12/30/2014 Frame 6B GT IGV problem http://control.com/thread/1379617896 1/2 Frame 6B GT IGV problem Frame 6B Gas Turbine with MarkV, IGV problem during Startup. By Jigs on 19 September, 2013 3:11 pm April 2013 MI was performed. IGV blades, gears, pinion and actuator were replaced. Since then during start up at @ 85 % of GT speed IGV starts opening and not limiting at 57 Deg A but reaches upto 72 DEG A for a while and then come back to 57 GEG A before FSNL. Exhaust temp reaches 576 deg C max. before IGV starts opening. What could be cause? By CSA on 20 September, 2013 1:46 pm Jigs, The problem started when the IGV actuator was replaced during the outage. It's not clear if the electrohydraulic servovalve was also replaced at the same time, and if the proper servovalve was used for the replacement, and if the polarity of the current applied to each coil was verified during the commissioning/startup activities. It is also presumed that the IGV LVDTs were "zeroed" properly and calibrated properly after the outage. Have you tried manually positioning ("stroking") the IGVs using AutoCalibrate's Manual Position feature to see how the IGVs are behaving? If so, what did you observe? Have you used the 'Verify Position' or 'Verify Current' features of AutoCalibrate, and if so, what were the results? Since the IGV actuator was replaced, it's likely the IGV LVDTs were calibrated. Was the Null Bias Current value changed during the calibration procedure, and if so, what is the current value? Was the regulator gain changed during the commissioning/startup, and if so, what was it changed to? Even if the Null Bias Current and IGV Regulator Gains weren't changed during commissioning/startup, what are they? From the information provided, it would seem that no Control Constants were changed. So, presuming the reference is being calculated correctly (and there's no reason to believe changing the IGV actuator would change the way the IGV position reference is being calculated) then the most likely cause is some problem with the IGV assembly (actuator, bushings, etc.) binding, or the actuator isn't properly bolted down, or the servovalve isn't the right one, or the actuator isn't working properly. But, from the information provided, it would seem something is causing the actuator/IGV assembly to overshoot (travel past) the reference setpoint and then the Mark V has to change servocurrent to make it return to the proper value. If the Mark V has to keep putting out more current to make the IGVs move because they are either not moving or are sluggish to move (mechanically sticking or binding) and then when they do move they travel past the reference setpoint and the Mark V has to change servo current to get them to

Upload: mohamed-khalil

Post on 11-Aug-2015

59 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Frame 6 b gt igv problem

12/30/2014 Frame 6B GT IGV problem

http://control.com/thread/1379617896 1/2

Frame 6B GT IGV problemFrame 6B Gas Turbine with Mark­V, IGV problem during Startup.

By Jigs  on 19 September, 2013 ­ 3:11 pm

April 2013 MI was performed. IGV blades, gears, pinion and actuator were replaced. Since thenduring start up at @ 85 % of GT speed IGV starts opening and not limiting at 57 Deg A but reachesupto 72 DEG A for a while and then come back to 57 GEG A before FSNL. Exhaust temp reaches576 deg C max. before IGV starts opening. What could be cause?

By CSA  on 20 September, 2013 ­ 1:46 pm

Jigs,

The problem started when the IGV actuator was replaced during the outage. It's not clear if theelectro­hydraulic servo­valve was also replaced at the same time, and if the proper servo­valve wasused for the replacement, and if the polarity of the current applied to each coil was verified duringthe commissioning/start­up activities.

It is also presumed that the IGV LVDTs were "zeroed" properly and calibrated properly after theoutage.

Have you tried manually positioning ("stroking") the IGVs using AutoCalibrate's Manual Positionfeature to see how the IGVs are behaving? If so, what did you observe?

Have you used the 'Verify Position' or 'Verify Current' features of AutoCalibrate, and if so, whatwere the results?

Since the IGV actuator was replaced, it's likely the IGV LVDTs were calibrated. Was the Null BiasCurrent value changed during the calibration procedure, and if so, what is the current value? Wasthe regulator gain changed during the commissioning/start­up, and if so, what was it changed to?

Even if the Null Bias Current­ and IGV Regulator Gains weren't changed duringcommissioning/start­up, what are they?

From the information provided, it would seem that no Control Constants were changed. So,presuming the reference is being calculated correctly (and there's no reason to believe changing theIGV actuator would change the way the IGV position reference is being calculated) then the mostlikely cause is some problem with the IGV assembly (actuator, bushings, etc.) binding, or theactuator isn't properly bolted down, or the servo­valve isn't the right one, or the actuator isn'tworking properly. But, from the information provided, it would seem something is causing theactuator/IGV assembly to overshoot (travel past) the reference setpoint and then the Mark V has tochange servo­current to make it return to the proper value.

If the Mark V has to keep putting out more current to make the IGVs move because they are eithernot moving or are sluggish to move (mechanically sticking or binding) and then when they do movethey travel past the reference setpoint and the Mark V has to change servo current to get them to

Page 2: Frame 6 b gt igv problem

12/30/2014 Frame 6B GT IGV problem

http://control.com/thread/1379617896 2/2

come back to reference setpoint, it's not a control system problem­­it's a mechanical problem.

Please write back and let us know how you fare, or if you need more help/information.

By Jigs  on 6 October, 2013 ­ 3:13 pm

Thanks CSA,

All data pertaining IGV calibration, gain etc. are with C&I dept, i'm from operation, i will get itand post here. We also believe its mechanical, problem. Anyway thanks for details and reply.

Your use of this site is subject to the terms and conditions set forth under Legal Notices and thePrivacy Policy. Please read those terms and conditions carefully. Subject to the rights expresslyreserved to others under Legal Notices, the content of this site and the compilation thereof is © 1999­2014 Nerds in Control, LLC. All rights reserved.