Cooling Solutionsfor the IT environment

Page 2: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

� For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-�89-6�68

Heat Density

(per rack)

Server Room / Wiring Closet

Solutions Product / Applications Data Center Solutions Product / Applications30 kW &

above

Rack Air ContainmentHigh Density RacksBest predictability

23 kW Hot Aisle Containment SystemHigh Density ZonesBest capacity sharingBest predictabilityBest floor space utilizationImproved redundancy and efficiency

10 kW

InRow™ RC & CDU, RPMedium to high densitymodular and scalable

7 kW

InRow SCIn-row air conditioning for server rooms and wiring closets

Air Removal UnitHot spot problem solver

4 kW

NetworkAIR PAPortable, self-contained air conditioning

NetworkAIR FMLow densityVery flexible

Wiring Closet Ventilation UnitRapidly deployable wall and ceiling mount heat removal

Air Distribution UnitRaised floor air distribution

Side Air Distribution UnitSide to side air distribution

System-level solutions for data centers on demand

InfraStruXure, APC’s innovative methodology for designing, deploy-

ing and optimizing data centers, fully integrates power, cooling,

security, and environmental management within a rack-optimized

design. Using an open, building-block approach, InfraStruXure

allows the selection of standardized components to create a solu-

tion through modular configurations. This standardization enables

an easily scalable architecture designed to meet changing needs

and future expansion. This award-winning, patent-pending approach

increases availability, improves adaptability, speeds deployment,

and lowers the total cost of ownership for IT environments—from

wiring closets to server rooms to data centers.

“ APC has the complete cooling solutions line for your data center

needs. We offer a range of products to meet all density levels for

wiring closets, small, medium, and large data centers. Our highly

efficient, scaleable solutions with active response controls offer pre-

dictable cooling for your needs today and in the future.”

Donna WilliamSDirector, Product Line Management, Cooling Solutions

moDular/HigH-DenSity air ConDitioning 4infraStruXure® inrow™ rC

infraStruXure® Cooling Distribution unit

infraStruXure® inrow™ rP

infraStruXure® inrow™ SC

Hot aisle Containment System

rack air Containment System

air DiStribution/FanS 9Wiring Closet Ventilation unit

rack air removal unit SX

rack air Distribution unit

rack Side air Distribution unit

room air ConDitioning 13networkair Fm

networkair Pa

Heat rejeCtion 15Chillers

The support structure of all highly available networks consists of power, cooling, racks and physical structure, security and fire protection, cabling, and the management and servicing of these elements.

Page 3: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-�89-6�68 3

Heat Density

(per rack)

Server Room / Wiring Closet

Solutions Product / Applications Data Center Solutions Product / Applications30 kW &

above

Rack Air ContainmentHigh Density RacksBest predictability

23 kW Hot Aisle Containment SystemHigh Density ZonesBest capacity sharingBest predictabilityBest floor space utilizationImproved redundancy and efficiency

10 kW

InRow™ RC & CDU, RPMedium to high densitymodular and scalable

7 kW

InRow SCIn-row air conditioning for server rooms and wiring closets

Air Removal UnitHot spot problem solver

4 kW

NetworkAIR PAPortable, self-contained air conditioning

NetworkAIR FMLow densityVery flexible

Wiring Closet Ventilation UnitRapidly deployable wall and ceiling mount heat removal

Air Distribution UnitRaised floor air distribution

Side Air Distribution UnitSide to side air distribution

3 kW

Ensuring the proper environment for IT systems is essen-

tial to maintaining high availability. Regardless of applica-

tion, IT equipment produces heat that can be damaging to

both uptime and the longevity of your investment.

Designed to provide cool air distribution and heat remov-

al in any IT environment at the rack, row, and room level,

APC cooling solutions give you the maximum amount

of cooling in the least amount of floor space. Scalable

solutions, including air distribution/fans, portables, and

precision cooling systems, are tailored to meet the unique

cooling demands of your environment, from wiring clos-

ets and computer rooms to data centers of all sizes.

Page 4: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

4 For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-289-6268

Modular/HIgH denSITy aIr CondITIonIng

InfraStruXure® Inrow™ rCIn-row air conditioning for medium to large data centers

including high density applications.

Data center heat densities continue to increase, making it more diffi-

cult to provide adequate cooling. To ensure proper airflow paths the

distance between the heat source and heat removal system must

decrease. The in-row concept closely couples cooling with heat load,

preventing exhaust air recirculation to sensitive IT equipment. The

InfraStruXure InRow RC is a computer room air conditioning system

designed for installation in the row to maximize sensible cooling

and increase efficiency. The unit captures heat directly from the hot

aisle and distributes cool air ensuring that equipment temperatures

are constantly held to setpoint conditions. The energy-efficient

design lowers total cost of ownership by monitoring IT equipment

inlet temperatures to modulate capacity based on the demand for

cooling. Fan speed is controlled based on the demand to reduce

energy consumption during off-peak cooling periods. Heat rejection

for the unit can be handled through an existing chilled water system

or an APC-supplied chiller. The modular, scalable solution improves

agility by enabling you to add cooling as demand increases, making

the InRow RC ideal for small to large datacenters.

Features and benefits

Availability • Active response controls Monitor and actively adjust cooling capacity

to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.

• Predictable cooling Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.

• Dual A-B power inputs Draws power from the UPS for power protection with dual feeds for redundancy.

• Top and bottom chilled water connections Allows chilled water to be connected from the top, if routing from overhead, or bottom, if on a raised floor.

Total Cost of Ownership • Variable speed fans Variable speed fans reduce energy consumption

during off-peak cooling periods.

• In-Row architecture In-row architecture enables pay-as-you-grow deployment of cooling.

Manageability • Microprocessor controller Utilizes intelligent, proactive control and

real-time capacity monitoring. The system is controlled by a master microprocessor providing high level control functionality and human interface via a four line, eighty character, alphanumeric display.

• Building management system integration Sends alarms and data points allowing you to manage critical building infrastructure from a single system.

• Infrastruxure manager compatible Enables centralized management via the APC InfraStruXure® Manager.

ACRC100 ACRC103

Cooling Option Chilled Water

Capacity up to 30 kW

Airflow 2900 CFM

Nominal Input Voltage 100V,120V 200V

Input Power 1100 Watts 1380 Watts

Input Frequency 50/60 Hz

Rack Height 42U

Input Connections NEMA L5-20P IEC 309 16A 2P+E

Control panel Multi-function LCD status and control console

Maximum Height 78.39 in (1991.00 mm)

Maximum Width 11.81 in (300.00 mm)

Maximum depth 42.126 in (1070.00 mm)

Net Weight 358 lbs. (162.73 kg)

Color Black

Units per Pallet 1

Regulatory Approvals cUL Listed,FCC Part 15 Class A,ICES-003,Industry

Canada,MEA,UL Listed,VCCI

C-tick,CE,EN 55022 Class A,EN 55024,EN 60950,IEC 60950,IEC 61000-3-2,IEC

61000-3-3,MEA,VDE

Standard Warranty 1 year (parts only)

Agility • Modular design Provides scalable solutions to add cooling as demand

increases.

Serviceability • Hot swappable fans Allow system to remain operational if a fan

replacement is required.

Page 5: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

5For more information about APC’s Availability Cooling, visit www.apc.com or call 1-888-289-6268

InfraStruXure® Cooling distribution unitFlexible chilled water distribution system for the

InfraStruXure® Inrow™ rC.

The Cooling Distribution Unit provides centralized cooling, balanc-

ing and distribution through jointless and flexible chilled water

piping in the data center. The Cooling Distribution Unit and Chilled

Water Whip system allows for quick deployment and enables

customer infrastructure the flexibility to grow and change with

minimal labor and installation costs.

PEX-AL-PEX piping, used for chilled water piping between the

CDU and InRow RC, allows the chilled water to be routed without

the use of elbows or any intermediate joints from the CDU to each

InRow RC. This application greatly improves the reliability of the

system by dramatically reducing the chance of leakage.

PEX-AL-PEX is a multi-layered composite tubing consisting of

aluminum tubing sandwiched between inner and outer layers of

cross-linked polyethylene, providing flexibility of the piping to be

routed through the data center with the rigidity to stay in place.

With smooth interior walls and the chemical properties of the

material, PEX-AL-PEX is resistant to mineral buildup, corrosion,

and the risk of pinholes. The multi-press fittings provide a reliable

and leak resistant connection to both the CDU and InRow RC.

The individual chilled water lines to the RC are both flexible and

jointless, enabling customer infrastructure to be deployed quickly,

added for future expansion, or rerouted with minimal time as

demands change.

Features and benefits

Agility • Flexible piping Flexible piping allows for quick deployment and start up.

Availability • Jointless piping Jointless piping minimizes the risk of fluid leaks.

Serviceability • Coolant isolation Allows isolation of cooling circuits for servicing.

ACFD12-CXX-T ACFD12-CXX-B

Cooling Options Glycol, Chilled Water

Capacity up to 12 InRow RC units

Maximum Height 78.40 inches (1991 mm)

Maximum Width 42.13 inches (1070 mm)

Maximum depth 29.53 inches (750 mm)

Net Weight 500 lbs. (227.27 kg)

Color Black

Units per Pallet 1

Regulatory Approvals cUL Listed,MEA,UL Listed

Standard Warranty 1 year (parts only)

Modular/HIgH denSITy aIr CondITIonIng

Page 6: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

6 For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-289-6268

Modular/HIgH denSITy aIr CondITIonIng

InfraStruXure® Inrow™ rPIn-row precision air conditioning for medium to large data

centers including high density applications.

InfraStruXure InRow RP is a high capacity precision air condition-

ing unit designed to maximize sensible cooling for high efficiency

operation. The InRow RP product increases the capacity range

for chilled water applications and includes an air cooled solution.

Both the chilled water and air cooled products offer the ability to

control humidity with canister humidifiers and electric reheat,

enabling data center designs to leverage the InRow Architecture

for both sensible cooling of the IT load in the row, and humidity

control of the entire data center. The in-row concept closely cou-

ples cooling with the heat load, preventing exhaust air recircula-

tion to sensitive IT equipment. The energy-efficient design lowers

total cost of ownership by monitoring IT equipment inlet tem-

peratures to modulate capacity based on the demand for cooling.

Fan speed is controlled based on the demand to reduce energy

consumption during off-peak cooling periods. The modular, scal-

able solution improves agility by enabling you to add cooling as

demand increases, making the InRow RP ideal for small to large

data centers.

Features and benefits

Availability • Active response controls Monitor and actively adjust cooling capacity

to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.

• Predictable cooling Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.

• Rack inlet control Guarantees inlet temperature to IT equipment.• Steam humidifier Humidity is managed through a self-contained steam

canister humidifier for maximum efficiency and ease of maintenance. The pure-steam canister maintains consistent capacity output, and requires very little scheduled maintenance.

• Real-Time capacity monitoring Real-time display of current and available cooling.• Electric reheat Prevents overcooling during dehumidification

Total Cost of Ownership • Variable speed fans Reduce energy consumption during off-peak cooling

periods.• In-Row architecture Enables pay-as-you-grow deployment of cooling.

Agility• Modular design Provides scalable solutions to add cooling as demand

increases.

Serviceability• Field replaceable components Fans and electronics module can be

readily replaced without uninstalling the unit.

Manageability• Microprocessor controller An 80-character LCD backlit alphanumeric

display provides communication and alarm indication.

ACRP100 ACRP101 ACRP102 ACRP500 ACRP501 ACRP502

Cooling Options R407C Chilled Water

Capacity 10–37 kW up to 70 kW

Airflow 4800 6950

Nominal Inout Voltage 200–240 3PH 460–480 3PH 380–415 3PH 200–240 3PH 460–480 3PH 380–415 3PH

Input Power 13737W 11212W 13056W 3204W 2054W 2818W

Input Frequency 50/60 60 50 50/60 60 50

Input Connections Hardwire 4-wire (3PH+G)

Warranty 1 year parts only

Page 7: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

7For more information about APC’s Availability Cooling, visit www.apc.com or call 1-888-289-6268

Modular/HIgH denSITy aIr CondITIonIng

InfraStruXure® Inrow™ SCrapidly deployable, in-row air conditioning for server rooms

and wiring closets.

New technologies are increasing heat loads in today’s server rooms

and wiring closets, which often lack adequate cooling. The APC

InfraStruXure InRow SC is a self-contained cooling solution that

maximizes availability within small IT rooms. This energy-efficient

unit lowers operating costs by using variable speed fans, capacity

modulation, and an in-row form factor. The InRow SC’s plug-and-

play design allows for rapid installation without the need for running

refrigerant lines or providing remote heat exchangers. The predictive

failure notification and high head pressure protection features, along

with hot-swappable fans, improve the availability of IT equipment.

Features and benefits

Agility • Easy to install Self-contained design allows for fast installation without

refrigerant lines or remote heat exchangers. Unit requires only power, condensate drain and an available return plenum to provide effective cooling.

• In-Row architecture Provides increased predictability of cooling performance.

• Modular design Provides scalable solutions to add cooling as demand increases.

Manageability • Real-Time capacity monitoring Displays current and available cooling.

• Microprocessor controller Displays an 80-character LCD backlit alphanumeric display that provides communication and alarm indication.

• Network manageable View the user interface with a browser. Gives quick access from anywhere on the network

• InfraStruXure Manager compatible Enables centralized management via the APC InfraStruXure Manager.

• Building management system integration Allows you to send alarms and data points to manage critical building infrastructure from a single system.

Availability • Ducted condenser air Uses unconditioned air from plenum space to reject

the heat rather than conditioned room air.

• Built-In condensate pump Factory installed pump collects and removes water from the air conditioner, ensuring continuous operation.

• High head pressure protection Ensures the InRow SC remains operational even when the condenser inlet air is restricted or very hot.

• Coil freeze protection Hot gas bypass prevents evaporator coil from freezing during light load conditions.

• Predictive failure notification Maximizes system availability by providing early warning of required fan or filter replacement.

• Automatic restart In the event of a power failure the InRow™ SC will resume operation.

Serviceability • Hot swappable fans Allow system to remain operational if a fan

replacement is required.

• Washable filters Easy to maintain, cleanable, deep loading mesh filter removes particles from the return air stream.

Total Cost of Ownership • Rack inlet temperature control Reduces the risk of hot spots at the rack level.• Variable speed fans Reduce energy consumption during off-peak cooling

periods.• Green refrigerant Environmentally friendly refrigerant that can offer LEED points.

ACSC100 ACSC101Cooling Option R410A

Capacity up to 7 kW

Compressor Type Rotary

Air Discharge Patterns Horizontal

Intake Air Rear Return

Refrigerant R410A

Air Flow 1200 CFM

Nominal Input Voltage 200V, 208V, 230V

Input Power 2940 Watts 2530 Watts

Input Frequency 60 Hz +/- 3 Hz 50 Hz +/- 3 Hz

Input Connections NEMA L6–20P IEC 309 16A 2P+E

Control panel Multi-function LCD status and control console

Maximum Height 1991.00 mm

Maximum Width 300.00 mm

Maximum depth 1069.00 mm

Net Weight 165.91 kg

Color Black

Regulatory Approvals BSMI,EN 55022 Class A,FCC Part 15 Class A,ICES-003,UL

Listed,VCCI,VDE, CCC

BSMI, EN 55022 Class A, FCC Part 15 Class A,

ICES-003,UL Listed, VDE, VCCI C-tick, CE, CCC

Standard Warranty 1 year repair or replace

Modular/HIgH denSITy aIr CondITIonIng

Page 8: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

8 For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-289-6268

Modular/HIgH denSITy aIr CondITIonIng

Hot aisle containment for high-density configurations.

Mixing of hot and cold air streams in the data center lowers avail-

ability of IT equipment. Returning the warmest possible air to the

computer room air conditioners increases the efficiency and capacity

of the system. The hot aisle containment system ensures proper air

distribution by completely separating supply and return air paths.

The hot aisle is sealed off using doors and transparent ceiling tiles

that extend the width of the hot aisle. Ceiling tiles are available for

both 19” and 23” racks. Two-rack kits complete with ceiling tile and

hardware are available for future expansion.

Features and benefits

Availability • Cable access brush strip Blocks air from escaping through holes

surrounding cabling.

Agility • Ceiling tiles Close off the top of the hot aisle to prevent warm air from

mixing with room air.

Hot aisle Containment

rack air Containment

Modular air containment system designed to maximize

cooling predictability, capacity, and efficiency.

Deployment of high density loads in IT environments can create areas

of unpredictable cooling performance. APC’s Rack Air Containment

is a modular system designed to work in conjunction with APC

NetShelter® SX enclosures and InRow™ cooling units to provide max-

imum cooling predictability, capacity, and efficiency. By attaching

to the rear of the NetShelter SX, air exhausted from IT equipment

is forced to pass through the cooling unit where it is conditioned.

This ensures that warm exhaust air does not find its way back to

the air inlets of installed servers. N+1 and 2N configurations allow

for maximum availability. Front containment can also be added to

provide additional isolation and noise dampening.

Features and benefits

Adaptability • Modular design Compatible with standard NetShelter SX racks, providing

maximum system flexibility and scalability.

• Front containment Ensures cold supply air is not captured by neighboring equipment.

• Rear containment Ensures server exhaust air is returned to the InRow cooling units for maximum cooling predictability.

• One-way locking door Secures the hot aisle while allowing for quick exit in case of emergency.

• Scaleable densities Allow higher density cooling to be achieved by integrating the hot aisle containment system with in-row architecture.

• Modular design Modular design provides scalable solutions to add cooling as demand increases.

Total Cost of Ownership • Energy efficiency Increases cooling capacity of the associated air

conditioners without driving up power consumption.

Availability • Redundancy Systems can be configured to included an additional InRow

cooling unit to provide N+1 or 2N redundancy.

• Integrated pressure sensors Pressure sensors in the InRow cooling units provide fan speed control for optimum system efficiency.

Convenience • Noise dampening Containment of both front and rear provides reduction of

noise caused by installed equipment.

• Plexiglass door inserts Provides required air containment and a consistent look across the racks while allowing visibility to installed IT equipment.

• Easy to install Innovative design allows for fast, easy installation by almost anybody.

Modular/HIgH denSITy aIr CondITIonIng

Page 9: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

9For more information about APC’s Availability Cooling, visit www.apc.com or call 1-888-289-6268

Wiring Closet Ventilation unitrapidly deployable wall and ceiling mount heat removal for

wiring closets.

Wiring closet heat loads are rising due to deployment of tech-

nologies such as VoIP and Power over Ethernet. The Wiring Closet

Ventilation Unit is a rapidly deployable wall and ceiling mount heat

removal system designed specifically for the wiring closet environ-

ment. By exhausting hot air from the closet to an adjacent space

it allows conditioned air (entering through the Air Intake Grill) to

cool the load. Dual fans increase availability while LED status indi-

cators and dry contact outputs enhance the unit’s manageability.

Selectable fan speeds allow the user to choose between maximum

performance and quiet operation.

Features and benefits

Availability • Fault-tolerant fan system In event of a fan failure the remaining fan

automatically speeds up to compensate. Fans are N+1 redundant up to 300 CFM of airflow.

• Selectable speed fans Selectable fan speed (high/low) via toggle switch provides options for maximum performance or quiet operation.

Adaptability • Multiple mounting methods Flexible design allows for both drywall and

ceiling mount installations.

• Easy to install Innovative design allows for fast, easy installation by almost anybody.

• Hardwire capable For installations where hard wiring is required or prefered.

• Architecturally neutral Unobstrusive design and coloring blends in with the surroundings.

Manageability • Predictive failure notification Maximizes system availability by providing

early warning of required fan replacement.

• Dry contact output Provides remote notification of failures when used with APC environmental monitoring unit or system.

• LED status indicators Provide visual notification of fan failure.

ACF301

Cooling Capacity Options 3 kW of heat removal

Air Flow 475.00 CFM

Nominal Input Voltage 100–240V, 50/60 Hz

Input Power 85 Watts Input

Input Connections Hard Wire 3-wire, IEC-320 C14, NEMA 5-15P

Maximum Height 12.80 inches (325 mm)

Maximum Width 17.10 inches (434 mm)

Maximum depth 7.00 inches (178 mm)

Color White

Regulatory Approvals cUL Listed,CE,EN 55022 Class A,EN 55024, FCC Part 15 Class A,VCCI

Standard Warranty 2 years repair or replace

aIr dISTrIbuTIon/FanS

Page 10: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

10 For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-289-6268

rack air removal unit SXPerformance heat removal for high-density equipment in

netShelter® SX and VX enclosures.

High-density equipment creates an environment where traditional

air distribution methods are often not effective. Densely packed

enclosures can cause IT equipment to overheat, resulting in down-

time. The Rack Air Removal Unit SX captures exhaust heat, duct-

ing it to the return air plenum and eliminating hot spots. Through

automatic fan speed adjustment based on temperature or power

consumption, the fans will self-adjust for optimal performance.

With a unit-mounted LCD display users can view temperatures at

the rack, monitor alarm conditions and adjust unit set points. The

integrated network management card allows for remote monitor-

ing and control of the Rack Air Removal Unit SX. This space-sav-

ing product mounts to the back of either the NetShelter SX or VX

enclosure – requiring zero U space.

Features and benefits

Manageability • Network manageable View the user interface with a browser. Gives quick

access from anywhere on the network

• InfraStruXure® Manager compatible Enables centralized management via the APC InfraStruXure Manager.

• Temperature monitoring Allows up to 3 remote sensors to monitor rack inlet temperature.

• LCD display Accessible without opening the door for easy operation. Allows user to locally monitor and control the unit.

Availability • Fault-tolerant fan system In event of a fan failure the remaining fans will

speed up to compensate. Fans are N+1 redundant up to 1500 CFM of airflow.

• Dual A-B power inputs Draw power from the UPS for power protection with dual feeds for redundancy.

• Ducted Exhaust System Removes hot air from the data center to prevent recirculation and eliminate air mixing.

• Field replaceable components Fans and electronics module can be readily replaced without uninstalling the unit.

Adaptability • Adjustable mounting frame The frame can mount on Netshelter SX or VX

enclosures and extends to accommodate 42U, 47U or 48U rack heights.

• Zero “U” Solution Mounts to the rear of the rack, leaving valuable rack space for other equipment.

Total Cost of Ownership • Easy to install Innovative design allows for fast, easy installation by almost

anybody.

• Variable speed fans Reduce energy consumption during off-peak cooling periods.

• Increased capacity Higher rate of heat removal allows more equipment to be installed in each rack.

ACF400 ACF402

Cooling Capacity Options 23 kW

Air Discharge Patterns Upflow,Ducted Upflow,Ducted

Air Flow 2000 CFM

Nominal Input Voltage 100V,120V,200V,208V,230V

Input Power 1200 Watts

Input Frequency 50/60 Hz

Input Connections IEC-320 C14, NEMA 5–15P

Control panel Multi-function LCD status and control console

Maximum Height 1918.00 mm

Maximum Width 597.00 mm 737.00 mm

Maximum depth 254 mm

Net Weight 67.27 KG 77.27 KG

Color Black

Regulatory Approvals cUL Listed,CE,EN 55022 Class A,EN 55024,FCC Part 15 Class A,ICES-003,IEC 61000-3-2,IEC 61000-3-3,UL Listed,VDE,VCCI

Standard Warranty 2 years repair or replace

aIr dISTrIbuTIon/FanS

Page 11: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

11For more information about APC’s Availability Cooling, visit www.apc.com or call 1-888-289-6268

rack air distribution unitair distribution for power dense enclosures and low

pressure areas

The Rack Air Distribution Unit is a 2U fan unit that works with an

existing precision air conditioning system to deliver cool air to the

equipment contained in a rack enclosure. The Rack Air Distribution

Unit connects into the raised floor and pulls supply air directly into

the enclosure. This prevents the conditioned air from mixing with

warmer room air before reaching the equipment.

The Rack Air Distribution Unit minimizes temperature differences

between the top and bottom of the enclosure. It also prevents hot

exhaust air from recirculating to the inlet of the enclosure.

The product is recommended for rack enclosures with loads

greater than 1.5kW and can provide airflow for loads up to 3.5kW.

It is also ideal for enclosures in raised floor environments where

underfloor air distribution is inadequate.

Features and benefits:

Availability• Dual fans Deliver air to equipment in the rack where floor tile velocity is

inadequate for proper cooling.

• Raised floor duct Delivers cool, conditioned air directly from the raised floor to the inlet of the IT equipment.

Agility• Air filtration Removes dirt and other particulates from the intake air for

cleaner supply air.

• Fan control switches Users can turn one or both fans on and off depending on the heat load.

• Mounting rails Adjustable depth allows the unit to fit APC's NetShelter® enclosure or other 19" EIA-310-D enclosure.

• Fan guards A safety measure that provides protection from the fan opening by covering the inlet.

Total Cost of Ownership• Dual A-B power inputs Draw power from the UPS for power protection

with dual feeds for redundancy.

ACF001 ACF002 ACF003

Air Flow 503 CFM 420 CFM 503 CFM

Amp Draw Nominal 2A 1A 2A

Nominal Input Voltage 120V 208V, 230V 100V

Input Power 240 Watts 230 Watts 200 Watts

Input Frequency 60 Hz +/- 1Hz 50/60 Hz 50/60 Hz

Rack Height 2U

Input Connections C-13 NEMA 5–15P

C-13 IEC-320 C14

C-13 NEMA 5–15P

Maximum Height 89.00 mm

Maximum Width 422.00 mm 421.00 mm

Maximum depth 737 mm

Net Weight 18.64 KG

Color Black

Regulatory Approvals UL Recognized CE, UL Recognized

METI Denan, UL Recognized

Standard Warranty 2 years repair or replace

aIr dISTrIbuTIon/FanS

Page 12: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

12 For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-289-6268

ACF201BLK ACF202BLK

Nominal Input Voltage 120V 208V, 230V

Input Power 150 Watts

Input Frequency 60Hz 50/60Hz

Air Flow 260 CFM

Amp Draw Nominal 2 A 1 A

Net Weight 32 lbs (15kg)

Max. Height 3.44 inches (87.4 mm)

Max. Width 16.98 inches (431 mm)

Max. Depth 26.34 inches (669 mm)

Color Black

Approvals UL Recognized CE

Standard warranty 2 years repair or replace

air distribution for networking equipment with side to

side airflow

Housing equipment with side to side airflow creates many chal-

lenges for IT and facility managers, particularly in regards to cool-

ing. Because most enclosures are designed for a front to back air-

flow pattern, it is difficult to maintain ideal operating temperatures

on side to side airflow equipment. The Rack Side Air Distribution

Unit allows for greater security and organization by allowing racks

to be placed adjacent to one another without impeding airflow.

The Rack Side Air Distribution Unit is a 2U rack mountable air

distribution product for networking equipment or servers with

side to side airflow. It pulls in conditioned air from the front of

the rack and distributes it to the side air intake of the networking

equipment. This extends equipment life by providing proper inlet

temperatures.

This product is recommended for one or more networking products

that are stacked consecutively in a rack. Rack Side Air Distribution

Units may be placed above and/or below the networking equip-

ment. Airflow pattern is user configurable via an interchangeable

air turning vane.

Features and benefits:

Availability• Dual fans Deliver air to equipment in the rack where floor tile velocity is

inadequate for proper cooling.

• Fan control switches Users can turn one or both fans on and off depending on the heat load.

Agility• Mounting rails Adjustable depth allows the unit to fit APC's NetShelter®

enclosure or other 19" EIA-310-D enclosure.

• Fan guard A safety measure that provides protection from the fan opening by covering the inlet.

Total Cost of Ownership• Dual A-B power inputs Draw power from the UPS for power protection

with dual feeds for redundancy.

• Air turning vane Directs air up or down the side of the rack, supplying cool air to the inlet of side to side airflow equipment.

Manageability• LED status indicators Indicate the operating condition of the unit including

power-on and alarm state.

rack Side air distribution unit

aIr dISTrIbuTIon/FanS

Page 13: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

13For more information about APC’s Availability Cooling, visit www.apc.com or call 1-888-289-6268

Economy• Dedicated dehumidification Boosts system efficiency by adding latent

capacity without overcooling or increasing the requirement for reheat, resulting in up to 15% lower energy consumption (N/A chilled water systems).

• SCR electric reheat Modulates capacity to save energy. Exacting amounts of reheat loaded equally on all three phases.

Manageability• Programmable input/output contacts Allows device contacts to be

connected to the air conditioner and mapped to customer outputs or system alarms.

• Microprocessor controller Provides proactive control and real-time monitoring via a four line, eighty character alphanumeric display.

• Network interface Provides management by connecting the device directly to the network with a dedicated IP address, avoiding the need for a proxy such as a server. Management is available via Web browser, Telnet or SSH. Notification features inform you of problems as they occur.

• Redundant group control Allows up to 4 groups of precision air conditioners to communicate with each other for redundancy, demand fighting prevention, mode assist, and global sharing of certain settings.

networkaIr® FMModular floor mount precision air conditioning for

environmentally sensitive equipment areas

The NetworkAIR FM utilizes leading edge precision air technolo-

gies. Modular construction, variable frequency drives, dedicated

dehumidification, tandem scroll compressors, and front service

access are all integrated into one high efficiency system. A scal-

able design enables customers to meet the changing needs of their

environments.

Features and benefits

Availability• Tandem scroll compressors Quiet and efficient operation of scroll

compressors, connected on a common circuit for staged capacity control (N/A chilled water systems).

• Direct drive motors Stress on bearings is nearly eliminated, increasing useful life. Allows integral fan/motor assembly to be factory balanced which lowers vibration and expedites startup. Eliminates the need for unreliable belts, pulleys and special bearings.

• Variable frequency drives Enable the fans to be soft started, saving energy during power up. Controlling the motor speed simplifies the adjustment for static pressure and gives the option of back-draft prevention.

• Steam humidifier Humidity is managed through a self-contained steam canister humidifier for maximum efficiency and ease of maintenance. The pure-steam canister maintains consistent capacity output, and requires very little scheduled maintenance.

Serviceability• Front service access The system has full service, front access for routine

servicing of components. Front access also narrows the footprint of the system making it possible for units to be placed side by side.

Protection• Double-walled panels Separates insulation from the air stream, which

prevents periodic maintenance of the insulation and reduces noise levels. Small particles of insulation can be picked up by the air stream if not isolated.

FM-DX 60Hz FM-CW 60Hz FM40H-AGB-ESD FM40B-CFB-ESD

Cooling Options Air, Water, Glycol, Economizer, Multicool Chilled Water Air Chilled Water

Humidification Capacity 10 lbs/hr 10 lbs/hr

Compressor Type / Refrigerant Tandem Scroll / R22 N/A Tandem Scroll / R407C N/A

Input Frequency 60 Hz 50 Hz

Nominal Input Voltage 208V 3PH, 480V 3PH, 600V 3PH 400V 3PH

Air Discharge Patterns Downflow, Upflow Front Return, Upflow Rear Return Downflow

Control Panel Microprocessor Controller

Net Weight 2,360 lbs (1072.73 kg) 1,180 lbs (536 kg) 2,360 lbs (1072.73 kg) 1,180 lbs (536 kg)

Max. Height 76.89 inches(1953.01 mm)

Max. Width 70.87 inches (1800.1 mm)

Max. Depth 35.00 inches (889.00 mm)

Approvals CSA, MEA, UL Listed CE, Eurovent

Standard Warranty 1 year (parts only) optional extended warranties available.

rooM aIr CondITIonIng

Page 14: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

14 For more information about APC’s Cooling Solutions, visit www.apc.com or call 1-888-289-6268

ACPA4000 AP7003

Cooling Capacity 3.9kW 1.6kW

Cooling Options Air

Compressor Type Rotary

Nominal Input Voltage 120V

Input Power 1,610 Watts 692 Watts

Input Frequency 60Hz

Coolant R22

Air Flow 600 CFM 170 CFM

Condensate Tank N/A 3.5 qt

Condensate Pump 1.6 gal/hr N/A

Approvals UL Listed

Standard Warranty 1 year repair or replace

networkaIr® Pa*

Portable, self-contained air conditioning solutions for small

rooms and data closets

Inconsistent and high temperatures can lower the expected life of,

and permanently damage your electronic equipment. IT refreshes

and equipment relocation result in unpredictable and ever-chang-

ing environments. The NetworkAIR PA provides portable cooling

for your sensitive electronic equipment to meet the environmental

demands of small rooms and data closets.

This self-contained solution does not require an external con-

denser, refrigerant piping, or building water source for operation.

Heat is rejected to a drop ceiling or adjacent area via a flexible duct

kit. The NetworkAIR PA can be installed quickly and inexpensively,

without the need for building modifications.

Features and benefits:

Availability • Automatic restart Returns the unit to its last operating status in the event

of a power failure, in order to protect the compressor and the environment. (Not available on the AP7003 unit).

• Ducting kit Allows hot air to be removed and distributed to a drop ceiling or hard-ducted return. This increases the efficiency of the computer room air conditioning system in both capacity and dehumidification.

• High head pressure protection Prevents compressor damage (not available on AP7003 unit).

Agility • Easy to install Self-contained, air cooled design allows for fast, easy

installation.

• Replacement ceiling tile Fits into a standard drop ceiling to provide a connection point for the ducting kit. (Not available on the AP7003 unit).

• Casters Provide flexibility to move the unit to wherever cooling is required.

Manageability • Network manageable Remotely monitor and control NetworkAIR PA4000

environmental information from anywhere on the network via a Web browser (not available on the AP7003 unit).

• LED status indicators Four (4) external status indicator LEDs represent: major alarm; minor alarm; check log (new alarm/warning has occurred); system on (evaporator blower is running). Not available on the AP7003 unit.

• On/off scheduling Allows the user to determine when the unit operates, saving energy costs. (Not available on the AP7003 unit).

*available in North America only

rooM aIr CondITIonIng

Page 15: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

15For more information about APC’s Availability Cooling, visit www.apc.com or call 1-888-289-6268

air Cooled Modular Chillers*

air Cooled Chillers for air conditioning equipment in data

centers, server rooms and wiring closets.

APC air cooled chillers for air conditioning equipment in data

centers are a new generation of leading-edge technology. These

all-in-one integrated packages reduce time and cost of installation.

Features and benefits:

Manageability • Microprocessor controller Provides proactive control and real-time

monitoring via a four line, eighty character, alphanumeric display.

• ModBus translator Optional feature allows integration with Building Management System.

Total Cost of Ownership • Variable speed fans Reduce energy consumption during off-peak cooling

periods.

• Integrated hydronics package Includes all the necessary components to make one connection to the chilller without the need of external connections to auxiliary equipment such as pumps, increasing the speed of deployment.

Availability • Scroll compressors Utilize few moving parts for increased reliability and

life expectancy.

• Independent power feed Optional feed to the pumps allows for wiring to the UPS, thus ensuring chilled water availability during generator start-up when used with a storage tank.

• Dual redundant pumps Provide reliable chilled water flow sized for full capacity.

• Low ambient controls Enable chiller operation in temperatures down to -20°F.

Convenience• Optional storage tank Fits under chiller without increasing footprint.

SKU Series ACCH050 ACCH084 ACCH120 ACCH167 ACCH200 ACCH220

Capacity 50kW 84KW 120KW 167KW 200KW 220KW

UPSable pump (optional) Yes Yes Yes Yes N/A N/A

Storage tank option ACTA1100 ACTA1101 ACTA1102 ACTA1102 N/A N/A

Windbaffle option ACAC30001 ACAC30002 ACAC30003 ACAC30004 ACAC30005 ACAC30005

Voltages 208/3PH, 480/3PH 208/3PH, 480/3PH 208/3PH, 480/3PH 208/3PH, 480/3PH 208/3PH, 480/3PH 208/3PH, 480/3PH

Height in inches* 52 52 52 52 90 90

Width in inches* 82 108 108 108 95 95

Depth in inches* 43 43 90 90 89 89

Weight in lbs* 1298 1819 3134 3603 4705 4911

Standard Warranty 1 year (parts only), optional extended warranties available

* Weights and dimensions do not include storage tank or windbaffles

*available in North America only

HeaT rejeCTIon

Page 16: for the IT environment - apcmedia.comapcmedia.com/pdf_downloads/litpdfs/996-2854B.pdf · 23 kW Hot Aisle Containment System High Density Zones Best capacity sharing Best predictability

For more information call:Tel: 800 800 4APC - US & CanadaTel: 401 789 0204 - World wide

APC CorporateAPC North America132 Fairgrounds RoadWest Kingston, RI 02892 USACall: 800 800 4APCFax: 401 789 3710

APC Latin America5301 Blue Lagoon Drive Suite #610Miami, FL 33126 USACall: 305 266 5005Fax: 305 266 9695

APC EuropeAPC IrelandBallybrit Business ParkGalway, IrelandCall: +353 91 702000Fax: +353 91 756909

APC Asia PacificAPC AustraliaLevel 13 The Denison65 Berry StreetNorth Sydney, NSW 2060Call: +61 2 9955 9366Fax: +61 2 9955 2844

Visit: www.apc.come-mail: [email protected] Support: : support. apc.com

©2007. All rights reserved. All APC trademarks are property of American Power Conversion. Other trademarks are property of their respective owners. Specifications are subject to change without notice. PART# 996-2854B

APC’s quality system is certified by ISO 9002 standards

Since 1981, APC has been a global leader in power availability solutions, setting the

industry standard for quality, innovation, and support. From its corporate head-

quarters in West Kingston, Rhode Island, APC operates sales offices throughout

the world and manufacturing facilities on four continents and distribution facilities on

five continents. APC ships products to over 150 countries.

Over 30 million satisfied customers worldwide depend on APC’s Legendary Reliability®.

Propelled by real-world experience and a drive towards technological innovation, APC

has the experience, scale, global presence, and stability to respond to emerging IT

availability needs.

Choose the optimal service solution to increase your system availability.

Receive your FREE APC white paper “Cooling Strategies for Ultra-High

Density Racks and Blade Servers”. Visit us online at http://promo.apc.com

and enter key code s369y.

As the recipient of hundreds of awards worldwide, APC is recognized for excellence in both its business and product performance. Every year since 1999, APC has been named to the Forbes Platinum 400 list of the Best Big Companies in America. For 11 years in a row, APC has received the Channel Champion award in the UPS category.