    GEA Chillers and Heat Pumps with H Factor

    Energy-efficient and compact models

    for inside and outside installation

    Product Brochure

    ~ db^ e~ b~

    X-

  • 7/21/2019 GEA Heat Exchangers

    2/76

    x2] PR-2014-0100-GB Subject to modifications K0-06/2014

    Economy and ecology in harmony

    The signs of the times are clear

    Investors, systems builders, planners and architects no longer ask whether, but how

    they can improve the sustainability trend of their plant and building engineering.

    Buildings are unique objects. Position, size, construction quality and increasingly the build-

    ing technology determine values and yields. The energetic state is considerably gaining

    in significance, because buildings are responsible for about 40 percent of world energy

    consumption and contribute to 21 percent of the world-wide greenhouse gas emissions.

    The proportion of the energy costs in the "second rent" for users and residents is constantly

    increasing.

    You come across the air condi-

    tioning technology with H

    Factor in all walks of life.

    Where heating, cooling, cleaning, filtering, humidification and dehumidification of air is

    required, GEA makes its contribution to progress. Customized climate-control and air treat-ment, with the maximum-possible reduction of energy consumption over the entire life

    cycle of the facilities: this all pays out handsomely in euros and cents, in comfort, and in

    work productivity. In highly sensitive areas, such as clinical and cleanroom applications,

    our solutions reliably satisfy all international standards and achieve high rankings in the

    demanding classification of the Eurovent Compliance Committee for Air Handling Units.

    They furthermore set new standards for sustainability and perfect system integration in

    modern sport arenas, factory buildings, airport facilities, and swimming pools, as well as

    in offices, museums and hotels. Summarized with the concept "HX actor", this quality jus-

    tifies our technological advantage. The HX Factor is more than just technology. It is an atti-

    tude and creates value with a future: quality of life for residents and users. Protection of

    energy resources and our climate. Security for investors and planners.

    Good climate with H Factor:

    Reliable. Efficient. Sustainable.

    The HX-Factor is our performance promise. It

    stands for unique competence in heat exchang-

    ers (HX = HEAT EXCHANGE) and character-

    izes all its products and services. The many

    advantages associated with the HX-Factor offer

    you maximum benefit over the entire lifetime

    of the systems.

    X-

    X-

    -F

    -

  • 7/21/2019 GEA Heat Exchangers

    3/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x3]

    Technical quality

    Whoever treats air must master it

    The fact that our air treatment is neither seen nor heard, although one is agreeably aware

    of it, and that in the meantime it avoids energy and wasteful costs, is due to our precision

    air-treatment work in both hardware and software.

    Can a building with large glazed areas be heated during spring and autumn on its north

    side and cooled on its south side, with only one system and without having to switch on

    the central heating? Does a plant in the pharmaceutical or electronic industry, for instance,

    which heats, cools, humidifies and dehumidifies the air, also offer protection from dirt and

    bacteria? Can investors and building owners calculate the life cycle costs of a central plant

    air handling unit, determine the effect of energy-saving equipment on the operating cost

    for this purpose, and thus select the optimal efficiency class right in the configuration stage

    of the plant?

    GEA has found answers to this and many other questions concerning air treatment and cli-mate control and has implemented them in solutions which reflect its experience gained

    in many and various successful applications. The core proposal consists of a broad spec-

    trum of central and decentral air treatment plants, separators and filter plants up to com-

    plete clean room systems. The function, control, and design of such facilities can be

    precisely customized according to the desired task, adapted to the design characteristics

    and infrastructure of specific buildings, and designed according to the calculation of oper-

    ating costs as well as the highest standards of energy efficiency and climate protection. Cut-

    ting-edge control technology from our own development permits individual control in

    single rooms as well as central handling within a building management system.

    Control units with access through interfaces to all leading systems of building automation,

    provide for the trouble-free integration of all equipment in the building management sys-

    tem. The fact that planners and users can implement their own wishes at the design stage

    of the plant itself is proof of the precision work involved in the air-conditioning equip-

    ment.

    You can see that the HX Factor has many facets. Generations of cross-functional experience

    play a role, as do our customized engineering, worldwide proximity to our customers, and

    our well-proven innovative abilities. Every individual GEA employee contributes to quality

    by adding positive characteristics to the HX Factor.

    By enthusiasm for a technology that shapes the lives of people in progressive ways.

    By special diligence and precision. By commitment at all levels. This quality transfers one-

    to-one to our products and services. Thus you can personally experience the HX Factor. It

    assures you many diverse product benefits. It rewards your trust with reliable, efficient

    and sustainable solutions. Therefore count on the HX Factor!

    GEA stands for:

    Customized air quality and a

    healthy, comfortable indoor cli-

    mate with extremely quiet

    operation

    Maximum energy efficiency

    and reduction in CO2 emis-

    sions

    Precise control and regulation,

    centrally and decentrally

    High adaptability to the most

    diverse tasks and environments

    Simple system integration

    Durability and high availability

    at low maintenance cost

    -

    -

    -

    -

  • 7/21/2019 GEA Heat Exchangers

    4/76

    x4] PR-2014-0100-GB Subject to modifications K0-06/2014

    GEA chiller

    Variety for your comfort

    Irrespective of whether your requirement is for indoor or outdoor

    installation, air or water-cooled, there is a vast variety of equipment

    with or without heat pump and an extensive spectrum of accessories

    available to you within the capacity range of 4.9 - 2.749 KW.

    Last but not least, GEA chillers are characterized by their efficiency and

    high energy conservation potential, additionally underlined by the use

    of high-quality components and environmentally-friendly refrigerants

    R-410A and R-134a, which are used in most GEA chillers depending

    upon the model. With GEA chillers and heat pumps with reversible cir-

    cuit, you can provide energy not only for cooling, but also for heating.

    And if you require a compressor/condensing unit or want a system

    with external condenser, our program includes the correct unit for you

    here as well. The choice is yours.

    Legend

    Explanation of the pictograms used in this document

    Pictogram Description Pictogram Description

    Screw compressor Plate Heat Exchanger

    Scrollcompressor Shell and tube heat exchanger

    Inverter compressor Master/slave operation is possible

    Refrigerant R-134a Direct evaporator

    Refrigerant R -410A BMS integration is possible

    R -407C refrigerant Plate Heat Exchanger

    Unit with free cooling Heating

    Unit as low-noise model Cooling

    Unit as high-performance model Outdoor installation

    Unit as high-temperature model Indoor installation

    Unit as low-noise model with extended operatinglimits

    Eurovent certified

  • 7/21/2019 GEA Heat Exchangers

    5/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x5]

    Contents

    Our Products

    Economy and ecology in harmony - HX Factor 2

    Explanation of the pictograms used in this document 4

    GEA chiller and heat pumps for outdoor installation 6

    GEA chiller and heat pump for indoor mounting 8

    Chiller outdoor installation air-cooled 10

    GSAC 0011 ... 0061 FD5 / FD1 4.9 kW to 15.4 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

    GAC(N,P) 016 064 FD1 20 kW to 75 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    GLAC 2015 2081 CD1/2 / .SL (.HE) 39 kW to 227 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    GLAC 4061 4121 CD2 / .SL (.HE) 159 kW to 352 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    GLAC 4131 ... 8321 CD2 / .SL (.HE) 354 kW to 885 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    GLAC 0751 1301 BA2 / .SL 145 kW to 266 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    GLAC 1532 2632 BA2 / .SL 277 kW to 516 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    GLAC 1542 2642 BA2 / .SL 277 kW to 516 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling . . . . . . . . . . . . . . . . . . . . . .29

    GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling . . . . . . . . . . . . . . . . . . . . . 32

    GLFC 2150 ... 2482 DA2 / .SL 286 kW to 1212 kW with free cooling . . . . . . . . . . . . . . . . . . . . 35

    Compressor/condensing unit outdoor installation air-cooled 38

    GLCU 2015 ... 4060 BC1/2 / .SL 40 kW to 171 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Chiller indoor installation air-cooled 39

    GSDC 0011 ... 0041 FD5 / FD1 4.9 kW to 15.4 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

    GLDC 0152 1204 BD2 37 kW to 312 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    GLRC 2015 4160 CD2 41 kW to 442 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    GLWC 0152 1204 BD2 43 kW to 371 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    GLWC 0401 1902 BA2 87 kW to 447 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    GLWC 1130 4960 CA2 / .HE 306 kW to 2416 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48

    Heat pump outdoor installation air-cooled 50

    GSAH 0011 ...0061 FD5 / FD1 5.7 kW to 16.8 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

    GAH(N,P) 016 064 FD1 20 kW to 75 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    GLAH 0152 0612 BD1 / .LT 42 kW to 174 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    GLAH 0524 1204 BD2 / .LT 147 kW to 359 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

    GLAH 4131 ...8321 CD2 / .LT 373 kW to 902 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56

    GCH 100 250 CD4 / CD1 13 kW to 32 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    Heat pump indoor mounting air-cooled 59

    GSDH 0011 ...0061 FD5 / FD1 5.7 kW to 16.8 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

    Heat pump indoor installation water-cooled 60

    GLWH 0152 1204 BD2 50 kW to 419 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    GLWH 0401 1902 BA2 97 kW to 494 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

    GLWH 1130 ...4960 CA2 339 kW to 2663 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    GLWH 1130 ...4960 CA2.HT 345 kW to 2581 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66

    Hydraulic module indoor and outdoor installation 68

    GLHM#03# ... #25#-00 Buffer Volume 300 l to 2500 l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70

    Controls 69

    Overview of accessories 70

    First Service 74

    -

  • 7/21/2019 GEA Heat Exchangers

    6/76

    x6] PR-2014-0100-GB Subject to modifications K0-06/2014

    GEA chiller and heat pumps for outdoor installation

    Overview of capacityCooling/heating duty [kW] 0 10 20 40 60 80 100 150 200 300 400

    Chiller air cooled

    Chillerair cooled, with free cooling

    Heat pump configurationair/water

    Compressorcondensing unit

    Hydraulic moduleexternal buffer tank module

    GSAC 0011...0061 FD1/5

    GAC(N,P) 016...064 FD1

    GLAC 2015...2081 CD1/2

    GLAC 4061 ...4121 CD2

    GLAC 4131... 8

    GLAC 0751...1301 BA2

    GLAC 1532...2632 BA2

    GLAC 1542...2642 BA2

    GLAC 2150...4840

    GLFC 0152...0612 BD2

    GLFC 0604...1204 BD2

    GLFC 2150...2482

    GSAH 0011...0061 FD1/5

    GAH(N,P) 016...064 FD1

    GLAH 0152...0612 BD1

    GLAH 0524...1204 BD2

    GLAH 4131 .

    GCH 100...250 CD1/CD4

    GLCU 2015...2052 BC1

    GLCU 4052...4060 BC2

    GLHM-00

  • 7/21/2019 GEA Heat Exchangers

    7/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x7]

    750 1000 2000 R410A R 407C R 134aScrew com-

    pressorScroll

    compressorHydraulic mod-ule as standard

    Hydraulic mod-ule as option

    Pump moduleas option

    CD2

    1 CD2

  • 7/21/2019 GEA Heat Exchangers

    8/76

    x8] PR-2014-0100-GB Subject to modifications K0-06/2014

    GEA chiller and heat pump for indoor installation

    Overview of capacity

    Cooling/heating duty [kW] 0 10 20 40 60 80 100 150 200 300 400

    Chillerair cooled, for duct connection

    Heat pump modelair/water

    Chillerwithout condenser

    Chiller,water cooled

    Heat pump modelwater/water

    Hydraulic moduleexternal buffer tank module

    GSDC 0011...0061 FD1/5

    GLDC 0152...0612 BD2

    GLDC 0604...1204 BD2

    GSDH 0011...0061 FD1/5

    GLRC 2015...2061 CD2

    GLRC 4060...4160 CD2

    GLWC 0152...0612 BD2

    GLWC 0604...1204 BD2

    GLWC 0401 ... 1902 BA2

    GLWC 1130 ... 49

    GLWH 0152...0612 BD2

    GLWH 0604...1204 BD2

    GLWH 0401...1902 BA2

    GLWH 1130

    GLHM-00

  • 7/21/2019 GEA Heat Exchangers

    9/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x9]

    750 1000 2000 R410A R 407C R 134a

    Screw com-

    pressor

    Scroll

    compressor

    Hydraulic mod-

    ule as standard

    Hydraulic mod-

    ule as option

    Pump module

    as option

    2

    GLWC 2450 ... 4960 CA2

    20 CA2 (.HT)

    GLWH 2450 ...4960 CA2 (.HT)

  • 7/21/2019 GEA Heat Exchangers

    10/76

    x10] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GSAC 0011 ... 0061 FD5 / FD1 4.9 kW to 15.4 kW

    Equipment

    Optimized packaged model with 1 scroll compressor

    self-supporting sheet steel construction

    - galvanized

    - powder-coated

    Standard pump module integrated

    additionally fitted with safety valve, expansion tank, pressure

    gauge, air vent and fill connection

    Following pump heads for pipework provided on-site

    Second pump to enlarge the delivery head

    as option for model sizes 0041 ... 0061

    Buffer tank to be mounted below the unit is available as an option

    Cooling operation down to -10 C air inlet temperature Condensing pressure is used to regulate fan speed

    Autoadaptive microprocessor control

    Can be delivered in two different versions:

    GSAC 0011 ... 0041 FD5 with 230 V supply voltage

    GSAC 0021 ... 0061 FD1 with 400 V supply voltage

    Supply voltage 1~230 Volt (Series FD5) 3~400 Volt (Series FD1)

    Refrigerant R-410a GSAC 0011 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061

    Cooling capacity kW 4.9 5.6 6.9 8.6 11.0 5.6 7.0 8.7 11.4 13.2 15.4

    ESEER - 3.1 3.4 3.3 3.3 3.2 3.4 3.4 3.3 3.3 3.3 3.5

    Max. current consumption A 17.6 17.6 20.6 24.6 28.6 7.1 7.6 9.6 11.6 13.4 16.6

    Max. power consumption kW 1.9 2.1 2.5 3.4 4.1 2.0 2.4 3.1 4.2 4.7 5.2

    Scrollcompressor Quantity 1 1 1 1 1 1 1 1 1 1 1

    Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1

    Capacity stages Quantity 1 1 1 1 1 1 1 1 1 1 1Delivery head of remain-ing pipework kPa 59.0 57.0 54.0 54.0 43.0 57.0 54.0 54.0 40.0 33.0 30.0

    Rated volume flow m/h 0.8 1.0 1.2 1.5 1.9 1.0 1.2 1.5 2.0 2.3 2.7

    Sound power level dB(A) 65 66 66 66 69 66 66 66 69 69 69

    Sound pressure level dB(A) 37 38 38 38 41 38 38 38 41 41 41

    Length mm 900 900 900 900 900 900 900 900 900 900 900

    Width mm 370 370 370 370 370 370 370 370 370 370 420

    Height mm 640 640 940 940 1240 640 940 940 1240 1240 1390

    Weight kg 80 85 100 105 125 85 100 105 125 145 155

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    11/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x11]

    Chiller outdoor installation air-cooled

    GAC(N,P) 016 064 FD1 20 kW to 75 kW

    Equipment

    Space-saving optimized version with 1 or 2 DC invertersScroll compressors

    Cooling operation from -15 C to +43 C air inlet temperature

    Microprocessor control

    Automatic self-diagnostics

    Integrated 24h real-time clock with indication of weekdays

    Inverter-controlled condenser fans

    Electronic pressure sensing HP/LP

    Unit main switch

    Electronic pressure sensor for high pressure and low pressure

    Installed water filter

    Shut-off valves for water inlet and outlet are supplied separately

    Flow switch mounted and cabled in the unit

    Noise-reduced operation possible

    Leading/following operation of several units with accessories

    GZSEQUENC.E18 is possible

    Connection to the building management system with Modbus Pro-

    tocol with accessory GZAMODBUS.E14 is possible

    Additional controller functions, see page 69

    Can be delivered in two different versions:GACN - without hydraulic unit.

    GACP - with pump module, manometer, safety valve, expan-

    sion tank

    Refrigerant R -410A GAC_* 016 021 025 032 040 050 064

    Cooling capacity kW 20.0 25.0 30.0 37.5 50.0 60.0 75.0

    ESEER - 4.8 4.7 4.5 4.0 4.6 4.4 4.0

    Max. current consumption A 22.0 25.0 26.0 35.0 47.0 50.0 67.0

    Max. power consumption kW 7.4 9.2 12.7 18.2 19.3 27.3 39.3

    Scrollcompressor Quantity 1 2 2 3 4 4 6

    Refrigeration Circuits Quantity 1 1 1 1 1 1 1

    Capacity stages Quantity 1 2 2 3 4 4 6

    Sound power level dB(A) 78 78 78 80 81 81 83

    Sound pressure level dB(A) 46 46 46 48 49 49 51

    Length mm 1371 1371 1371 1684 2358 2358 2980

    Width mm 774 774 774 774 780 780 780

    Height mm 1684 1684 1684 1684 1684 1684 1684

    *Weight GACN without pump kg 267 320 320 401 577 577 738

    *Weight GACP with pump kg 282 235 335 415 610 610 771

    Performance dataSound power levelSound pressure level

    At evaporation temperature 7 C and air inlet temperature 35 CRequirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    12/76

    x12] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 2015 2081 CD1/2 / .SL (.HE) 39 kW to 227 kW

    Equipment

    Standard configuration with 2 scroll compressors

    Buffer tank and pump optional (hydraulics module GLHM)

    In addition, with flow switch, regulating valve, safety valve, expan-

    sion vessel, venting and filler connection

    Aluminium "Micro Channel" condenser with special corrosion pro-

    tection coating (E-Coating)

    Cooling operation down to -10 C ambient temperature

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step I/II

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item Connection to BMS via optional interface

    Deliverable in three different versions:

    GLAC 2015 2070 CD1/2 as standard unit

    GLAC 2015 2070 CD1/2.SL especially quiet version

    GLAC 2015 2081 CD1/2.HE as highly efficient version

    Refrigerant R -410A GLAC 2015 2018 2020 2025 2026 2030 2035 2040 2045 2050 2055 2060 2070

    Cooling capacity kW 39.2 44.3 51.9 58.9 65.0 77.6 88.5 102.0 114.5 127.4 144.3 165.7 189.5

    El. power consumption kW 13.5 15.6 18.1 20.5 23.5 26.8 31.3 35.4 40.2 44.9 52.3 57.7 67.9

    EER - 2.9 2.8 2.9 2.9 2.8 2.9 2.8 2.9 2.9 2.8 2.8 2.9 2.8

    ESEER - 4.4 4.4 4.4 4.4 4.3 4.2 4.4 4.0 4.1 4.1 4.2 4.1 4.2

    Performance valuesaccording toEN14511:2011

    Cooling capacity kW 39.0 44.0 51.6 58.6 64.7 77.3 88.0 101.4 113.8 126.8 143.5 164.9 188.6

    El. power consumption kW 13.7 15.9 18.4 20.8 23.8 27.1 31.9 35.9 40.8 45.6 53.0 58.5 68.8

    EER - 2.8 2.8 2.8 2.8 2.7 2.9 2.8 2.8 2.8 2.8 2.7 2.8 2.7

    ESEER - 4.2 4.2 4.2 4.2 4.2 4.1 4.2 3.9 4.0 4.0 4.0 3.9 4.0

    Max. current conmp. A 33.9 36.1 45.2 49.6 55.4 67.6 73.2 80.0 89.7 99.4 112.5 129.5 152.5

    Max. power consumption kW 18.8 21.0 24.6 27.4 29.8 35.5 40.8 48.6 53.7 58.8 67.2 77.6 91.8

    Scroll compressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1

    Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2

    Sound power level dB(A) 83 83 84 84 84 85 86 88 88 88 89 90 90

    Sound pressure level dB(A) 51 51 52 52 52 53 54 56 56 56 57 58 58

    Length mm 1755 1755 1755 2290 2290 2290 2290 2825 2825 2825 3360 3980 3980

    Width mm 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195 1195

    Height mm 1885 1885 1885 1885 1885 1885 1885 2010 2010 2010 2010 2010 2010

    Weight kg 470 480 490 540 550 570 660 830 870 900 980 1130 1110

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    13/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x13]

    Chiller outside installation air-cooled

    GLAC 2015 2081CD1/2.SL (.HE) 39 kW to 227 kW

    Refrigerant R -410A GLAC.SL 2015 2018 2020 2025 2026 2030 2035 2040 2045 2050 2055 2060 2070

    Cooling capacity kW 39.4 44.6 52.3 58.9 65.9 77.8 88.5 100.0 113.4 124.3 140.5 153.0 175.4

    El. power consumption kW 13.9 16.1 18.2 20.3 22.9 27.4 30.5 35.1 39.3 44.8 52.5 61.7 72.1

    EER - 2.8 2.8 2.9 2.9 2.9 2.8 2.9 2.9 2.9 2.8 2.7 2.5 2.4ESEER - 4.3 4.3 4.5 4.2 4.2 4.3 4.4 4.4 4.4 4.3 4.3 4.1 4.0

    Performance valuesaccording toEN14511:2011

    Cooling capacity kW 39.2 44.3 52.0 58.6 65.5 77.4 87.9 99.4 112.8 123.7 139.8 152.3 174.6

    El. power consumption kW 14.1 16.3 18.5 20.6 23.2 27.8 31.1 35.7 39.9 45.4 53.2 62.4 72.8

    EER - 2.8 2.7 2.8 2.9 2.8 2.8 2.8 2.8 2.8 2.7 2.6 2.4 2.4

    ESEER - 4.1 4.1 4.3 4.0 4.1 4.1 4.1 4.2 4.2 4.2 4.1 4.0 3.8

    Max. current conmpt. A 34.4 36.6 44.6 53.0 58.8 68.8 71.1 76.7 89.7 103.3 116.4 129.5 152.5

    Max. power consumption kW 19.0 21.2 24.6 28.8 31.2 36.4 41.6 46.9 52.1 58.4 66.8 75.2 91.8

    Scrollcompressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1

    Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2

    Sound power level dB(A) 76 77 77 78 78 78 79 80 81 81 82 82 83

    Sound pressure level dB(A) 44 45 45 46 46 46 47 48 49 49 50 50 51

    Weight kg 540 550 560 670 680 680 860 960 1070 1080 1110 1180 1150

    Refrigerant R -410A

    GLAC.HE 2015 2018 2020 2025 2026 2030 2035 2040 2045 2050 2056 2061 2071 2081

    Cooling capacity kW 41.7 47.4 55.0 62.5 69.6 85.1 96.6 108.0 121.9 137.8 160.4 178.4 201.2 227.1

    El. power consumption kW 12.9 14.5 16.7 19.3 21.8 26.5 30.2 33.6 38.3 42.6 48.9 55.4 63.5 70.5

    EER - 3.2 3.3 3.3 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2

    ESEER - 4.6 4.7 4.5 4.5 4.5 4.3 4.4 4.4 4.5 4.3 4.3 4.3 4.4 4.2

    Performance val-ues according toEN14511:2011

    Cooling capacity kW 41.4 47.1 54.7 62.1 69.2 84.6 95.9 107.3 121.2 137.0 159.4 177.5 200.2 225.7

    El. power consumption kW 13.1 14.8 17.1 19.6 22.2 26.9 30.9 34.3 39.0 43.4 49.8 56.4 64.5 71.9

    EER - 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.1 3.1

    ESEER - 4.3 4.4 4.2 4.3 4.3 4.1 4.1 4.2 4.3 4.1 4.1 4.1 4.2 4.0

    Max. current con-

    sumption

    A 35.0 37.2 47.4 51.8 57.6 68.8 74.4 79.7 89.4 103.3 121.1 134.2 148.6 167.1

    Max. power con-sumption kW 19.0 21.2 25.1 27.9 30.3 38.0 43.3 48.3 53.4 60.8 71.2 79.6 88.5 99.4

    Scrollcompressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1

    Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    Sound power level dB(A) 84 84 85 85 86 88 88 90 90 90 91 91 92 93

    Sound pressure level dB(A) 52 52 53 53 54 56 56 58 58 58 59 59 60 61

    Weight kg 480 540 550 560 570 680 830 960 1000 1080 1510 1550 1570 1810

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!Dimensions on previous page.

  • 7/21/2019 GEA Heat Exchangers

    14/76

    x14] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 4061 4121 CD2 / .SL (.HE) 159 kW to 352 kW

    Equipment

    Standard configuration with 4 scroll compressors Buffer tank and pump are optional (hydraulic module GLHM) addi-

    tionally fitted with a regulating valve, safety valve, expansion tank,

    air vent and fill connection

    Aluminium "Micro Channel" condenser

    Cooling operation down to -15 C ambient temperature possible

    (accessories)

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step II

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item Connection to BMS via optional interface

    Deliverable in three different versions:GLAC 4061 4121 CD2 as standard unit

    GLAC 4061 4121 CD2.SL as especially quiet version

    GLAC 4061 4121 CD2.HE as highly efficient version

    Refrigerant R -410A GLAC 4061 4071 4081 4091 4101 4111 4121

    Cooling capacity kW 164.7 194.1 217.8 248.2 289.2 308.4 326.7

    El. power consumption kW 58.3 66.7 78.9 88.6 99.0 108.4 118.2

    EER - 2.8 2.9 2.8 2.8 2.9 2.8 2.8

    ESEER - 4.1 4.4 4.3 4.4 4.3 4.3 4.2

    Performance valuesaccording toEN14511:2011

    Cooling capacity kW 163.9 193.2 216.8 247.1 287.9 307.2 325.2

    El. power consumption kW 59.1 67.6 79.9 89.7 100.3 109.7 119.6

    EER - 2.8 2.9 2.7 2.8 2.9 2.8 2.7

    ESEER - 3.9 4.2 4.1 4.2 4.0 4.1 4.0

    Max. current consumption A 133.0 157.0 176.0 198.0 229.0 243.0 256.0

    Max. power consumption kW 77.0 90.0 103.0 116.0 132.0 143.0 153.0

    Scrollcompressor Quantity 4 4 4 4 4 4 4

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2

    Capacity stages Quantity 4 4 4 4 4 4 4

    Sound power level dB(A) 92 92 93 94 95 95 95

    Sound pressure level dB(A) 60 60 61 62 63 63 63

    Length mm 3160 3160 3160 3160 4335 4335 4335

    Width mm 2250 2250 2250 2250 2250 2250 2250

    Height mm 2170 2170 2170 2170 2170 2170 2170

    Weight kg 1510 1680 1690 1830 2250 2300 2330

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    15/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x15]

    Chiller outside installation air-cooled

    GLAC 4061 4121 CD2.SL (.HE) 159 kW to 352 kW

    Refrigerant R -410A

    GLAC.SL 4061 4071 4081 4091 4101 4111 4121

    Cooling capacity kW 159.0 179.9 214.3 241.3 264.0 296.1 312.2

    El. power consumption kW 56.3 70.7 77.8 89.4 103.7 109.1 119.6

    EER - 2.8 2.5 2.8 2.7 2.6 2.7 2.6ESEER - 4.3 4.4 4.4 4.4 4.3 4.3 4.3

    Performance val-ues according toEN14511:2011

    Cooling capacity kW 158.3 179.2 213.4 240.3 263.0 294.9 311.0

    El. power consumption kW 57.0 71.5 78.7 90.4 104.7 110.2 120.9

    EER - 2.8 2.5 2.7 2.7 2.5 2.7 2.6

    ESEER - 4.1 4.2 4.2 4.2 4.1 4.2 4.1

    Max. current consump-tion A 133.0 157.0 184.0 207.0 229.0 251.0 264.0

    Max. powerconsumption kW 74.0 87.0 102.0 115.0 127.0 140.0 151.0

    Scrollcompressor Quantity 4 4 4 4 4 4 4

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2

    Capacity stages Quantity 4 4 4 4 4 4 4

    Sound power level dB(A) 82 83 83 84 84 86 86

    Sound pressure level dB(A) 50 51 51 52 52 53 53

    Weight kg 1550 1730 2030 2170 2300 2700 2730

    Refrigerant R -410A

    GLAC.HE 4061 4071 4081 4091 4101 4111 4121

    Cooling capacity kW 174.1 205.2 235.4 266.4 301.9 330.0 352.0

    El. power consumption kW 54.4 65.0 72.9 84.1 95.8 102.8 111.1

    EER - 3.2 3.2 3.2 3.2 3.2 3.2 3.2

    ESEER - 4.3 4.3 4.5 4.5 4.4 4.4 4.4

    Performance val-ues according toEN14511:2011

    Cooling capacity kW 173.6 204.5 234.2 265.2 300.9 328.8 350.6

    El. power consumption kW 54.9 65.8 74.1 85.3 96.7 104.0 112.5

    EER - 3.2 3.1 3.2 3.1 3.1 3.2 3.1

    ESEER - 4.2 4.1 4.2 4.2 4.3 4.2 4.2

    Max. current consum A 133.0 165.0 184.0 207.0 229.0 251.0 264.0

    Max. power consum. kW 77.0 94.0 107.0 120.0 132.0 147.0 157.0

    Scrollcompressor Quantity 4 4 4 4 4 4 4

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2

    Capacity stages Quantity 4 4 4 4 4 4 4

    Sound power level dB(A) 92 93 94 95 95 96 97

    Sound pressure level dB(A) 60 61 62 63 63 64 65

    Weight kg 1700 2150 2160 2290 2550 2930 2950

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2

    For project-related sound data calculations - use the obligatory sound power level!Dimensions on previous page.

  • 7/21/2019 GEA Heat Exchangers

    16/76

    x16] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 4131 ... 8321 CD2 / .SL (.HE) 354 kW to 885 kW

    Equipment

    High-efficiency optimized version with 4, 6 or 8 scroll compressors Buffer tank and pump are optional (hydraulic module GLHM) addi-

    tionally fitted with a safety valve, expansion tank, air vent and fill

    connection

    Aluminium "Micro Channel" condenser

    Cooling operation down to -15 C ambient temperature

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step II

    Unit main switch

    Configuration with an electronic expansion valve EEV

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item Connection to BMS via optional interface

    Deliverable in three different versions:GLAC 4131 8321 CD2 as standard unit

    GLAC 4131 8321 CD2.SL as especially quiet version

    GLAC 4131 8321 CD2.HE as highly efficient version

    Refrigerant R -410A GLAC 4131 4141 4161 5171 6181 5201 6211 6231 6241 8241 8261 8281 8301 8321

    Cooling capacity kW 354.3 378.8 413.4 458.3 501.3 525.6 569.4 603.7 634.9 665.3 707.9 759.4 793.5 826.6

    El. power consumption kW124.4 130.2 147.8 160.4 171.9 183.9 195.4 214.1 218.6 233.7 248.8 260.5 279.1 295.7

    EER - 2.9 2.9 2.8 2.9 2.9 2.9 2.9 2.8 2.9 2.9 2.9 2.9 2.8 2.8

    ESEER - 4.2 4.2 4.0 4.2 4.2 4.1 4.2 4.1 4.1 4.1 4.2 4.3 4.2 4.1

    Performance valuesaccording toEN14511:2011

    Cooling capacity kW 352.8 377.5 411.7 456.5 499.1 524.0 567.4 601.7 632.5 662.9 705.0 756.9 790.8 823.5

    El. power consumption kW 126.0 131.5 149.6 162.1 174.1 185.5 197.4 216.2 221.0 236.1 251.6 262.9 281.9 298.7

    EER - 2.8 2.9 2.8 2.8 2.9 2.8 2.9 2.8 2.9 2.8 2.8 2.9 2.8 2.8

    ESEER - 4.0 4.1 3.9 4.0 4.0 3.9 4.0 4.0 3.9 4.0 4.0 4.1 4.0 3.9

    Max. current consum. A 273.0 288.0 317.0 351.0 384.0 398.0 432.0 461.0 480.0 534.0 572.0 609.0 630.0 650.0

    Max. power consum. kW 166.0 177.0 198.0 214.0 231.0 249.0 265.0 286.0 299.0 329.0 348.0 367.0 381.0 395.0

    Scroll compressor Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 3 2 4 4 4 4 4

    Capacity stages Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8

    Sound power level dB(A) 96 96 96 96 97 97 97 97 98 98 98 99 99 99

    Sound pressure level dB(A) 64 64 64 64 65 65 64 64 65 65 65 66 66 66

    Length mm 3905 3905 5080 5080 5080 5080 6255 6255 6255 7430 7430 7430 7430 7430

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450

    Weight kg 2730 2770 2800 3400 3650 3690 4200 4220 4350 5260 5300 5370 5400 5430

    Performance data

    Sound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35C

    EUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    17/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x17]

    Chiller outside installation air-cooled

    GLAC 4131 ... 8321 CD2.SL (.HE) 354 kW to 885 kW

    Refrigerant R -410A GLAC.SL 4131 4141 4161 5171 6181 5201 6211 6231 6241 8241 8261 8281 8301 8321

    Cooling capacity kW 333.6 358.1 397.4 431.5 465.0 497.7 532.3 579.3 595.9 615.9 666.4 717.7 757.8 794.6

    El. power consump-tion kW 129.2 137.3 153.1 168.1 182.7 191.6 206.0 220.0 229.7 244.6 258.3 274.8 288.4 306.2

    EER - 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.6 2.6 2.6 2.6

    ESEER - 4.3 4.3 4.2 4.3 4.4 4.3 4.4 4.4 4.3 4.3 4.4 4.4 4.4 4.3

    Performance valuesas of EN14511:2011

    Cooling capacity kW 332.2 356.9 395.9 430.0 463.2 496.2 530.6 577.5 593.9 613.9 664.0 715.6 755.4 791.8

    El. power consumption kW 130.5 138.5 154.7 169.6 184.5 193.0 207.7 221.9 231.7 246.6 260.7 276.9 290.8 309.0

    EER - 2.6 2.6 2.6 2.5 2.5 2.6 2.6 2.6 2.6 2.5 2.6 2.6 2.6 2.6

    ESEER - 4.1 4.2 4.1 4.2 4.1 4.1 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1

    Max. current con-sumption A 266.0 283.0 312.0 344.0 375.0 390.0 422.0 453.0 468.0 524.0 561.0 598.0 619.0 640.0

    Max. power consumption kW 162.0 174.0 196.0 211.0 227.0 245.0 260.0 283.0 293.0 324.0 343.0 362.0 376.0 390.0

    Scrollcompressor Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 3 2 4 4 4 4 4

    Capacity stages Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8

    Sound power level dB(A) 86 86 86 87 87 87 87 88 88 88 89 90 90 90

    Sound pressure level dB(A) 53 53 53 54 54 54 54 55 55 55 56 57 57 57

    Weight kg 3060 3160 3200 3900 4110 4190 4640 4730 4790 5410 5810 6160 6200 6250

    Refrigerant R -410A GLAC.HE 4131 4141 4161 5171 6181 5201 6211 6231 6241 8241 8261 8281 8301 8321

    Cooling capacity kW 370.5 391.4 438.4 481.1 517.5 549.2 591.4 632.7 657.3 701.5 740.0 784.6 830.6 884.7

    El. power consumption kW 119.6 125.1 141.5 154.0 166.3 177.0 189.4 204.0 212.3 225.3 239.0 250.4 266.5 283.0

    EER - 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

    ESEER - 4.5 4.5 4.4 4.5 4.5 4.4 4.5 4.5 4.4 4.4 4.5 4.5 4.5 4.5

    Performance valuesas of EN14511:2011

    Cooling capacity kW 368.7 389.9 436.4 479.1 515.1 547.3 589.2 630.4 654.7 698.7 736.8 782.0 827.5 881.1

    El. power consumption kW 121.3 126.6 143.6 155.9 168.7 178.8 191.6 206.3 214.8 228.1 242.2 253.0 269.6 286.6

    EER - 3.0 3.1 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.1 3.1 3.1

    ESEER - 4.2 4.3 4.2 4.3 4.2 4.2 4.3 4.3 4.2 4.2 4.2 4.3 4.3 4.2

    Max. current con-sumption A 281.0 295.0 325.0 358.0 391.0 406.0 439.0 473.0 487.0 534.0 579.0 624.0 645.0 666.0

    Max. power consumption kW 170.0 181.0 202.0 218.0 235.0 253.0 269.0 292.0 303.0 329.0 352.0 375.0 389.0 403.0

    Scrollcompressor Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 3 2 4 4 4 4 4

    Capacity stages Quantity 4 4 4 5 6 5 6 6 6 8 8 8 8 8

    Sound power level dB(A) 97 97 97 97 98 98 98 99 99 99 99 100 100 100

    Sound pressure level dB(A) 65 65 65 64 65 65 65 66 66 66 66 67 67 67

    Weight kg 3060 3100 3130 3800 4050 4090 4540 4630 4690 5930 5970 6040 6070 6110

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!Dimensions on previous page.

  • 7/21/2019 GEA Heat Exchangers

    18/76

    x18] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 0751 1301 BA2 / .SL 145 kW to 266 kW

    Equipment

    Standard model with 1 screw compressor Buffer tank and pump are optional (hydraulic module GLHM) addi-

    tionally fitted with a regulating valve, safety valve, expansion tank,

    air vent and fill connection

    Cooling operation down to -15 C ambient temperature

    With separately enclosed water filter

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step III

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item

    Connection to BMS via optional interfaceCan be delivered in two different versions:

    GLAC 0751 1301 BA2 als Standardgert

    GLAC 0751 1301 BA2.SL in especially quiet version

    Refrigerant R-134a GLAC 0751 0851 0951 0961 1021 1301

    Cooling capacity kW 144.5 162.5 182.4 201.3 234.3 266.1

    El. power consumption kW 51.5 60.9 68.7 75.1 85.4 93.5

    EER - 2.8 2.7 2.7 2.7 2.8 2.9

    ESEER - 3.5 3.4 3.5 3.6 3.5 3.5

    Performance values asof EN14511:2011

    Cooling capacity kW 144.0 161.9 181.8 200.7 233.5 265.3

    El. power consumption kW 52.1 61.5 69.3 75.7 86.1 94.3

    EER - 2.8 2.6 2.6 2.7 2.7 2.8

    ESEER - 3.4 3.4 3.5 3.6 3.4 3.5

    Max. current consumption A 117.0 127.0 144.0 144.0 154.0 201.0

    Max. power consumption kW 70.1 76.0 87.9 87.9 94.1 121.0

    Screw compressor Quantity 1 1 1 1 1 1

    Refrigeration Circuits Quantity 1 1 1 1 1 1

    Minimum partial load level % 50 50 50 50 50 50

    Sound power level dB(A) 94 94 94 94 96 96

    Sound pressure level dB(A) 62 62 62 62 64 64

    Length mm 3110 3110 3110 3110 4610 4610

    Width mm 2222 2222 2222 2222 2222 2222

    Height mm 2150 2150 2150 2150 2150 2150

    Weight kg 1680 1710 1780 1860 2590 2720

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    19/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x19]

    Chiller outside installation air-cooled

    GLAC 0751 1301 BA2 / .SL 145 kW to 266 kW

    Refrigerant R-134a GLAC.SL 0751 0851 0951 0961 1021 1301

    Cooling capacity kW 134.3 150.9 165.8 197.4 223.1 238.3

    El. power consumption kW 53.3 62.7 73.5 76.2 90.3 101.5

    EER - 2.5 2.4 2.3 2.6 2.5 2.4ESEER - 3.5 3.4 3.4 3.7 3.6 3.3

    Performance values asof EN14511:2011

    Cooling capacity kW 133.8 150.4 165.3 196.8 222.4 237.7

    El. power consumption kW 53.8 63.2 74.0 76.8 91.0 102.1

    EER - 2.5 2.4 2.2 2.6 2.4 2.3

    ESEER - 3.5 3.3 3.3 3.6 3.5 3.3

    Max. current consumption A 112.0 122.0 139.0 143.0 148.0 195.0

    Max. power consumption kW 67.7 73.6 85.5 87.2 90.5 117.0

    Screw compressor Quantity 1 1 1 1 1 1

    Refrigeration Circuits Quantity 1 1 1 1 1 1

    Capacity stages Quantity 50 50 50 50 50 50

    Sound power level dB(A) 84 84 84 84 86 86

    Sound pressure level dB(A) 52 52 52 52 54 54

    Length mm 3110 3110 3110 4110 4610 4610

    Width mm 2222 2222 2222 2222 2222 2222

    Height mm 2150 2150 2150 2150 2150 2150

    Weight kg 1680 1770 1840 1980 2670 2720

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    20/76

    x20] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 1532 2632 BA2 / .SL 277 kW to 516 kW

    Equipment

    Standard configuration with 2 screw compressors

    Standard hydraulics module GLHM with integrated buffer tank and

    pump

    Pumps with larger delivery head are available

    Following pump heads for remaining pipework provided on-site

    Cooling operation down to -15 C ambient temperature

    With separately enclosed water filter

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step III

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item Connection to BMS via optional interface

    Can be delivered in two different versions:

    GLAC 1532 2632 BA2 als Standardgert

    GLAC 1532 2632 BA2.SL in especially quiet version

    Refrigerant R-134a GLAC 1532 1732 1932 1952 2432 2632

    Cooling capacity kW 276.9 328.9 366.3 398.2 466.1 515.9

    El. power consumption kW 103.8 121.4 138.9 154.3 178.6 193.0

    EER - 2.7 2.7 2.6 2.6 2.6 2.7

    ESEER - 3.6 3.6 3.6 3.6 3.6 3.5

    Performance values asof EN14511:2011

    Cooling capacity kW 275.9 327.6 364.8 396.5 463.9 513.3

    El. power consumption kW 104.8 122.7 140.4 155.9 180.9 195.5

    EER - 2.6 2.7 2.6 2.5 2.6 2.6

    ESEER - 3.6 3.5 3.5 3.8 3.5 3.4

    Max. current consumption A 233.0 259.0 295.0 295.0 371.0 413.0

    Max. power consumption kW 140.0 156.0 181.0 181.0 225.0 249.0

    Screw compressor Quantity 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2

    Minimum partial load level Quantity 25 25 25 25 25 25

    Sound power level dB(A) 97 97 97 97 99 99

    Sound pressure level dB(A) 65 65 65 65 67 67

    Length mm 4610 4610 4610 4610 5610 5610

    Width mm 2222 2222 2222 2222 2222 2222

    Height mm 2150 2420 2420 2420 2430 2430

    Weight kg 3130 3340 3490 3530 4590 4820

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    21/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x21]

    Chiller outside installation air-cooled

    GLAC 1532 2632 BA2 / .SL 277 kW to 516 kW

    Refrigerant R-134a GLAC.SL 1532 1732 1932 1952 2432 2632

    Cooling capacity kW 252.3 295.6 333.5 376.6 442.5 484.3

    El. power consumption kW 111.5 128.0 148.8 164.4 183.4 199.5

    EER - 2.3 2.3 2.2 2.3 2.4 2.4ESEER - 3.5 3.5 3.5 3.6 3.7 3.5

    Performance values ac-cording to EN14511:2011

    Cooling capacity kW 251.4 294.6 332.4 375.2 440.5 482.1

    El. power consumption kW 112.4 129.0 150.0 165.8 185.4 201.7

    EER - 2.2 2.3 2.2 2.3 2.4 2.4

    ESEER - 3.4 3.4 3.4 3.3 3.6 3.4

    Max. current consumption A 229.0 264.0 305.0 309.0 383.0 421.0

    Max. power consumption kW 138.0 154.0 180.0 182.0 222.0 244.0

    Screw compressor Quantity 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25

    Sound power level dB(A) 86 87 87 87 89 89

    Sound pressure level dB(A) 54 55 55 55 57 57

    Length mm 4610 4610 5610 5610 6610 6610

    Width mm 2222 2222 2222 2222 2222 2222

    Height mm 2150 2420 2430 2430 2430 2430

    Weight kg 3220 3450 3640 3840 5180 5450

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    22/76

    x22] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 1542 2642 BA2 / .SL 277 kW to 516 kW

    Equipment

    Standard configuration with 2 screw compressors

    Cooling operation down to -15 C ambient temperature

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step III

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item

    Connection to BMS via optional interface

    Can be delivered in two different versions:

    GLAC 1542 2642 BA2 als Standardgert

    GLAC 1542 2642 BA2.SL in especially quiet version

    Refrigerant R-134a GLAC 1542 1742 1942 1962 2442 2642

    Cooling capacity kW 276.9 328.9 366.3 398.2 466.1 515.9

    El. power consumption kW 103.8 121.4 138.9 154.3 178.6 193.0

    EER - 2.7 2.7 2.6 2.6 2.6 2.7

    ESEER - 3.6 3.6 3.6 3.6 3.6 3.5

    Performance valuesaccording toEN14511:2011

    Cooling capacity kW 275.9 327.3 364.8 397.1 464.8 514.1

    El. power consumption kW 104.8 122.9 140.3 155.4 179.9 194.7

    EER - 2.6 2.7 2.6 2.6 2.6 2.6

    ESEER - 3.5 3.4 3.4 3.5 3.5 3.4

    Max. current consumption A 227.0 253.0 287.0 287.0 360.0 398.0

    Max. power consumption kW 137.0 153.0 177.0 177.0 219.0 241.0

    Screw compressor Quantity 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25

    Sound power level dB(A) 97 99 97 97 99 99

    Sound pressure level dB(A) 65 67 65 65 67 67

    Length mm 4610 4610 4610 4610 5610 5610

    Width mm 2222 2222 2222 2222 2222 2222

    Height mm 2150 2420 2420 2420 2430 2430

    Weight kg 3490 3680 3810 4100 5140 5340

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    23/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x23]

    Chiller outside installation air-cooled

    GLAC 1542 2642 BA2 / .SL 277 kW to 516 kW

    Refrigerant R-134a GLAC.SL 1542 1742 1942 1962 2442 2642

    Cooling capacity kW 252.3 295.6 333.5 376.6 442.5 484.3

    El. power consumption kW 111.5 128.0 148.8 164.4 183.4 199.5

    EER - 2.3 2.3 2.2 2.3 2.4 2.4ESEER - 3.5 3.5 3.5 3.6 3.7 3.5

    Performance values ac-cording to EN14511:2011

    Cooling capacity kW 251.4 294.5 332.4 375.6 441.4 482.8

    El. power consumption kW 112.3 129.1 149.9 165.3 184.5 201.0

    EER - 2.2 2.3 2.2 2.3 2.4 2.4

    ESEER - 3.4 3.4 3.4 3.6 3.6 3.4

    Max. current consumption A 221.0 253.0 294.0 294.0 368.0 406.0

    Max. power consumption kW 134.0 148.0 174.0 174.0 214.0 236.0

    Screw compressor Quantity 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25

    Sound power level dB(A) 86.0 87.0 87.0 87.0 89.0 89.0

    Sound pressure level dB(A) 54.3 55.1 55.0 55.0 56.8 56.8

    Length mm 4610 4610 5610 5610 6610 6610

    Width mm 2222 2222 2222 2222 2222 2222

    Height mm 2150 2420 2430 2430 2430 2430

    Weight kg 3580 3790 3960 4410 5730 5970

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    24/76

  • 7/21/2019 GEA Heat Exchangers

    25/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x25]

    Chiller outside installation air-cooled

    GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW

    Refrigerant R-134a GLAC 2360 2390 2420 2450 2480 2482 2541 2600 2602

    Cooling capacity kW 794.4 848.3 917.1 989.4 1051.1 1134.4 1213.4 1243.9 1328.1

    El. power consumption kW 279.7 303.5 323.7 344.4 357.5 398.8 417.8 443.5 465.2

    EER - 2.8 2.8 2.8 2.9 2.9 2.8 2.9 2.8 2.9ESEER - 3.9 3.9 4.0 4.0 4.1 4.1 4.1 4.0 4.2

    Performance values accordingto EN14511:2011

    Cooling capacity kW 792.0 845.5 914.0 986.4 1047.5 1130.3 1210.2 1240.5 1324.0

    El. power consumption kW 282.1 306.3 326.9 347.4 361.0 402.9 421.1 447.0 469.3

    EER - 2.8 2.8 2.8 2.8 2.9 2.8 2.9 2.8 2.8

    ESEER - 3.7 3.7 3.9 3.9 3.9 4.0 4.0 3.9 4.1

    Max. current consumption A 590.0 635.0 673.0 722.0 763.0 763.0 852.0 926.0 926.0

    Max. power consumption kW 365.0 390.0 410.0 440.0 466.0 466.0 518.0 562.0 562.0

    Screw compressor Quantity 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 102 103 103 104 104 104 106 106 106

    Sound pressure level dB(A) 69 70 70 71 71 71 73 73 73

    Length mm 5800 7000 7000 7600 7600 7600 9400 9400 11200

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 6560 7010 7220 7860 8030 8090 9290 9380 10040

    Refrigerant R-134a GLAC 3630 3690 3720 3721 3722 4840

    Cooling capacity kW 1397.7 1495.1 1616.4 1681.4 1740.8 1817.5

    El. power consumption kW 478.1 532.3 541.9 579.9 604.1 672.5

    EER - 2.9 2.8 3.0 2.9 2.9 2.7

    ESEER - 4.0 3.9 4.1 4.2 4.2 4.0

    Performance values accordingto EN14511:2011

    Cooling capacity kW 1393.4 1490.0 1611.4 1675.9 1734.3 1811.6

    El. power consumption kW 482.4 537.5 546.9 585.5 610.7 678.4

    EER - 2.9 2.8 3.0 2.9 2.8 2.7

    ESEER - 3.9 3.8 - - - -

    Max. current consumption A 1021.0 1103.0 1144.0 1144.0 1144.0 1331.0

    Max. power consumption kW 621.0 673.0 699.0 699.0 699.0 812.0

    Screw compressor Quantity 3 3 3 3 3 4

    Refrigeration Circuits Quantity 3 3 3 3 3 4

    Minimum partial load level % 16 16 16 16 16 12

    Sound power level dB(A) 106 106 106 106 106 106

    Sound pressure level dB(A) 73 73 73 73 73 73

    Length mm 11200 11200 11200 11200 11200 12400

    Width mm 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500

    Weight kg 11440 11780 12350 12420 12480 13650

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    26/76

    x26] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW

    Refrigerant R-134a GLAC.SL 2150 2170 2190 2192 2220 2265 2270 2272 2315

    Cooling capacity kW 295.0 325.5 377.7 425.1 485.8 558.3 592.4 662.2 726.6

    El. power consumption kW 98.3 115.5 131.2 147.2 168.6 197.8 208.1 231.4 250.7

    EER - 3.0 2.8 2.9 2.9 2.9 2.8 2.9 2.9 2.9ESEER - 4.1 4.1 4.1 4.3 4.0 4.1 4.1 4.3 4.1

    Performance values accord-ing to EN14511:2011

    Cooling capacity kW 294.3 324.6 376.6 423.5 484.5 556.8 590.6 660.2 724.1

    El. power consumption kW 99.0 116.4 132.4 148.7 169.9 199.4 209.9 233.4 253.2

    EER - 3.0 2.8 2.9 2.9 2.9 2.8 2.8 2.8 2.9

    ESEER - 4.0 4.0 4.0 4.1 3.9 4.0 4.0 4.2 3.9

    Max. current consumption A 232.0 253.0 294.0 294.0 367.0 437.0 462.0 462.0 533.0

    Max. power consumption kW 141.0 152.0 180.0 180.0 221.0 263.0 279.0 279.0 326.0

    Screw compressor Quantity 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 87 87 88 88 89 89 90 90 91

    Sound pressure level dB(A) 55 55 56 56 57 57 57 57 58

    Length mm 4000 4000 4000 4000 4900 4900 4900 5800 5800

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 3870 3890 3970 4230 5340 5700 5810 6520 7190

    Refrigerant R-134a GLAC.SL 2360 2390 2420 2450 2480 2482 2541 2600 2602

    Cooling capacity kW 781.8 846.6 905.5 992.4 1032.6 1140.1 1175.8 1230.7 1293.5

    El. power consumption kW 275.9 290.3 317.8 335.7 361.1 392.0 419.9 436.0 472.1

    EER - 2.8 2.9 2.9 3.0 2.9 2.9 2.8 2.8 2.7

    ESEER - 3.9 4.0 4.0 4.1 4.1 4.3 4.2 4.1 4.2

    Performance values accordingto EN14511:2011

    Cooling capacity kW 779.6 843.8 902.5 989.3 1029.2 1135.9 1172.8 1227.3 1289.7

    El. power consumption kW 278.2 293.1 320.8 338.7 364.5 396.1 422.9 439.4 475.9

    EER - 2.8 2.9 2.8 2.9 2.8 2.9 2.8 2.8 2.7

    ESEER - 3.8 3.9 3.9 4.0 3.9 4.1 4.1 4.0 4.1

    Max. current consumption A 597.0 643.0 681.0 737.0 778.0 778.0 852.0 941.0 941.0

    Max. power consumption kW 369.0 394.0 414.0 448.0 474.0 474.0 518.0 570.0 570.0

    Screw compressor Quantity 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 91 92 92 93 93 94 94 94 94

    Sound pressure level dB(A) 58 59 59 60 60 61 61 61 61

    Length mm 4000 4000 4000 4000 4900 4900 4900 5800 5800

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 7590 7950 8370 9530 9550 10120 10590 10830 10990

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    27/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x27]

    Chiller outside installation air-cooled

    GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW

    Refrigerant R-134a GLAC.SL 3630 3690 3720 3721 3722 4840

    Cooling capacity kW 1358.9 1460.9 1531.3 1597.6 1654.4 1761.9

    El. power consumption kW 475.6 527.8 561.3 607.6 637.4 682.1

    EER - 2.9 2.8 2.7 2.6 2.6 2.6ESEER - 4.1 4.0 4.0 4.0 4.1 3.9

    Performance values accordingto EN14511:2011

    Cooling capacity kW 1354.9 1456.0 1527.0 1592.7 1648.7 1756.5

    El. power consumption kW 479.6 532.6 565.6 612.5 643.1 687.5

    EER - 2.8 2.7 2.7 2.6 2.6 2.6

    ESEER - 3.9 3.9 3.9 3.9 3.9 3.8

    Max. current consumption A 1021.0 1103.0 1144.0 1144.0 1144.0 1346.0

    Max. power consumption kW 621.0 673.0 699.0 699.0 699.0 820.0

    Screw compressor Quantity 3 3 3 3 3 4

    Refrigeration Circuits Quantity 3 3 3 3 3 4

    Minimum partial load level % 16 16 16 16 16 12

    Sound power level dB(A) 94 94 94 94 95 96

    Sound pressure level dB(A) 61 61 61 61 62 63

    Length mm 11200 11200 11200 11200 11200 11200

    Width mm 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500

    Weight kg 12830 12880 13390 13430 13470 15230

    Refrigerant R-134a GLAC.HE 2150 2170 2190 2192 2220 2260 2265 2270 2272

    Cooling capacity kW 310.9 356.3 406.1 455.1 512.3 558.4 596.9 633.8 703.5

    El. power consumption kW 97.9 112.9 127.4 144.6 162.7 178.1 188.8 199.2 223.2

    EER - 3.2 3.2 3.2 3.2 3.2 3.1 3.2 3.2 3.2

    ESEER - 4.1 4.1 4.2 4.4 4.1 4.2 4.2 4.2 4.2

    Performance values accord-ing to EN14511:2011

    Cooling capacity kW 310.1 355.3 404.7 454.0 510.8 556.8 595.1 631.6 701.2

    El. power consumption kW 98.6 113.9 128.8 145.8 164.2 179.6 190.6 201.4 225.6

    EER - 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

    ESEER - 4.0 4.0 4.1 4.2 3.9 4.1 4.0 4.1 4.0

    Max. current consumption A 232.0 260.0 294.0 294.0 367.0 406.0 437.0 462.0 477.0

    Max. power consumption kW 141.0 156.0 180.0 180.0 221.0 244.0 263.0 279.0 287.0Screw compressor Quantity 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 98 98 99 99 100 100 101 101 101

    Sound pressure level dB(A) 66 66 67 67 68 67 68 68 68

    Length mm 4000 4000 4000 4000 4000 4000 4000 4000 4000

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 3530 3650 3780 4260 4920 5370 5460 5920 6660

    Performance dataSound power level

    Sound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Cube-shaped radiaton 10 m distance reflection factor Q=2

    For project-related noise calculations, please only employ the binding sound power level!.

  • 7/21/2019 GEA Heat Exchangers

    28/76

    x28] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLAC 2150 4840 CA2 / .SL (.HE) 295 kW to 1818 kW

    Refrigerant R-134a GLAC.HE 2315 2360 2390 2420 2450 2480 2482 2541 3570

    Cooling capacity kW 775.3 851.0 905.9 977.6 1049.6 1103.1 1202.9 1255.1 1362.9

    El. power consumption kW 244.5 268.5 286.3 307.0 326.9 345.6 377.2 400.2 433.1

    EER - 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.2ESEER - 4.1 3.9 4.0 4.1 4.2 4.2 4.2 4.2 4.0

    Performance values accordingto EN14511:2011

    Cooling capacity kW 772.3 848.2 902.6 974.0 1046.0 1099.1 1198.1 1251.5 1360.6

    El. power consumption kW 247.5 271.4 289.7 310.6 330.4 349.6 381.9 403.7 435.4

    EER - 3.1 3.1 3.1 3.1 3.2 3.1 3.1 3.1 3.1

    ESEER - 3.9 3.8 3.9 3.9 4.0 4.0 4.0 4.1 3.9

    Max. current consumption A 541.0 605.0 650.0 696.0 737.0 778.0 793.0 867.0 945.0

    Max. power consumption kW 330.0 373.0 398.0 422.0 448.0 474.0 482.0 526.0 581.0

    Screw compressor Quantity 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 3

    Minimum partial load level % 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 101 102 102 103 103 103 103 104 104

    Sound pressure level dB(A) 68 69 69 70 70 70 70 71 71

    Length mm 7600 7600 7600 7600 7600 7600 7600 7600 7600

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 7070 7460 8220 8800 9340 9570 9820 10150 12270

    Refrigerant R-134a GLAC.HE 3630 3660

    Cooling capacity kW 1468.9 1542.8

    El. power consumption kW 467.9 491.3

    EER - 3.1 3.1

    ESEER - 4.2 4.2

    Performance values according toEN14511:2011

    Cooling capacity kW 1466.1 1539.6

    El. power consumption kW 470.7 494.4

    EER - 3.1 3.1

    ESEER - 4.1 0.0

    Max. current consumption A 1021.0 1062.0

    Max. power consumption kW 621.0 647.0Screw compressor Quantity 3 2

    Refrigeration Circuits Quantity 3 3

    Minimum partial load level % 16 25

    Sound power level dB(A) 104 104

    Sound pressure level dB(A) 71 71

    Length mm 11200 11200

    Width mm 2260 2260

    Height mm 2500 2500

    Weight kg 12720 12830

    Performance dataSound power levelSound pressure level

    At chilled water 12/7C and air intake temperature 35CEUROVENT certified figure, requirement specified by Eurovent 8/1 and ISO 9614

    Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    29/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x29]

    Chiller outside installation air-cooled

    GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling

    Equipment

    Unit with a free-cooling function with high energy-saving potential The free cooling mode is activated starting from 1 C temperature

    difference between outdoor air and water

    3-way valve for optimizing water circuits and efficiency

    with 2 scroll compressors

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step II

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item

    Connection to BMS via optional interface

    Can be delivered in two different versions:GLFC 0152 0612 BD2 as standard unit

    GLFC 0152 0612 BD2.SL in especially quiet version

    Refrigerant R -410A GLFC 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612

    Cooling capacity kW 37.4 44.3 53.5 58.7 76.7 90.3 99.2 113.4 129.2 143.9 161.6

    El. power consumption kW 15.2 16.4 20.7 23.9 30.1 32.7 37.7 43.3 46.2 54.2 62.8

    EER - 2.5 2.7 2.6 2.5 2.6 2.8 2.6 2.6 2.8 2.7 2.6Performance values ac-cording to EN14511:2011

    Cooling capacity kW 37.0 43.9 52.9 58.0 75.8 89.4 98.4 112.4 127.8 142.7 160.2

    El. power consumption kW 15.6 16.9 21.3 24.5 30.9 33.6 38.5 44.3 47.6 55.5 64.3

    EER - 2.4 2.6 2.5 2.4 2.5 2.7 2.6 2.5 2.7 2.6 2.5

    Max. current consumption A 33.6 35.8 48.4 52.8 63.4 71.6 79.8 93.3 103.0 116.1 133.0

    Max. power consumption kW 19.5 21.7 27.8 30.6 38.0 43.4 48.8 56.0 61.1 69.5 80.0

    Scrollcompressor

    Quanti-ty 2 2 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quanti-ty 1 1 1 1 1 1 1 1 1 1 1

    Capacity stages Quanti-ty 2 2 2 2 2 2 2 2 2 2 2

    Sound power level dB(A) 87 87 90 90 91 91 92 92 93 93 94

    Sound pressure level dB(A) 55 55 58 58 59 59 60 60 61 61 62

    Length mm 2200 2200 2602 2602 2602 3602 3602 3602 4602 4602 4602

    Width mm 920 920 1104 1104 1104 1104 1104 1104 1104 1104 1104

    Height mm 1780 1780 2175 2175 2175 2175 2175 2175 2175 2205 2205

    Weight kg 670 710 870 880 1060 1310 1340 1410 1650 1680 1740

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    30/76

    x30] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling

    Free cooling operation* GLFC 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612

    Performance data withoutfree cooling operation at

    35 C outdoor temperatureCooling capacity kW 41.0 48.0 58.0 64.0 83.0 98.0 108.0 123.0 140.0 156.0 175.0

    El. power consumption kW 16.0 17.0 21.0 24.0 32.0 34.0 39.0 45.0 47.0 56.0 65.0

    Performance data withfree cooling operation at 5C outdoor temperature

    Cooling capacity kW 31.0 36.0 42.0 44.0 55.0 70.0 72.0 84.0 99.0 102.0 114.0

    Share of free-cooling capacity % 77.0 74.0 73.0 69.0 66.0 71.0 67.0 68.0 70.0 65.0 65.0

    Capacity data at 100 % free-cooling mode

    Cooling capacity kW 41.0 48.0 58.0 64.0 83.0 98.0 108.0 123.0 140.0 156.0 175.0

    power consumption kW 1.5 1.5 4.2 4.2 4.2 4.2 4.2 6.3 6.3 6.3 8.4

    Air Inlet Temperature C 2.0 1.6 1.3 0.5 -0.1 0.9 0.0 0.2 0.8 -0.3 -0.3

    EER - 27.0 32.0 13.8 15.0 19.8 23.4 25.7 19.5 22.3 24.8 20.9

    Refrigerant R -410A GLFC.SL 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612

    Cooling capacity kW 35.4 43.2 48.5 54.7 72.3 84.2 96.1 105.2 118.4 134.0 154.3

    El. power consumption kW 15.4 17.1 20.4 23.3 29.9 34.2 37.6 43.6 48.3 56.1 62.4

    EER - 2.3 2.5 2.4 2.4 2.4 2.5 2.6 2.4 2.5 2.4 2.5

    Performance valuesas of EN14511:2011

    Cooling capacity kW 35.0 42.7 48.0 54.1 71.5 83.4 95.3 104.3 117.3 132.7 152.7

    El. power consumption kW 15.7 17.5 20.9 23.9 30.7 35.0 38.4 44.5 49.5 57.4 64.0

    EER - 2.2 2.5 2.3 2.3 2.3 2.4 2.5 2.3 2.4 2.3 2.4

    Max. current consumption A 32.4 40.4 48.4 52.8 63.4 75.4 83.6 93.3 106.8 119.9 133.0

    Max. power consumption kW 18.9 22.6 26.0 28.8 36.2 42.8 48.2 53.3 59.6 68.0 76.4

    Scrollcompressor Quantity 2 2 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 1 1 1 1 1 1 1 1 1 1 1

    Capacity stages Quantity 2 2 2 2 2 2 2 2 2 2 2

    Sound power level dB(A) 77 78 78 79 80 81 81 82 83 84 85

    Sound pressure level dB(A) 45 46 46 47 48 49 49 50 51 51 52

    Length mm 2200 2602 2602 2602 3602 3602 4602 4602 4602 4602 4602

    Width mm 920 1104 1104 1104 1104 1104 1104 1104 1104 1277 1277

    Height mm 1780 2175 2175 2175 2175 2175 2205 2175 2205 2350 2350

    Weight kg 680 860 920 940 1240 1350 1590 1610 1690 1920 2000

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    31/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x31]

    Chiller outside installation air-cooled

    GLFC 0152 0612 BD2 / .SL 37 kW to 162 kW with free cooling

    Free cooling operation* GLFC.SL 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612

    Performance data with-out free cooling opera-tion at 35 C outdoor

    temperature

    Cooling capacity kW 38.0 47.0 53.0 59.0 79.0 92.0 105.0 114.0 128.0 145.0 167.0

    El. power consumption kW 16.0 18.0 21.0 24.0 31.0 34.0 39.0 45.0 50.0 58.0 64.0

    Performance data with freecooling operation at 5 Coutdoor temperature

    Cooling capacity kW 25.0 30.0 34.0 38.0 50.0 59.0 69.0 72.0 80.0 90.0 98.0

    Share of free-coolingcapacity % 77.0 74.0 73.0 69.0 66.0 71.0 67.0 68.0 70.0 65.0 65.0

    Capacity data at 100 %free-cooling mode

    Cooling capacity kW 38.0 47.0 53.0 59.0 79.0 92.0 105.0 114.0 128.0 145.0 167.0

    Power consumption kW 0.6 1.5 1.5 1.7 1.7 2.6 2.6 2.6 3.4 3.4 4.4Air Inlet Temperature C -0.5 -0.9 -0.5 -0.6 -0.8 -0.6 -0.2 -0.9 -0.9 -1.1 -2.1

    EER - 63.7 31.3 35.0 34.6 46.2 35.2 40.3 43.8 37.6 42.5 37.9

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    32/76

    x32] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling

    Equipment

    Unit with a free-cooling function with high energy-saving potential

    The free-cooling operation begins from 1 C temperature difference

    between outdoor air and water

    3-way valve for optimizing water circuits and efficiency

    with 4 scroll compressors in two refrigeration circuits

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step II

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item

    Connection to BMS via optional interfaceCan be delivered in two different versions:

    GLFC 0604 ... 1204 BD2 as standard unit

    GLFC 0604 ... 1204 BD2.SL in especially quiet Ausfhrung

    Refrigerant R -410A GLFC 0604 0704 0804 0904 1004 1104 1204

    Cooling capacity kW 153.7 179.1 202.5 231.9 253.9 291.0 326.3

    El. power consumption kW 60.0 66.2 77.5 84.2 94.4 107.0 124.2

    EER - 2.6 2.7 2.6 2.8 2.7 2.7 2.6

    Performance values accordingto EN14511:2011

    Cooling capacity kW 152.1 176.9 199.8 229.7 251.4 287.9 322.6

    El. power consumption kW 61.6 68.3 80.3 86.4 96.9 110.0 127.9

    EER - 2.5 2.6 2.5 2.7 2.6 2.6 2.5

    Max. current consumption A 126.8 143.2 167.2 186.6 206.0 232.2 266.0

    Max. power consumption kW 76.0 86.8 101.8 112.0 122.2 139.0 160.0

    Scrollcompressor Quantity 4 4 4 4 4 4 4

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2

    Capacity stages Quantity 4 4 4 4 4 4 4

    Sound power level dB(A) 93 93 94 94 94 95 96

    Sound pressure level dB(A) 61 61 62 62 62 63 64

    Length mm 4110 4110 4110 5110 5110 5110 5110

    Width mm 2220 2220 2220 2220 2220 2220 2220

    Height mm 2150 2150 2150 2150 2150 2430 2430

    Weight kg 2200 2330 2510 2880 2940 3260 3400

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    33/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x33]

    Chiller outside installation air-cooled

    GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling

    Free cooling operation* GLFC 0604 0704 0804 0904 1004 1104 1204

    Performance data withoutfree cooling operation at 35 Coutside temperature

    Cooling capacity kW 167.0 195.0 221.0 252.0 275.0 316.0 354.0

    El. power consumption kW 62.0 68.0 80.0 86.0 97.0 110.0 128.0

    Performance data with freecooling operation at 5 C out-door temperature

    Cooling capacity kW 129.0 135.0 156.0 193.0 199.0 227.0 254.0

    Share of free-cooling capacity % 77.0 69.0 71.0 77.0 72.0 72.0 72.0

    Capacity data at 100 % free-cool-ing mode

    Cooling capacity kW 167.0 195.0 221.0 252.0 275.0 316.0 354.0

    Power consumption kW 8.4 8.4 12.6 12.6 12.6 12.6 16.8

    Air Inlet Temperature C 2.0 0.5 0.9 1.9 1.2 1.1 1.0EER - 19.9 23.2 17.5 20.0 21.8 25.0 21.1

    Refrigerant R -410A GLFC.SL 0604 0704 0804 0904 1004 1104 1204

    Cooling capacity kW 142.5 165.4 184.8 208.8 236.1 269.7 302.5

    El. power consumption kW 61.0 70.0 79.1 87.9 95.3 109.7 125.9

    EER - 2.3 2.4 2.3 2.4 2.5 2.5 2.4

    Performance values accordingto EN14511:2011

    Cooling capacity kW 141.1 163.7 182.7 207.1 234.0 267.2 299.4

    El. power consumption kW 62.3 71.8 81.3 89.6 97.4 112.2 128.9

    EER - 2.3 2.3 2.3 2.3 2.4 2.4 2.3

    Max. current consumption A 126.8 150.8 167.2 186.6 206.0 232.2 266.0

    Max. power consumption kW 72.4 85.6 96.4 106.6 116.8 133.6 152.8

    Scrollcompressor Quantity 4 4 4 4 4 4 4

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2

    Capacity stages Quantity 4 4 4 4 4 4 4

    Sound power level dB(A) 82 83 83 84 84 85 86Sound pressure level dB(A) 50 51 51 52 52 53 54

    Length mm 4110 4110 4110 5110 5110 5110 5110

    Width mm 2220 2220 2220 2220 2220 2220 2220

    Height mm 2150 2150 2150 2150 2150 2430 2430

    Weight kg 2280 2410 2580 2880 3040 3380 3520

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    34/76

    x34] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLFC 0604 ... 1204 BD2 / .SL 153 kW to 326 kW with free cooling

    Free cooling operation* GLFC.SL 0604 0704 0804 0904 1004 1104 1204

    Performance data withoutfree cooling operation at 35 Coutdoor temperature

    Cooling capacity kW 155.0 180.0 201.0 226.0 255.0 291.0 326.0

    El. power consumption kW 63.0 73.0 82.0 91.0 98.0 113.0 130.0

    Performance data with freecooling operation at 5 C out-door temperature

    Cooling capacity kW 97.0 112.0 115.0 140.0 148.0 166.0 188.0

    Share of free-cooling capacity % 63.0 62.0 57.0 62.0 58.0 57.0 58.0

    Capacity data at 100 % free-cool-ing mode

    Cooling capacity kW 155.0 180.0 201.0 226.0 255.0 291.0 326.0

    power consumption kW 3.4 5.2 5.2 5.2 5.2 5.2 6.9

    Air Inlet Temperature C -1.0 -1.0 -2.5 -1.1 -2.2 -2.5 -2.4EER - 45.5 34.6 38.7 43.5 49.0 56.0 47.3

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    35/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x35]

    Chiller outside installation air-cooled

    GLFC 2150 ... 2600 DA2 / .SL 286 kW to 1212 kW with free cooling

    Equipment

    Unit with a free-cooling function with high energy-saving potential

    The free cooling mode is activated starting from 1 C temperature

    difference between outdoor air and water

    3-way valve for optimizing water circuits and efficiency

    Autoadaptive microprocessor control

    Controller type: HVAC Systems Step III

    Unit main switch

    Master/slave operation with GEA HVAC System unit series availa-

    ble as an accessory item

    Connection to BMS via optional interface

    Can be delivered in two different versions:

    GLFC 2150 ... 2600 DA2 as standard unit

    GLFC 2150 ... 2540 DA2.SL as especially quiet version

    Refrigerant R-134a GLFC 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540 2600

    Cooling capacity kW 286.0 320.2 370.6 412.6 454.9 529.8 570.4 596.1 646.0 709.1 754.8 807.5 866.5 938.4 1025.7 1140.9 1212.4

    El. power consumption kW 92.4 106.6 119.3 138.3 146.8 179.5 192.4 207.6 219.7 233.8 256.2 275.5 286.9 317.3 331.8 386.1 429.6

    EER - 3.1 3.0 3.1 3.0 3.1 3.0 3.0 2.9 2.9 3.0 3.0 2.9 3.0 3.0 3.1 3.0 2.8

    Performance valuesas of EN14511:2011

    Cooling capacity kW 284.6 318.4 368.7 410.3 453.0 527.3 568.1 593.5 643.5 706.0 751.5 803.2 861.9 934.0 1020.2 1135.4 1205.9

    El. power consumption kW 93.7 108.4 121.1 140.6 148.7 182.0 194.7 210.2 222.2 236.9 259.6 279.8 291.5 321.6 337.3 391.6 436.1

    EER - 3.0 2.9 3.0 2.9 3.1 2.9 2.9 2.8 2.9 3.0 2.9 2.9 3.0 2.9 3.0 2.9 2.8

    Max. current con-sumption

    A 234.0 241.0 262.0 303.0 314.0 377.0 414.0 439.0 471.0 506.0 533.0 572.0 609.0 663.0 716.0 800.0 882.0

    Max. power consumption kW 116.0 145.0 157.0 185.0 192.0 226.0 248.0 264.0 284.0 306.0 324.0 350.0 375.0 404.0 433.0 485.0 537.0

    Screw compressor Quan-tity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quan-tity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    Minimum partial load level % 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 99.0 100.0 100.0 100.0 101.0 102.0 102.0 102.0 102.0 102.0 103.0 103.0 103.0 105.0 106.0 106.0 106.0

    Sound pressure level dB(A) 66.4 67.4 67.3 67.3 68.2 69.2 69.1 69.1 69.0 68.9 69.9 69.9 69.7 71.7 72.5 72.5 72.4

    Length mm 4000 4000 4900 4900 5800 5800 6400 6400 7000 7900 7900 7900 10000 10000 11800 11800 13000

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 4880 4990 5520 5700 7000 7410 8270 8310 8750 9600 10470 10570 12680 13180 13710 14930 15810

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    36/76

    x36] PR-2014-0100-GB Subject to modifications K0-06/2014

    Chiller outside installation air-cooled

    GLFC 2150 ... 2600 DA2 / .SL 286 kW to 1212 kW with free cooling

    Free cooling oper-ation*

    GLFC 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540 2600

    Performance data with-out free cooling opera-tion at 35 C outdoortemperature

    Cooling capacity kW 314.0 351.5 407.3 452.8 501.1 580.6 625.8 653.1 708.6 777.8 826.6 882.8 946.8 1027 1125 1250 1329

    El. power consumption kW 96.2 111.0 124.1 144.0 153.0 187.3 200.8 216.9 229.3 243.0 266.7 287.2 298.8 330.4 344.5 402.5 447.5

    Performance datawith free cooling op-eration at 5 C out-door temperature

    Cooling capacity kW 208.9 237.4 272.8 304.1 337.0 397.7 424.6 433.1 482.4 517.5 556.6 573.3 613.1 674.1 747.9 821.7 873.2

    Share of free-coolingcapacity

    % 67.0 68.0 67.0 67.0 67.0 68.0 68.0 66.0 68.0 67.0 67.0 65 65 66 66 66 66

    Capacity data at 100% free-cooling mode

    Cooling capacity kW 314.0 351.5 407.3 452.8 501.1 580.6 625.8 653.1 708.6 777.8 826.6 882.8 946.8 1027 1125 1250 1329

    Power consumption kW 11.9 15.9 15.9 19.9 19.9 23.9 23.9 23.9 27.8 31.8 31.8 31.8 31.8 39.8 47.7 47.7 47.7

    Air Inlet Temperature C 1.6 1.8 1.7 1.8 1.8 2.1 2.1 1.8 2.1 1.6 2.0 1.5 1.5 1.7 1.6 1.7 1.7

    EER - 26.4 22.1 25.6 22.8 25.2 24.3 26.2 27.3 25.5 24.5 26.0 27.8 29.8 25.8 23.6 26.2 27.9

    Refrigerant R-134a GLFC.SL 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540

    Cooling capacity kW 282.2 319.4 364.5 407.4 446.7 534.6 561.9 610.6 638.2 673.5 750.9 839.7 801.3 940.4 979.7 1107.0

    El. power consumption kW 93.3 103.0 120.6 135.4 148.7 174.1 194.1 201.4 219.7 242.2 255.6 293.8 276.3 312.0 340.8 391.9

    EER - 3.0 3.1 3.0 3.0 3.0 3.0 2.9 3.0 2.9 2.8 2.9 2.9 2.9 3.0 2.9 2.8

    Performance valuesas of EN14511:2011

    Cooling capacity kW 280.9 317.6 362.7 405.3 445.0 532.0 559.7 607.8 635.8 670.7 747.8 835.4 797.4 936.0 974.9 1101.8

    El. power consumption kW 94.6 104.8 122.4 137.6 150.4 176.7 196.3 204.1 222.1 244.9 258.7 298.1 280.2 316.4 345.7 397.0

    EER - 2.9 3.0 2.9 2.9 2.9 3.0 2.9 3.0 2.9 2.7 2.9 2.8 2.9 3.0 2.8 2.9

    Max. current con-sumption A 241.0 241.0 269.0 303.0 321.0 384.0 422.0 454.0 479.0 506.0 549.0 624.0 587.0 678.0 716.0 800.0

    Max. power consump-tion kW 120.0 145.0 161.0 185.0 196.0 230.0 252.0 272.0 288.0 306.0 332.0 383.0 358.0 412.0 433.0 485.0

    Screw compressor Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

    Minimum partial loadlevel % 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

    Sound power level dB(A) 89.0 89.0 89.0 90.0 91.0 91.0 91.0 92.0 92.0 92.0 92.0 92.0 92.0 94.0 94.0 95.0

    Sound pressure level dB(A) 56.8 56.7 56.7 57.6 58.4 58.3 58.3 59.2 59.2 59.2 58.9 58.9 58.9 61.0 61.0 61.9

    Length mm 4000 4900 4900 5800 5800 7000 7000 7900 7900 7900 10000 10000 10000 11800 11800 13000

    Width mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260

    Height mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500

    Weight kg 5380 5950 6040 6600 7500 8250 9070 9550 10040 10590 13020 13560 13060 14970 15060 16360

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 35C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    37/76

    PR-2014-0100-GB Subject to modifications K0-06/2014 x37]

    Chiller outside installation air-cooled

    GLFC 2150 ... 2600 DA2 / .SL 286 kW to 1212 kW with free cooling

    Free cooling oper-ation*

    GLFC.SL 2150 2170 2190 2200 2220 2260 2270 2300 2320 2340 2360 2390 2420 2450 2480 2540

    Performance datawithout free coolingoperation at 35 Coutdoor temperature

    Cooling capacity kW 309.3 350.1 399.6 446.2 491.1 585.4 615.2 669.3 698.6 735.3 821.0 874 912.7 1028 1071 1209

    El. power consumption kW 97.4 107.6 125.8 141.7 155.6 182.1 203.4 210.5 230.1 253.9 267.1 288.9 307.1 325.8 356.6 411

    Performance datawith free cooling op-eration at 5 C out-door temperature

    Cooling capacity kW 201.7 221.5 257.5 283.4 327.5 376.2 400.4 431.8 458.3 469.9 541.5 558.2 570.2 669.5 682.9 743.1

    Share of free-coolingcapacity

    % 65.0 63.0 64.0 64.0 67.0 64.0 65.0 65.0 66.0 64.0 66.0 64 62 65 64 61

    Capacity data at 100% free-cooling mode

    Cooling capacity kW 309.3 350.1 399.6 446.2 491.1 585.4 615.2 669.3 698.6 735.3 821.0 874 912.7 1028 1071 1209

    Power consumption kW 9.5 9.5 11.9 11.9 14.3 16.7 16.7 19.1 19.3 19.1 23.9 23.8 23.8 28.6 28.6 28.6

    Air Inlet Temperature C 1.0 1.0 1.0 0.9 1.0 0.9 1.3 1.0 1.3 1.0 1.3 0.9 0.6 1.2 0.9 0.4

    EER - 32.4 36.7 33.6 37.5 34.3 35.1 36.8 35.0 36.2 38.5 34.4 36.7 38.3 35.9 37.4 42.3

    Performance data*Free-cooling modeSound power levelSound pressure level

    Performance data in normal mode with chilled water 12/7C and air inlet temperature 30C with 30% ethylene glycolPerformance data in optimized conditions with chilled water free-cooling 15/10 with 30% ethylene glycolRequirement specified by ISO 3744Rectangular-shaped radiation 10 m distance reflection factor Q=2For project-related sound data calculations - use the obligatory sound power level!

  • 7/21/2019 GEA Heat Exchangers

    38/76

    x38] PR-2014-0100-GB Subject to modifications K0-06/2014

    Compressor/condensing unit outside installation air-cooled

    GLCU 2015 ... 4060 BC1/2 / .SL 40 kW to 171 kW

    Equipment

    Standard configuration with 2 or 4 scroll compressors

    2-circuit system

    Frame and panels made of galvanized steel

    Coated plastic

    Condenser made of copper pipes and corrugated aluminium fins

    Cooling operation down to -15 C ambient temperature

    Activation on-site

    Switch cabinet produced according to EN60204-1 / IEC204-1

    Unit main switch

    Shut off valve in liquid and suction line

    High and low pressure switch

    Continuously variable fan speed control

    Recommended accessories

    Refrigerating engineering accessories GLZCU... .R06

    (expansion valve, solenoid valve, filter drier and sight glass, to be

    mounted in each circuit by others on site)

    Can be delivered in two different versions:

    GLCU 2015 ... 4060 BC1 as standard unit

    GLCU 4052 ... 4060 BC2.SL in especially quiet version

    R -407C refrigerant GLCU(.SL) 2015 2018 2020 2025 2030 2041 2051 4052 40604052

    .SL

    4060

    .SL

    Cooling capacity kW 40.3 50.4 58.5 71.1 85.2 120.2 148.0 150.8 171.1 141.0 161.6

    El. power consumption kW 14.8 18.2 20.7 25.9 30.2 38.8 47.4 56.5 65.9 55.2 64.7

    EER - 2.7 2.8 2.8 2.8 2.8 3.1 3.1 2.7 2.6 2.6 2.5

    Max. current consumption A 31.4 41.3 46.7 59.7 64.7 88.0 105.0 115.0 129.0 115.0 129.0

    Max. power consumption kW 16.2 19.4 22.2 27.7 36.7 50.3 60.5 66.0 76.4 62.4 72.8

    Scrollcompressor Quantity 2 2 2 2 2 2 2 4 4 4 4

    Refrigeration Circuits Quantity 2 2 2 2 2 2 2 2 2 2 2

    Capacity stages Quantity 2 2 2 2 2 2 2 4 4 4 4

    Sound power level dB(A) 78 79 79 81 81 85 85 94 94 79 79

    Sound pressure level dB(A) 47 47 48 50 50 53 53 62 62 47 47

    Length mm 1695 2195 2195 2745 2745 3245 3245 3110 3110 3110 3110

    Width mm 1120 1120 1120 1120 1120 1120 1120 2220 2220 2220 2220

    Height mm 1420 1420 1420 1420 1420 1620 1620 1700 1700 1700 2150

    Weight kg 510 570 600 675 775 910 980 1520 1600 1620 1700

    Per ormance ataSound power levelSound pressure level

    Ony t e mo e s zes 4052 an 4060 are ava a e as SL untsAt evaporation temperature 7 C and air inlet temperatur