GENERAI_A_ire INSTALLER: PLEASE FILL OUT AND MAIL GUARANTEE CARD AFTER INSTALLATION IS COMPLETE. LEAVE INSTALLATION INSTRUCTIONS WITH HOME OWNER PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before beginning installation. Do not install where temperatures fall below 32 degrees F or where plenum temperatures exceed 200 degrees F. When wiring into a multi-speed blower circuit see Step 7D. INSTALLATION: The humidifier may be mounted with the 6" outlet to the right or left by reversing the position of the Bypass Cover. The humidifier may be mounted on the warm or return air plenum with equal efficiency. See Typical Installations below. ADDITIONAL MATERIALS THAT MAY BE NESSESARY: 1.1/4" diameter copper or plastic water supply tubing (G.F. #747-38 suggested) 2. 5/8" diameter drain tubing (G.F. #1099-16 suggested) 3. 3/4" O.D. drain tube clamp (G.F. #P-163 suggested) 4. 6" diameter galvanized by-pass pipe 5. 6" diameter galvanized elbow 6. 6" diameter galvanized damper 7. 6" diameter collar 8. wire, two-conductor #18 or heavier (G.F. #727-48 suggested) 9. transformer 120V, 60HZ primary 24V, 1OVA or greater secondary (G.F. #727-58 suggested) 10. air pressure switch (G.F. Model #12500 suggested) HIGH BOY ',,, ", WARMAIR ' GENERALAIre"ACSERIES HIGH EFFICIENCYAIRCLEANER WARM AIR COUNTER-FLOW LOW BOY COPPER TUBING PLASTIC TUBING Cut 6" hole and install connecting collar, 6" elbow and by-pass pipe (not supplied). USE UNCRIMPED END IN HUMIDIFIER CABINET. Connect by-pass pipe to collar and humidifier cabinet. Using holes at top and bottom of humidifier bypass opening drill 2---1/8" holes through bypass pipe and screw by-pass pipe to humidifier cabinet. Install bypass cover by placing the tab of the bypass cover marked "TOP" behind the top flange of the humidifier cabinet, push up on the bottom clip until it clears the opening of the humidifier cabinet then push in on the bottom of the bypass cover. NOTE: If furnace is used for summer cooling, install inline damper in by-pass pipe. Mount the self tapping saddle valve on either a cold or a hot water pipe. A side or top mount is best to avoid clogging from pipe sediment. Connect 1/4" O.D. tubing to the saddle valve. Copper tubing requires a brass compression nut and brass sleeve. Plastic tubing requires a brass insert inside the tubing, a plastic sleeve on the outside with a brass compression nut. NOTE: DO NOT USE PLASTIC TUBING ON HOT WATER OR IN CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT. INSTALLATION OF THIS SADDLE VALVE MUST MEET OR EXCEED LOCAL CODES AND ORDINANCES. TOP DUCT HUMIDISTAT MOUNTING TEMPLATE + 1, REMOVE ADHESIVE BACKING AND APPLY TO THE DUCT IN THE SELECTED LOCATION, 2, ACCU RATE|Y CENTER PUNCH ALL HOLES, 3. DRILl FOUR MOUNTING HOLES SIZE 3/32", DRILL NO, 42 OR 2 ram, 4. DRILl OTHER HOtES WITH 118" OR 3 mm DRILL, 5, BREAK METAL FROM GROUP OF HOLES AND CUT OUT ON SOLID LINE WITH SHEARS. + OUTDOOR SUGC TEMPERATURE SE oF oC % RH -20 29 IS°/o 0 -lS 2S_ +I0 -12 30_ *2O -7 3S% +3O -I 40_ GENERALAire _ E ] M _UMIDISTAT \ /

Upload: others

Post on 13-Nov-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

GENERAI_A_ire

INSTALLER: PLEASE FILL OUT AND MAIL GUARANTEE CARD AFTER INSTALLATIONIS COMPLETE. LEAVE INSTALLATION INSTRUCTIONS WITH HOME OWNER

PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before beginning installation. Do not install wheretemperatures fall below 32 degrees F or where plenum temperatures exceed 200 degrees F. When wiring into a multi-speed blower circuit see Step 7D.

INSTALLATION: The humidifier may be mounted with the 6" outlet to the right or left by reversing the position of the Bypass Cover. The humidifier maybe mounted on the warm or return air plenum with equal efficiency. See Typical Installations below.

ADDITIONAL MATERIALS THAT MAY BE NESSESARY:1.1/4" diameter copper or plastic water

supply tubing (G.F. #747-38 suggested)2. 5/8" diameter drain tubing (G.F. #1099-16 suggested)3. 3/4" O.D. drain tube clamp (G.F. #P-163 suggested)4. 6" diameter galvanized by-pass pipe5. 6" diameter galvanized elbow6. 6" diameter galvanized damper7. 6" diameter collar8. wire, two-conductor #18 or heavier

(G.F. #727-48 suggested)9. transformer 120V, 60HZ primary 24V,

1OVA or greater secondary (G.F. #727-58 suggested)10. air pressure switch (G.F. Model #12500 suggested)

HIGH BOY

',,,

", WARMAIR

' GENERALAIre"ACSERIES

HIGH EFFICIENCYAIRCLEANER

WARM AIRCOUNTER-FLOW LOW BOY

COPPERTUBING

PLASTICTUBING

Cut 6" hole and install connecting collar, 6" elbow and by-pass pipe(not supplied). USE UNCRIMPED END IN HUMIDIFIER CABINET.Connect by-pass pipe to collar and humidifier cabinet. Using holesat top and bottom of humidifier bypass opening drill 2---1/8" holesthrough bypass pipe and screw by-pass pipe to humidifier cabinet.Install bypass cover by placing the tab of the bypass cover marked"TOP" behind the top flange of the humidifier cabinet, push up on thebottom clip until it clears the opening of the humidifier cabinet thenpush in on the bottom of the bypass cover.

NOTE: If furnace is used for summer cooling, install inlinedamper in by-pass pipe.

Mount the self tapping saddle valve on either a cold or a hot water pipe. Aside or top mount is best to avoid clogging from pipe sediment. Connect 1/4"O.D. tubing to the saddle valve. Copper tubing requires a brass compressionnut and brass sleeve. Plastic tubing requires a brass insert inside the tubing,a plastic sleeve on the outside with a brass compression nut.

NOTE: DO NOT USE PLASTIC TUBING ON HOT WATER OR INCONTACT WITH ANY HOT PLENUM SURFACE OR DUCT.INSTALLATION OF THIS SADDLE VALVE MUST MEET OREXCEED LOCAL CODES AND ORDINANCES.

TOPDUCT HUMIDISTAT

MOUNTING TEMPLATE

+

1, REMOVE ADHESIVE BACKING AND APPLY TO

THE DUCT IN THE SELECTED LOCATION,

2, ACCU RATE|Y CENTER PUNCH ALL HOLES,

3. DRILl FOUR MOUNTING HOLES SIZE 3/32",

DRILL NO, 42 OR 2 ram,

4. DRILl OTHER HOtES WITH 118" OR 3 mm

DRILL,

5, BREAK METAL FROM GROUP OF HOLES AND

CUT OUT ON SOLID LINE WITH SHEARS.

+

OUTDOOR SUGC

TEMPERATURE SE

oF oC % R H

-20 29 IS°/o

0 -lS 2S_

+I0 -12 30_

*2O -7 3S%+3O -I 40_

GENERALAire_E ]

M _UMIDISTAT

\ /

Page 2: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

+ +

Select location on vertical surface of warm or return air plenum formounting humidifier and tape mounting template. Make sure thetemplate is level. Do not install humidifier or 6" bypass pipe where theblanked off ends of a cooling coil will restrict air flow to the humidifier.Extend horizontal centerline from template to the adjacent plenum.Scribe 6" circle 10" to 15" from side of humidifier, on cabinet centerline.

Center punch all 9 mounting holes on the template and drill with an1/8" drill bit. Cut out center section of template and save humidistatmounting template. Remove remaining template and start the threeinitial mounting screws. Mount humidifier cabinet in level positionand tighten screws. Install six additional screws at top and sides ofcabinet.

SADDLE VALVE INSTALLATION INSTRUCTIONS

Copper Pipe1. Retract piercing pin into valve body by turning handle counterclockwise.2. Screw valve body into upper bracket and tighten.3. Place rubber gasket over piercing pin.4. Assemble saddle valve over copper pipe using enclosed screws, nuts

and lower bracket.5. Tighten screws evenly and firmly. Brackets should be parallel.6. Complete compression connection to saddle valve outlet.7. Turn handle clockwise to pierce tubing and close saddle valve.8. Turn handle counterclockwise to open saddle valve, leave open for

several seconds to flush dirt from pipe and tubing.

Steel, Brass or Hard Plastic Pipe1. Shut off water supply and drain pipe.2. Turn handle clockwise to expose piercing pin and close saddle valve.3. Place rubber gasket over piercing pin.4. Drill 1/8" hole in pipe using a hand crank drill to avoid shock hazard.5. Assemble saddle valve over steel, brass or hard plastic pipe using

enclosed screws, nuts and lower bracket.6. Tighten screws evenly and firmly. Brackets should be parallel.7. Complete compression connection to saddle valve outlet.8. Turn handle counterclockwise to open saddle valve, leave open for

several seconds to flush dirt from pipe and tubing.

Threaded Pipe Fittings1. Turn handle clockwise to expose piercing pin and close saddle valve.2. Seal valve body threads using pipe tape or sealant.3. Install valve into 1/8" NPT fitting.4. Complete compression connection to saddle valve outlet.5. Turn handle counterclockwise to open saddle valve, leave open forseveral seconds to flush dirt from pipe and tubing.

COPPER TUBING PLASTIC TUBING

Attach solenoid valve into top of humidifier cover using 1/4 turn rotation.If using copper tube, leave two coils of tube next to cabinet to allowcover movement for changing pad. If using plastic tube, anchor tube 2inches below humidifier and leave some slack. This will allow full covermovement.

Loosen the fitting nut on the solenoid valve 1/2 turn. Push the 1/4" O.D.tubing straight into fitting until it bottoms on the fitting's shoulder.TIGHTEN NUT BY HAND. Additional tightening is not required.

DO NOT OVERTIGHTEN NUT AS THE THREADS WILLSTRIP AND THE FITTING WILL NOT FUNCTION PROPERLY.DO NOT USE PLASTIC TUBING IN CONTACT WITH ANYHOT PLENUM SURFACE OR DUCT.

HUMIDIFIER

24v. SOLENOID VALVE

24v. HU I60CY.

GRD

_1 ON-OFF HUMIDIFIER

727-58 24v. 24v. SOLENOID

ACC SWITCH TRANSFORMER VALVEEAC

50cv.11sv"(HOT)_llGRD

C

L1

115v. (HOT)60CY.

L2

OL1

115v. (HOT)

60CY.

FAN CONTROL

BLOWER MOTOR

727_8 24v. HUMIDIFIER

ON-OFF 24v. SOLENOID VALVETRANSFORMER

SWITCH _

12500 AIR HUMIDIFIERON-OFF

SWITCH PRESSURE 727-58 24v. 24v. SOLENOIDSWITCH TRANSFORMER VALVE

__ IIORD

Page 3: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

GENERAI_Aire

INSTALLATEUR : VEUILLEZ REMPLIR ET POSTER LA CARTE DE GARANTIE UNE FOIS L'INSTALLATIONTERMINI_E. LAISSER LES DIRECTIVES D'INSTALLATION AU PROPRII_TAIRE DE LA MAISON.

PRE_CAUTION : L'installateur doit etre un technicien qualifie et experimente. Couper I'alimentation electrique avant de commencer I'installation. Ne pas installerI'appareil dans un endroit o0 la temperature peut descendre sous 0 °C (32 °F) ou si la temperature du plenum depasse 93 °C (200 °F). Lors dIun branchement& un circuit de ventilateur & plusieurs vitesses, voir I'etape 7D.INSTALLATION : LIhumidificateur peut etre installe avec la sortie de 15 cm (6 po) & droite ou & gauche en inversant le couvercle de derivation. L'humidificateurfournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous.

MATE_RIAUX ADDITIONNELS POUVANT I_TRE REQUIS :

1. Tuyau d'alimentation en cuivre ou en plastique de 6 mm (1/4 po) (G.F. n°747-38 suggere)

2. Tube de drain de 1,6 cm (5/8 po) de diametre (G.F. n° 1099-16 suggere)3. Collier de tube de drain de 1,9 cm (3/4 po) de diametre exterieur (G.F. n °

P-163 suggere)4. Tuyau de derivation galvanise de 15 cm (6 po)5. Coude galvanise de 15 cm (6 po)6. Registre galvanise de 15 cm (6 po)7. Collier de 15 cm (6 po)8. Fil, deux conducteurs n° 18 ou plus Iourd (G.F. n° 727-48 suggere)9. Transformateur 120 V, 60 Hz primaire 24 V, 10 VA ou plus grand

secondaire (G.F n° 727-58 suggere)10. Commutateur de pression d'air (G.F. modele n° 12500 sugger6)

DRAIN

AIR CHAUD

GENERALAIre'SERIES AC

HAUT RENDEMENT FILTRE A AIR

.>..-".J

. y....--''

z.J ...--"

Couper un trou de 15 cm (6 po) et installer le collier de connexion, le coudeet le tuyau de derivation de 15 cm (6 po) (ne sont par fournis). UTILISERL'EXTR#MITE_ NON SERTIE DANS LE BO/TIER DE L'HUMIDIFICATEUR.Connecter le tuyau de derivation au collier et au boitier de IIhumidificateur.En utilisant les trous du haut et du bas de I'ouverture de derivation de

IIhumidificateur, percer 2 trous de 3 mm (1/8 po) & travers le tuyau dederivation et le visser au boTtier de I'humidificateur. Installer le couvercle dederivation en pla?ant sa patte, marquee " TOP ,1derriere la bridesuperieure du boftier de IIhumidificateur, pousser sur le taquet du basjusqu'A ce qu'il d6gage I'ouverture du boTtier de I'humidificateur, puispousser vers Ilinterieur sur le fond du couvercle de derivation.REMARQUE : Si la fournaise sert b rafrafchir I'air durant I'_te, installerle registre en ligne dans le tuyau de derivation.

TUYAUX ENCUIVRE

TUYAUX ENPLASTIQUE

Monter le robinet-vanne & etrier autotaraudeur sur un tuyau d'eau chaude oudIeau froide. Un montage lateral ou sur le dessus est ideal pour eviter unengorgement cause par les sediments du tuyau. Connecter un tuyau d'undiam. ext. de 6 mm (1/4 po) au robinet-vanne & etrier. Les tuyaux en cuivreexigent un ecrou & compression et un manchon en laiton. Les tuyaux enplastique exigent un insert en laiton & I'interieur des tuyaux et un manchon enplastique & Ilexterieur avec un ecrou & compression.

REMARQUE : NE PAS UTILISER DE TUYAUX EN PLASTIQUE AVEC DEL'EAU CHAUDE OU SUR UNE SURFACE DE CONTACT CHAUDE DEPLleNUM OU DE CONDUIT. L'INSTALLATION DE CE ROBINET-VANNE ,_,I_TRIER DOlT RESPECTER OU DI_PASSER LES EXIGENCES DESCODES LOCAUX ET AUTRES ORDONNANCES.

HAUTGABARIT DE FIXATION

DE L'HUMIDISTAT

POUR CONDUITS

1. ENLEVEZ LE SUPPORT ADHESIF ET POSEZ

SUR LE CONDUIT A L'ENDROIT CHOISI.

2, CENTREZ TOUS LES TROUS AU POINTEAU

AVEC PRECISION.

3. PERCEZ QUATRE TROUS DE MONTAGE DE

3/32 PO (MECHE N° 42 OU DE 2 ram),

4, PERCEZ LES AUTRES TROUS AVEC UNEMECIIE DE 1/8 PO OU DE 3 ram,

5, DETACHEZ LE METAL DU GROUPE DE

) TROUS ET DECOUPEZ SUR LA LIGNE

._!,E......................

OUTDOOR SUGGTEMPERATURE SE ¸

OF oC _ R H

-2O 29 15%

-10 -23 20_

0 -18 25_

+_O -12 30_

*20 -_ 3S_+_0 -1 40_

GENERALAir_

J

Page 4: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

/,

//

+

+

Selectionner un emplacement sur la surface verticale d'un plenum d'air chaud oude retour d'air pour monter rhumidificateur et appliquer du ruban adh6sif sur lamatrice de montage. S'assurer que la matrice est & niveau. Ne pas installerrhumidificateur ou le tuyau de derivation de 15 cm (6 po) & rendroit oQ I'extremit6de la plaque d'obturation d'un serpentin refroidisseur pourra restreindre le debitd'air vers rhumidificateur. I_tendre la ligne horizontale centrale de la matrice versle pl6num adjacent. Tracer un cercle de 15 cm (6 po) entre 25 et 38 cm (10 & 15po) du c6t6 de rhumidificateur, sur la ligne centrale du boftier.

INSTRUCTIONS D'INSTALLATION POUR LE ROBINET-VANNE A ETRIER

Tuyau en cuivre1. R6tracter la tige & perforation clans le corps de la vanne en tournant la poignee dans lesens horaire.

2. Visser le corps de la vanne dans le support superieur et serrer.

3. Placer le joint d'etanch6it6 en caoutchouc par-dessus la tige de perforation.4. Assembler le robinet-vanne & _trier par-dessus le tuyau en cuivre en utilisant les vis ecrous

supports inferieurs fournis.5. Serrer les vis de fa£on egale et ferme. Les supports doivent _tre paralleles.

6. Terminer la connexion de compression vers la sortie du robinet-vanne & etrier.7. Tourner la poign_e dans le sens horaire pour percer le tuyau et fermer le robinet-vanne & et

8. Tourner la poignee dans le sens antihoraire pour ouvrir le robinet-vanne & etrier et le laisserouvert pendant quelques secondes pour evacuer la salete du tuyau et de la tuyauterie.

Tuyau en acier, en laiton ou en plastique dur.

1. Fermer ralimentation en eau et vidanger le tuyau.2. Tourner la poignee dans le sens horaire pour exposer la tige de perforation et fermer le robinet-vanne a. etrier.

3. Placer le joint d'_tancheite en caoutchouc par-dessus la tige de perforation.

4. Percer un trou de 3 mm (1/8 po) avec une perceuse & manivelle pour eviter les risques de chocelectrique.

5. Assembler le robinet-vanne & _trier par-dessus le tuyau en acier, laiton ou plastique dur enutilisant les vis, ecrous et supports inferieurs fournis.

6. Serrer les vis de fa_on egale et ferme. Les supports doivent _tre paralleles.7. Terminer la connexion de compression vers la sortie du robinet-vanne & #trier.

8. Tourner la poignee dans le sens antihoraire pour ouvrir le robinet-vanne & etrier et le laisserouvert pendant quelques secondes pour evacuer la salete du tuyau et de la tuyauterie.

Raccords de tuyau filetes

1. Tourner la poignee dans le sens horaire pour exposer la tige de perforation et fermer le robinet-vanne & _trier.

2. Sceller le filetage du corps de la vanne avec un scellant ou du ruban adhesif.3. Installer la vanne dans un raccord NPT de 3 mm (1/8 po).

4. Terminer la connexion de compression vers la sortie du robinet-vanne &etder.5. Tourner la poignee dans le sens antihoraire pour ouvrir le robinet-vanne & etrier et le laisser

ouvert pendant quelques secondes pour evacuer la salete du tuyau et de la tuyauterie.

24 VOLTS DE LA VANNE

ELECTROMAGNI_TIQUE

24v. HU [60CY.

TERRE

727-58

TRANSFORMATEUR 24 VOLTS DE LA VANNE

ACC BOUTON DE 24 VOLTS ELECTROMAGN_TIQUI:EAC

115v . HUMIDISTAT_OCY (ELECTRIFI I I

TERREC

Marquer au pointeau centreur les 9 trous de montage de la matriceet percer avec un foret de 3 mm (1/8 po). Couper la section centralede la matrice et conserver la matrice de montage de rhumidistat.Enlever la matrice restante et engager les trois vis du montageinitial. Monter le boftier de rhumidificateur & niveau et serrer les vis.Installer six (6) vis supplementaires sur le dessus et sur les c6tes dubo_tier.

TUYAUX EN CUIVRE TUYAUX ENPLASTIQUE

Fixer I'electrovalve au dessus de I'humidificateur en lui appliquant une rotation de¼ de tour. Si des tuyaux de cuivre sont utilises, laisser deux serpentins de tuyau &

cSte de renceinte afin de permettre le mouvement du couvercle au moment deremplacer le tampon. Si, par contre, le tuyau de plastique est utilise, ancrer ce

dernier & 5 cm (2 po) sous rhumidificateur tout en laissant un certain jeu. Ainsi, lecouvercle pourra _tre deplace librement.

Desserrer I'ecrou du raccord de I'electrovalve de 1/2tour. Enfoncer le tuyau de ¼

po de diam. ext. dans le raccord jusqu'& ce qu'il s'appuie sur son epaulement.SERRER L'C:cROU ,&,LA MAIN. Un serrage supplementaire n'est pas requis.

NE PAS TROP SERRER L'ECROU; SES FILETS FOIRERAIENT, ET LERACCORD NE FONCTIONNERAIT PAS CORRECTEMENT. I_VITER

D'UTILISER TOUTE TUBULURE DE PLASTIQUE QUI ENTRERAIT ENCONTACT AVEC UNE CHAMBRE DE DISTRIBUTION OU UNE CONDUITE

CHAUDES.

L1

115v.60CY.

L2

COMMANDE DE VENTILATEUR

[_ [ ///_ VENTILATUR UNE

TRANSFORMATEUR 24 VOLTS DE LA VANNE

BOUTON DE 24 VOLTS F_LECTROMAGNETIQUE

_ _ TERRE

O BOUTON

PRESSOSTAT 727-58

D'AIR MODI_LE TRANSFORMATEUR 24 VOLTS DE LA VANNE12508 DE 24 VOLTS ELECTROMAGN_TIQUE

Li HUMIDISTAT115v. (F_LECTRI [6OCY.

-- TERRE

Page 5: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

MOUNTING ON THE RETURN AIR DUCTDo not install the humidistat on the warm air duct.

1. Locate the humidistat at least 24" upstream of the humidifier or bypass onthe return air duct. Avoid areas of direct radiation like secondary heatexchangers in the fan compartment•

2. Place template using level. Cut sensor hole as shown on template. Drillfour 3/32" holes as shown.

3. Remove the housing from the base by prying with a small screwdriver atthe notch in the side of the housing. Copy serial number, located onhousing back, onto the warranty registration.

4. Place the outer part of the foam gasket on the humidistat base and mountthe base with four screws. Low voltage wire may enter the humidistatunder the foam seal.

5. Connect wires to screw terminals on the control assembly as shown inwiring diagram. Replace housing.

WALL MOUNTING INSTRUCTIONS

1. Chose a location for the humidistat about five feet above the floor on an

inside wall with average room temperature and humidity conditions.2. Drill a small hole in the wall and run low voltage wiring to the location

chosen. Pull about 6" of wire through the hole. Plug the opening toprevent drafts from affecting the humidistat operation•

3. Remove the housing from the base by prying with a small screwdriver atthe notch in the side of the housing. Copy serial number, located onhousing back, onto the warranty registration.

4. Mount the base horizontally over the wires using level. Attach directly tothe wall, using four screws provided.

5. Connect wires to screw terminals on the control assembly as shown inwiring diagram. Replace housing.

Remove plastic bag from 990-13 evaporator pad, replace 16-4distributor trough and close 16-2 cover. Turn on water supply andcheck operation of humidifier• Set humidistat to a demand setting.With the furnace off, the solenoid valve should be closed. Start thefurnace, the solenoid valve should open when the blower or burnercircuit is energized. Check flow of water through distributor troughand evaporator pad. The solenoid valve will supply approximately 3.5GPH of water at a line water pressure of 60 psi. Leave humidistat setat the recommended setting.

Connect drain hose to 5/8" spout on humidifier cabinet using a 3/4" hoseclamp. Run 5/8" I.D. hose to suitable drain such as floor drain, sewer orlaundry sink. Be sure hose has continuous slope and is not kinked at anypoint.

Your Humidifier is engineered to give helpful and trouble-freehumidification. For maximum efficiency the following cleaningprocedures should be carried out at the end of each heating season:

1. Turn off water supply and electrical power to humidifier.2. Open humidifier cover, remove trough and evaporatorpad. If water line prevents cover opening disconnect waterline from solenoid valve• Clean excessive mineral depositsfrom the distributor trough, humidifier cover and humidifiercabinet. A solution of 1/2 vinegar & 1/2 water will helploosen mineral deposits.3. If the evaporator pad has excessive mineral deposits,replace with a new "990-13" evaporator pad. Install troughand replace cover.4. In heavy mineral areas or if the solenoid valve fails tofunction disconnect the 1/4" water supply line from thesolenoid valve. Carefully pull the filter from the solenoidvalve. Clean the mineral deposits from all parts. If theorificebeyond the filter is clogged, it may be opened byinserting a small needle• Reinsert the filter into the solenoidvalve.5. Reconnect the 1/4" water line to the solenoid valve ifnecessary. Tighten nut by hand, additional tightening is not

required. DO NOT OVERTIGHTEN NUT AS THETHREADS WILL STRIP AND THE FITTING WILL

NOT FUNCTION PROPERLY. Turn on the water

supply and check all points for leakage. The operation ofthe unit may be checked by starting the furnace• Thehumidifier operates only when the furnace blower is runningor the burner circuit is energized. The humidifier is nowready for operation.

DISTRIBUTORTROUGH

PART #990-13EVAPORATOR

PAD

PART #16-1HUMIDIFIER

CABINET

PARTS NOT SHOWN:

800UST SADDLE VALVEM-2 HUMIDISTAT ASSY.

6. During the summer, turn off water supply and electricalpower to humidifier• Close inline air damper if installed. @ Copyright 2001,2002 GENERAL FILTERS, INC.

All Rights ReservedFORM NO. 16-18 (FILE 11068) REV. D

PART #16-2COVER

PART #16-20SOLENOIDVALVE ASS'Y

PART #16-12NER

SCREEN

PART #P-236\,4_"_ SOLENOID

•+j FITTINGHARDWARE

Litho in U.S.A.

CUT TEMPLATE ALONG THIS LINE

Page 6: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

INSTRUCTIONSFORWIRINGPROVIDE SUFFICIENT WIRE TO ALLOW COVER TO

FULLY OPEN. Ground wire may be omitted in most

municipalities, CHECK WITH LOCAL AUTHORITIES

FOR COMPLIANCE.

FIG. 7A, 7B WlTH FURNACE CIRCUIT BOARD

On furnaces with output terminals HUM, ACC, or EAC checkoutput voltage to determine if terminals are 24V. or 115V.

NOTE: ALL WIRING SHOULD COMPLY WITH LOCAL

ELECTRICAL CODES.

FIG. 7C WITH SINGLE SPEED BLOWER MOTOR

On furnaces with single speed blowers, mount a 24v. transformer on ajunction box with 115v. primary leads connected in parallel with the blowercircuit. Connect the leads from the 24v. solenoid valve to the terminalscrews on the transformer. Connect humidistat in series with the 24v.circuit.

FIG. 7D WITH TWO SPEED BLOWER MOTOR

On furnaces with a two speed blower, the humidifier and a Model 12500Air Pressure Switch may be wired from a continuous 115 volt powersource. Install the on/off switch and Air Pressure Switch in series with thetransformer primary on the hot or black wire. The Air Pressure Switch willdetect furnace operation and supply power to the humidifier accordingly.

The operating principle of the humidifier is based on the most efficient and economical means of evaporating water tothe air. The humidifier uses only five watts of electrical power during operation, less than the smallest household lightbulb. The heat necessary for evaporating water is produced by the furnace.

The water supply to the humidifier is controlled by the electric solenoid valve. The humidistat connected in serieswith the solenoid provides low voltage control of the humidifier. The humidistat has a SPST switch and is designed forwall mounting in the living area or surface mounting on the return air duct. RANGE: 10% to 60% RH ELECTICALRATING: 24 VAC / 60 Hz. DO NOT SET RELATIVE HUMIDITY TOO HIGH DURING COLD WEATHER. EXCESSIVEHUMIDITY MAY CAUSE CONDENSATION ON WINDOWS OR IN WALLS. REFER TO RECOMMENDEDSETTINGS ON HUMIDISTAT.

Water flows through a strainer, is metered through an orifice to provide the proper amount of water, and is supplied tothe evaporator pad by the distributor trough. Approximately 200 CFM of air is by-passed from the warm air plenumthrough the humidifier and returned to the cold air plenum. Moisture is evaporated to the air passing through theevaporator pad.

Minerals are not blown into the air stream as occurs in atomizing humidifiers; they are left on the evaporator padwhere a high percentage is carried off with the waste water.

When the humidifier is installed and operating, no adjustments are necessary other than setting the control knob onthe humidistat to the desired level of humidification.

To turn the humidifier off, close water supply valve, switch electrical power off and turn humidistat off. If furnace isused for summer cooling or ventilating close inline air damper if installed..

ATOUTSIDE RECOMMENDED

TEMPERATURE SETTING

-20OF -29°C

-10°F -23°C0°F -18°C

+10°F -29°C+20OF - 7oc

+30OF - 1oc

15%

20%25%

30%

35%40%

This humidifier, if properly registered by the return of the warrantyregistration card to the manufacturer, is warranted to the

consumer against defects in materials and workmanship for aperiod of one year from the date of installation. Evaporator pads,

sleeves or plates are not covered by this limited warranty or anyother warranties. Any other defective parts will be repaired without

charge except for removal, reinstallation and transportation costs.To obtain repair service under this limited warranty, the consumer

must send the defective part or the complete humidifier to themanufacturer.

THERE ARE NO EXPRESS WARRANTIES COVERING THIS

HUMIDIFIER OTHER THAN AS SET FORTH ABOVE, THEIMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS

FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATIONTO ONE YEAR. THE MANUFACTURER ASSUMES NO

LIABILITY IN CONNECTION WITH THE INSTALLATION OR USE

OF THIS PRODUCT, EXCEPT AS STATED IN THIS LIMITEDWARRANTY. THE MANUFACTURER WILL IN NO EVENT BE

LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.

This limited warranty gives you specific legal rights, and you may

also have other rights which vary from state to state. Some statesdo not allow either limitations on implied warranties, or exclusions

from incidental or consequential damages, so the above exclusionand limitation may not apply to you.

Any questions pertaining to this limited warranty should be

addressed to the manufacturer. (U.S.A.: The manufacturer haselected not to make available the informal dispute settlement

mechanism which is specified in the Magnuson-Moss Warranty

Act.)

GENERAL FILTERS, INC. CANADIAN GENERAL FILTERS,43800 GRAND RIVER AVE. LTD. 39 CROCKFORD BLVD.

NOVI, MICHIGAN 48375-1115 SCARBOROUGH, ONTARIOMIR3B7

Visit our website at

WWW. GENERA LA IRE. COM

OWNER REGISTER ONLINE AT WWW.GENERALAIRE.COM ORFILL IN REGISTRATIONAND MAIL TO:

GENERAL FILTERS, INC.43800 GRAND RIVER AVE.

NOVl, MICHIGAN 48375-1115

WAR RANTY REGISTRATION

MODEL SL-16 FLOW THROUGH BYPASS HUMIDIFIER

OWNER'S NAME

STREET ADDRESS

CITY STATE

DEALER'S NAME

STREET ADDRESS

CITY STATE

Humidifier HumidistatSERIAL NUMBER SERIAL NUMBER

POSTAL CODE

POSTAL CODE

DATE OF INSTALLATION

CUT TEMPLATE ALONG THIS LINE

Page 7: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

INSTALLATION SUR LE CONDUIT DE REPRISE D'AIR

Ne pas installer rhumidistat sur le conduit d'air chaud.

1. Installez I'humidistat au moins 24 po en amont de I'humidificateur ou de la d6rivationdu conduit de reprise d'air. Evitez les zones de radiation directe, relies que les

echangeurs de chaleur secondaires darts le compartiment du ventilateur.2. Orientez le gabarit au moyen d'un niveau. Decoupez I'orifice du capteur comme le

gabarit le montre. Percez quatre trous de 3/32 po tel qu'illustre.

3. Retirez le boitier du socle en soulevant celui-ci par effet de levier au moyen d'un petittournevis enfonce dans I'encoche laterale du boTtier. Recopiez le num_ro de s6rie,

qui figure & I'arriere du be_tier, sur la carte d'enregistrement de la garantie.4. Posez la partie exterieure de la garniture en mousse sur le socle de I'humidistat et

fixez le socle en place au moyen de quatre vis. Les fils #.basse tension peuvent _tre

glisses darts I'humidistat sous la garniture en mousse.5. Branchez les fils aux bornes & vis du module de commande tel qu'illustr6s aux

schemas de c&blage. Remettez le boTtier en place.

DIRECTIVES POUR FIXER L'APPAREIL AU MUR

1. Choisissez un emplacement pour de I'humidistat sur une paroi interieure qui se trouveau

moins cinq pieds au dessus du sol, et o3 r6gne une temperature et un taux d'humiditerelative moyenne par rapport aux conditions dans la salle.

2. Percez un petit trou dans le tour et amenez un c&ble a basse tension jusqu'&I'emplacement choisi. Tirez sur le c&ble jusqu'& ce qu'environ 6 po de fil depassent

du trou. Rebouchez le trou pour eviter que les courants d'air ne nuisent au bonfonctionnement de I'humidistat.

3. Retirez le bouton et le boftier du socle en soulevant le boftier par effet de levierau moyen d'un petit tournevis enfonce dans I'encoche laterale du boftier. Inscrivez le

numero de serie, inscrit & I'arriere du boitier, sur le bon de garantie.4. Montez le socle & I'horizontale, au dessus des fils. Vissez-le directement au mur,

en utilisant les vis fournies.

5. Branchez les ills aux bornes & vis du module de commande tel qu'illustre aux

schemas de c&blage. Remettez le boftier et le bouton en place.

Enlever le sac de plastique recouvrant le bloc evaporateurn° 990-13, replacer la goulotte du distributeur n ° 16-4 et fermer le

couvercle n ° 16-2. Ouvrir I'alimentation en eau et verifier le fonctionnement

de I'humidificateur. Regler I'humidistat en mode de demande. Lorsque lafournaise est eteinte, la vanne 61ectromagnetique doit _tre fermee.Demarrer la fournaise, la vanne electromagnetique devrait s'ouvrir Iorsque lecircuit du ventilateur ou du br01eur est activ6. Verifier le debit d'eau passantpar la goulotte du distributeur et le bloc evaporateur. La vanne61ectromagn6tique fournit environ 13,2 I/h (3,5 gal/h) d'eau & une ligne depression de 60 psi. Laisser I'humidistat au reglage recommande.

Connecter le tuyau d'evacuation au bec de 1,6 cm (5/8 po) situe sur leboftier de I'humidificateur en utilisant un collier de durite de 1,9 cm (3/4po). Acheminer un boyau d'un diam. int. de 1,6 cm (5/8 po) vers un drainadequat, comme un drain de sol, d'egout ou d'evier de lavage. S'assurerque le boyau est en pente continue et n'est d6forme en aucun point.

LE PROPRII_TAIRE DOlT REMPLIR LA CARTED'ENREGISTREMENT ET LA POSTER AU :

GENERAL FILTERS, INC.43800 GRAND RIVER AVE.

NOVI, MICHIGAN 48375-1115

Enregistrement de la garantie

Humidificateur&derivationventileeMODI_LESL-16

Nom du proprietaire:

Adresse:.

Ville:

Nom du marchand:

Adresse:.

Ville:HumidifierNum6ro de S6rie:.

DATE DE INSTALLATION:

Province: Code postal:

Province: Code postal:HumidistatNumero de Serie:.

Votre humidificateur est con£u pour fournir une humidific

sans problemes. Pour b6neficier d'un fonctionnement m

etapes de nettoyage ci-dessous & la fin de chaque saisc

1. Fermer I'alimentation en eau et en electricit6 de I'hurr

2. Ouvrir le couvercle de I'humidificateur, enlever la gou

bloc evaporateur. Si le niveau d'eau emp_che I'ouvertur

couvercle, debrancher la conduite d'eau de la vanne

electromagn6tique. Nettoyer les dep6ts excessifs de mil

goulotte du distributeur, du couvercle de I'humidificateur

boRier. Une solution moitie vinaigre, moitie eau aide a d

dep(Sts de mineraux.

3. Si le bloc 6vaporateur contient trop de dep(Sts de min_

remplacer par un neuf" 990-13 ". Installer la goulotte et

couvercle en place.4. Dans les endroits riches en min6raux ou si la vanne

61ectromagn6tique est d6faillante, d6connecter la ligne

d'alimentation en eau de 6 mm (1/4 po) de la vanne

electromagn6tique. Tirer avec precaution le filtre de lav

electromagn6tique. Nettoyer les dep6ts de mineraux de

pieces. Si I'orifice est bloque, on peut I'ouvrir en y ins6r_

petite aiguille. R6ins6rer le filtre dans la vanne electrom

5. Raccorder la conduite d'eau de 6 mm (1/4 po) a lava

electromagnetique au besoin. Serrer I'ecrou a la main,

serrage supplementaire n'est requis. NE PAS TROP SEL'€:CROU SOUS PEINE D'ENDOMMAGER LE FILETA_

D'ENTRAINER UN MAUVAIS FONCTIONNEMENT DU

Ouvrir I'alimentation en eau et verifier tousles points de

fonctionnement de I'appareil peut _tre verifie en demarn

fournaise. L'humidificateur fonctionne uniquement Iorsq_

ventilateur de la fournaise est en marche ou que le circL

est active. L'humidificateur est maintenant pr_t & fonctio

6. Pendant la periode d'ete, fermer ralimentation en ea_

_lectricite de I'humidificateur. Fermer le registre en ligrinstalle.

FORMULAIRE N ° 16-18 (DOSSIER 1106_

COUPER LA MATRICE LE LONG DE CETTE LIGNE

Page 8: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

INSTRUCTIONS POUR LE CABLAGE

LAISSER SUFFISAMMENT DE C,&BLAGE POUR

PERMETTRE D'OUVRIR COMPL#TEMENT LE COUVERCLE.

Dans la plupart des municipalites, le fil de terre n'est pasn6cessaire, V¢:RIFIER AVEC LES AUTORIT¢:S LOCALES

POUR VOUS INFORMER DE LA RE_GLEMENTATION.

FIG. 7A, 7B AVEC CARTE DE CIRCUIT IMPRIME

Sur les fournaises equip6es des bornes de sortie HUM, ACC ou EAC,verifier la tension de sortie pour determiner si les bomes sont de 24 Vou 115 V.

REMARQUE : TOUT LE C,4BLAGE DOlT RESPECTER LES CODESELECTRIQUES LOCAUX.

FIG. 7C AVEC MOTEUR DE VENTILATEUR A VITESSE UNIQUE

Sur les fournaises equip6es de ventilateurs a_une seule vitesse, monter untransformateur de 24 volts sur un boftier de raccordement avec les fils de

connexions principaux de 115 volts connectes en parallele avec le circuit duventilateur. Connecter les ills de 24 volts de la vanne electromagnetique auxvis de borne du transformateur. Connecter rhumidistat en serie avec le circuitde 24 volts.

FIG. 7D AVEC MOTEUR DE VENTILATEUR A DEUX VITESSES

Sur les fournaises equip6es d'un ventilateur & deux vitesses, I'humidificateuret un pressostat d'air modele 12500 peuvent 6tre raccord6s & une sourced'alimentation electrique continue de 115 volts. Installer le commutateurmarche/arr6t et le pressostat d'air en serie avec le transformateur pfimaire surle fil chaud ou le fil noir. Le pressostat d'air detectera le fonctionnement de lafournaise et foumira I'alimentation electrique necessaire & I'humidificateur.

Le principe de fonctionnement de rhumidificateur est bas6 sur la fa?on la plus efficace et la plus economique d'6vaporer I'eaudans I'air. L'humidificateur utilise uniquement cinq (5) watts de courant 61ectfique Iorsqu'il fonctionne, c'est-&-dire moins que laplus petite ampoule electrique de votre maison. La chaleur necessaire pour 1'6vaporation de I'eau est produite par la fournaise.

L'alimentation en eau vers I'humidificateur est contr61ee par la vanne electromagn6tique. L'humidistat connecte en serie avecla vanne 61ectromagn6tique fournit automatiquement un contrSle de basse tension & I'humidificateur. L'humidistat est munid'un commutateur SPST et est con£u pour le montage mural dans la pattie habitee, le montage & fleur ou en surface sur leconduit de retour. PLAGE : 10 & 60 % HR. CARACT#RISTIQUES ELECTRIQUES : 24 V c.a. / 60 Hz. NE PAS RI_GLERL'HUMIDIT¢: RELATIVE TROP HAUT PENDANT LA PI_RIODE HIVERNALE. TROP D'HUMIDIT¢: PEUT ENTRAiNER DE LACONDENSATION SUR LES VlTRES OU SUR LES MURS. SE R¢:FI_RER AUX RC:GLAGES RECOMMAND¢:S SURL'HUMIDISTAT.

L'eau s'ecoule par une crepine, est mesuree par un orifice pour fournir la quantite adequate et alimente le bloc evaporateur parla goulotte du distributeur. Environ 5,66 metres cubes par minute st deriv6 du plenum d'air chaud, passe par rhumidificateur etest renvoye au plenum d'air froid. L'humidite est evapor6e dans I'air en passant par le bloc evaporateur.

Les mineraux ne sont pas souffles dans le courant d'air, comme c'est le cas avec les humidificateurs a pulverisation; ils restentsur le bloc evaporateur oQ un fort pourcentage est evacu6 avec les eaux usees.

Lorsque I'humidificateur est installe et fonctionne, aucun reglage n'est n6cessaire sauf le r6glage du niveau voulud'humidification par le bouton de commande sur I'humidistat.

Pour eteindre I'humidificateur, fermer la vanne d'alimentation en eau, mettre hors tension et fermer I'humidistat. Si la urnaisesert a rafrafchir ou & ventiler I'air durant I'et6, fermer le registre en ligne s'il a 6te installe.

_. LATEMP#:RATURE RI_GLAGE

EXTleRIEURE RECOMMANDI_

-20°F -29°0-10°F -23°0

0°F -18°O+10°F -29°0

+20°F - 7°C+30°F - 1°O

15%20%

25%30%

35%40%

,'ation d'appointaximum, suivre les PIECESNONMONTREES:)n froide ! 800UST ROBINET-VANNE }k ETRIER

M-2 ASSEMBLAGE DE L'HUMIBISTATfidificateur.Iotte et lee du

neraux de laet dueloger les

N° 16-4GOULOTTE DUDISTRIBUTEUR /"

-Sraux,le N° 990-13remettre le BLOC

EVAPORATEUR

anne N° 16-1

toutes les BO'ITIER DE

lnt uneagnetique.nnelucun N ° 16-5

COUVERCLE _!RRER DE DERIVATION _1_.GE ET

RACCORD. i!//_¢ _

fuite. Le /_nt la \Je le \\_fit du br_leur _.nner.i et enle, s'il est

]) REVISION D

N° 16-2COUVERCLE

N° 16-20VANNEELECTROMAGNETIQUE

N° 16-12FILTRE ,/_EAU

N ° P-236RACCORDEMENTDE LA VANNEELECTROMAGNETIQUE

(£) Copyright 2001,2002 GENERAL FILTERS, INC.All Rights Reserved Lithographie aux E.-U.

Cet humidificateur, s'il est enregistr6 correctement en retournant la

carte d'enregistrement de la garantie au fabriquant, est garanti auconsommateur contre tout defaut de materiaux et de main d'ceuvre

pour une periode de un (1) an a partir de la date d'installation. Lesblocs evaporateur ou les plaques ne sont pas couverts par cette

garantie limit6e ou par toute autre garantie. Toute autre pieced_fectueuse sera reparee sans frais, hormis les coots dedesinstallation, de reinstallation et de transport. Pour obtenir un service

de reparation avec cette garantie limitee, le consommateur doit

envoyer la pi#ce defectueuse ou I'humidificateur au complet aufabricant.

AUCUNE AUTRE GARANTIE QUE LA PRESENTE NE COUVRE CET

HUMIDIFICATEUR, LES GARANTIES IMPLIClTES DE QUALITI_MARCHANDE OU D'ADAPTATION ,ikUN USAGE PARTICULIER

SONT LIMITEES ,&,UN (1) AN. LE FABRICANT NE PEUT €:TRETENU RESPONSABLE POUR L'INSTALLATIQN OU L'UTILISATION

DE CE PRODUlT, SAUF DE LA MANI#RE INDIQUEE DANS LAPRESENTE GARANTIE LIMITEE. LE FABRICANT NE PEUT ENAUCUN CAS ETRE TENU RESPONSABLE POUR DES DQMMAGES

ACCESSOIRES OU INDIRECTS.

Cette garantie limitee vous donne des droits legaux specifiques et vous

pouvez jouir d'autres droits qui varient d'une juridiction & I'autre.Certaines juridictions ne permettent pas de limites sur les garanties

implicites ou d'exclusions pour les dommages accessoires ou indirects;les exclusions sus mentionnees peuvent donc ne pas s'appliquer dansvotre cas.

Toute question relative a cette garantie limitee dolt _tre soumise aufabriquant. (E.-U. : Le fabricant & choisi de ne pas divulguer les termes

de I'accord specifi_s dans le " Magnuson-Moss Waranty Act ".)

GENERAL FILTERS, INC. CANADIAN GENERAL FILTERS,43800 GRAND RIVER AVE. LTD.39 CROCKFORD BLVD.

NOVI, MICHIGAN 48375-1115 SCARBOROUGH, ONTARIOMIR3B7

Visitez notre site web au

WWW. GENERA LA IRE. COM

COUPER LA MATRICE LE LONG DE CETTE LIGNE

Page 9: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

D¢:GAGEMENT D'OUVERTURE

AU-DESSUS DE CETTE LIGNE

PRC:FE_RE : 7,0 CM (2 3/4 PO)

MINIMUM{: 4,5 CM (1 3/4 PO)

II

J

o

TROU DE

MONTAGE

INITIAL

TROU DE

MONTAGE

INITIAL

_J

COUPER LA FEUILLE DE METAL LE LONG DE CETTE LIGNE

COUPER LA MATRICE LE LONG DE CETTE LIGNE

HAUTGABARIT DE FIXATION

DE L'HUMIDISTATPOUR CONDUITS

1. ENLEVEZ LE SUPPORTADHESIF ET POSEZ

SUR LE CONDUIT,ik L'ENDROIT CHOISI.

2. CENTREZ TOUS LES TROUS AU POINTEAU

AVEC PRECISION.

3. PERCEZ QUATRE TROUS DE MONTAGE DE

3/32 PO (MECHE N° 42 OU DE 2 mm).4. PERCEZ LES AUTRES TROUS AVEC UNE

MECHE DE 1/8 PO OU DE 3 ram.

5. DETACHEZ LE METAL DU GROUPE DE

TROUS ET DE_COUPEZ SUR LA LIGNE

PLEINE AU MOYEN DE CISAILLES.

3N_17 3±±30 30 _NO9 37 7V13_ 30 3771n3J V7 EI3dNOO

+

o

LIGNE CENTRALE

+

Q

TROU DE

MONTAGE

INITIAL

i

k___

7I

I

J

Page 10: GENERAI A ire · fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous. MATE_RIAUX ADDITIONNELS

OPENING CLEARANCE ABOVE THIS LINEPREFERRED: 2 3/4 INCH.

MINIMUM: 1 3/4 INCH.

tII

l t-J

o

INITIAL

MOUNTING

HOLE

INITIAL

MOUNTING

HOLE

\J

CUT SHEETMETAL ALONG THIS LINE

CUT TEMPLATE ALONG THIS LINE

TOP

DUCT HUMIDISTATMOUNTING TEMPLATE

1. REMOVE ADHESIVE BACKING AND APPLY TO

THE DUCT IN THE SELECTED LOCATION.

2. ACCURATELY CENTER PUNCH ALL HOLES.

3. DRILL FOUR MOUNTING HOLES SIZE 3/32",

DRILL NO. 42 OR 2 ram.

4. DRILL OTHER HOLES WITH 1/8" OR 3 mm

DRILL.

5. BREAK METAL FROM GROUP OF HOLES, AND

CUT OUT ON SOLID LINE WITH SHEARS.

+

CENTERLINE

+

e

+

INITIAL

MOUNTING

HOLE

I