gcl gcx operator manual warranty - amazon web services

44
08-12 This Installation Manual provides the information required to install, troubleshoot and maintain a GCL-GCX Counter Door Operator. NOT FOR RESIDENTIAL USE PROPER APPLICATION Door Type Operator Type Max Door Weight/HP Rolling Steel Counter Door 1/2HP = 500 lbs. Counter Door 112070.501539 COMMERCIAL LINE COUNTER DOOR OPERATOR GCL-GCX

Upload: others

Post on 24-Feb-2022

5 views

Category:

Documents


0 download

TRANSCRIPT

™ 08-12

This Installation Manual provides the information required to install, troubleshoot andmaintain a GCL-GCX™ Counter Door Operator.

NOT FOR RESIDENTIAL USE

PROPER APPLICATION

Door Type Operator Type Max Door Weight/HP

Rolling Steel Counter Door 1/2HP = 500 lbs.Counter Door

112070.501539

COMMERCIAL LINE

COUNTER DOOR OPERATOR

GCL-GCX

Section 1 How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1

Section 2 Safety Information & Instructions . . . . . . . . . . . . . . . . . . . . 2.1

Section 3 Critical Installation Information . . . . . . . . . . . . . . . . . . .3.1-3.3Section 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1-4.3

Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1-4.2

Manual Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3

Optional Timer-Close or Aux. Output Modules . . . . . . . . . 4.4

Section 5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-5.8

Line Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1

Low Voltage Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2

External Wire Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3

Wall Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4

Montored/Non-monitored Photocells . . . . . . . . . . . . . . . . . 5.5

Locking Bottom Bar / Interlock Switch. . . . . . . . . . . . . . . . . . 5.7 Montored/Non-monitored Sensing Edge . . . . . . . . . . . . . . 5.6

External Radio/Safety Instructions . . . . . . . . . . . . . . . . . . . . . 5.8

Section 6 Operator Setup Procedures . . . . . . . . . . . . . . . . . . . . . . .6.1-6.7

Setting Close Direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2

6.3

Setting

Travel

Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.4

Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Setting

Limit

Overrun . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.5

Setting

Open

&

Close

Modes . . . . . . . . . . . . . . . . . . . . . . . . . .

6.6

6.7

Setting Mid-Stop Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Resetting the MRT, Monitored Reversing Devices . . . . .

Section 7 Special Operational Features. . . . . . . . . . . . . . . . . . . . . 7.1-7.4 Operator Cycle Count. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 GDO & Display Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.1 Operator Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.2 Optional Hand Crank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3-7.4

Section 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-8.5 Display Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.1 Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-8.2 Run Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2-8.3 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.4 Safe-T-Beam® Self-Diagnostic Troubleshooting Chart . .8.5

Section 9 Service & Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9.1 Periodic Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . .9.1

Section 10 Appendixes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-10.7 Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-10.2 Operator Parts Breakdown (Exploded View) . . . . . . 10.1 Operator Parts Breakdown (Parts List) . . . . . . . . . . . . 10.2 Base Electric Box Parts Breakdown . . . . . . . . . . . . . . . 10.3 Appendix B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.4 Screw Terminal Assignments. . . . . . . . . . . . . . . . . . . . . 10.4 Appendix C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5-10.7 Run Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5 Error Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.6-10.7

Section 11 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.1

Table of Contents

6.1

TOCwww.geniecompany.com 08-12Counter Door OperatorGCL-GCX

Section 1: How to use this manualThe 11 sections of this Installation Manual provide the information required to install, troubleshoot and maintain an GCX commercial/industrial door operator.

Section 2 Provides important defining information related to safety terminology used throughout this manual, as well as safety related instructions which must be followed at all times while doing any steps/tasks/instructions detailed in this manual.

Section 3 Details pre-installation concerns/issues/decisions that are recommended to be considered and/or resolved prior to beginning any commercial door operator installation.

Sections 4-6 Provide step by step installation and set-up instructions for the GCX commercial door operator. Each section is written such that it must be followed in a step by step order to complete a successful installation.

Sections 7-8 Detail important features and troubleshooting information for typical installation and normal operations that may occur.

Sections 9-11 Provide related information on service and maintenance items, operator drawings for use in troubleshooting and service activities, along with important warranty and returned goods policy information.

Failure to correctly perform all steps in sections 4-6 can result in serious injury or death. WARNING

1.1www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

Section 2: Safety Information & Instructions

WARNINGOverhead Doors are large, heavy objects that move with the help of springs under high tension and electric motors. Since moving

gnidaer uoy no dneped srehto fo ytefas eht dna ytefas ruoy ,seirujni esuac nac srotom cirtcele dna ,noisnet rednu sgnirps ,stcejbo ecivres tseraen ruoy llac ,detneserp noitamrofni eht dnatsrednu ton od ro snoitseuq yna evah uoy fI .launam siht ni noitamrofni eht

representative. For the number of your local Genie® Dealer, call 800-OK-GENIE, and for Genie® Factory Technical call 800-843-4084.

Advice,

In this Manual, the words Danger, Warning, and Caution are used to stress important safety information. The word: DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in injury or property damage.

The word NOTE is used to indicate important steps to be followed or important considerations.

IMPORTANTREAD PRIOR TO ANY DOOR OPERATION

POTENTIAL HAZARD EFFECT PREVENTION

Do Not operate unless the doorway is in sight and free of obstructions. Keep people clear of opening while door is moving.Do Not allow children to play with the door operator.Do Not change operator control to momentary contact unless an external reversing means is installed.Do Not operate a door that jams or one that has a broken spring

Could result inSerious Injury

or Death

Turn off electrical power before removing operator cover. When replacing the cover, make sure wires are not pinched or near moving parts.Operator must be electrically grounded.

ELECTRICAL SHOCKDo Not try to remove, repair or adjust springs or anything to which door spring parts are fastened, such as, wood block, steel bracket, cable or any other structure or like item.Repairs and adjustments must be made by a trained service

.snoitcurtsni dna sloot reporp gnisu evitatneserperHIGH SPRING TENSION

WARNING

MOVING DOOR

1. Read manual and warnings carefully.2. Keep the door in good working condition. Periodically lubricate all moving parts of door.3. If door has a sensing edge, check operations monthly. Make any necessary repairs to keep it functional.4. AT LEAST twice a year, manually operate door by disconnecting it from the operator. The Door should open and close freely. If it does not, the door must be taken out of service and a trained service representative must correct the condition causing the malfunction.5. The Operator Motor is protected against overheating by an internal thermal protector. If the operator ceases to function because motor protector has tripped, a trained service technician may need to correct the condition which caused the overheating. When motor has cooled, thermal protector will automatically reset and normal operation can be resumed.6. In case of power failure, the door can be operated manually by pulling the release cable to disconnect the operator drive system. 7. Keep instructions in a prominent location near the pushbutton.

Could result inSerious Injury

or Death

WARNING

Could result inSerious Injury

or Death

WARNING

2.1www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

3.1

Job Site Issues to Consider/ConcernsThe following list of items should be considered prior to selecting an operator for a given job site.1-Available power supply. 2-Type of door. 3-Potential operator mounting obstructions. Items to consider include, but are not limited to: side room, room above door shaft, room below door shaft, available mounting

surface integrity, power supply location, and convenient chain hoist and release cable positioning. 4-Size of door for appropriate operator torque and door travel speed selection. 5-Operator mounting environment. Items to consider include operator location, dampness of location, dustiness of the location and corrosiveness of the location. 6-Door activation needs/requirements. Examples include 3 button control stations, 1 button control stations, radio controls, pull cords, loop detectors, photoelectric controls,

key switches, etc. See “Entrapment Protection” section below. 7-Interlock switches are required under certain conditions for doors with pass doors and door locks. See Section

5.5 below.

8-Accessory equipment. Examples include reversing edges and/or photocell beams, which are required for doors set to operate as momentary contact, auxiliary control relays, warning lights, etc. See “Entrapment Protection” section below.

WARNING: DO NOT apply line voltage until instructed to do so.

CAUTION: Check working condition of door before installing the operator. Door must be free from sticking and binding. If equipped, deactivate any door locking device(s). Door repairs and adjustments, including cables and spring assemblies MUST be made by a trained service representative using proper tools and instructions.

Section 3: Critical Installation Information

ENTRAPMENT PROTECTIONThe installation of a fail safe external reversing device (such as a monitored reversing edge or photocell system, etc.) is required on all momentary contact electronicallyoperated commercial doors. If such a reversing device is not installed, the operator will revert to a constant contact control switch for operation (Closing only). The Reversing Devices currently UL Approved with this model are:

MillerEdge ME, MT and CPT series monitored edge sensors used in combination with Timer-Close Module P/N OPABTCX.S, and/or OPAKMEIGX.S INTERFACE MODULE.

2) Residential Safe-T-Beam® Monitored Photocells from The Genie® Company, model OSTB-BX (P/N 38176R).3) Series II Commercial Safe-T-Beam®, Monitored Photocells P/N OPAKPE.S. 4) Series II Commercial Safe-T-Beam®, Monitored Photocells P/N OPAKPEN4GX.S.

1)

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCX

ENTRAPMENT PROTECTIONThe GCX can be used with the following UL Listed entrapment devices in compliance with UL325 requirements active starting August 29, 2010.UNTIL ONE OF THESE MONITORED EXTERNAL ENTRAPMENT DEVICES IS INSTALLED, THE OPERATOR WILL NOT ALLOW MOMENTARY CONTACT OPERATION IN THE CLOSE DIRECTION.

Model HPFIRESTAR 3” SLAT

FIRESTAR 3” SLAT INSULATED SHEET DOOR

16GA. 18GA. 20GA. 22GA. 24GA. 26GA. 18GA. 20GA. 22GA. ALUM. STL/SST 20GA. 22GA.142 108 82 94 N/A

STEEL, NON-INSULATED STEEL, INSULATEDULL is ted

FIRESTAR 2” SLATGRILLESCOUNTER DOOR

ALUM. STL/SST

126 126

Rolling Steel Door Chart (sq. ft.)

Note: Total door weight and not square footage is the critical factor in selecting the proper operator. These Sq.Ft. measurements are based on square doors, e.g. 16' x 16'.

Unbalanced Fire Shutters have a maximum square footage of 52 for 22GA. steel and 42 for 20GA. steel.

GCL-GCX 1/2 YES N/A N/A 144 144 144 144 N/A N/A N/A 16GA. 18GA. 20GA. 22GA.

N/A N/A N/A

20GA. 22GA. 26GA.

N/A N/A N/A

3.2

APPROVED

DEVICES

ALLOWABLE DOOR WIDTH

ANY

WIDTH

30 FEET

30 FEET

30 FEET

Miller Edge ME, MT & CPT series monitored edge sensors used in combination with either the Genie® Timer-Close Module or Direct connect through STB inputs using the OPAKMEIGX.S Interface Module.

Commercial Photoeye Kit—P/N OPAKPE.S.

Safe-T-Beam® from Genie®—P/N 38176R.

Monitored Photocells—P/N OPAKPEN4GX.S.

www.geniecompany.com 08-12Counter Door Operator

3.3www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

IMPORTANTINSTALLATION INSTRUCTIONS

WARNING To reduce the risk of severe injury or death:

1) READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS.2) Install only on a properly operating and balanced door. A door that is operating improperly could cause severe injury. Have qualified service personnel make repairs to cables, spring assemblies and other hardware before installing the operator.3) Remove all pull ropes and remove, or make inoperative, all locks (unless mechanically and/or electronically interlocked to the power unit) that are connected to the door before installing the operator.4) Install the door operator at least 8 feet above the floor if the operator has exposed moving parts.5) Do not connect the door operator to the power source until instructed to do so.6) Locate the control station: (a) within sight of the door, (b) a minimum of 5 feet above the floor so that small children cannot reach it, and (c) away from all moving parts of the door.7) Install the Entrapment Warning Placard next to the control station and in a prominent location.8) For products having a manual release, instruct the end user on the operation of the manual release.

4.1

Unless otherwise stated, these instructions will show right side mount installations. Left side mount is opposite. 1) Insert four(4) 3/8"-16 x 1" carriage bolts into headplate. FIG. 1. • Threads to outside of plate. • Retain by pushing 4 speed nuts onto bolts. 2) Complete installation of door as instructed in door installation manual up to "mounting of hood." 3) Make certain both headplates are at 90° to wall. • If not at 90°, use temporary external brace to hold in place. 4) Install hood and secure with hood mounting screws. • When hood is secure, remove temporary brace if used (in step3). • Leave door in FULL OPEN position. 5) Place 3/8" flat washers and 3/8"-16 keps nuts on 3/8" carriage bolts closest to wall. FIG. 2. • Leave nuts flush with ends of bolts.

.rotarepo XCG morf draug niahc evomeR )6

Section 4: InstallationMounting

Figure 1 Figure 2

CARRIAGEBOLT WALL

FLAT WASHERS & KEPS NUTS

SPEEDNUT

nuts flush with end of bolts

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCXGCL-GCX

Mounting (continued)

7) Slide open ended slots of frame under flat washers installed in step 5. FIG. 3. • Locate other frame slots over remaining two(2) carriage bolts and bring frame against headplate. • Put 3/8" washers and keps nuts on remaining bolts. • DO NOT fully tighten nuts. • Slide operator toward wall as far as slots allow. FIG. 4. 8) Place driven sprocket and key on door shaft and align with output sprocket on operator. FIG. 4A. • Secure sprocket and key in place with set screws. 9) Wrap #25 roller chain around both sprockets and join with connecting link. FIG. 5 & 6. • Chain length is correct for 9-1/2" headplate. • For 11-1/2" headplate, add short #25 chain (provided) to long chain using extra connecting link. • Slide operator away from hood until drive chain is tensioned but not tight. FIG. 7. • Tighten mounting nuts.

Figure 3

Figure 6

Figure 5

Figure 7

4.2

TOWARD WALL AS FAR AS SLOTS WILL ALLOW

Figure 4

Figure 4A

90°

www.geniecompany.com 08-12Counter Door Operator

GCL-GCXGCL-GCX

Manual Release

NOTE: In case of power failure, door can be operated manually. The operator can be disconnected from door by pulling red pull rope attached to Drop Release Lever to allow opening door. FIG. 8.

FIG. 8.

• When door is in manual operation, limit switch setting is not affected. • Releasing pull rope will re-engage operator.

Figure 8

Figure

DROP RELEASE LEVER

4.3

1) Install Release Cord.

2) Locate and install the wall control.

3) Locate and install Warning Placard. FIG. 9.

Warning Placard MUST BE ATTACHED

to push button.

111735 00 1

(install release cord here)

9

ADJACENT

4) Remove four (4) self-tapping screws from front panel of the enclosure and remove front panel to expose control circuits and allow for installation of

any optional accessory board. to

www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

These instructions apply to either board. Although they perform different functions, they mount in the same way.

2) Orient the module so mounting bracket tabs are to the left and wire terminals are facing up. 3) Make desired wiring connections, in accordance with instruction manual accompanying the module. 4) Insert module into the area indicated and slide front mounting tab into slot on side panel of the enclosure. FIG. 10 & 11. 5) Adjust module so that it is level with GCX enclosure. • There is a mounting hole on side panel of enclosure which will line up with hole in module mounting bracket. • Attach module by inserting self-tapping screw (provided in kit) through module bracket and into hole in side panel. Do not overtighten. 6) Replace front panel.

Optional Timer-Close Module or Auxiliary Output ModuleFigure 10

Figure 11

MOUNTINGBRACKETTAB

Self tapping screw

4.4www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

WARNING • DO NOT apply power to operator until instructed to do so. • The Genie® Company recommends that line voltage wiring be performed by a qualified electrician. • Be sure that electrical power has been disconnected from the input power wires being connected to the operator prior to handling these wires. An appropriate lock-out /tag-out procedure is recommended. • Line voltage wiring must meet all local building codes. • Make sure operator voltage, phase and frequency nameplate ratings are identical to the job site line voltage ratings. • Input power wiring must be properly sized for the operators amperage rating located on the nameplate. • To reduce the risk of electric shock, make sure the chassis of this unit is properly grounded.

1) Remove LINE VOLTAGE INPUT PLUG and install proper fittings and 1/2”conduit. 2) Route proper LINE VOLTAGE wires into operator. 3) Locate LINE INPUT terminals on circuit board. Using correct connectors, attach wires to LINE INPUTS, and GROUND terminal. • Keep low voltage and line voltage wires separate. • Route all line voltage wires as shown. • Plug all unused conduit holes.

S S B S Y

S YS B S B

STBENAB+ 4VACEXTIN LKHOISTIN LK

CALRUN

SETCLR

SCROLL

SCROLL

Section 5: Wiring

Figure 1

Line Voltage Wiring Fig. 1

5.1www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

1) Connect all LOW VOLTAGE control circuit wires to this side

of unit using 1/2” conduit or flexible convoluted

tubing.

• Keep low voltage and line voltage wires separate. • Route all low voltage control wiring as shown. This

includes

all control circuit wires such as wall controls, timers and single

button

input

devices

as

well

as radio control and safety

circuit wiring.

• Plug all unused conduit holes.

Low Voltage Control Wiring Fig. 2

S S B S Y

SS B S B

STBENAB+ 24VACEXTNTLK

HO STNTLK

CALRUN

SETCLR

SCROLL

SCROLL

Figure 2

5.2www.geniecompany.com 08-12Counter Door Operator

5.3

External Wire DiagramSee Appendix B for detailed description of terminals.

1-BTNSTATION

KEYSWITCHSTATION

CARD READER

O/C PULLSWITCH

N/O

N/O

N/O

N/O

REMOVE JUMPER WHEN INSTALLING EXTERNAL INTERLOCK

MULT PLE 3 BUTTONSTAT ON NSTALLAT ONS

REQU RE THE STOP BUTTON TO BE W REDN SER ES

See Fig 5 pg 5 4

*

EXTINTLK

EXTINTLK

N-OREVERSE

N-OREVERSE

ODCSTB

ODCSTB

1-BTNGNDSTOPCLOSEOPEN

EXT RAD O CONNECTOR

SENSING EDGE SWITCH

(DO NOT CONNECT 2-WIRE MONITORED SENSING EDGE SWITCH TO THESE INPUTS)

THRU-BEAM PHOTOCELLS

2-WIRE MONITORED SENSING EDGE SWITCH

+

-

+-

PWR 20 40 VDC @ 315mA MAX CURRENT

RELAY

GNDNOM+ 24VDC

RADIO

SERIES II SAFE-T-BEAM® (STB)

(*CONNECT STB WIRES TO EITHER TERMINAL)

*

OPEN

CLOSE

STOP

REMOVEJUMPERIF STOPBUTTONIS USED

3-BUTTON STATION*

BLU

E

ORA

NG

E

YEL

LOW

Located inside Electrical Box

MONITORED EDGE INTERFACE MODULE(OPAKMEIGX.S)

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCX

1) For one 3 - button installation, make connections as shown in Fig. 3.

2) For single button accessory controls, make connections as shown in Fig. 4. 3) For a multiple 3 - button installations, make connections as shown in Fig. 5.NOTE: If an External STOP button is NOT being installed, a jumper wire must be installed between the “STOP” AND “GND” terminals as shown.NOTE: Long Distance Relay Kit wiring is not required for long distance control runs and should not be used

Wall Control

WARNING: • Wall Control(s) must be located so that the door is within sight of the user. • Attach the Warning placard adjacent to the Wall Control. Fig. 3A. • Attach the Caution Label adjacent to the Wall Control. Fig. 3B.

WARNING: If momentary contact control is to be used, an external monitored reversing device such as a photocell system or sensing edge switch must be used. See pages 5.6-5.7 for installation of entrapment protection devices.

NOTE:JUMPER BETWEEN STOP AND GND TERMINALS MUST BE REMOVED

3-BUTTON STATION

CONTROL SIGNAL TERMINAL STRIP

OPEN CLOSE STOP GND

3-BUTTON STATION

OPEN

CLOSE

STOP

OPEN

CLOSE

STOP

Figure 4

1-BTNSTATION

KEYSWITCHSTATION

CARD READER

OPEN/CLOSEPULL SWITCH

CONTROL SIGNAL TERMINAL STRIPODCSTBGNDSTOP 1-BTN

Figure 5

OPEN

CLOSE

STOP

3-BUTTON STATION

CONTROL SIGNAL TERMINAL STRIP

NOTE:JUMPER BETWEEN STOP AND GND TERMINALS MUST BE REMOVED

OPEN CLOSE STOP GND

Figure 3

11 35 0 1

Entrapment Warning Placard

Figure 3A

Figure 3B CAUTIONTo prevent the motor protector from tripping,

do not exceed 4 door operations per hour.

For light-duty use ONLYNot for residential use.

P/N 111980.0001

5.4www.geniecompany.com 08-12Counter Door Operator

5.5

Photocell Wiring

1) Monitored SERIES II (STB) photocells (P/N 38176R.S or OPAKPE.S) can be installed as shown in Fig. 6. Wiring to these photocells can be connected to either terminal (they are not polarity sensitive). ( Troubleshooting in Section 8).

NOTE: Installer must enable ODC STB in calibration mode. See page 6.7.

2) To Mount Photocells: (Kit includes detailed Instructions). • Determine location for mounting. They do not need to be directly adjacent to the door but must be somewhere along the wall where there will be an unobstructed line between them. Fig 7. • Screws provided for mounting on soft material (wood, drywall, etc.) • They must extend out away from the wall sufficiently that no door hardware breaks the plane of the photo-beam.

1) Nominal 24 Volt DC Commercial photocells with normally open contacts can be connected as shown in Fig. 8.

NOTE: Blue wire supplies 20 – 40VDC. Photocells used must be compatible with this voltage range.

NOTE: If no voltage is present at Blue wire, check fuse F-1 on Control board.

Series II Safe-T-Beam® Monitored Photocells

Commercial Non-Monitored Photocells

WARNING: Photocell systems provide entrapment protection when mounted near the doorway in such a way that the lower portion of an individual’s leg will break the photocell beam during normal walking conditions.

WARNING: Actuating operator using constant contact on the CLOSE button will override external reversing devices, including photocells.

SERIES II (STB)RESIDENTIAL SAFE-T-BEAMS®

CONTROL SIGNAL TERMINAL STRIP

ODCSTB

ODCSTBFigure 6

CONNECT WIRES TO EITHER TERMINAL. (NOT POLARITY SENSITIVE)

Figure 7

N-OREVERSE

N-OREVERSE

+

-

+-

THRU-BEAMPHOTOCELLS

CONTROL SIGNALTERMINAL STRIP

RECEIVER

TRANSMITTER

EXT RADIO CONNECTOR

PWR 20 40 VDC @ 315mA

MAX CURRENT

RELAY

GNDNOM+ 24VDC

RADIO

Blu

e

Ora

ng

e

Yelo

w

Figure 8

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

If connection is to be made through a take up reel cord: NON-MONITORED EDGE ONLY.

WARNING: Actuating the operator using constant contact on the CLOSE button will override external reversing devices, including sensing edges or reversing edges.

SENSING EDGE SWITCH

N-OREVERSE

N-OREVERSE

CONTROL SIGNA TERMINAL STRIP

Figure 9B

NOTE : Monitored 2-wiresensing or reversing edge can

Figure 9A

NOTE: Do not connect a 2-wire monitored semsing edge switch to these termiinals.

only be used in combination with a Timer-Close Module.

Figure 10

SENSING EDGE SWITCH

TIMER-CLOSE MODULE TERMINAL STRIP

GNDMONEDGE

VER VER

TERM NAL STR P

Figure 10 shows an example of a typical sensing edge installation. Left hand side is shown but right hand is a mirror image of this. 1A) If wiring from sensing edge switch to operator is coiled cord or 2 wire jacketed cord: • Install junction box 12” above the center of the door opening on same side as sensing switch. • Secure one end of cord to junction box using a cable clamp. 1B) • Install on same side as sensing edge switch and above door opening and slightly to the side. • Install junction box adjacent to take up reel and route the stationary cord from the reel to the box and secure with a cable clamp. 2) Secure other end of cord (straight, coiled or reel) to sensing edge switch enclosure using a cable clamp. 3) Connect wires of cord to sensing edge switch using wire nuts or other suitable wire connectors. 4) Run a straight 2 wire cord from the junction box to the operator electrical box. • Secure using cable clamp on each end. 5) Join wires in cord from operator to wires in cord from switch using wire nuts or other suitable wire connectors.

9A)

9B)

Non-Monitored sensing or reversing edge connects to terminal strip using N-O Safety inputs. See Fig. 9A .

9C)

Monitored sensing or reversing edge connects to Timer-Close Module terminals as shown in Fig. 9B .

Monitored sensing or reversing edge (no monitored Safety-T-Beam®) using the Monitored Edge Interface Module (OPAKMEIGX.S) connects to ODC STB terminals as

shown in Fig. 9C .

7) Operate the door to make certain cord is free to travel and does not become

snared during door opening or closing. • Check sensing edge switch for proper operation.

Sensing Edge Switch Installation

5.6

NOTE: Monitored sensing edge connects to main circuit board ODC STB terminals using optional OPAKMEIGX.S INTERFACE MODULE.

ODCSTB

ODCSTB

SENSING EDGE SWITCH

INTERFACE MODULE

MAIN CIRCUIT BOARDFigure 9C

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCX

Figure 11 shows an example of a typical locking bottom bar. Left hand side Interlock

Switch is shown. Right hand mount is mirror image.

Locking Bottom Bar / Interlock

NOTE: Interlock Switch is mandatory on doors equipped with an electronically controlled commercial operator.

OPEN CLOSE STOP GND 1 BTN N O SAFETY

N O SAFETY

ODCSTB

ODCSTB

EXTINTLK

EXTINTLK

CONTROL SIGNAL TERMINAL STRIP

* REMOVE JUMPER WHENINSTALLING EXTERNAL INTERLOCK

*

T-HANDLE TYPE LOCKING BOTTOM BAR

SLIDE TYPE LOCKING BOTTOM BAR

Figure 11

5.7www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

RADIO CONNECTOR

S YSS B S BS S B

TBNAB

+ 4ACXT

N LKOI T

N LK

CALRUN

SETCLR

CROLL

CROLL

To Add the External Radio 1) Plug the pigtail with the 3-terminal strip attached (provided) onto the plug connector marked “EXT RAD.” Fig. 12. 2) Make wiring connections to the terminal strip per the diagram below.

External Radio Installation

EXT RAD O CONNECTOR

PWR 20-40 VDC @ 315mA MAX CURRENT

RELAY

GNDNOM+ 24VDC

RADIO

Blu

e

Ora

ng

e

Yello

w

Figure 12

IMPORTANTSAFETY INSTRUCTIONS

WARNING - To reduce the risk of severe injury or death:

1) READ AND FOLLOW ALL INSTRUCTIONS.2) Never let children operate or play with door controls. Keep the

remote control (where provided) away from children. 3) Personnel should keep away from a door in motion and keep the moving door in sight until it is completely closed or opened. NO ONE SHOULD CROSS THE PATH OF A MOVING DOOR.4) Test the door’s safety features at least once a month. After adjusting either the force or the limit of travel, retest the door operator’s safety features.5) For products having a manual release, if possible, use the manual release only when the door is closed. Use caution when operating the release while the door is open. Weak or broken springs may cause the door to fall rapidly, causing severe injury or death.6) KEEP DOOR PROPERLY OPERATING AND BALANCED. See Door Manufacturer’s Owner’s Manual. An improperly operating or improperly balanced door could cause severe injury or death. Have only trained door systems technicians make repairs to cables, spring assemblies, other hardware and any wooden blocks or like items to which they may be attached.7) SAVE THESE INSTRUCTIONS.

5.8www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Section 6: Operator Setup Procedure

These operators include a full function control panel including a liquid crystal display (LCD), calibration keys and Open, Close and Stop keys for on board operator control. See Fig. 1. The open, close and stop keys function as a 3-button wall control. The Display will show current operator conditions and calibration information. Due to limited character space, some displays will be abbreviated. See Appendix C (pgs. 10.5-10.7) for full display descriptions.The operators also include a non-volatile memory. The unit will remember all calibration settings plus error code and run code logs, if power is removed from unit.

DANGER: After power is supplied to the operator, Do Not make contact with components inside the control panel except for the Keypad Keys. Fig. 1.

Control Operating Modes Operator control boards operate in two modes: Run Mode and Calibration Mode. The control board should normally operate in the Run Mode. The operator is calibrated in Calibration Mode.With the operator standing idle: PRESS CAL/RUN TO TOGGLE BETWEEN OPERATING MODES. • ”.RID ESOLC TES“ si edom noitarbilac ni yalpsid tsrif ehT

• The display in run mode will be one of the condition codes listed in Appendix C.

Control Panel

Apply Power to the Operator Now

Operation Keys, operate unit like a 3-button wall station.

Scroll Keys, used in Calibration Mode.

Set/Clear Key, used to reset and adjust calibration settings.

Figure 1

Calibration & Run Mode Toggle Key.

Display Backlighting Toggle Key.

LCD DISPLAY

WARNING: DO NOT calibrate operator or operate door unless doorway is in sight and free of obstructions. Keep people clear of opening while door is moving.

6.1www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SETCLEAR

Setting Close Direction

SET CLOSE DIR Figure 2

OPEN

CLOSE

STOP

CAL SET

HIT CLOSE KEY

OPEN

CLOSE

STOP

CAL SET

DID DOOR CLOSE?

Figure 3

Figure 4

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Figure 5

SCROLL KEY

CALRUN

CLOSE

SCROLL

SCROLL

SETCLEAR

CALRUN

YES NO

The direction of motor rotation depends on mounting position. This setting is

used to insure the door is closing and opening according to the input commands.

1) If operator is in RUN mode, press CAL/RUN to enter calibration mode. 2) Press SCROLL until “SET CLOSE DIR” is displayed. Figure 2.

SETCLEAR 2) Press SET/CLEAR to begin the calibration procedure and advance to

the next screen. Figure 3. 3 ) Briefly press the CLOSE key. (Pressing the Scroll key at this point will exit this control function.) • The display will read “ DID DOOR CLOSE? “ Figure 4 4) Press SCROLL key (up or down) to toggle between YES and NO. Figure 5. • If YES is selected, no change to operator calibration is made. If NO is selected — the POD will change the operator’s down direction. 5) Press the SET/CLEAR key. 6) Press CAL/RUN to return to run mode or, press SCROLL to shift to another function.

6.2

SCROLL

www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Setting Travel Limits

UP LIMIT SET

Figure 7

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

DOWN LIMIT SET

Figure 8

NOTE: The recommended setpoint for the DOWN Travel Limit is normally at approximately 2 inches off the floor. This final distance will be covered by the Limit Overrun Function to establish a more accurate seal.

CALRUN

CAL

CROL

SETCLEAR

OPEN

CROLL

CALRUN

CLOSE

Resetting Travel Limits

CALRUN

CAL

SCROLL

OPEN

SETCLEAR

CALRUN

CLOSE

SETCLEAR

UP and/or DOWN 1) If operator is in RUN mode, press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “UP LIMIT>CLR ” or “DOWN LIMIT>CLR ” Figure 7. 3) Jog the door using the OPEN or CLOSE key until you reach the desired height. 4) Press SET/CLEAR key to switch display to “UP LIMIT>SET “ or “DOWN LIMIT>SET .“ Figure 8. 5) Press a SCROLL key to shift to a new function and lock in the limit setting. 6) Press CAL/RUN to return to run mode.

UP and/or DOWN 1) If operator is in RUN mode, press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “UP LIMIT>SET ” or “DOWN LIMIT>SET.” Figure 8. 3) Press SET/CLEAR to switch display to ”UP LIMIT>CLR” or ”DOWN LIMIT>CLR” 4) Jog the door using the OPEN or CLOSE key until you reach the desired height. 5) Press SET/CLEAR to switch display to ”UP LIMIT>SET” or ”DOWN LIMIT>SET” 6) Press CAL/RUN to return to run mode.

6.3www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Setting Limit Overrun

LIMIT OVERRUN #

Figure 9

NOTE: The actual distance that the Overrun function covers is variable depending on model of operator and size of the door (nominally about 2 inches of travel).

WARNING: The Limit Overrun function will override external reversing devices, including photocells and sensing or reversing edges. Therefore, any externally connected devices will be disabled during that portion of door travel which is controlled by the Limit Overrun function.

CALRU

CROLL

SETCLEAR

SCROLL

CLO E

CALRUN

R

This Setting is a matter of trial and Error 1) If operator is in RUN mode, press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “LIMIT OVERRUN>#” where # is the increment of travel beyond the CLOSE Limit ranging from 0 to 9. Zero turns off the Overrun function and the door stops at the DOWN Limit. Nine is the maximum distance the door will travel passed the limit. This function is used to insure a good seal at the bottom of the door. Figure 9. 3) Press SET/CLEAR key to toggle between 0 and 9—one digit at a time. 4) Pick a value and operate the door. Adjust as necessary. 5) Press a SCROLL key to shift to a new function and lock in the setting. 6) Press CAL/RUN to return to run mode.

EN

CALRUN

S ROLL

R

SET

6.4www.geniecompany.com 08-12Counter Door Operator

“CLOSE MODE>C-STP” or “CLOSE MODE>C-REV.” 2) Press SCROLL until display reads “CLOSE MODE>MOM,”

2) Press SCROLL until display reads “OPEN MODE>MOM”

6.5

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Setting Open and Close Modes (Constant vs Momentary Contact)

OPEN MODE MOM

Figure 10

NOTE: Momentary contact (MOM) or Constant Reverse (C-REV) may not be used unless both the OPEN and CLOSE Limits have been set.In situations where an external reversing device is either not installed or not operating properly, Constant Contact (C-STP) MUST BE USED.

NOTE:

:

During

NOTE THIS OPERATOR MUST COMPLETE 2 FULL TRAVEL CYCLES BEFORE THE MODE CAN BE SET.

adjustment of a Travel Limit, the Open and Close Modes will automatically fail-safe to Constant Contact until the Limit has been set or reset. At that time the Open and Close Modes will revert to their previous setting.

CALRUN

OPEN CLOSE

SETCLEAR

SCROLL

CALRUN

CALRUN

OPEN CLOSE

SETCLEAR

SCROLL

CALRUN

WARNING: If momentary contact close control is to be used, a monitored external reversing device such as a photocell system or sensing edge switch must be used. See pages 5.5-5.6 for installation of entrapment protection devices.

OPEN 1) If operator is in RUN mode, press CAL/RUN to enter calibration mode.

“OPEN MODE>C-STP.”Figure 10.• MOM=momentary contact, meaning you press and release the

OPEN or CLOSE key and the door will continue to move until it reaches its travel limit. (See NOTE)

• C-STP=constant contact-stop, meaning if you release the key prior to the door reaching its travel limit, the door will stop. 3) Press SET/CLEAR key to toggle between “OPEN MODE>C-STP” or “OPEN MODE>MOM” on the display. 4) Press a SCROLL key to shift to a new function and lock in the setting. 5) Press CAL/RUN to return to run mode.

CLOSE 1) If operator is in RUN mode, press CAL/RUN to enter calibration mode.

Figure 10. MOM=momentary contact, meaning you press and release the

OPEN or CLOSE key and the door will continue to move until it reaches its travel limit. (See NOTE)

• C-STP=constant contact-stop, meaning if you release the key prior to the door reaching its travel limit, the door will stop.

• C-REV=constant contact-reverse, meaning if you release the key prior to the door reaching its travel limit, the door will reverse direction. (See NOTE)

3) Press SET/CLEAR key to toggle between “CLOSE MODE>C-STP” or “CLOSE MODE>C-REV” or ”CLOSE MODE>MOM” on the display. 4) Press a SCROLL key to shift to a new function and lock in the setting.

5) Press CAL/RUN to return to run mode.

SCROLL

SCROLL

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCX

OPEN

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Setting Mid-Stop Limit

MID-STOP SET

Figure 14

CALRUN

SCROL

SETCLEAR

RUN

CLOSE

CALRUN

CALRUN

AL

SETCLEAR

SCROLL

The operator includes a programmable Mid-Stop. This feature allows the operator to stop at a user selectable point when opening. It is used when operating very tall doors that only open to their full height occasionally. The Mid-Stop does not effect the operator when closing. To operate door to full open position from mid-stop, press open button again.

NOTE: Setting of the MID-STOP should only be performed AFTER TravelLimit and Max Run Timer settings have been made. 1) Press CAL/RUN to enter calibration mode. 2) Press the CLOSE to close the door to the down limit. 3) Press SCROLL until display reads “MID-STOP >CLR” Figure 14

NOTE: If the display reads MID-STOP > SET at this point, first clear MID-STOP as described below then repeat steps 1-3 and continue.

4) Press the OPEN to open the door to desired mid-stop height. 5) Press SET/CLEAR until the display reads ”MID-STOP > SET” 6) Press CAL/RUN to return to run mode.To CLEAR the Limit 1) Press CAL/RUN to enter calibration mode. 3) Press SCROLL until display reads “MID-STOP >SET” 5) Press SET/CLEAR until the display reads ”MID-STOP > CLR” 8) Press CAL/RUN to return to run mode.

6.6www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

MAX RUN TMR SET

Figure 15

Resetting the MRT (The Max Run Timer is set automatically once the unit is cycled between Limits. The Max Run Timer prevents the unit from running continuously in the event of a problem. The MRT’s are set to the time required to run from one limit to the other, plus 5 seconds (nominal). When the MRT is exceeded, the operator stops and will not respond to any command until it is reset by pressing one of the calibration keys or by cycling power to the unit.

CAUTION: The MID-STOP feature must be turned off in order to properly set the Max Run Timer.

CALRUN

ALUN

LL

SCROLL

SETCLEAR

O

CALRUN

ROLL

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

ODC STB ON

Figure 16

NOTE Installation of Series II Monitored Photocells DOES NOT make the GCX unit legal for residential use. The Genie® Company strictly prohibits any installation of a commercial unit in any residentially zoned construction.

Monitored Reversing Devices

WARNING: Photocell systems provide entrapment protection when mountednear the doorway in such a way that the lower portion of an individuals leg willbreak the photocell beam during normal walking through the doorway.

CALRUN

CAL

SETCLEAR

SCROLL

OP N

LOS

CALRUN

SCROLL

C O

C A

CARUN

CROLL

TO RESET 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL (up or down) until display reads ”MAX RUN TMR > SET.” Fig. 15. 3) Press SET/CLEAR until display reads ”MAX RUN TMR > CLR.” 4) Press CAL/RUN to return to RUN mode. 5) Cycle the door between limits. NOTE:

:

The Max Run Time must be reset each and every time the Travel Limits are adjusted.

ODC Safe-T-Beams® (OPTIONAL) 1) If operator is in RUN mode, press CAL/RUN to enter calibration

2) Press SCROLL (up or down) until display reads “ODC STB>ON” “ODC STB>OFF” Figure 16

3) Press SET/CLEAR key to toggle between ON and OFF.4) Press SCROLL (up or down) to shift to a new function and lock setting.5) Press CAL/RUN to return to run mode.

6.7

Current UL Approved Monitored Reversing Devices:

1) MillerEdge ME and MT series monitored edge sensors used in combination with Timer-Close Module P/N OPABTCX.S.

2) MillerEdge ME and MT series monitored edge sensors used in combination with OPAKMEIGX.S Interface Module. (Direct connect through STB inputs).

5) Monitored Photocells P/N OPAKPEN4GX.S.

3) Residential Safe-T-Beam® Monitored Photocells from The Genie® Company, model OSTB-BX (P/N 38176R.S).

4) Series II Safe-T-Beam® Monitored Photocells (P/N OPAKPE.S).

www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

Section 7: Special Operator Features (No user input)

OPEN

CLOSE

STOP

CYCLES 1

Figure A

OPEN

CLOSE

STOP

GDO V# #########

OPEN

CLOSE

STOP

CALRUN SCROLL

SETCLEAR

DISPLAY V# #######

Figure B

Operator Cycle Count

GDO and Display Firmware

CALRUN

R N

SCROLL

P

CALRUN

CALRUN

CN

SCROLL

CALRUN

1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “GDO V# > ######.” Figure B. This display will cycle between the version number of the current GDO firmware and the current Display Firmware. 3) Press CAL/RUN to return to run mode.

1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “CYCLES>1,2,3 etc. where the number is the number of open/close cycles the operator has performed. Figure A. 3) Press CAL/RUN to return to run mode.

7.1www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

GDO TYPE J-SHAFT

Figure 3

Operator Type Fig. 3

CALRUN

CALRUN

SCROLL

S

SETCLEAR

Operator circuit boards are available for use in jackshaft or trolley configurations. The same control board is used for either configuration, however the control board must be set for the appropriate GDO configuration. A board set for trolley mode will not work in a jackshaft operator and vice-versa. NOTE: The GDO type is factory set. The installer should not have to set this feature. However, if the GDO type is inadvertently changed, or if a board needs to be replaced in the field, follow these instructions to set GDO type. 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “GDO TYPE > .” This will display the current GDO type. 3) Press SET/CLEAR until display indicates correct GDO type

.)TFAHS-J ( 4) Press CAL/RUN to return to run mode.

7.2www.geniecompany.com 08-12Counter Door Operator

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

Section 8: Troubleshooting

These operators display their status on the integrated display. Each time the operator runs, stops, reverses or refuses to run, the display will indicate why the action did, or did not, take place.Once an error code has been generated, the operator will continue to display the error code while the operator is not running. This error code can be cleared by pressing the STOP button or STOP key on the keypad. The error code will automatically clear when the operator stops at the down limit. Error codes will continue to be stored in the operator’s Error Code Memory after they have been cleared from the display in the Run Mode.

Display Operation in Run Mode

To aid in troubleshooting problems, these operators include an error code memory that stores the last 10 error events. These codes are stored with or without power. The last error code detected is also displayed on the LCD until the stop button or key is pressed or the operator stops at the down limit.The error code memory stores the last 10 error codes in sequence. Once 10 codes are stored, the oldest code is erased to make room for the newest code. These codes are displayed in calibration mode. The display will flash the number of the error code and the 2-digit error code followed by a description of the error code. Fig. 1 & 2.

Error Codes

ERROR CODE 1 41

Figure 1

REV ONE BUTTON

Figure 2

3.18.1www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCX

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

OPEN

CLOSE

STOP

CALRUN SCROLL

SCROLL

SETCLEAR

The operators also include a run code memory that stores the last 10 run events. These codes are stored with or without power. Each time the operator runs or stops, it generates a code that it stores in this memory (Why the operator ran or stopped). Used together with the error code memory, it becomes a powerful troubleshooting aid. The run code memory stores the last 10 codes in sequence. Once 10 codes are stored, the oldest code is erased to make room for the newest code. These codes are displayed in calibration mode. The display will flash the number of the run code and the 2-digit run code followed by a description of the run code. Fig. 3 & 4.

Run Codes

RUN CODE 1 3C

Figure 3

HALT DOWN LIMIT

Figure 4

Error Codes (continued)

CALRUN

SCROLL

CR

SETCLEAR

CALRUN

To view the error code memory: 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “ERROR CODE 1 >”. • The display will begin flashing the error code number and 2-digit error code followed by its description. • Reminder: Error code number 1 is the latest code generated. 3) Press SET/CLEAR . The display will now read “ERROR CODE 2 > .” (This is the error code which was generated before error code 1.) 4) Repeat step 3 until all 10 error codes have been displayed or move on to step 5 when ready. 5) Press CAL/RUN to return to run mode.

NOTE: For all error codes see Appendix C, Sections 10.6 - 10.7.

8.2www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

TROUBLESHOOTING EXAMPLE USING RUN AND ERROR

CODE MEMORIES. Fig. 51. In Calibration Mode, display and write down each Run Code and Error Code stored in memory.2. List as shown in Fig. 5.3. Refer to Appendix C to interpret the codes.In this example, the operator was opened using the OPEN key on the keypad and stopped at the up limit. The OPEN wall button was then activated, causing the “6D” code to be generated since the operator could not open when it is already at the up limit. The CLOSE wall button was then activated, causing the operator to close. While closing, the Normally-Open (N-O) Safety Input was activated, causing the operator to stop and then reverse, stopping at the up limit.

ERRORCODES

RUNCODES

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

45

6D

00

00

00

00

00

00

00

00

00

00

00

00

00

3D

35

20

3D

14

REVERSED DUE TO ACTIVE N-O SAFETY INPUT

WOULD NOT OPEN —ALREADY AT UP LIMIT

STOPPED AT UP LIMIT

STOPPED DUE TO ACTIVE N-O SAFETY INPUT

CLOSED FROM CLOSE WALL BUTTON

STOPPED AT UP LIMIT

OPENED FROM OPEN KEY ACTIVATION

OPERATOR STORES “00” CODES IN UNUSED RUN AND ERROR CODE MEMORY LOCATIONS AT THE TIME OF MANUFACTURE. AS ERROR OR RUN CODES ARE RECORDED, THE “00” CODES ARE REPLACED WITH VALID CODES

NUMBER CODE NUMBERCODE

Figure 5

Run Codes (continued)

CALRUN

L

SCROLL

SETCLEAR

S OP

CALRUN

SETCLEAR

To view the run code memory: 1) Press CAL/RUN to enter calibration mode. 2) Press SCROLL until display reads “RUN CODE 1 > .” • The display will begin flashing the run code number and code followed by its description. • Remember: run code number 1 is the latest code generated. 3) Press SET/CLEAR . The display will now read “RUN CODE 2 > .” (This is the run code which was generated before run code 1.) 4) Repeat step 3 until all 10 run codes have been displayed or move on to step 5 when ready. 5) Press CAL/RUN to return to run mode.

NOTE: For all run codes see Appendix C, Section 10.5.

8.3www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

The operators include a self-diagnostic circuit board using troubleshooting LED indicators to signal the technician of a problem.

LED Indicators Fig. 6

TROUBLESHOOTING LEDs

S YS YS B S BS S B

S BE AB+ 24VACEXTNTLK

HO STNTLK

CALRUN

SETCLR

SCROLL

SCROLL

Figure 6

+ 24 VOLTSDC

STBENABLE

1. CHECK AC POWER SUPPLY

8.4

STB ENABLED STB DISABLED

POWER AVAILABLE

EXTINTLK

HOISTINTLK

1. INTLK SWITCH OPEN

INTLK ENABLED 1. INTLK SWITCH OPEN 2. CHECK POWER SUPPLY 3. CHECK MAIN POWER FUSE 4. CHECK SECONDARY FUSE (2A)

INTLK ENABLED 2. HOIST RELEASE NEEDS RESET 3. INTLK CONNECTOR NOT PLUGGED IN 4. INTERLOCK DEFECTIVE

LED ON OFF

2. CHECK FUSES

www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

Safe-T-Beam® Monitored Photocell Self-diagnostic Troubleshooting Chart

ON ON NORMAL OPERATION NONE REQUIRED

OFF OFF1. POWER HEAD NOT POWERED 2. WIRING FROM POWER HEAD BAD

1. CHECK BREAKERS, FUSES, PLUGS 2. CHECK WIRING FOR OBVIOUS SHORTS

OFF ON 1. WIRING TO SOURCE MISSING OR BAD 2. POWER HAS BEEN INTERRUPTED

1. CHECK WIRING 2. REMOVE POWER AND REAPPLY

2 BLINKS, PAUSE (REPEAT)

ON1. BEAM NOT ALIGNED 2. BEAM OBSTRUCTED 3. SENSOR DEFECTIVE

1. CHECK ALIGNMENT 2. CHECK FOR OBSTRUCTION 3. CALL CUSTOMER SERVICE

1. WIRE TO SENSOR MISSING OR BAD 2. SENSOR DEFECTIVE

1. CHECK WIRING 2. CALL CUSTOMER SERVICEOFF

ON1. SENSOR RECEIVING INTERFERENCE 1. ATTEMPT TO DETERMINE SOURCE OF

INTERFERENCE 2. CALL CUSTOMER SERVICE

ON 1. SOURCE NOT SENDING PULSES 2. SOURCE DEFECTIVE

1. CALL CUSTOMER SERVICE 2. CALL CUSTOMER SERVICE

SOURCE (RED LED) SENSOR (GREEN LED) INDICATED CONDITION REQUIRED ACTION

2 BLINKS, PAUSE (REPEAT)

3 BLINKS, PAUSE (REPEAT)

4 BLINKS, PAUSE (REPEAT)

WARNING: ACTUATING THE OPERATOR BY USING CONSTANT CONTACT ON THE CLOSE BUTTON WILL OVERRIDE EXTERNAL REVERSING DEVICES, INCLUDING PHOTOCELLS.

WARNING: THE GENIE® COMPANY RECOMMENDS THAT LINE VOLTAGE WIRING BE PERFORMED BY A QUALIFIED ELECTRICIAN. SEE SECTION 5 FOR ADDITIONAL WIRING INSTRUCTIONS.

8.5www.geniecompany.com 08-12Counter Door Operator

9.1

Section 9: Service and MaintenanceMaintenance Schedule

The following table provides a schedule of recommended Service and Maintenance items to be completed by a trained service representative.

CAUTION: Failure to perform the recommended Service & Maintenance may result in premature failure of the operator.

SERVICE ITEM SERVICE INTERVAL (FREQUENCY) EVERY 6 MO. EVERY 12 MO. EVERY 36 MO. MONTHLY OR OR OR 5,000 CYCLES 10,000 CYCLES 30,000 CYCLE MANUAL OPERATION OF DOOR CHECK DRIVE CHAINS AND LUBRICATE * PHOTOCELL/ SENSING EDGE OPERATION

CHECK FOR LOOSE OR MISSING HARDWARE CHECK LIMIT POSITION GEAR TRAIN WEAR

* If Installed.

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

GCL-GCXGCL-GCX

Section 10: Appendix AOperator Parts Breakdown (Exploded

View)

23

158

156

10.1

1

3

13

19 32

35

12

86

143142

91109

141

144 145

150

157

15916499

32

www.geniecompany.com 08-12Counter Door Operator

GCL-GCXGCL-GCX

Section 10: Appendix AOperator Parts Breakdown (Parts List)

10.2

ELECTRIC MOTOR13

12131923323586

9199

109141142

143144145

150

156

KIT, PCBTRANSFORMER

CHAIN GUARD

OUTPUT SHAFT

OUTPUT SPROCKETOPERATOR CHASSIS, COVER

157158159

164

TEM NO. DESCRIPTIONPART NUMBER

PARTS LIST

** CONTACT DEALER FOR PROPER PART BASED ON YOUR SPECIFIC MODEL.

108802.0001

112365.0001.S111421.0001.S108563.0001

110846.0001.S

108819.0001

107871.0001.S

111933.0001

108608.0001.S

108822.0001.S106062.0002.S

108807.0001.S

108609.0001108802.0001

108796.0001

LIMIT MODULE KIT

CAPACITORRELEASE LEVERSHAFT BEARINGCOVER POWERHEADOUTPUT HELICAL GEAR

WORM GEAR

MAIN CIRCUIT BOARD INSULATORDENTILOUTPUT PINION THRUST WASHERSET COLLARWASHER, NYLON

105961.0001077852.0000106124.0007

111629.0001108855.0001

MAIN FRAMEFRAME SIDE MOUNTING, RH

FRAME ASSY, MTR & GEAR

111679.0002

111950.0001

111932.0001FRAME SIDE MOUNTING, LH111932.0002

MAIN FRAME, BACK

www.geniecompany.com 08-12Counter Door Operator

GCL-GCXLINE GROUNDTROUBLESHOOTING LED'STRANSFORMER

SA ESA ES B S B N KO EN C OSE S O GND B N N O N O ODC ODC EX EXN K

N

CONTROL WIRE

AUX BOARD(OPTIONAL)

TERMINALS

STBENAB+ 24VACEXTNTLK

HO STNTLK

RADIO FUSE SECONDARY FUSEREPLACE RADIO FUSE WITH GDC-315mA ORS504-315mA ONLY

REPLACE SECONDARY FUSE WITH GDB-2A OR S500-2A ONLY

EXPANSIONPORT

RADIO CONNECTOR

CALRUN

SETCLR

SCROLL

SCROLL

HOISTINTERLOCK CONNECTOR

MOTORCONNECTOR

LINE INPUTTERMINALS

XFMRCONNECTOR

BRAKECONNECTOR

Control Board Area BreakdownSection 10: Appendix A

10.3www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

Section 10: Appendix BScrew Terminal Assignments

FUNCTION CONNECTION TYPE11-POSITION TERMINAL BLOCK INSIDE ELECTRIC BOX

OPEN Causes door to open if not at Up Limit. Causes a closing door to reverse.CLOSE Causes door to close if not at Down Limit. Normally-Open Dry Contact to GND.

Normally-Open Dry Contact to GND.

STOP Causes a moving door to stop. Prevents the operator from running. Normally-Closed Dry Contact to GND.GND Common ground connection for Open, Close, Stop & 1-Btn Inputs.

1-BTNCauses door to open if not at Up Limit or Mid-Stop Limit. Causes door to close if at Up Limit or Mid-Stop Limit. Causes door to stop if opening. Causes a closing door to reverse.

Normally-Open Dry Contact to GND.

ODC STB

Reverses a closing door if photocell beam is blocked. NOTE: STB's must be enabled in Calibration Mode.

ODC Series II Safe-T-Beams® ONLY to these inputs.

ODC STB

Reverses a closing door if photocell beam is blocked.NOTE: STB's must be enabled in Calibration Mode.

N-O REVERSE Causes a closing door to reverse. NOTE: Will not open a stopped door. Normally-Open 2-Wire Non-Monitored Edge Sensor.

N-O REVERSE Causes a closing door to reverse. NOTE: Will not open a stopped door. Normally-Open 2-Wire Non-Monitored Edge Sensor.

EXT INTLKCauses a moving door to stop. Prevents the operator from running when contact is open. Operates even if microcontroller is non-functional.

Normally-Closed dry contacts. (board will energize these contacts at nominal +24VDC).

EXT INTLKCauses a moving door to stop. Prevents the operator from running when contact is open. Operates even if microcontroller is non-functional.

Normally-Closed dry contacts. (board will energize these contacts at nominal +24VDC).

2-POSITION TERMINAL L1 / L1 120VAC: Connect to Line (Hot) Power to operator.BLOCK (INSIDE ELECTRIC BOX) N / L2 120VAC: Connect to Neutral Power to operator.

PWR Power for radio & other accessories. +20 to +40VDC, fused at 315mA (F1). Connect to radio or other accessory's power input.

RAD

GND

Causes door to open if not at Up Limit or Mid-Stop Limit. Causes door to close if at Up Limit or Mid-Stop Limit. Causes a closing door to reverse.Common ground connection for PWR and RAD terminals. Connect to radio or other accessory's ground input.

EXPANSION PORT Accessory Module Ribbon Cable.PLUG CONNECTIONSINSIDE ELECTRIC BOX TRANSFORMER Connects main transformer to control board. Transformer Plug.

BRAKE Connects brake solenoid to control board. Brake Solenoid Plug.Motor Plug.

HOIST INTLK Causes moving door to stop. Prevents the operator from running. Operates even if microcontroller is non-functional.

Limit Sensor Plug.

Hoist Interlock Plug or Jumper.

INPUT

(Radio Input Control)

(not polarity sensitive)

ODC Series II Safe-T-Beams® ONLY to these inputs. (not polarity sensitive)

(not polarity sensitive)

(not polarity sensitive)

LIMIT SENSOR Causes door to stop at top and bottom of normal travel.

MOTOR Connects motor and capacitor to control board.

Connects accessory modules to operator.

RADIO ANDACCESSORIES

PIGTAIL

10.4www.geniecompany.com 08-12Counter Door Operator

GCL-GCX

Section 10: Appendix CRun Code Displays

Condition Code DISPLAY Condition Code Description

0C IDLE > DOWN LIMIT STANDING BY AT DOWN LIMIT (NOTE: THIS MESSAGE IS DISPLAYED IF BOTH LIMITS ARE ACTIVE) 0D IDLE > UP LIMIT STANDING BY AT UP LIMIT 0E IDLE > MID STOP STANDING BY AT MID-STOP LIMIT 0F IDLE > NO LIMIT STANDING BY BETWEEN LIMITS 10 OPENING > OPEN BTN OPENING FROM OPEN BUTTON 11 OPENING > ONE BTN OPENING FROM 1 BUTTON 12 OPENING > RADIO OPENING FROM RADIO 13 OPENING > AUX OPEN OPENING FROM AUXILIARY OPEN INPUT 14 OPENING > OPEN KEY OPENING FROM KEYPAD OPEN KEY 20 CLOSING > CLOSE PB CLOSING FROM CLOSE BUTTON 21 CLOSING > ONE BTN CLOSING FROM 1 BUTTON 22 CLOSING > RADIO CLOSING FROM RADIO 24 CLOSING > CLOSE KP CLOSING FROM KEYPAD CLOSE KEY 2A CLOSING > TCM CLS CLOSING FROM TIMER CLOSE MODULE 2B CLOSING > FDM CLS CLOSING FROM FORE DOOR MODULE 30 HALT > WALL BUTTON GDO STOPPED BECAUSE STOP OR OPEN BUTTON WAS ACTIVATED, POSSIBLY STARTING A REVERSAL 31 HALT > ONE BUTTON GDO STOPPED BECAUSE 1 BUTTON WAS ACTIVATED, POSSIBLY STARTING A REVERSAL 32 HALT > RADIO GDO STOPPED BECAUSE RADIO INPUT WAS ACTIVATED, STARTING A REVERSAL 33 HALT > AUX. OPEN GDO STOPPED BECAUSE AUXILIARY OPEN INPUT WAS ACTIVATED, STARTING A REVERSAL 34 HALT > KEYPAD KEY GDO STOPPED BECAUSE KEYPAD STOP OR OPEN KEY WAS ACTIVATED, POSSIBLY STARTING A REVERSAL 35 HALT > N-O SAFETY GDO STOPPED BECAUSE N-O REVERSING INPUT WAS ACTIVATED, STARTING A REVERSAL 36 HALT > ODC STB GDO STOPPED BECAUSE ODC STB WAS BLOCKED, STARTING A REVERSAL 37 HALT > N-C SAFETY GDO STOPPED BECAUSE N-C REVERSING INPUT WAS ACTIVATED, STARTING A REVERSAL 38 HALT > MON. EDGE GDO STOPPED BECAUSE MONITORED EDGE SENSOR INPUT WAS ACTIVATED, STARTING A REVERSAL 39 HALT > DOOR FORCE GDO STOPPED BECAUSE THE FORCE REQUIRED TO OPERATE THE DOOR WAS TOO HIGH, POSSIBLY STARTING A REVERSAL 3A HALT > LOSS OF C/C GDO STOPPED BECAUSE CONSTANT CONTACT ON CONTROL REMOVED BEFORE REACHING A LIMIT, POSSIBLY STARTING A REVERSAL 3B HALT > SHUTDOWN GDO STOPPED BECAUSE THE GDO DETECTED A FAULT SUCH AS AN OPEN INTERLOCK, OVERHEATED MOTOR, ETC. 3C HALT > DOWN LIMIT GDO STOPPED BECAUSE IT REACHED THE DOWN LIMIT 3D HALT > UP LIMIT GDO STOPPED BECAUSE IT REACHED THE UP LIMIT 3E HALT > MID STOP GDO STOPPED BECAUSE IT REACHED THE MID-STOP LIMIT 3F HALT > MODULE FAIL GDO STOPPED BECAUSE AN EXPANSION MODULE WAS NOT WORKING PROPERLY 40 REV > OPEN BUTTON GDO REVERSED BECAUSE THE OPEN BUTTON WAS ACTIVATED 41 REV > ONE BUTTON GDO REVERSED BECAUSE THE 1 BUTTON WAS ACTIVATED 42 REV > RADIO GDO REVERSED BECAUSE THE RADIO INPUT WAS ACTIVATED 43 REV > AUX OPEN GDO REVERSED BECAUSE THE AUXILIARY OPEN INPUT WAS ACTIVATED 44 REV > OPEN KEY GDO REVERSED BECAUSE THE KEYPAD OPEN KEY WAS ACTIVATED 45 REV > N-O SAFETY GDO REVERSED BECAUSE THE N-O REVERSING INPUT WAS ACTIVATED

10.5www.geniecompany.com 08-12Counter Door Operator

www .geniecompany.com 08-12 10.6Counter Door OperatorGCL-GCX

Condition Code DISPLAY Condition Code Description 46 REV > ODC STB GDO REVERSED BECAUSE THE ODC STB WAS BLOCKED 47 REV > N-C SAFETY GDO REVERSED BECAUSE THE N-C REVERSING INPUT WAS ACTIVATED 48 REV > MON. EDGE GDO REVERSED BECAUSE THE MONITORED EDGE SENSOR WAS ACTIVATED 49 REV > DOOR FORCE GDO REVERSED BECAUSE THE FORCE REQUIRED TO CLOSE THE DOOR WAS TOO HIGH 4A REV > LOSS OF C/C GDO REVERSED BECAUSE CONSTANT CONTACT ON THE CONTROL WAS REMOVED BEFORE REACHING THE DOWN LIMIT 4B REV > MAX RUN TMR GDO REVERSED BECAUSE THE CLUTCH SLIPPED OR SOME OTHER FAULT OCCURRED THAT ALLOWED THE GDO TO RUN TOO LONG 4F REV > EXP MOD FAIL GDO REVERSED BECAUSE AN EXPANSION MODULE WAS NOT WORKING PROPERLY 50 STOP > HOT MOTOR GDO STOPPED BECAUSE THE MOTOR WAS OVERHEATED 51 STOP > OPEN MRT GDO STOPPED BECAUSE THE CLUTCH SLIPPED OR SOME OTHER FAULT OCCURRED THAT ALLOWED THE GDO TO RUN OPEN TOO LONG 52 STOP > CLOSE MRT GDO STOPPED BECAUSE THE CLUTCH SLIPPED OR SOME OTHER FAULT OCCURRED THAT ALLOWED THE GDO TO RUN DOWN TOO LONG 53 STOP > BRAKE FAULT GDO STOPPED BECAUSE OF BRAKE ERRONEOUSLY ENGAGED 57 STOP > OPEN INTLK GDO STOPPED BECAUSE THE HOIST INTERLOCK OR EXTERNAL INTERLOCK IS OPEN 58 STOP > WRONG GDO GDO STOPPED BECAUSE THE BOARD IS SET FOR JACKSHAFT MODE, BUT INSTALLED IN A TROLLEY OPERATOR 59 STOP > DOOR FORCE GDO STOPPED BECAUSE THE FORCE REQUIRED TO OPEN THE DOOR WAS TOO HIGH 5A STOP > WRONG LIMIT GDO STOPPED BECAUSE THE UP LIMIT ACTIVATED WHEN CLOSING OR THE DOWN LIMIT ACTIVATED WHEN OPENING 5B STOP > WRONG DIR GDO STOPPED BECAUSE THE DOOR MOVED IN THE WRONG DIRECTION 5C STALL > DOWN LIMIT GDO STOPPED BECAUSE IT COULDN'T LEAVE THE DOWN LIMIT DUE TO A SLIPPING CLUTCH OR OTHER PROBLEM 5D STALL > UP LIMIT GDO STOPPED BECAUSE IT COULDN'T LEAVE THE UP LIMIT DUE TO A SLIPPING CLUTCH OR OTHER PROBLEM 5E STALL > MID-STOP GDO STOPPED BECAUSE IT COULDN’T LEAVE THE MID-STOP LIMIT DUE TO A SLIPPING CLUTCH OR OTHER PROBLEM 5F STALL > NO LIMIY GDO STOPPED BECAUSE TRAVEL LIMITS HAVE NOT BEEN SET 60 CHECK STOP BTN GDO WON'T RUN BECAUSE THE STOP BUTTON IS ACTIVE 61 TCM DISABLED TIMER CLOSE WON'T WORK BECAUSE NO SAFETIES ARE ENABLED 62 NO RADIO >> C/C RADIO INPUT WON'T WORK WITH OPEN OR CLOSE FUNCTION IN CONSTANT CONTACT MODE 63 CHECK AUX OPEN GDO WON'T CLOSE BECAUSE AUXILIARY OPEN INPUT IS ACTIVE 64 CHECK STOP KEY GDO WON'T RUN BECAUSE THE KEYPAD STOP KEY IS ACTIVE 65 CHECK N-O SAFETY GDO WON'T CLOSE BECAUSE THE N-O REVERSING IS ACTIVE 66 CHECK ODC STB GDO WON'T CLOSE BECAUSE THE ODC STB IS BLOCKED 67 CHECK N-C SAFETY GDO WON'T CLOSE BECAUSE THE N-C REVERSING INPUT IS ACTIVE 68 CHECK MON. EDGE GDO WON'T CLOSE BECAUSE THE MONITORED EDGE SENSOR IS ACTIVE 69 OVERHEATED MOTOR GDO WON'T RUN BECAUSE THE MOTOR IS OVERHEATED 6A POWER WIRING ERROR GDO WON’T RUN BECAUSE POWER SUPPLY WIRED INCORRECTLY 6B FIRE DOOR SHTDN GDO WON’T RUN BECAUSE OF LOSS OF POWER 6C NO RUN > DOWN LIM GDO WON'T CLOSE BECAUSE ITS ALREADY AT THE DOWN LIMIT 6D NO RUN > UP LIMIT GDO WON'T OPEN BECAUSE ITS ALREADY AT THE UP LIMIT 6E NO RUN > MID STOP GDO WON'T RUN BECAUSE ITS AT OR ABOVE THE MID-STOP LIMIT & CAN'T RUN UP & A REVERSING INPUT IS PREVENTING IT FROM CLOSING 6F EXP MODULE FAIL GDO WON'T RUN BECAUSE AN EXPANSION MODULE FAILURE IS PREVENTING IT

Error Code DisplaysSection 10: Appendix C

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

Error Codes Displays (continued)Section 10: Appendix C

Condition Code DISPLAY Condition Code Description

70 BOARD FAILURE 70 CONTROL BOARD FAILURE 70, CONTACT FACTORY TECHNICAL SERVICE DEPT. 71 BOARD FAILURE 71 CONTROL BOARD FAILURE 71, CONTACT FACTORY TECHNICAL SERVICE DEPT. 74 BOARD FAILURE 74 CONTROL BOARD FAILURE 74, CONTACT FACTORY TECHNICAL SERVICE DEPT. 75 BOARD FAILURE 75 CONTROL BOARD FAILURE 75, CONTACT FACTORY TECHNICAL SERVICE DEPT. 76 BOARD FAILURE 76 CONTROL BOARD FAILURE 76, CONTACT FACTORY TECHNICAL SERVICE DEPT. 77 BOARD FAILURE 77 CONTROL BOARD FAILURE 77, CONTACT FACTORY TECHNICAL SERVICE DEPT. 80 BOARD FAILURE 80 CONTROL BOARD FAILURE 80, CONTACT FACTORY TECHNICAL SERVICE DEPT. 81 BOARD FAILURE 81 CONTROL BOARD FAILURE 81, CONTACT FACTORY TECHNICAL SERVICE DEPT. 82 BOARD FAILURE 82 CONTROL BOARD FAILURE 82, CONTACT FACTORY TECHNICAL SERVICE DEPT. 83 BOARD FAILURE 83 CONTROL BOARD FAILURE 83, CONTACT FACTORY TECHNICAL SERVICE DEPT. 84 BOARD FAILURE 84 CONTROL BOARD FAILURE 84, CONTACT FACTORY TECHNICAL SERVICE DEPT. 85 EXP PORT PROBLEM EXPANSION PORT IS SHORT CIRCUITED, TRY DISCONNECTING EXPANSION MODULES OR CONTACT FACTORY TECHNICAL SERVICE DEPT. 86 BOARD FAILURE 86 CONTROL BOARD FAILURE 86, DISCONNECT EXPANSION MODULES. IF NO CHANGE, CONTACT FACTORY TECHNICAL SERVICE DEPT. 87 IEM FAILURE RESERVED--NOT CURRENTLY USED 88 TCM FAILURE TIMER CLOSE MODULE (TCM) HAS FAILED 89 FDM FAILURE FIRE DOOR MODULE (FDM) HAS FAILED 8A AOM FAILURE AUXILIARY OUTPUT MODULE (AOM) HAS FAILED 8B SPARE MOD FAILURE RESERVED--NOT CURRENTLY USED 8C LOW SYSTEM VOLTS POWER SUPPLY LINE VOLTAGE LOW 8D HI SYSTEM VOLTS POWER SUPPLY LINE VOLTAGE HIGH 8E REV INTERRUPTED GDO LOST POWER OR ENCOUNTERED ANOTHER PROBLEM DURING THE REVERSAL PROCESS, REVERSAL IS COMPLETING NOW 8F LIMIT MOD. FAIL GDO WON'T RUN, LIMIT MODULE HAS FAILED 90 DIAGNOSTIC MODE GDO IS IN DIAGNOSTIC MODE, NORMAL FUNCTIONS ARE NOT ALLOWED A0 OPEN BTN BAD > PU OPEN & CLOSE BUTTONS WON'T WORK, THE OPEN BUTTON WAS ACTIVE WHEN THE GDO WAS POWERED-UP A1 CLOSE BTN BAD > PU OPEN & CLOSE BUTTONS WON'T WORK, THE CLOSE BUTTON WAS ACTIVE WHEN THE GDO WAS POWERED-UP A2 ONE BTN BAD > PU 1 BUTTON WON'T WORK, THE 1 BUTTON WAS ACTIVE WHEN THE GDO WAS POWERED-UP A3 RADIO BAD > PWR UP RADIO INPUT WON'T WORK, THE RADIO INPUT WAS ACTIVE WHEN THE GDO WAS POWERED-UP A4 AUX OPEN BAD > PU AUXILIARY OPEN INPUT WON'T WORK, THE AUXILIARY OPEN INPUT WAS ACTIVE WHEN THE GDO WAS POWERED-UP A5 OPEN KEY BAD > PU KEYPAD OPEN & CLOSE KEYS WON'T WORK, THE OPEN KEY WAS ACTIVE WHEN THE GDO WAS POWERED-UP A6 CLOSE KEY BAD > PU KEYPAD OPEN & CLOSE KEYS WON'T WORK, THE CLOSE KEY WAS ACTIVE WHEN THE GDO WAS POWERED-UP A7 MULT KEYS BAD > PU 1 OR MORE KEYPAD CALIBRATION KEYS WON'T WORK, 1 OR MORE WERE ACTIVE WHEN THE GDO WAS POWERED-UP AA TCM BAD > POWER UP RESERVED--NOT CURRENTLY USED AB FDM BAD > POWER UP RESERVED--NOT CURRENTLY USED B0 OPENING > XMTR # OPENING FROM TRANSMITTER # __ B1 CLOSING > XMTR # CLOSING FROM TRANSMITTER # __ B2 HALT > XMTR # HALT FROM TRANSMITTER # __ B3 NO XMTR > CC NO CONTROL FROM TRANSMITTER, CONSTANT CONTACT EMPLOYED AT LOCAL CONTROL

10.7

GCL-GCXGCL-GCX 11.1

The G

enie

Comp

any (

"Sell

er") w

arran

ts to

the or

igina

l purc

haser

of th

is co

mmerc

ial do

or op

erator

(“P

roduc

t”) su

bject

to all

of th

e term

s and

cond

itions

hereo

f tha

t the P

roduc

t and

all c

ompo

nents

the

reof w

ill be

free

from

defec

ts in

mater

ials a

nd w

orkma

nship

unde

r norm

al us

e for

the fo

llowi

ng

perio

d(s) m

easu

red fr

om th

e date

of in

stalla

tion

Tw

o (2)

years

or W

hen t

he O

perat

or ex

ceed

s 200

00 cy

cles o

f ope

ration

as m

easu

red by

the

integ

rated

cycle

coun

ter co

ntaine

d in t

he O

perat

or.

Selle

r’s ob

ligati

on un

der t

his w

arran

ty is

spec

ifica

lly lim

ited t

o rep

airing

or re

placin

g at

its op

tion

any

part

which

is de

termi

ned b

y Sell

er to

be de

fectiv

e duri

ng th

e app

licab

le wa

rranty

perio

d.

Any l

abor

charg

es are

exclu

ded a

nd w

ill be

the r

espon

sibilit

y of t

he pu

rchase

r.

This

warra

nty is

mad

e to t

he or

igina

l purc

haser

of th

e Prod

uct o

nly an

d is n

ot tra

nsfer

able

or ass

ignab

le.

This

warra

nty do

es no

t app

ly to

any u

nauth

orize

d alte

ration

or re

pair

of the

Prod

uct o

r to a

ny Pr

oduc

t or

comp

onen

t whic

h has

been

dama

ged o

r dete

riorat

ed du

e to m

isuse

negle

ct ac

ciden

t fail

ure to

prov

ide

nece

ssary

maint

enan

ce no

rmal

wear

and t

ear o

r acts

of G

od or

any o

ther c

ause

beyo

nd th

e rea

sona

ble

contr

ol of

Selle

r.

THIS

WAR

RANT

Y IS

EXC

LUSI

VE A

ND IN

LIE

U OF

ANY

OTH

ER W

ARRA

NTIE

S EI

THER

EX

PRES

SED

OR IM

PLIE

D IN

CLUD

ING

BUT

NOT

LIM

ITED

TO

ANY

IMPL

IED

WAR

RANT

Y OF

M

ERCH

ANTA

BILI

TY O

R FI

TNES

S FOR

A PA

RTIC

ULAR

PURP

OSE.

IN N

O EV

ENT S

HALL

SELL

ER B

E RE

SPON

SIBL

E FO

R O

R LI

ABLE

TO A

NYON

E FO

R SP

ECIA

L

INDI

RECT

COL

LATE

RAL

PUNI

TIVE

INCI

DENT

AL O

R CO

NSEQ

UENT

IAL D

AMAG

ES ev

en if

Se

ller h

as be

en ad

vised

of th

e pos

sibilit

y of s

uch d

amag

es. S

uch e

xclud

ed da

mage

s inc

lude

but a

re no

t limi

ted to

loss

of go

odwi

ll los

s of p

rofits

loss

of us

e co

st of

any s

ubsti

tute p

roduc

t inte

rrupti

on of

bu

siness

or ot

her s

imila

r ind

irect

finan

cial lo

ss.Cl

aims u

nder

this w

arran

ty mu

st be

mad

e prom

ptly a

fter d

iscov

ery w

ithin

the ap

plica

ble w

arran

ty pe

riod

and i

n writ

ing to

the S

eller

or to

the au

thoriz

ed di

stribu

tor or

insta

ller w

hose

name

and a

ddres

s app

ear b

elow.

The p

urcha

ser m

ust a

llow

Selle

r a re

asona

ble op

portu

nity t

o ins

pect

any P

roduc

t clai

med t

o be d

efecti

ve

prior

to rem

oval

or an

y alte

ration

of its

cond

ition.

Proo

f of t

he pu

rchase

and/o

r ins

tallat

ion da

te an

d ide

ntific

ation

as th

e orig

inal p

urcha

ser m

ay be

requ

ired.

ORIG

INAL

PURC

HASE

R

INST

ALLA

TION

ADD

RESS

SELL

ER:

SELL

ERS A

DDRE

SS:

FACT

ORY

ORDE

R #:

DATE

OF I

NSTA

LLAT

ION:

SIGN

ATUR

E OF

SELL

ER:

Com

mer

cial

Ope

rato

r L

imite

d W

arra

nty

www.geniecompany.com 08-12Counter Door Operator

THIS PAGE LEFT BLANK

www.geniecompany.com 08-12Counter Door OperatorGCL-GCX

1 Door DriveMt. Hope, Ohio 44660