7/21/2019 GEA Heat Exchangers
1/76
GEA Chillers and Heat Pumps with H Factor
Energy-efficient and compact models
for inside and outside installation
Product Brochure
~ db^ e~ b~
X-
-
7/21/2019 GEA Heat Exchangers
2/76
x2] PR-2014-0100-GB Subject to modifications K0-06/2014
Economy and ecology in harmony
The signs of the times are clear
Investors, systems builders, planners and architects no longer ask whether, but how
they can improve the sustainability trend of their plant and building engineering.
Buildings are unique objects. Position, size, construction quality and increasingly the build-
ing technology determine values and yields. The energetic state is considerably gaining
in significance, because buildings are responsible for about 40 percent of world energy
consumption and contribute to 21 percent of the world-wide greenhouse gas emissions.
The proportion of the energy costs in the "second rent" for users and residents is constantly
increasing.
You come across the air condi-
tioning technology with H
Factor in all walks of life.
Where heating, cooling, cleaning, filtering, humidification and dehumidification of air is
required, GEA makes its contribution to progress. Customized climate-control and air treat-ment, with the maximum-possible reduction of energy consumption over the entire life
cycle of the facilities: this all pays out handsomely in euros and cents, in comfort, and in
work productivity. In highly sensitive areas, such as clinical and cleanroom applications,
our solutions reliably satisfy all international standards and achieve high rankings in the
demanding classification of the Eurovent Compliance Committee for Air Handling Units.
They furthermore set new standards for sustainability and perfect system integration in
modern sport arenas, factory buildings, airport facilities, and swimming pools, as well as
in offices, museums and hotels. Summarized with the concept "HX actor", this quality jus-
tifies our technological advantage. The HX Factor is more than just technology. It is an atti-
tude and creates value with a future: quality of life for residents and users. Protection of
energy resources and our climate. Security for investors and planners.
Good climate with H Factor:
Reliable. Efficient. Sustainable.
The HX-Factor is our performance promise. It
stands for unique competence in heat exchang-
ers (HX = HEAT EXCHANGE) and character-
izes all its products and services. The many
advantages associated with the HX-Factor offer
you maximum benefit over the entire lifetime
of the systems.
X-
X-
-F
-
-
7/21/2019 GEA Heat Exchangers
3/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x3]
Technical quality
Whoever treats air must master it
The fact that our air treatment is neither seen nor heard, although one is agreeably aware
of it, and that in the meantime it avoids energy and wasteful costs, is due to our precision
air-treatment work in both hardware and software.
Can a building with large glazed areas be heated during spring and autumn on its north
side and cooled on its south side, with only one system and without having to switch on
the central heating? Does a plant in the pharmaceutical or electronic industry, for instance,
which heats, cools, humidifies and dehumidifies the air, also offer protection from dirt and
bacteria? Can investors and building owners calculate the life cycle costs of a central plant
air handling unit, determine the effect of energy-saving equipment on the operating cost
for this purpose, and thus select the optimal efficiency class right in the configuration stage
of the plant?
GEA has found answers to this and many other questions concerning air treatment and cli-mate control and has implemented them in solutions which reflect its experience gained
in many and various successful applications. The core proposal consists of a broad spec-
trum of central and decentral air treatment plants, separators and filter plants up to com-
plete clean room systems. The function, control, and design of such facilities can be
precisely customized according to the desired task, adapted to the design characteristics
and infrastructure of specific buildings, and designed according to the calculation of oper-
ating costs as well as the highest standards of energy efficiency and climate protection. Cut-
ting-edge control technology from our own development permits individual control in
single rooms as well as central handling within a building management system.
Control units with access through interfaces to all leading systems of building automation,
provide for the trouble-free integration of all equipment in the building management sys-
tem. The fact that planners and users can implement their own wishes at the design stage
of the plant itself is proof of the precision work involved in the air-conditioning equip-
ment.
You can see that the HX Factor has many facets. Generations of cross-functional experience
play a role, as do our customized engineering, worldwide proximity to our customers, and
our well-proven innovative abilities. Every individual GEA employee contributes to quality
by adding positive characteristics to the HX Factor.
By enthusiasm for a technology that shapes the lives of people in progressive ways.
By special diligence and precision. By commitment at all levels. This quality transfers one-
to-one to our products and services. Thus you can personally experience the HX Factor. It
assures you many diverse product benefits. It rewards your trust with reliable, efficient
and sustainable solutions. Therefore count on the HX Factor!
GEA stands for:
Customized air quality and a
healthy, comfortable indoor cli-
mate with extremely quiet
operation
Maximum energy efficiency
and reduction in CO2 emis-
sions
Precise control and regulation,
centrally and decentrally
High adaptability to the most
diverse tasks and environments
Simple system integration
Durability and high availability
at low maintenance cost
-
-
-
-
-
7/21/2019 GEA Heat Exchangers
4/76
x4] PR-2014-0100-GB Subject to modifications K0-06/2014
GEA chiller
Variety for your comfort
Irrespective of whether your requirement is for indoor or outdoor
installation, air or water-cooled, there is a vast variety of equipment
with or without heat pump and an extensive spectrum of accessories
available to you within the capacity range of 4.9 - 2.749 KW.
Last but not least, GEA chillers are characterized by their efficiency and
high energy conservation potential, additionally underlined by the use
of high-quality components and environmentally-friendly refrigerants
R-410A and R-134a, which are used in most GEA chillers depending
upon the model. With GEA chillers and heat pumps with reversible cir-
cuit, you can provide energy not only for cooling, but also for heating.
And if you require a compressor/condensing unit or want a system
with external condenser, our program includes the correct unit for you
here as well. The choice is yours.
Legend
Explanation of the pictograms used in this document
Pictogram Description Pictogram Description
Screw compressor Plate Heat Exchanger
Scrollcompressor Shell and tube heat exchanger
Inverter compressor Master/slave operation is possible
Refrigerant R-134a Direct evaporator
Refrigerant R -410A BMS integration is possible
R -407C refrigerant Plate Heat Exchanger
Unit with free cooling Heating
Unit as low-noise model Cooling
Unit as high-performance model Outdoor installation
Unit as high-temperature model Indoor installation
Unit as low-noise model with extended operatinglimits
Eurovent certified
-
7/21/2019 GEA Heat Exchangers
5/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x5]
Contents
Our Products
Economy and ecology in harmony - HX Factor 2
Explanation of the pictograms used in this document 4
GEA chiller and heat pumps for outdoor installation 6
GEA chiller and heat pump for indoor mounting 8
Chiller outdoor installation air-cooled 10
GSAC 0011 ... 0061 FD5 / FD1 4.9 kW to 15.4 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
GAC(N,P) 016 064 FD1 20 kW to 75 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
GLAC 2015 2081 CD1/2 / .SL (.HE) 39 kW to 227 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
GLAC 4061 4121 CD2 / .SL (.HE) 159 kW to 352 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
GLAC 4131 ... 8321 CD2 / .SL (.HE) 354 kW to 885 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GLAC 0751 1301 BA2 / .SL 145 kW to 266 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
GLAC 1532 2632 BA2 / .SL 277 kW to 516 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
GLAC 1542 2642 BA2 / .SL 277 kW to 516 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling . . . . . . . . . . . . . . . . . . . . . .29
GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling . . . . . . . . . . . . . . . . . . . . . 32
GLFC 2150 ... 2482 DA2 / .SL 286 kW to 1212 kW with free cooling . . . . . . . . . . . . . . . . . . . . 35
Compressor/condensing unit outdoor installation air-cooled 38
GLCU 2015 ... 4060 BC1/2 / .SL 40 kW to 171 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Chiller indoor installation air-cooled 39
GSDC 0011 ... 0041 FD5 / FD1 4.9 kW to 15.4 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
GLDC 0152 1204 BD2 37 kW to 312 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
GLRC 2015 4160 CD2 41 kW to 442 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
GLWC 0152 1204 BD2 43 kW to 371 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
GLWC 0401 1902 BA2 87 kW to 447 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
GLWC 1130 4960 CA2 / .HE 306 kW to 2416 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Heat pump outdoor installation air-cooled 50
GSAH 0011 ...0061 FD5 / FD1 5.7 kW to 16.8 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
GAH(N,P) 016 064 FD1 20 kW to 75 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
GLAH 0152 0612 BD1 / .LT 42 kW to 174 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
GLAH 0524 1204 BD2 / .LT 147 kW to 359 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
GLAH 4131 ...8321 CD2 / .LT 373 kW to 902 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
GCH 100 250 CD4 / CD1 13 kW to 32 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Heat pump indoor mounting air-cooled 59
GSDH 0011 ...0061 FD5 / FD1 5.7 kW to 16.8 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Heat pump indoor installation water-cooled 60
GLWH 0152 1204 BD2 50 kW to 419 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
GLWH 0401 1902 BA2 97 kW to 494 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
GLWH 1130 ...4960 CA2 339 kW to 2663 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
GLWH 1130 ...4960 CA2.HT 345 kW to 2581 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
Hydraulic module indoor and outdoor installation 68
GLHM#03# ... #25#-00 Buffer Volume 300 l to 2500 l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Controls 69
Overview of accessories 70
First Service 74
-
-
7/21/2019 GEA Heat Exchangers
6/76
x6] PR-2014-0100-GB Subject to modifications K0-06/2014
GEA chiller and heat pumps for outdoor installation
Overview of capacityCooling/heating duty [kW] 0 10 20 40 60 80 100 150 200 300 400
Chiller air cooled
Chillerair cooled, with free cooling
Heat pump configurationair/water
Compressorcondensing unit
Hydraulic moduleexternal buffer tank module
GSAC 0011...0061 FD1/5
GAC(N,P) 016...064 FD1
GLAC 2015...2081 CD1/2
GLAC 4061 ...4121 CD2
GLAC 4131... 8
GLAC 0751...1301 BA2
GLAC 1532...2632 BA2
GLAC 1542...2642 BA2
GLAC 2150...4840
GLFC 0152...0612 BD2
GLFC 0604...1204 BD2
GLFC 2150...2482
GSAH 0011...0061 FD1/5
GAH(N,P) 016...064 FD1
GLAH 0152...0612 BD1
GLAH 0524...1204 BD2
GLAH 4131 .
GCH 100...250 CD1/CD4
GLCU 2015...2052 BC1
GLCU 4052...4060 BC2
GLHM-00
-
7/21/2019 GEA Heat Exchangers
7/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x7]
750 1000 2000 R410A R 407C R 134aScrew com-
pressorScroll
compressorHydraulic mod-ule as standard
Hydraulic mod-ule as option
Pump moduleas option
CD2
1 CD2
-
7/21/2019 GEA Heat Exchangers
8/76
x8] PR-2014-0100-GB Subject to modifications K0-06/2014
GEA chiller and heat pump for indoor installation
Overview of capacity
Cooling/heating duty [kW] 0 10 20 40 60 80 100 150 200 300 400
Chillerair cooled, for duct connection
Heat pump modelair/water
Chillerwithout condenser
Chiller,water cooled
Heat pump modelwater/water
Hydraulic moduleexternal buffer tank module
GSDC 0011...0061 FD1/5
GLDC 0152...0612 BD2
GLDC 0604...1204 BD2
GSDH 0011...0061 FD1/5
GLRC 2015...2061 CD2
GLRC 4060...4160 CD2
GLWC 0152...0612 BD2
GLWC 0604...1204 BD2
GLWC 0401 ... 1902 BA2
GLWC 1130 ... 49
GLWH 0152...0612 BD2
GLWH 0604...1204 BD2
GLWH 0401...1902 BA2
GLWH 1130
GLHM-00
-
7/21/2019 GEA Heat Exchangers
9/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x9]
750 1000 2000 R410A R 407C R 134a
Screw com-
pressor
Scroll
compressor
Hydraulic mod-
ule as standard
Hydraulic mod-
ule as option
Pump module
as option
2
GLWC 2450 ... 4960 CA2
20 CA2 (.HT)
GLWH 2450 ...4960 CA2 (.HT)
-
7/21/2019 GEA Heat Exchangers
10/76
x10] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GSAC 0011 ... 0061 FD5 / FD1 4.9 kW to 15.4 kW
Equipment
Optimized packaged model with 1 scroll compressor
self-supporting sheet steel construction
- galvanized
- powder-coated
Standard pump module integrated
additionally fitted with safety valve, expansion tank, pressure
gauge, air vent and fill connection
Following pump heads for pipework provided on-site
Second pump to enlarge the delivery head
as option for model sizes 0041 ... 0061
Buffer tank to be mounted below the unit is available as an option
Cooling operation down to -10 C air inlet temperature Condensing pressure is used to regulate fan speed
Autoadaptive microprocessor control
Can be delivered in two different versions:
GSAC 0011 ... 0041 FD5 with 230 V supply voltage
GSAC 0021 ... 0061 FD1 with 400 V supply voltage
Supply voltage 1~230 Volt (Series FD5) 3~400 Volt (Series FD1)
Refrigerant R-410a GSAC 0011 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
Cooling capacity kW 4.9 5.6 6.9 8.6 11.0 5.6 7.0 8.7 11.4 13.2 15.4
ESEER - 3.1 3.4 3.3 3.3 3.2 3.4 3.4 3.3 3.3 3.3 3.5
Max. current consumption A 17.6 17.6 20.6 24.6 28.6 7.1 7.6 9.6 11.6 13.4 16.6
Max. power consumption kW 1.9 2.1 2.5 3.4 4.1 2.0 2.4 3.1 4.2 4.7 5.2
Scrollcompressor Quantity 1 1 1 1 1 1 1 1 1 1 1
Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1
Capacity stages Quantity 1 1 1 1 1 1 1 1 1 1 1Delivery head of remain-ing pipework kPa 59.0 57.0 54.0 54.0 43.0 57.0 54.0 54.0 40.0 33.0 30.0
Rated volume flow m/h 0.8 1.0 1.2 1.5 1.9 1.0 1.2 1.5 2.0 2.3 2.7
Sound power level dB(A) 65 66 66 66 69 66 66 66 69 69 69
Sound pressure level dB(A) 37 38 38 38 41 38 38 38 41 41 41
Length mm 900 900 900 900 900 900 900 900 900 900 900
Width mm 370 370 370 370 370 370 370 370 370 370 420
Height mm 640 640 940 940 1240 640 940 940 1240 1240 1390
Weight kg 80 85 100 105 125 85 100 105 125 145 155
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
11/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x11]
Chiller outdoor installation air-cooled
GAC(N,P) 016 064 FD1 20 kW to 75 kW
Equipment
Space-saving optimized version with 1 or 2 DC invertersScroll compressors
Cooling operation from -15 C to +43 C air inlet temperature
Microprocessor control
Automatic self-diagnostics
Integrated 24h real-time clock with indication of weekdays
Inverter-controlled condenser fans
Electronic pressure sensing HP/LP
Unit main switch
Electronic pressure sensor for high pressure and low pressure
Installed water filter
Shut-off valves for water inlet and outlet are supplied separately
Flow switch mounted and cabled in the unit
Noise-reduced operation possible
Leading/following operation of several units with accessories
GZSEQUENC.E18 is possible
Connection to the building management system with Modbus Pro-
tocol with accessory GZAMODBUS.E14 is possible
Additional controller functions, see page 69
Can be delivered in two different versions:GACN - without hydraulic unit.
GACP - with pump module, manometer, safety valve, expan-
sion tank
Refrigerant R -410A GAC_* 016 021 025 032 040 050 064
Cooling capacity kW 20.0 25.0 30.0 37.5 50.0 60.0 75.0
ESEER - 4.8 4.7 4.5 4.0 4.6 4.4 4.0
Max. current consumption A 22.0 25.0 26.0 35.0 47.0 50.0 67.0
Max. power consumption kW 7.4 9.2 12.7 18.2 19.3 27.3 39.3
Scrollcompressor Quantity 1 2 2 3 4 4 6
Refrigeration Circuits Quantity 1 1 1 1 1 1 1
Capacity stages Quantity 1 2 2 3 4 4 6
Sound power level dB(A) 78 78 78 80 81 81 83
Sound pressure level dB(A) 46 46 46 48 49 49 51
Length mm 1371 1371 1371 1684 2358 2358 2980
Width mm 774 774 774 774 780 780 780
Height mm 1684 1684 1684 1684 1684 1684 1684
*Weight GACN without pump kg 267 320 320 401 577 577 738
*Weight GACP with pump kg 282 235 335 415 610 610 771
Performance dataSound power levelSound pressure level
At evaporation temperature 7 C and air inlet temperature 35 CRequirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
12/76
x12] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 2015 2081 CD1/2 / .SL (.HE) 39 kW to 227 kW
Equipment
Standard configuration with 2 scroll compressors
Buffer tank and pump optional (hydraulics module GLHM)
In addition, with flow switch, regulating valve, safety valve, expan-
sion vessel, venting and filler connection
Aluminium "Micro Channel" condenser with special corrosion pro-
tection coating (E-Coating)
Cooling operation down to -10 C ambient temperature
Autoadaptive microprocessor control
Controller type: HVAC Systems Step I/II
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item Connection to BMS via optional interface
Deliverable in three different versions:
GLAC 2015 2070 CD1/2 as standard unit
GLAC 2015 2070 CD1/2.SL especially quiet version
GLAC 2015 2081 CD1/2.HE as highly efficient version
Refrigerant R -410A GLAC 2015 2018 2020 2025 2026 2030 2035 2040 2045 2050 2055 2060 2070
Cooling capacity kW 39.2 44.3 51.9 58.9 65.0 77.6 88.5 102.0 114.5 127.4 144.3 165.7 189.5
El. power consumption kW 13.5 15.6 18.1 20.5 23.5 26.8 31.3 35.4 40.2 44.9 52.3 57.7 67.9
EER - 2.9 2.8 2.9 2.9 2.8 2.9 2.8 2.9 2.9 2.8 2.8 2.9 2.8
ESEER - 4.4 4.4 4.4 4.4 4.3 4.2 4.4 4.0 4.1 4.1 4.2 4.1 4.2
Performance valuesaccording toEN14511:2011
Cooling capacity kW 39.0 44.0 51.6 58.6 64.7 77.3 88.0 101.4 113.8 126.8 143.5 164.9 188.6
El. power consumption kW 13.7 15.9 18.4 20.8 23.8 27.1 31.9 35.9 40.8 45.6 53.0 58.5 68.8
EER - 2.8 2.8 2.8 2.8 2.7 2.9 2.8 2.8 2.8 2.8 2.7 2.8 2.7
ESEER - 4.2 4.2 4.2 4.2 4.2 4.1 4.2 3.9 4.0 4.0 4.0 3.9 4.0
Max. current conmp. A 33.9 36.1 45.2 49.6 55.4 67.6 73.2 80.0 89.7 99.4 112.5 129.5 152.5
Max. power consumption kW 18.8 21.0 24.6 27.4 29.8 35.5 40.8 48.6 53.7 58.8 67.2 77.6 91.8
Scroll compressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1
Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2
Sound power level dB(A) 83 83 84 84 84 85 86 88 88 88 89 90 90
Sound pressure level dB(A) 51 51 52 52 52 53 54 56 56 56 57 58 58
Length mm 1755 1755 1755 2290 2290 2290 2290 2825 2825 2825 3360 3980 3980
Width mm 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195
Height mm 1885 1885 1885 1885 1885 1885 1885 2010 2010 2010 2010 2010 2010
Weight kg 470 480 490 540 550 570 660 830 870 900 980 1130 1110
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
13/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x13]
Chiller outside installation air-cooled
GLAC 2015 2081CD1/2.SL (.HE) 39 kW to 227 kW
Refrigerant R -410A GLAC.SL 2015 2018 2020 2025 2026 2030 2035 2040 2045 2050 2055 2060 2070
Cooling capacity kW 39.4 44.6 52.3 58.9 65.9 77.8 88.5 100.0 113.4 124.3 140.5 153.0 175.4
El. power consumption kW 13.9 16.1 18.2 20.3 22.9 27.4 30.5 35.1 39.3 44.8 52.5 61.7 72.1
EER - 2.8 2.8 2.9 2.9 2.9 2.8 2.9 2.9 2.9 2.8 2.7 2.5 2.4ESEER - 4.3 4.3 4.5 4.2 4.2 4.3 4.4 4.4 4.4 4.3 4.3 4.1 4.0
Performance valuesaccording toEN14511:2011
Cooling capacity kW 39.2 44.3 52.0 58.6 65.5 77.4 87.9 99.4 112.8 123.7 139.8 152.3 174.6
El. power consumption kW 14.1 16.3 18.5 20.6 23.2 27.8 31.1 35.7 39.9 45.4 53.2 62.4 72.8
EER - 2.8 2.7 2.8 2.9 2.8 2.8 2.8 2.8 2.8 2.7 2.6 2.4 2.4
ESEER - 4.1 4.1 4.3 4.0 4.1 4.1 4.1 4.2 4.2 4.2 4.1 4.0 3.8
Max. current conmpt. A 34.4 36.6 44.6 53.0 58.8 68.8 71.1 76.7 89.7 103.3 116.4 129.5 152.5
Max. power consumption kW 19.0 21.2 24.6 28.8 31.2 36.4 41.6 46.9 52.1 58.4 66.8 75.2 91.8
Scrollcompressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1
Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2
Sound power level dB(A) 76 77 77 78 78 78 79 80 81 81 82 82 83
Sound pressure level dB(A) 44 45 45 46 46 46 47 48 49 49 50 50 51
Weight kg 540 550 560 670 680 680 860 960 1070 1080 1110 1180 1150
Refrigerant R -410A
GLAC.HE 2015 2018 2020 2025 2026 2030 2035 2040 2045 2050 2056 2061 2071 2081
Cooling capacity kW 41.7 47.4 55.0 62.5 69.6 85.1 96.6 108.0 121.9 137.8 160.4 178.4 201.2 227.1
El. power consumption kW 12.9 14.5 16.7 19.3 21.8 26.5 30.2 33.6 38.3 42.6 48.9 55.4 63.5 70.5
EER - 3.2 3.3 3.3 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2
ESEER - 4.6 4.7 4.5 4.5 4.5 4.3 4.4 4.4 4.5 4.3 4.3 4.3 4.4 4.2
Performance val-ues according toEN14511:2011
Cooling capacity kW 41.4 47.1 54.7 62.1 69.2 84.6 95.9 107.3 121.2 137.0 159.4 177.5 200.2 225.7
El. power consumption kW 13.1 14.8 17.1 19.6 22.2 26.9 30.9 34.3 39.0 43.4 49.8 56.4 64.5 71.9
EER - 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.1 3.1
ESEER - 4.3 4.4 4.2 4.3 4.3 4.1 4.1 4.2 4.3 4.1 4.1 4.1 4.2 4.0
Max. current con-
sumption
A 35.0 37.2 47.4 51.8 57.6 68.8 74.4 79.7 89.4 103.3 121.1 134.2 148.6 167.1
Max. power con-sumption kW 19.0 21.2 25.1 27.9 30.3 38.0 43.3 48.3 53.4 60.8 71.2 79.6 88.5 99.4
Scrollcompressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Sound power level dB(A) 84 84 85 85 86 88 88 90 90 90 91 91 92 93
Sound pressure level dB(A) 52 52 53 53 54 56 56 58 58 58 59 59 60 61
Weight kg 480 540 550 560 570 680 830 960 1000 1080 1510 1550 1570 1810
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!Dimensions on previous page.
-
7/21/2019 GEA Heat Exchangers
14/76
x14] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 4061 4121 CD2 / .SL (.HE) 159 kW to 352 kW
Equipment
Standard configuration with 4 scroll compressors Buffer tank and pump are optional (hydraulic module GLHM) addi-
tionally fitted with a regulating valve, safety valve, expansion tank,
air vent and fill connection
Aluminium "Micro Channel" condenser
Cooling operation down to -15 C ambient temperature possible
(accessories)
Autoadaptive microprocessor control
Controller type: HVAC Systems Step II
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item Connection to BMS via optional interface
Deliverable in three different versions:GLAC 4061 4121 CD2 as standard unit
GLAC 4061 4121 CD2.SL as especially quiet version
GLAC 4061 4121 CD2.HE as highly efficient version
Refrigerant R -410A GLAC 4061 4071 4081 4091 4101 4111 4121
Cooling capacity kW 164.7 194.1 217.8 248.2 289.2 308.4 326.7
El. power consumption kW 58.3 66.7 78.9 88.6 99.0 108.4 118.2
EER - 2.8 2.9 2.8 2.8 2.9 2.8 2.8
ESEER - 4.1 4.4 4.3 4.4 4.3 4.3 4.2
Performance valuesaccording toEN14511:2011
Cooling capacity kW 163.9 193.2 216.8 247.1 287.9 307.2 325.2
El. power consumption kW 59.1 67.6 79.9 89.7 100.3 109.7 119.6
EER - 2.8 2.9 2.7 2.8 2.9 2.8 2.7
ESEER - 3.9 4.2 4.1 4.2 4.0 4.1 4.0
Max. current consumption A 133.0 157.0 176.0 198.0 229.0 243.0 256.0
Max. power consumption kW 77.0 90.0 103.0 116.0 132.0 143.0 153.0
Scrollcompressor Quantity 4 4 4 4 4 4 4
Refrigeration Circuits Quantity 2 2 2 2 2 2 2
Capacity stages Quantity 4 4 4 4 4 4 4
Sound power level dB(A) 92 92 93 94 95 95 95
Sound pressure level dB(A) 60 60 61 62 63 63 63
Length mm 3160 3160 3160 3160 4335 4335 4335
Width mm 2250 2250 2250 2250 2250 2250 2250
Height mm 2170 2170 2170 2170 2170 2170 2170
Weight kg 1510 1680 1690 1830 2250 2300 2330
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
15/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x15]
Chiller outside installation air-cooled
GLAC 4061 4121 CD2.SL (.HE) 159 kW to 352 kW
Refrigerant R -410A
GLAC.SL 4061 4071 4081 4091 4101 4111 4121
Cooling capacity kW 159.0 179.9 214.3 241.3 264.0 296.1 312.2
El. power consumption kW 56.3 70.7 77.8 89.4 103.7 109.1 119.6
EER - 2.8 2.5 2.8 2.7 2.6 2.7 2.6ESEER - 4.3 4.4 4.4 4.4 4.3 4.3 4.3
Performance val-ues according toEN14511:2011
Cooling capacity kW 158.3 179.2 213.4 240.3 263.0 294.9 311.0
El. power consumption kW 57.0 71.5 78.7 90.4 104.7 110.2 120.9
EER - 2.8 2.5 2.7 2.7 2.5 2.7 2.6
ESEER - 4.1 4.2 4.2 4.2 4.1 4.2 4.1
Max. current consump-tion A 133.0 157.0 184.0 207.0 229.0 251.0 264.0
Max. powerconsumption kW 74.0 87.0 102.0 115.0 127.0 140.0 151.0
Scrollcompressor Quantity 4 4 4 4 4 4 4
Refrigeration Circuits Quantity 2 2 2 2 2 2 2
Capacity stages Quantity 4 4 4 4 4 4 4
Sound power level dB(A) 82 83 83 84 84 86 86
Sound pressure level dB(A) 50 51 51 52 52 53 53
Weight kg 1550 1730 2030 2170 2300 2700 2730
Refrigerant R -410A
GLAC.HE 4061 4071 4081 4091 4101 4111 4121
Cooling capacity kW 174.1 205.2 235.4 266.4 301.9 330.0 352.0
El. power consumption kW 54.4 65.0 72.9 84.1 95.8 102.8 111.1
EER - 3.2 3.2 3.2 3.2 3.2 3.2 3.2
ESEER - 4.3 4.3 4.5 4.5 4.4 4.4 4.4
Performance val-ues according toEN14511:2011
Cooling capacity kW 173.6 204.5 234.2 265.2 300.9 328.8 350.6
El. power consumption kW 54.9 65.8 74.1 85.3 96.7 104.0 112.5
EER - 3.2 3.1 3.2 3.1 3.1 3.2 3.1
ESEER - 4.2 4.1 4.2 4.2 4.3 4.2 4.2
Max. current consum A 133.0 165.0 184.0 207.0 229.0 251.0 264.0
Max. power consum. kW 77.0 94.0 107.0 120.0 132.0 147.0 157.0
Scrollcompressor Quantity 4 4 4 4 4 4 4
Refrigeration Circuits Quantity 2 2 2 2 2 2 2
Capacity stages Quantity 4 4 4 4 4 4 4
Sound power level dB(A) 92 93 94 95 95 96 97
Sound pressure level dB(A) 60 61 62 63 63 64 65
Weight kg 1700 2150 2160 2290 2550 2930 2950
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2
For project-related sound data calculations - use the obligatory sound power level!Dimensions on previous page.
-
7/21/2019 GEA Heat Exchangers
16/76
x16] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 4131 ... 8321 CD2 / .SL (.HE) 354 kW to 885 kW
Equipment
High-efficiency optimized version with 4, 6 or 8 scroll compressors Buffer tank and pump are optional (hydraulic module GLHM) addi-
tionally fitted with a safety valve, expansion tank, air vent and fill
connection
Aluminium "Micro Channel" condenser
Cooling operation down to -15 C ambient temperature
Autoadaptive microprocessor control
Controller type: HVAC Systems Step II
Unit main switch
Configuration with an electronic expansion valve EEV
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item Connection to BMS via optional interface
Deliverable in three different versions:GLAC 4131 8321 CD2 as standard unit
GLAC 4131 8321 CD2.SL as especially quiet version
GLAC 4131 8321 CD2.HE as highly efficient version
Refrigerant R -410A GLAC 4131 4141 4161 5171 6181 5201 6211 6231 6241 8241 8261 8281 8301 8321
Cooling capacity kW 354.3 378.8 413.4 458.3 501.3 525.6 569.4 603.7 634.9 665.3 707.9 759.4 793.5 826.6
El. power consumption kW124.4 130.2 147.8 160.4 171.9 183.9 195.4 214.1 218.6 233.7 248.8 260.5 279.1 295.7
EER - 2.9 2.9 2.8 2.9 2.9 2.9 2.9 2.8 2.9 2.9 2.9 2.9 2.8 2.8
ESEER - 4.2 4.2 4.0 4.2 4.2 4.1 4.2 4.1 4.1 4.1 4.2 4.3 4.2 4.1
Performance valuesaccording toEN14511:2011
Cooling capacity kW 352.8 377.5 411.7 456.5 499.1 524.0 567.4 601.7 632.5 662.9 705.0 756.9 790.8 823.5
El. power consumption kW 126.0 131.5 149.6 162.1 174.1 185.5 197.4 216.2 221.0 236.1 251.6 262.9 281.9 298.7
EER - 2.8 2.9 2.8 2.8 2.9 2.8 2.9 2.8 2.9 2.8 2.8 2.9 2.8 2.8
ESEER - 4.0 4.1 3.9 4.0 4.0 3.9 4.0 4.0 3.9 4.0 4.0 4.1 4.0 3.9
Max. current consum. A 273.0 288.0 317.0 351.0 384.0 398.0 432.0 461.0 480.0 534.0 572.0 609.0 630.0 650.0
Max. power consum. kW 166.0 177.0 198.0 214.0 231.0 249.0 265.0 286.0 299.0 329.0 348.0 367.0 381.0 395.0
Scroll compressor Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 3 2 4 4 4 4 4
Capacity stages Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8
Sound power level dB(A) 96 96 96 96 97 97 97 97 98 98 98 99 99 99
Sound pressure level dB(A) 64 64 64 64 65 65 64 64 65 65 65 66 66 66
Length mm 3905 3905 5080 5080 5080 5080 6255 6255 6255 7430 7430 7430 7430 7430
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Weight kg 2730 2770 2800 3400 3650 3690 4200 4220 4350 5260 5300 5370 5400 5430
Performance data
Sound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35C
EUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
17/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x17]
Chiller outside installation air-cooled
GLAC 4131 ... 8321 CD2.SL (.HE) 354 kW to 885 kW
Refrigerant R -410A GLAC.SL 4131 4141 4161 5171 6181 5201 6211 6231 6241 8241 8261 8281 8301 8321
Cooling capacity kW 333.6 358.1 397.4 431.5 465.0 497.7 532.3 579.3 595.9 615.9 666.4 717.7 757.8 794.6
El. power consump-tion kW 129.2 137.3 153.1 168.1 182.7 191.6 206.0 220.0 229.7 244.6 258.3 274.8 288.4 306.2
EER - 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.6 2.6 2.6 2.6
ESEER - 4.3 4.3 4.2 4.3 4.4 4.3 4.4 4.4 4.3 4.3 4.4 4.4 4.4 4.3
Performance valuesas of EN14511:2011
Cooling capacity kW 332.2 356.9 395.9 430.0 463.2 496.2 530.6 577.5 593.9 613.9 664.0 715.6 755.4 791.8
El. power consumption kW 130.5 138.5 154.7 169.6 184.5 193.0 207.7 221.9 231.7 246.6 260.7 276.9 290.8 309.0
EER - 2.6 2.6 2.6 2.5 2.5 2.6 2.6 2.6 2.6 2.5 2.6 2.6 2.6 2.6
ESEER - 4.1 4.2 4.1 4.2 4.1 4.1 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1
Max. current con-sumption A 266.0 283.0 312.0 344.0 375.0 390.0 422.0 453.0 468.0 524.0 561.0 598.0 619.0 640.0
Max. power consumption kW 162.0 174.0 196.0 211.0 227.0 245.0 260.0 283.0 293.0 324.0 343.0 362.0 376.0 390.0
Scrollcompressor Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 3 2 4 4 4 4 4
Capacity stages Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8
Sound power level dB(A) 86 86 86 87 87 87 87 88 88 88 89 90 90 90
Sound pressure level dB(A) 53 53 53 54 54 54 54 55 55 55 56 57 57 57
Weight kg 3060 3160 3200 3900 4110 4190 4640 4730 4790 5410 5810 6160 6200 6250
Refrigerant R -410A GLAC.HE 4131 4141 4161 5171 6181 5201 6211 6231 6241 8241 8261 8281 8301 8321
Cooling capacity kW 370.5 391.4 438.4 481.1 517.5 549.2 591.4 632.7 657.3 701.5 740.0 784.6 830.6 884.7
El. power consumption kW 119.6 125.1 141.5 154.0 166.3 177.0 189.4 204.0 212.3 225.3 239.0 250.4 266.5 283.0
EER - 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
ESEER - 4.5 4.5 4.4 4.5 4.5 4.4 4.5 4.5 4.4 4.4 4.5 4.5 4.5 4.5
Performance valuesas of EN14511:2011
Cooling capacity kW 368.7 389.9 436.4 479.1 515.1 547.3 589.2 630.4 654.7 698.7 736.8 782.0 827.5 881.1
El. power consumption kW 121.3 126.6 143.6 155.9 168.7 178.8 191.6 206.3 214.8 228.1 242.2 253.0 269.6 286.6
EER - 3.0 3.1 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.1 3.1 3.1
ESEER - 4.2 4.3 4.2 4.3 4.2 4.2 4.3 4.3 4.2 4.2 4.2 4.3 4.3 4.2
Max. current con-sumption A 281.0 295.0 325.0 358.0 391.0 406.0 439.0 473.0 487.0 534.0 579.0 624.0 645.0 666.0
Max. power consumption kW 170.0 181.0 202.0 218.0 235.0 253.0 269.0 292.0 303.0 329.0 352.0 375.0 389.0 403.0
Scrollcompressor Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 3 2 4 4 4 4 4
Capacity stages Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8
Sound power level dB(A) 97 97 97 97 98 98 98 99 99 99 99 100 100 100
Sound pressure level dB(A) 65 65 65 64 65 65 65 66 66 66 66 67 67 67
Weight kg 3060 3100 3130 3800 4050 4090 4540 4630 4690 5930 5970 6040 6070 6110
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!Dimensions on previous page.
-
7/21/2019 GEA Heat Exchangers
18/76
x18] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 0751 1301 BA2 / .SL 145 kW to 266 kW
Equipment
Standard model with 1 screw compressor Buffer tank and pump are optional (hydraulic module GLHM) addi-
tionally fitted with a regulating valve, safety valve, expansion tank,
air vent and fill connection
Cooling operation down to -15 C ambient temperature
With separately enclosed water filter
Autoadaptive microprocessor control
Controller type: HVAC Systems Step III
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item
Connection to BMS via optional interfaceCan be delivered in two different versions:
GLAC 0751 1301 BA2 als Standardgert
GLAC 0751 1301 BA2.SL in especially quiet version
Refrigerant R-134a GLAC 0751 0851 0951 0961 1021 1301
Cooling capacity kW 144.5 162.5 182.4 201.3 234.3 266.1
El. power consumption kW 51.5 60.9 68.7 75.1 85.4 93.5
EER - 2.8 2.7 2.7 2.7 2.8 2.9
ESEER - 3.5 3.4 3.5 3.6 3.5 3.5
Performance values asof EN14511:2011
Cooling capacity kW 144.0 161.9 181.8 200.7 233.5 265.3
El. power consumption kW 52.1 61.5 69.3 75.7 86.1 94.3
EER - 2.8 2.6 2.6 2.7 2.7 2.8
ESEER - 3.4 3.4 3.5 3.6 3.4 3.5
Max. current consumption A 117.0 127.0 144.0 144.0 154.0 201.0
Max. power consumption kW 70.1 76.0 87.9 87.9 94.1 121.0
Screw compressor Quantity 1 1 1 1 1 1
Refrigeration Circuits Quantity 1 1 1 1 1 1
Minimum partial load level % 50 50 50 50 50 50
Sound power level dB(A) 94 94 94 94 96 96
Sound pressure level dB(A) 62 62 62 62 64 64
Length mm 3110 3110 3110 3110 4610 4610
Width mm 2222 2222 2222 2222 2222 2222
Height mm 2150 2150 2150 2150 2150 2150
Weight kg 1680 1710 1780 1860 2590 2720
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
19/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x19]
Chiller outside installation air-cooled
GLAC 0751 1301 BA2 / .SL 145 kW to 266 kW
Refrigerant R-134a GLAC.SL 0751 0851 0951 0961 1021 1301
Cooling capacity kW 134.3 150.9 165.8 197.4 223.1 238.3
El. power consumption kW 53.3 62.7 73.5 76.2 90.3 101.5
EER - 2.5 2.4 2.3 2.6 2.5 2.4ESEER - 3.5 3.4 3.4 3.7 3.6 3.3
Performance values asof EN14511:2011
Cooling capacity kW 133.8 150.4 165.3 196.8 222.4 237.7
El. power consumption kW 53.8 63.2 74.0 76.8 91.0 102.1
EER - 2.5 2.4 2.2 2.6 2.4 2.3
ESEER - 3.5 3.3 3.3 3.6 3.5 3.3
Max. current consumption A 112.0 122.0 139.0 143.0 148.0 195.0
Max. power consumption kW 67.7 73.6 85.5 87.2 90.5 117.0
Screw compressor Quantity 1 1 1 1 1 1
Refrigeration Circuits Quantity 1 1 1 1 1 1
Capacity stages Quantity 50 50 50 50 50 50
Sound power level dB(A) 84 84 84 84 86 86
Sound pressure level dB(A) 52 52 52 52 54 54
Length mm 3110 3110 3110 4110 4610 4610
Width mm 2222 2222 2222 2222 2222 2222
Height mm 2150 2150 2150 2150 2150 2150
Weight kg 1680 1770 1840 1980 2670 2720
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
20/76
x20] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 1532 2632 BA2 / .SL 277 kW to 516 kW
Equipment
Standard configuration with 2 screw compressors
Standard hydraulics module GLHM with integrated buffer tank and
pump
Pumps with larger delivery head are available
Following pump heads for remaining pipework provided on-site
Cooling operation down to -15 C ambient temperature
With separately enclosed water filter
Autoadaptive microprocessor control
Controller type: HVAC Systems Step III
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item Connection to BMS via optional interface
Can be delivered in two different versions:
GLAC 1532 2632 BA2 als Standardgert
GLAC 1532 2632 BA2.SL in especially quiet version
Refrigerant R-134a GLAC 1532 1732 1932 1952 2432 2632
Cooling capacity kW 276.9 328.9 366.3 398.2 466.1 515.9
El. power consumption kW 103.8 121.4 138.9 154.3 178.6 193.0
EER - 2.7 2.7 2.6 2.6 2.6 2.7
ESEER - 3.6 3.6 3.6 3.6 3.6 3.5
Performance values asof EN14511:2011
Cooling capacity kW 275.9 327.6 364.8 396.5 463.9 513.3
El. power consumption kW 104.8 122.7 140.4 155.9 180.9 195.5
EER - 2.6 2.7 2.6 2.5 2.6 2.6
ESEER - 3.6 3.5 3.5 3.8 3.5 3.4
Max. current consumption A 233.0 259.0 295.0 295.0 371.0 413.0
Max. power consumption kW 140.0 156.0 181.0 181.0 225.0 249.0
Screw compressor Quantity 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2
Minimum partial load level Quantity 25 25 25 25 25 25
Sound power level dB(A) 97 97 97 97 99 99
Sound pressure level dB(A) 65 65 65 65 67 67
Length mm 4610 4610 4610 4610 5610 5610
Width mm 2222 2222 2222 2222 2222 2222
Height mm 2150 2420 2420 2420 2430 2430
Weight kg 3130 3340 3490 3530 4590 4820
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
21/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x21]
Chiller outside installation air-cooled
GLAC 1532 2632 BA2 / .SL 277 kW to 516 kW
Refrigerant R-134a GLAC.SL 1532 1732 1932 1952 2432 2632
Cooling capacity kW 252.3 295.6 333.5 376.6 442.5 484.3
El. power consumption kW 111.5 128.0 148.8 164.4 183.4 199.5
EER - 2.3 2.3 2.2 2.3 2.4 2.4ESEER - 3.5 3.5 3.5 3.6 3.7 3.5
Performance values ac-cording to EN14511:2011
Cooling capacity kW 251.4 294.6 332.4 375.2 440.5 482.1
El. power consumption kW 112.4 129.0 150.0 165.8 185.4 201.7
EER - 2.2 2.3 2.2 2.3 2.4 2.4
ESEER - 3.4 3.4 3.4 3.3 3.6 3.4
Max. current consumption A 229.0 264.0 305.0 309.0 383.0 421.0
Max. power consumption kW 138.0 154.0 180.0 182.0 222.0 244.0
Screw compressor Quantity 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25
Sound power level dB(A) 86 87 87 87 89 89
Sound pressure level dB(A) 54 55 55 55 57 57
Length mm 4610 4610 5610 5610 6610 6610
Width mm 2222 2222 2222 2222 2222 2222
Height mm 2150 2420 2430 2430 2430 2430
Weight kg 3220 3450 3640 3840 5180 5450
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
22/76
x22] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 1542 2642 BA2 / .SL 277 kW to 516 kW
Equipment
Standard configuration with 2 screw compressors
Cooling operation down to -15 C ambient temperature
Autoadaptive microprocessor control
Controller type: HVAC Systems Step III
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item
Connection to BMS via optional interface
Can be delivered in two different versions:
GLAC 1542 2642 BA2 als Standardgert
GLAC 1542 2642 BA2.SL in especially quiet version
Refrigerant R-134a GLAC 1542 1742 1942 1962 2442 2642
Cooling capacity kW 276.9 328.9 366.3 398.2 466.1 515.9
El. power consumption kW 103.8 121.4 138.9 154.3 178.6 193.0
EER - 2.7 2.7 2.6 2.6 2.6 2.7
ESEER - 3.6 3.6 3.6 3.6 3.6 3.5
Performance valuesaccording toEN14511:2011
Cooling capacity kW 275.9 327.3 364.8 397.1 464.8 514.1
El. power consumption kW 104.8 122.9 140.3 155.4 179.9 194.7
EER - 2.6 2.7 2.6 2.6 2.6 2.6
ESEER - 3.5 3.4 3.4 3.5 3.5 3.4
Max. current consumption A 227.0 253.0 287.0 287.0 360.0 398.0
Max. power consumption kW 137.0 153.0 177.0 177.0 219.0 241.0
Screw compressor Quantity 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25
Sound power level dB(A) 97 99 97 97 99 99
Sound pressure level dB(A) 65 67 65 65 67 67
Length mm 4610 4610 4610 4610 5610 5610
Width mm 2222 2222 2222 2222 2222 2222
Height mm 2150 2420 2420 2420 2430 2430
Weight kg 3490 3680 3810 4100 5140 5340
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
23/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x23]
Chiller outside installation air-cooled
GLAC 1542 2642 BA2 / .SL 277 kW to 516 kW
Refrigerant R-134a GLAC.SL 1542 1742 1942 1962 2442 2642
Cooling capacity kW 252.3 295.6 333.5 376.6 442.5 484.3
El. power consumption kW 111.5 128.0 148.8 164.4 183.4 199.5
EER - 2.3 2.3 2.2 2.3 2.4 2.4ESEER - 3.5 3.5 3.5 3.6 3.7 3.5
Performance values ac-cording to EN14511:2011
Cooling capacity kW 251.4 294.5 332.4 375.6 441.4 482.8
El. power consumption kW 112.3 129.1 149.9 165.3 184.5 201.0
EER - 2.2 2.3 2.2 2.3 2.4 2.4
ESEER - 3.4 3.4 3.4 3.6 3.6 3.4
Max. current consumption A 221.0 253.0 294.0 294.0 368.0 406.0
Max. power consumption kW 134.0 148.0 174.0 174.0 214.0 236.0
Screw compressor Quantity 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25
Sound power level dB(A) 86.0 87.0 87.0 87.0 89.0 89.0
Sound pressure level dB(A) 54.3 55.1 55.0 55.0 56.8 56.8
Length mm 4610 4610 5610 5610 6610 6610
Width mm 2222 2222 2222 2222 2222 2222
Height mm 2150 2420 2430 2430 2430 2430
Weight kg 3580 3790 3960 4410 5730 5970
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
24/76
-
7/21/2019 GEA Heat Exchangers
25/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x25]
Chiller outside installation air-cooled
GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW
Refrigerant R-134a GLAC 2360 2390 2420 2450 2480 2482 2541 2600 2602
Cooling capacity kW 794.4 848.3 917.1 989.4 1051.1 1134.4 1213.4 1243.9 1328.1
El. power consumption kW 279.7 303.5 323.7 344.4 357.5 398.8 417.8 443.5 465.2
EER - 2.8 2.8 2.8 2.9 2.9 2.8 2.9 2.8 2.9ESEER - 3.9 3.9 4.0 4.0 4.1 4.1 4.1 4.0 4.2
Performance values accordingto EN14511:2011
Cooling capacity kW 792.0 845.5 914.0 986.4 1047.5 1130.3 1210.2 1240.5 1324.0
El. power consumption kW 282.1 306.3 326.9 347.4 361.0 402.9 421.1 447.0 469.3
EER - 2.8 2.8 2.8 2.8 2.9 2.8 2.9 2.8 2.8
ESEER - 3.7 3.7 3.9 3.9 3.9 4.0 4.0 3.9 4.1
Max. current consumption A 590.0 635.0 673.0 722.0 763.0 763.0 852.0 926.0 926.0
Max. power consumption kW 365.0 390.0 410.0 440.0 466.0 466.0 518.0 562.0 562.0
Screw compressor Quantity 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 102 103 103 104 104 104 106 106 106
Sound pressure level dB(A) 69 70 70 71 71 71 73 73 73
Length mm 5800 7000 7000 7600 7600 7600 9400 9400 11200
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 6560 7010 7220 7860 8030 8090 9290 9380 10040
Refrigerant R-134a GLAC 3630 3690 3720 3721 3722 4840
Cooling capacity kW 1397.7 1495.1 1616.4 1681.4 1740.8 1817.5
El. power consumption kW 478.1 532.3 541.9 579.9 604.1 672.5
EER - 2.9 2.8 3.0 2.9 2.9 2.7
ESEER - 4.0 3.9 4.1 4.2 4.2 4.0
Performance values accordingto EN14511:2011
Cooling capacity kW 1393.4 1490.0 1611.4 1675.9 1734.3 1811.6
El. power consumption kW 482.4 537.5 546.9 585.5 610.7 678.4
EER - 2.9 2.8 3.0 2.9 2.8 2.7
ESEER - 3.9 3.8 - - - -
Max. current consumption A 1021.0 1103.0 1144.0 1144.0 1144.0 1331.0
Max. power consumption kW 621.0 673.0 699.0 699.0 699.0 812.0
Screw compressor Quantity 3 3 3 3 3 4
Refrigeration Circuits Quantity 3 3 3 3 3 4
Minimum partial load level % 16 16 16 16 16 12
Sound power level dB(A) 106 106 106 106 106 106
Sound pressure level dB(A) 73 73 73 73 73 73
Length mm 11200 11200 11200 11200 11200 12400
Width mm 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500
Weight kg 11440 11780 12350 12420 12480 13650
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
26/76
x26] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW
Refrigerant R-134a GLAC.SL 2150 2170 2190 2192 2220 2265 2270 2272 2315
Cooling capacity kW 295.0 325.5 377.7 425.1 485.8 558.3 592.4 662.2 726.6
El. power consumption kW 98.3 115.5 131.2 147.2 168.6 197.8 208.1 231.4 250.7
EER - 3.0 2.8 2.9 2.9 2.9 2.8 2.9 2.9 2.9ESEER - 4.1 4.1 4.1 4.3 4.0 4.1 4.1 4.3 4.1
Performance values accord-ing to EN14511:2011
Cooling capacity kW 294.3 324.6 376.6 423.5 484.5 556.8 590.6 660.2 724.1
El. power consumption kW 99.0 116.4 132.4 148.7 169.9 199.4 209.9 233.4 253.2
EER - 3.0 2.8 2.9 2.9 2.9 2.8 2.8 2.8 2.9
ESEER - 4.0 4.0 4.0 4.1 3.9 4.0 4.0 4.2 3.9
Max. current consumption A 232.0 253.0 294.0 294.0 367.0 437.0 462.0 462.0 533.0
Max. power consumption kW 141.0 152.0 180.0 180.0 221.0 263.0 279.0 279.0 326.0
Screw compressor Quantity 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 87 87 88 88 89 89 90 90 91
Sound pressure level dB(A) 55 55 56 56 57 57 57 57 58
Length mm 4000 4000 4000 4000 4900 4900 4900 5800 5800
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 3870 3890 3970 4230 5340 5700 5810 6520 7190
Refrigerant R-134a GLAC.SL 2360 2390 2420 2450 2480 2482 2541 2600 2602
Cooling capacity kW 781.8 846.6 905.5 992.4 1032.6 1140.1 1175.8 1230.7 1293.5
El. power consumption kW 275.9 290.3 317.8 335.7 361.1 392.0 419.9 436.0 472.1
EER - 2.8 2.9 2.9 3.0 2.9 2.9 2.8 2.8 2.7
ESEER - 3.9 4.0 4.0 4.1 4.1 4.3 4.2 4.1 4.2
Performance values accordingto EN14511:2011
Cooling capacity kW 779.6 843.8 902.5 989.3 1029.2 1135.9 1172.8 1227.3 1289.7
El. power consumption kW 278.2 293.1 320.8 338.7 364.5 396.1 422.9 439.4 475.9
EER - 2.8 2.9 2.8 2.9 2.8 2.9 2.8 2.8 2.7
ESEER - 3.8 3.9 3.9 4.0 3.9 4.1 4.1 4.0 4.1
Max. current consumption A 597.0 643.0 681.0 737.0 778.0 778.0 852.0 941.0 941.0
Max. power consumption kW 369.0 394.0 414.0 448.0 474.0 474.0 518.0 570.0 570.0
Screw compressor Quantity 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 91 92 92 93 93 94 94 94 94
Sound pressure level dB(A) 58 59 59 60 60 61 61 61 61
Length mm 4000 4000 4000 4000 4900 4900 4900 5800 5800
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 7590 7950 8370 9530 9550 10120 10590 10830 10990
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
27/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x27]
Chiller outside installation air-cooled
GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW
Refrigerant R-134a GLAC.SL 3630 3690 3720 3721 3722 4840
Cooling capacity kW 1358.9 1460.9 1531.3 1597.6 1654.4 1761.9
El. power consumption kW 475.6 527.8 561.3 607.6 637.4 682.1
EER - 2.9 2.8 2.7 2.6 2.6 2.6ESEER - 4.1 4.0 4.0 4.0 4.1 3.9
Performance values accordingto EN14511:2011
Cooling capacity kW 1354.9 1456.0 1527.0 1592.7 1648.7 1756.5
El. power consumption kW 479.6 532.6 565.6 612.5 643.1 687.5
EER - 2.8 2.7 2.7 2.6 2.6 2.6
ESEER - 3.9 3.9 3.9 3.9 3.9 3.8
Max. current consumption A 1021.0 1103.0 1144.0 1144.0 1144.0 1346.0
Max. power consumption kW 621.0 673.0 699.0 699.0 699.0 820.0
Screw compressor Quantity 3 3 3 3 3 4
Refrigeration Circuits Quantity 3 3 3 3 3 4
Minimum partial load level % 16 16 16 16 16 12
Sound power level dB(A) 94 94 94 94 95 96
Sound pressure level dB(A) 61 61 61 61 62 63
Length mm 11200 11200 11200 11200 11200 11200
Width mm 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500
Weight kg 12830 12880 13390 13430 13470 15230
Refrigerant R-134a GLAC.HE 2150 2170 2190 2192 2220 2260 2265 2270 2272
Cooling capacity kW 310.9 356.3 406.1 455.1 512.3 558.4 596.9 633.8 703.5
El. power consumption kW 97.9 112.9 127.4 144.6 162.7 178.1 188.8 199.2 223.2
EER - 3.2 3.2 3.2 3.2 3.2 3.1 3.2 3.2 3.2
ESEER - 4.1 4.1 4.2 4.4 4.1 4.2 4.2 4.2 4.2
Performance values accord-ing to EN14511:2011
Cooling capacity kW 310.1 355.3 404.7 454.0 510.8 556.8 595.1 631.6 701.2
El. power consumption kW 98.6 113.9 128.8 145.8 164.2 179.6 190.6 201.4 225.6
EER - 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
ESEER - 4.0 4.0 4.1 4.2 3.9 4.1 4.0 4.1 4.0
Max. current consumption A 232.0 260.0 294.0 294.0 367.0 406.0 437.0 462.0 477.0
Max. power consumption kW 141.0 156.0 180.0 180.0 221.0 244.0 263.0 279.0 287.0Screw compressor Quantity 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 98 98 99 99 100 100 101 101 101
Sound pressure level dB(A) 66 66 67 67 68 67 68 68 68
Length mm 4000 4000 4000 4000 4000 4000 4000 4000 4000
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 3530 3650 3780 4260 4920 5370 5460 5920 6660
Performance dataSound power level
Sound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Cube-shaped radiaton 10 m distance reflection factor Q=2
For project-related noise calculations, please only employ the binding sound power level!.
-
7/21/2019 GEA Heat Exchangers
28/76
x28] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW
Refrigerant R-134a GLAC.HE 2315 2360 2390 2420 2450 2480 2482 2541 3570
Cooling capacity kW 775.3 851.0 905.9 977.6 1049.6 1103.1 1202.9 1255.1 1362.9
El. power consumption kW 244.5 268.5 286.3 307.0 326.9 345.6 377.2 400.2 433.1
EER - 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.2ESEER - 4.1 3.9 4.0 4.1 4.2 4.2 4.2 4.2 4.0
Performance values accordingto EN14511:2011
Cooling capacity kW 772.3 848.2 902.6 974.0 1046.0 1099.1 1198.1 1251.5 1360.6
El. power consumption kW 247.5 271.4 289.7 310.6 330.4 349.6 381.9 403.7 435.4
EER - 3.1 3.1 3.1 3.1 3.2 3.1 3.1 3.1 3.1
ESEER - 3.9 3.8 3.9 3.9 4.0 4.0 4.0 4.1 3.9
Max. current consumption A 541.0 605.0 650.0 696.0 737.0 778.0 793.0 867.0 945.0
Max. power consumption kW 330.0 373.0 398.0 422.0 448.0 474.0 482.0 526.0 581.0
Screw compressor Quantity 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 3
Minimum partial load level % 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 101 102 102 103 103 103 103 104 104
Sound pressure level dB(A) 68 69 69 70 70 70 70 71 71
Length mm 7600 7600 7600 7600 7600 7600 7600 7600 7600
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 7070 7460 8220 8800 9340 9570 9820 10150 12270
Refrigerant R-134a GLAC.HE 3630 3660
Cooling capacity kW 1468.9 1542.8
El. power consumption kW 467.9 491.3
EER - 3.1 3.1
ESEER - 4.2 4.2
Performance values according toEN14511:2011
Cooling capacity kW 1466.1 1539.6
El. power consumption kW 470.7 494.4
EER - 3.1 3.1
ESEER - 4.1 0.0
Max. current consumption A 1021.0 1062.0
Max. power consumption kW 621.0 647.0Screw compressor Quantity 3 2
Refrigeration Circuits Quantity 3 3
Minimum partial load level % 16 25
Sound power level dB(A) 104 104
Sound pressure level dB(A) 71 71
Length mm 11200 11200
Width mm 2260 2260
Height mm 2500 2500
Weight kg 12720 12830
Performance dataSound power levelSound pressure level
At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614
Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
29/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x29]
Chiller outside installation air-cooled
GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling
Equipment
Unit with a free-cooling function with high energy-saving potential The free cooling mode is activated starting from 1 C temperature
difference between outdoor air and water
3-way valve for optimizing water circuits and efficiency
with 2 scroll compressors
Autoadaptive microprocessor control
Controller type: HVAC Systems Step II
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item
Connection to BMS via optional interface
Can be delivered in two different versions:GLFC 0152 0612 BD2 as standard unit
GLFC 0152 0612 BD2.SL in especially quiet version
Refrigerant R -410A GLFC 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612
Cooling capacity kW 37.4 44.3 53.5 58.7 76.7 90.3 99.2 113.4 129.2 143.9 161.6
El. power consumption kW 15.2 16.4 20.7 23.9 30.1 32.7 37.7 43.3 46.2 54.2 62.8
EER - 2.5 2.7 2.6 2.5 2.6 2.8 2.6 2.6 2.8 2.7 2.6Performance values ac-cording to EN14511:2011
Cooling capacity kW 37.0 43.9 52.9 58.0 75.8 89.4 98.4 112.4 127.8 142.7 160.2
El. power consumption kW 15.6 16.9 21.3 24.5 30.9 33.6 38.5 44.3 47.6 55.5 64.3
EER - 2.4 2.6 2.5 2.4 2.5 2.7 2.6 2.5 2.7 2.6 2.5
Max. current consumption A 33.6 35.8 48.4 52.8 63.4 71.6 79.8 93.3 103.0 116.1 133.0
Max. power consumption kW 19.5 21.7 27.8 30.6 38.0 43.4 48.8 56.0 61.1 69.5 80.0
Scrollcompressor
Quanti-ty 2 2 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quanti-ty 1 1 1 1 1 1 1 1 1 1 1
Capacity stages Quanti-ty 2 2 2 2 2 2 2 2 2 2 2
Sound power level dB(A) 87 87 90 90 91 91 92 92 93 93 94
Sound pressure level dB(A) 55 55 58 58 59 59 60 60 61 61 62
Length mm 2200 2200 2602 2602 2602 3602 3602 3602 4602 4602 4602
Width mm 920 920 1104 1104 1104 1104 1104 1104 1104 1104 1104
Height mm 1780 1780 2175 2175 2175 2175 2175 2175 2175 2205 2205
Weight kg 670 710 870 880 1060 1310 1340 1410 1650 1680 1740
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
30/76
x30] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling
Free cooling operation* GLFC 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612
Performance data withoutfree cooling operation at
35 C outdoor temperatureCooling capacity kW 41.0 48.0 58.0 64.0 83.0 98.0 108.0 123.0 140.0 156.0 175.0
El. power consumption kW 16.0 17.0 21.0 24.0 32.0 34.0 39.0 45.0 47.0 56.0 65.0
Performance data withfree cooling operation at 5C outdoor temperature
Cooling capacity kW 31.0 36.0 42.0 44.0 55.0 70.0 72.0 84.0 99.0 102.0 114.0
Share of free-cooling capacity % 77.0 74.0 73.0 69.0 66.0 71.0 67.0 68.0 70.0 65.0 65.0
Capacity data at 100 % free-cooling mode
Cooling capacity kW 41.0 48.0 58.0 64.0 83.0 98.0 108.0 123.0 140.0 156.0 175.0
power consumption kW 1.5 1.5 4.2 4.2 4.2 4.2 4.2 6.3 6.3 6.3 8.4
Air Inlet Temperature C 2.0 1.6 1.3 0.5 -0.1 0.9 0.0 0.2 0.8 -0.3 -0.3
EER - 27.0 32.0 13.8 15.0 19.8 23.4 25.7 19.5 22.3 24.8 20.9
Refrigerant R -410A GLFC.SL 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612
Cooling capacity kW 35.4 43.2 48.5 54.7 72.3 84.2 96.1 105.2 118.4 134.0 154.3
El. power consumption kW 15.4 17.1 20.4 23.3 29.9 34.2 37.6 43.6 48.3 56.1 62.4
EER - 2.3 2.5 2.4 2.4 2.4 2.5 2.6 2.4 2.5 2.4 2.5
Performance valuesas of EN14511:2011
Cooling capacity kW 35.0 42.7 48.0 54.1 71.5 83.4 95.3 104.3 117.3 132.7 152.7
El. power consumption kW 15.7 17.5 20.9 23.9 30.7 35.0 38.4 44.5 49.5 57.4 64.0
EER - 2.2 2.5 2.3 2.3 2.3 2.4 2.5 2.3 2.4 2.3 2.4
Max. current consumption A 32.4 40.4 48.4 52.8 63.4 75.4 83.6 93.3 106.8 119.9 133.0
Max. power consumption kW 18.9 22.6 26.0 28.8 36.2 42.8 48.2 53.3 59.6 68.0 76.4
Scrollcompressor Quantity 2 2 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1
Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2
Sound power level dB(A) 77 78 78 79 80 81 81 82 83 84 85
Sound pressure level dB(A) 45 46 46 47 48 49 49 50 51 51 52
Length mm 2200 2602 2602 2602 3602 3602 4602 4602 4602 4602 4602
Width mm 920 1104 1104 1104 1104 1104 1104 1104 1104 1277 1277
Height mm 1780 2175 2175 2175 2175 2175 2205 2175 2205 2350 2350
Weight kg 680 860 920 940 1240 1350 1590 1610 1690 1920 2000
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
31/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x31]
Chiller outside installation air-cooled
GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling
Free cooling operation* GLFC.SL 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612
Performance data with-out free cooling opera-tion at 35 C outdoor
temperature
Cooling capacity kW 38.0 47.0 53.0 59.0 79.0 92.0 105.0 114.0 128.0 145.0 167.0
El. power consumption kW 16.0 18.0 21.0 24.0 31.0 34.0 39.0 45.0 50.0 58.0 64.0
Performance data with freecooling operation at 5 Coutdoor temperature
Cooling capacity kW 25.0 30.0 34.0 38.0 50.0 59.0 69.0 72.0 80.0 90.0 98.0
Share of free-coolingcapacity % 77.0 74.0 73.0 69.0 66.0 71.0 67.0 68.0 70.0 65.0 65.0
Capacity data at 100 %free-cooling mode
Cooling capacity kW 38.0 47.0 53.0 59.0 79.0 92.0 105.0 114.0 128.0 145.0 167.0
Power consumption kW 0.6 1.5 1.5 1.7 1.7 2.6 2.6 2.6 3.4 3.4 4.4Air Inlet Temperature C -0.5 -0.9 -0.5 -0.6 -0.8 -0.6 -0.2 -0.9 -0.9 -1.1 -2.1
EER - 63.7 31.3 35.0 34.6 46.2 35.2 40.3 43.8 37.6 42.5 37.9
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
32/76
x32] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling
Equipment
Unit with a free-cooling function with high energy-saving potential
The free-cooling operation begins from 1 C temperature difference
between outdoor air and water
3-way valve for optimizing water circuits and efficiency
with 4 scroll compressors in two refrigeration circuits
Autoadaptive microprocessor control
Controller type: HVAC Systems Step II
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item
Connection to BMS via optional interfaceCan be delivered in two different versions:
GLFC 0604 ... 1204 BD2 as standard unit
GLFC 0604 ... 1204 BD2.SL in especially quiet Ausfhrung
Refrigerant R -410A GLFC 0604 0704 0804 0904 1004 1104 1204
Cooling capacity kW 153.7 179.1 202.5 231.9 253.9 291.0 326.3
El. power consumption kW 60.0 66.2 77.5 84.2 94.4 107.0 124.2
EER - 2.6 2.7 2.6 2.8 2.7 2.7 2.6
Performance values accordingto EN14511:2011
Cooling capacity kW 152.1 176.9 199.8 229.7 251.4 287.9 322.6
El. power consumption kW 61.6 68.3 80.3 86.4 96.9 110.0 127.9
EER - 2.5 2.6 2.5 2.7 2.6 2.6 2.5
Max. current consumption A 126.8 143.2 167.2 186.6 206.0 232.2 266.0
Max. power consumption kW 76.0 86.8 101.8 112.0 122.2 139.0 160.0
Scrollcompressor Quantity 4 4 4 4 4 4 4
Refrigeration Circuits Quantity 2 2 2 2 2 2 2
Capacity stages Quantity 4 4 4 4 4 4 4
Sound power level dB(A) 93 93 94 94 94 95 96
Sound pressure level dB(A) 61 61 62 62 62 63 64
Length mm 4110 4110 4110 5110 5110 5110 5110
Width mm 2220 2220 2220 2220 2220 2220 2220
Height mm 2150 2150 2150 2150 2150 2430 2430
Weight kg 2200 2330 2510 2880 2940 3260 3400
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
33/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x33]
Chiller outside installation air-cooled
GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling
Free cooling operation* GLFC 0604 0704 0804 0904 1004 1104 1204
Performance data withoutfree cooling operation at 35 Coutside temperature
Cooling capacity kW 167.0 195.0 221.0 252.0 275.0 316.0 354.0
El. power consumption kW 62.0 68.0 80.0 86.0 97.0 110.0 128.0
Performance data with freecooling operation at 5 C out-door temperature
Cooling capacity kW 129.0 135.0 156.0 193.0 199.0 227.0 254.0
Share of free-cooling capacity % 77.0 69.0 71.0 77.0 72.0 72.0 72.0
Capacity data at 100 % free-cool-ing mode
Cooling capacity kW 167.0 195.0 221.0 252.0 275.0 316.0 354.0
Power consumption kW 8.4 8.4 12.6 12.6 12.6 12.6 16.8
Air Inlet Temperature C 2.0 0.5 0.9 1.9 1.2 1.1 1.0EER - 19.9 23.2 17.5 20.0 21.8 25.0 21.1
Refrigerant R -410A GLFC.SL 0604 0704 0804 0904 1004 1104 1204
Cooling capacity kW 142.5 165.4 184.8 208.8 236.1 269.7 302.5
El. power consumption kW 61.0 70.0 79.1 87.9 95.3 109.7 125.9
EER - 2.3 2.4 2.3 2.4 2.5 2.5 2.4
Performance values accordingto EN14511:2011
Cooling capacity kW 141.1 163.7 182.7 207.1 234.0 267.2 299.4
El. power consumption kW 62.3 71.8 81.3 89.6 97.4 112.2 128.9
EER - 2.3 2.3 2.3 2.3 2.4 2.4 2.3
Max. current consumption A 126.8 150.8 167.2 186.6 206.0 232.2 266.0
Max. power consumption kW 72.4 85.6 96.4 106.6 116.8 133.6 152.8
Scrollcompressor Quantity 4 4 4 4 4 4 4
Refrigeration Circuits Quantity 2 2 2 2 2 2 2
Capacity stages Quantity 4 4 4 4 4 4 4
Sound power level dB(A) 82 83 83 84 84 85 86Sound pressure level dB(A) 50 51 51 52 52 53 54
Length mm 4110 4110 4110 5110 5110 5110 5110
Width mm 2220 2220 2220 2220 2220 2220 2220
Height mm 2150 2150 2150 2150 2150 2430 2430
Weight kg 2280 2410 2580 2880 3040 3380 3520
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
34/76
x34] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling
Free cooling operation* GLFC.SL 0604 0704 0804 0904 1004 1104 1204
Performance data withoutfree cooling operation at 35 Coutdoor temperature
Cooling capacity kW 155.0 180.0 201.0 226.0 255.0 291.0 326.0
El. power consumption kW 63.0 73.0 82.0 91.0 98.0 113.0 130.0
Performance data with freecooling operation at 5 C out-door temperature
Cooling capacity kW 97.0 112.0 115.0 140.0 148.0 166.0 188.0
Share of free-cooling capacity % 63.0 62.0 57.0 62.0 58.0 57.0 58.0
Capacity data at 100 % free-cool-ing mode
Cooling capacity kW 155.0 180.0 201.0 226.0 255.0 291.0 326.0
power consumption kW 3.4 5.2 5.2 5.2 5.2 5.2 6.9
Air Inlet Temperature C -1.0 -1.0 -2.5 -1.1 -2.2 -2.5 -2.4EER - 45.5 34.6 38.7 43.5 49.0 56.0 47.3
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
35/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x35]
Chiller outside installation air-cooled
GLFC 2150 ... 2600 DA2 / .SL 286 kW to 1212 kW with free cooling
Equipment
Unit with a free-cooling function with high energy-saving potential
The free cooling mode is activated starting from 1 C temperature
difference between outdoor air and water
3-way valve for optimizing water circuits and efficiency
Autoadaptive microprocessor control
Controller type: HVAC Systems Step III
Unit main switch
Master/slave operation with GEA HVAC System unit series availa-
ble as an accessory item
Connection to BMS via optional interface
Can be delivered in two different versions:
GLFC 2150 ... 2600 DA2 as standard unit
GLFC 2150 ... 2540 DA2.SL as especially quiet version
Refrigerant R-134a GLFC 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540 2600
Cooling capacity kW 286.0 320.2 370.6 412.6 454.9 529.8 570.4 596.1 646.0 709.1 754.8 807.5 866.5 938.4 1025.7 1140.9 1212.4
El. power consumption kW 92.4 106.6 119.3 138.3 146.8 179.5 192.4 207.6 219.7 233.8 256.2 275.5 286.9 317.3 331.8 386.1 429.6
EER - 3.1 3.0 3.1 3.0 3.1 3.0 3.0 2.9 2.9 3.0 3.0 2.9 3.0 3.0 3.1 3.0 2.8
Performance valuesas of EN14511:2011
Cooling capacity kW 284.6 318.4 368.7 410.3 453.0 527.3 568.1 593.5 643.5 706.0 751.5 803.2 861.9 934.0 1020.2 1135.4 1205.9
El. power consumption kW 93.7 108.4 121.1 140.6 148.7 182.0 194.7 210.2 222.2 236.9 259.6 279.8 291.5 321.6 337.3 391.6 436.1
EER - 3.0 2.9 3.0 2.9 3.1 2.9 2.9 2.8 2.9 3.0 2.9 2.9 3.0 2.9 3.0 2.9 2.8
Max. current con-sumption
A 234.0 241.0 262.0 303.0 314.0 377.0 414.0 439.0 471.0 506.0 533.0 572.0 609.0 663.0 716.0 800.0 882.0
Max. power consumption kW 116.0 145.0 157.0 185.0 192.0 226.0 248.0 264.0 284.0 306.0 324.0 350.0 375.0 404.0 433.0 485.0 537.0
Screw compressor Quan-tity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quan-tity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Minimum partial load level % 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 99.0 100.0 100.0 100.0 101.0 102.0 102.0 102.0 102.0 102.0 103.0 103.0 103.0 105.0 106.0 106.0 106.0
Sound pressure level dB(A) 66.4 67.4 67.3 67.3 68.2 69.2 69.1 69.1 69.0 68.9 69.9 69.9 69.7 71.7 72.5 72.5 72.4
Length mm 4000 4000 4900 4900 5800 5800 6400 6400 7000 7900 7900 7900 10000 10000 11800 11800 13000
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 4880 4990 5520 5700 7000 7410 8270 8310 8750 9600 10470 10570 12680 13180 13710 14930 15810
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
36/76
x36] PR-2014-0100-GB Subject to modifications K0-06/2014
Chiller outside installation air-cooled
GLFC 2150 ... 2600 DA2 / .SL 286 kW to 1212 kW with free cooling
Free cooling oper-ation*
GLFC 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540 2600
Performance data with-out free cooling opera-tion at 35 C outdoortemperature
Cooling capacity kW 314.0 351.5 407.3 452.8 501.1 580.6 625.8 653.1 708.6 777.8 826.6 882.8 946.8 1027 1125 1250 1329
El. power consumption kW 96.2 111.0 124.1 144.0 153.0 187.3 200.8 216.9 229.3 243.0 266.7 287.2 298.8 330.4 344.5 402.5 447.5
Performance datawith free cooling op-eration at 5 C out-door temperature
Cooling capacity kW 208.9 237.4 272.8 304.1 337.0 397.7 424.6 433.1 482.4 517.5 556.6 573.3 613.1 674.1 747.9 821.7 873.2
Share of free-coolingcapacity
% 67.0 68.0 67.0 67.0 67.0 68.0 68.0 66.0 68.0 67.0 67.0 65 65 66 66 66 66
Capacity data at 100% free-cooling mode
Cooling capacity kW 314.0 351.5 407.3 452.8 501.1 580.6 625.8 653.1 708.6 777.8 826.6 882.8 946.8 1027 1125 1250 1329
Power consumption kW 11.9 15.9 15.9 19.9 19.9 23.9 23.9 23.9 27.8 31.8 31.8 31.8 31.8 39.8 47.7 47.7 47.7
Air Inlet Temperature C 1.6 1.8 1.7 1.8 1.8 2.1 2.1 1.8 2.1 1.6 2.0 1.5 1.5 1.7 1.6 1.7 1.7
EER - 26.4 22.1 25.6 22.8 25.2 24.3 26.2 27.3 25.5 24.5 26.0 27.8 29.8 25.8 23.6 26.2 27.9
Refrigerant R-134a GLFC.SL 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540
Cooling capacity kW 282.2 319.4 364.5 407.4 446.7 534.6 561.9 610.6 638.2 673.5 750.9 839.7 801.3 940.4 979.7 1107.0
El. power consumption kW 93.3 103.0 120.6 135.4 148.7 174.1 194.1 201.4 219.7 242.2 255.6 293.8 276.3 312.0 340.8 391.9
EER - 3.0 3.1 3.0 3.0 3.0 3.0 2.9 3.0 2.9 2.8 2.9 2.9 2.9 3.0 2.9 2.8
Performance valuesas of EN14511:2011
Cooling capacity kW 280.9 317.6 362.7 405.3 445.0 532.0 559.7 607.8 635.8 670.7 747.8 835.4 797.4 936.0 974.9 1101.8
El. power consumption kW 94.6 104.8 122.4 137.6 150.4 176.7 196.3 204.1 222.1 244.9 258.7 298.1 280.2 316.4 345.7 397.0
EER - 2.9 3.0 2.9 2.9 2.9 3.0 2.9 3.0 2.9 2.7 2.9 2.8 2.9 3.0 2.8 2.9
Max. current con-sumption A 241.0 241.0 269.0 303.0 321.0 384.0 422.0 454.0 479.0 506.0 549.0 624.0 587.0 678.0 716.0 800.0
Max. power consump-tion kW 120.0 145.0 161.0 185.0 196.0 230.0 252.0 272.0 288.0 306.0 332.0 383.0 358.0 412.0 433.0 485.0
Screw compressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Minimum partial loadlevel % 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Sound power level dB(A) 89.0 89.0 89.0 90.0 91.0 91.0 91.0 92.0 92.0 92.0 92.0 92.0 92.0 94.0 94.0 95.0
Sound pressure level dB(A) 56.8 56.7 56.7 57.6 58.4 58.3 58.3 59.2 59.2 59.2 58.9 58.9 58.9 61.0 61.0 61.9
Length mm 4000 4900 4900 5800 5800 7000 7000 7900 7900 7900 10000 10000 10000 11800 11800 13000
Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight kg 5380 5950 6040 6600 7500 8250 9070 9550 10040 10590 13020 13560 13060 14970 15060 16360
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
37/76
PR-2014-0100-GB Subject to modifications K0-06/2014 x37]
Chiller outside installation air-cooled
GLFC 2150 ... 2600 DA2 / .SL 286 kW to 1212 kW with free cooling
Free cooling oper-ation*
GLFC.SL 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540
Performance datawithout free coolingoperation at 35 Coutdoor temperature
Cooling capacity kW 309.3 350.1 399.6 446.2 491.1 585.4 615.2 669.3 698.6 735.3 821.0 874 912.7 1028 1071 1209
El. power consumption kW 97.4 107.6 125.8 141.7 155.6 182.1 203.4 210.5 230.1 253.9 267.1 288.9 307.1 325.8 356.6 411
Performance datawith free cooling op-eration at 5 C out-door temperature
Cooling capacity kW 201.7 221.5 257.5 283.4 327.5 376.2 400.4 431.8 458.3 469.9 541.5 558.2 570.2 669.5 682.9 743.1
Share of free-coolingcapacity
% 65.0 63.0 64.0 64.0 67.0 64.0 65.0 65.0 66.0 64.0 66.0 64 62 65 64 61
Capacity data at 100% free-cooling mode
Cooling capacity kW 309.3 350.1 399.6 446.2 491.1 585.4 615.2 669.3 698.6 735.3 821.0 874 912.7 1028 1071 1209
Power consumption kW 9.5 9.5 11.9 11.9 14.3 16.7 16.7 19.1 19.3 19.1 23.9 23.8 23.8 28.6 28.6 28.6
Air Inlet Temperature C 1.0 1.0 1.0 0.9 1.0 0.9 1.3 1.0 1.3 1.0 1.3 0.9 0.6 1.2 0.9 0.4
EER - 32.4 36.7 33.6 37.5 34.3 35.1 36.8 35.0 36.2 38.5 34.4 36.7 38.3 35.9 37.4 42.3
Performance data*Free-cooling modeSound power levelSound pressure level
Performance data in normal mode with chilled water 12/7C and air inlet temperature 30C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!
-
7/21/2019 GEA Heat Exchangers
38/76
x38] PR-2014-0100-GB Subject to modifications K0-06/2014
Compressor/condensing unit outside installation air-cooled
GLCU 2015 ... 4060 BC1/2 / .SL 40 kW to 171 kW
Equipment
Standard configuration with 2 or 4 scroll compressors
2-circuit system
Frame and panels made of galvanized steel
Coated plastic
Condenser made of copper pipes and corrugated aluminium fins
Cooling operation down to -15 C ambient temperature
Activation on-site
Switch cabinet produced according to EN60204-1 / IEC204-1
Unit main switch
Shut off valve in liquid and suction line
High and low pressure switch
Continuously variable fan speed control
Recommended accessories
Refrigerating engineering accessories GLZCU... .R06
(expansion valve, solenoid valve, filter drier and sight glass, to be
mounted in each circuit by others on site)
Can be delivered in two different versions:
GLCU 2015 ... 4060 BC1 as standard unit
GLCU 4052 ... 4060 BC2.SL in especially quiet version
R -407C refrigerant GLCU(.SL) 2015 2018 2020 2025 2030 2041 2051 4052 40604052
.SL
4060
.SL
Cooling capacity kW 40.3 50.4 58.5 71.1 85.2 120.2 148.0 150.8 171.1 141.0 161.6
El. power consumption kW 14.8 18.2 20.7 25.9 30.2 38.8 47.4 56.5 65.9 55.2 64.7
EER - 2.7 2.8 2.8 2.8 2.8 3.1 3.1 2.7 2.6 2.6 2.5
Max. current consumption A 31.4 41.3 46.7 59.7 64.7 88.0 105.0 115.0 129.0 115.0 129.0
Max. power consumption kW 16.2 19.4 22.2 27.7 36.7 50.3 60.5 66.0 76.4 62.4 72.8
Scrollcompressor Quantity 2 2 2 2 2 2 2 4 4 4 4
Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2 2 2
Capacity stages Quantity 2 2 2 2 2 2 2 4 4 4 4
Sound power level dB(A) 78 79 79 81 81 85 85 94 94 79 79
Sound pressure level dB(A) 47 47 48 50 50 53 53 62 62 47 47
Length mm 1695 2195 2195 2745 2745 3245 3245 3110 3110 3110 3110
Width mm 1120 1120 1120 1120 1120 1120 1120 2220 2220 2220 2220
Height mm 1420 1420 1420 1420 1420 1620 1620 1700 1700 1700 2150
Weight kg 510 570 600 675 775 910 980 1520 1600 1620 1700
Per ormance ataSound power levelSound pressure level
Ony t e mo e s zes 4052 an 4060 are ava a e as SL untsAt evaporation temperature 7 C and air inlet temperatur