Signage Box Pressure Switch for Fed-back Signal
AUTO-MANUAL Mode Selection Provided Next to the Panel Outside the Room
When Personal Before Enter the Room:
- Switch the Auto-Manual Switch to “MANUAL” - “System Inoperative” Signal Box Flash - Switch Back to “AUTO” when Leave the Room
MODE SELECTION
Two Detection Zones for Each SystemCross Zone OperationActivating Anyone Zone:
- Alarm Sound - “Do Not Enter” Sign Flash, Don’t Enter the Room
FM200 OPERATION IN AUTO MODE
Two Zones Activated:
- Two-Tone Sounder Raised - “Evacuate” Sign Flash, Evacuate Room
Immediately - A/C in the Room Will Shunt Down - System Start Count Down for 30 Sec. - Gas Discharge to Room After Count Down
FM200 OPERATION IN AUTO MODE
When Personal Working inside the Room:One Zone of Alarm Activated and Alarm
Sound: - Check Any Fire Happened in Room - Inform Others to Leave the Room if Fire Happened - Go out of the Room, Push the “Manual Release”
Switch to Discharge Gas Two Zone Activated: - Evacuate Room Immediately - Go out of the Room, Push the “Manual Release”
Switch to Discharge Gas
FM200 SYSTEM OPERATION IN MANUAL MODE
Check Smoke Detectors- Corrosion- Dirty
- Generate False Alarm FrequentlyCheck Modules
- Simulate Tests to Check the Modules
Working Properly
MAINTENANCE OF AFA AND FM200 SYSTEMS
Monthly & Annual
- To Be Carried-Out By FS Contractor
MAINTENANCE
What is VESDA…
INTRODUCTION OF VESDA SYSTEM
Aspirating Smoke Detection吸气式烟雾探测
THEINTRODUCTION OF VESDA SYSTEM VESDA ADVANTAGE…
VESDA Panel VESDA Panel
INTRODUCTION OF VESDA SYSTEM
Kidde HSSD Panel Kidde HSSD Panel
INTRODUCTION OF HSSD SYSTEM
鐳射探測器主機板
風機
Kidde HSSD Sampling Point
INTRODUCTION OF HSSD SYSTEM
Pre-action System
INTRODUCTION OF PRE-ACTION SYSTEM
Pre-action System
INTRODUCTION OF PRE-ACTION SYSTEM