    General CalculationsRevision 4

    06/21/2006Page 1 of 20

    General CalculationsExcerptfrom

    PRYSMIANSWIRE AND CAB LE

    ENG IN EER ING GU IDE

  • 7/22/2019 General Calculations Rev 4

    2/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 2 of 20

    Voltage Rating

    The selection of the cable insulation level tobe used in a particular installation shall bemade on the basis of the applicable phase-

    to-phase voltage and the general systemcategory as outlined below:

    100 Percent Level - Cables in thiscategory may be applied where thesystem is provided with relay protectionsuch that ground faults will be cleared asrapidly as possible, but in any casewithin one minute. While these cablesare applicable to the great majority ofcable installations that are on groundedsystems, they may also be used on othersystems for which the application ofcables is acceptable, provided the above

    clearing requirements are met incompletely de-energizing the faultedsection.

    133 Percent Level - This insulation levelcorresponds to that formerly designatedfor ungrounded systems. Cables in thiscategory may be applied in situationswhere the clearing time requirements ofthe 100 percent level category cannot bemet, and yet there is adequateassurance that the faulted section will bede-energized in a time not exceeding

    one hour. Also, they may be used whenadditional insulation strength over the100 percent level category is desirable.

    173 Percent Level - Cables in thiscategory should be applied on systemswhere the time required to de-energize agrounded section is indefinite. Their useis recommended also for resonantgrounded systems. Consult the cablemanufacturer for insulation thicknesses.

    In common with other electrical equipment,

    the use of cable is not recommended onsystems where the ratio of the zero topositive sequence reactance of the systemat the point of cable application lies between-1 and -40 since excessively high voltagesmay be encountered in the case of groundfaults.

    Voltage Regulation

    Voltage regulation is often the limiting factorin the choice of either conductor or type ofinsulation. While the heat loss in the cable

    determines the maximum current it cansafely carry without excessive deterioration,many circuits will be limited to currents lowerthan this in order to keep the voltage dropwithin permissible values. In this connectionit should be remembered that the highvoltage circuit should be carried as far aspossible so that the secondary runs, wheremost of the voltage drop occurs, will besmall.

    The voltage drop of a feeder circuit may becalculated by the following formulae:

    ( )V

    V V

    V

    S L

    L

    =10 0

    Where:

    V = Voltage regulation in percentVL = Voltage across loadVS = Voltage at source

    And VS is defined by the formula:

    ( ) ( )22 sincos IXVIRVV LLS +++=

    Where:

    = Angle by which the load currentlags the voltage across the load

    cos = Power factor of loadR = Total AC resistance of feederX = Total reactance of feederI = Load current

    When the power factor angle is nearly thesame as the impedance angle, that is:

    tan X

    R

    The voltage regulation equation above willreduce to the following formula:

  • 7/22/2019 General Calculations Rev 4

    3/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 3 of 20

    ( ) cos sinV V RI XI S L = +

    The above formulas apply directly for single-phase lines when resistance and reactanceare loop values and voltage is voltagebetween lines.

    For three-phase circuits, use voltage toneutral and resistance and reactance ofeach conductor to neutral. This method willgive the voltage drop to neutral. To obtainthe voltage drop line-to-line, multiply the

    voltage drop by 3 .

    Note: The percent voltage drop is the samebetween conductors as from conductor to

    ground and should not be multiplied by 3 .

    Example:

    3 single copper conductors, 5 kV cables innon-metallic conduit.

    Size conductor = 350 kcmil copper, 90Insulation = 90 mils

    J acket = 70 milsOverall diameter = 1.13Voltage (VS) = 5,000 volts (3 phase)Current (I) = 460 amperes

    Power Factor = 0.8 (cos )Length = 2550 ft

    Resistance = 0.0308 ohms/1000 ftat 25C 0.096 ohmsor 2500 ft at 90C

    Reactance (X) = 0.024 ohms/1000 ft(See section onconductor reactance)0.072 ohms for 2500ft including 20%random lay

    ( ) ( )22 sincos IXVIRVV LLS +++=

    22 )]460072(.6[.)]460096(.8[.3

    5000+++=

    LLVV

    Solving for VL: VL = 2,831.6 volts

    Line-to-line voltage =2831.6 3 =4904 V

    Voltage Drop =5000 - 4904 =96 volts

    V =

    =5000 4904

    4904100 196%( ) .

    Approximate Formula:

    Voltage Drop = line to neutral

    = R I cos +X I sin= 0.096 460 0.8 +0.072

    460 0.6= 35.3 +19.8 =55.1

    Line-to-line drop =55.1 3 =95.4 V

    Conductor Reactance

    The reactance of any stranded or solid

    conductor can be calculated for a specificfrequency, conductor size, and spacing. Thefollowing equation can be utilized to find thereactance of a given configuration by usingthe concept of geometric mean radius.

    3

    10 100153.0log1404.02

    +=r

    gfX

    Where:

    X = Reactance in ohms/1000 ftf = Frequency in Hertz

    r = Radius of conductorg = geometric mean radius between

    conductors and is given by thefollowing formula:

    g a b znn= ...

    Where:n = number of conductorsa = distance from conductor a to bb = distance from conductor b to czn = distance from conductor n-1 to n

    Using the equations above, a nomogram (agraphic representation that consists ofseveral lines marked off to scale andarranged in such a way that by using astraightedge to connect known values ontwo lines an unknown value can be read at

  • 7/22/2019 General Calculations Rev 4

    4/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 4 of 20

    the point of intersection with another line)was constructed (the Nomogram is locatedat later in this document). This diagram canbe used to determine the reactance of anysolid or concentric stranded conductor. Itcovers spacing encountered for conduit

    wiring as well as for open wire circuits.Various modifications are necessary for useunder special conditions is covered in noteson the nomogram. The reactances shownare for 60-Hertz operation.

    Where regulation is an importantconsideration several factors should be keptin mind in order to obtain the best operatingconditions.Open wire lines have a high reactance. Thismay be improved by using parallel circuitsbut is much further reduced by usinginsulated cable. Three conductors in the

    same conduit have a lower reactance thanconductors in separate conduits.

    Single conductors should not be installed inindividual magnetic conduit because of theexcessive reactance.

    Three conductors in magnetic conduit willhave a somewhat higher reactance than

    cables in non-magnetic conduit.

    The following table lists equationscommonly used for determining variousparameters of an electrical system where:

    E = Phase-to-phase voltageI = Current, in amperes% Eff = Percent efficiency in decimalspf = Power factor in decimalskVA = Kilovolt-amperehp = HorsepowerkW = Kilowatts

    Electrical Formulas for Determining Amperes,Horsepower, Kilowatts, and Kilovolt-Amperes

    ALTERNATING CURRENTDesired

    DataSingle-Phase

    Two-Phase*Four-Wire

    Three-Phase(per phase)

    Amperes whenkVA is known E

    kVA 1000 E

    kVA

    2

    1000 E

    kVA

    3

    1000

    Amperes whenkilowatts is known pfE

    kW1000

    pfEkW

    21000

    pfEkW

    31000

    Amperes whenhorsepower is known

    hp

    E Eff pf

    746

    % hp

    E Eff pf

    746

    2 % hp

    E Eff pf

    746

    3 %

    Kilovolt-Amperes

    I E1000

    I E 21000

    I E 31000

    KilowattsI E pf

    1000 I E pf 2

    1000 I E pf 3

    1000

    HorsepowerI E Eff pf %

    746 I E Eff pf 2

    746

    % I E Eff pf 3746

    %

    In three-wire, two-phase balanced circuits, the current in the common conductor is 2 timesthat in either of the other conductors.

  • 7/22/2019 General Calculations Rev 4

    5/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 5 of 20

    Shielding of Insulated Cables

    Shielding should be considered for non-metallic covered cables operating at a circuitvoltage above 2000 volts for single

    conductor cables and 5000 volts forassembled conductors with a commonoverall jacket.

    Definition of shielding

    Shielding of an electric power cable is thepractice of confining the dielectric field of thecable to the insulation of the conductor orconductors. It is accomplished by means ofstrand and insulation shields.

    Functions of Shielding

    A strand shield is employed to precludeexcessive voltage stress on voids betweenconductor and insulation. To be effective, itmust adhere to or remain in intimate contactwith the insulation under all conditions.

    An insulation shield has a number offunctions:

    1. To confine the dielectric field within thecable.

    2. To obtain symmetrical radial distributionof voltage stress within the dielectric,thereby minimizing the possibility ofsurface discharges by precludingexcessive tangential and longitudinalstresses.

    3. To protect cable connected to overheadlines or otherwise subject to inducedpotentials.

    4. To limit radio interference.5. To reduce the hazard of shock. This

    advantage is obtained only if the shieldis grounded. If not grounded, the hazardof shock may be increased.

    Use of Insulation Shielding

    The use of shielding involves considerationof installation and operating conditions.Definite rules cannot be established on apractical basis for all cases. However,shielding should be considered fornonmetallic covered cables operating at acircuit voltage over 2000 where any of thefollowing conditions exist:

    1. Connection to aerial lines.2. Transition from conducting to non-

    conducting environment.3. Transition from moist to dry earth.4. Dry soil, such as in the desert.5. Damp conduits.6. Where the surface of cable collects

    conducting materials.7. Where electrostatic discharges are of

    low enough intensity not to damagecable but are sufficient in magnitude tointerfere with radio or televisionreception.

    8. Where safety to personnel is involved.

    More specific information on requirementsfor shielding by cable type is provided in thefollowing table.

  • 7/22/2019 General Calculations Rev 4

    6/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 6 of 20

    Operating Voltage Limits (kV) Above Which Insulation Shieldingis Required

    Power Cable - 100 and 133 Percent Insulation Level

    1. Single conductor (including assemblies of single conductors)a. With metallic sheath or armor ................................................ 5kVb. All others ................................................................................ 2kV

    2. Multiple conductors with common coveringa. With discharge-resisting jacket.............................................. 5kVb. With non-discharge-resisting jacket....................................... 2kVc. With metallic sheath or armor ................................................ 5kV

    Multiplying Factors for Equivalent Three-Phase Voltages for

    Single- or Two-Phase AC Systems or for DC SystemsSingle- and Two-Phase AC Systems*

    Over 5000 VoltsSingle- and Two-Phase ACSystems*

    and DC Systems 5000 Volts or Less One Side GroundedUngrounded and Midpoint

    Grounded

    1 1.73 0.866

    * Where it is not definitely specified that a line operates as an isolated single- or two-phase system, it will

    be considered as a branch of a 100% insulation level three-phase circuit, and the rating will be the line-

    to-line voltage of this 100% insulation level three-phase circuit.

    Importance of Shielding

    Where there is no metallic covering or shieldover the insulation, the electric field will bepartly in the insulation and partly in whateverlies between the insulation and ground. Theexternal field, if sufficiently intense in air, willgenerate surface discharge and convertatmospheric oxygen into ozone, which maybe destructive to rubber insulations and toprotective jackets. If the surface of the cableis separated from ground by a thin layer of

    air and the air gap is subjected to a voltagestress, which exceeds the dielectric strengthof air, a discharge will occur, causing ozoneformation.

    The ground may be a metallic conduit, adamp non-metallic conduit or a metallicbinding tape or rings on an aerial cable, a

    loose metallic sheath, etc. Likewise,damage to non-shielded cable may resultwhen the surface of the cable is moist, orcovered with soot, soapy grease or otherconducting film and the external field ispartly confined by such conducting film sothat the charging current is carried by thefilm to some spot where it can discharge toground. The resultant intensity of dischargemay be sufficient to cause burning of theinsulation or jacket.

    Where non-shielded non-metallic jacketedcables are used in underground ductscontaining several circuits, which must beworked on independently, the external fieldif sufficiently intense can cause shock tothose who handle or contact energizedcable. In cases of this kind, it may be

  • 7/22/2019 General Calculations Rev 4

    7/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 7 of 20

    advisable to use shielded cable. Shieldingused to reduce hazards of shock shouldhave a resistance low enough to operateprotective equipment in case of fault. Insome cases, the efficiency of protectiveequipment may require proper size ground

    wires as a supplement to shielding. Thesame considerations apply to exposedinstallations where personnel who may notbe acquainted with the hazards involvedhandle cables.

    Grounding of the Insulation Shield

    The insulation shield must be grounded atleast at one end and preferably at two ormore locations. This decreases thereactance to fault currents and increaseshuman safety factor. It is recommended that

    the shield be grounded at cable terminationsand at splices and taps. Stress conesshould be made at all shield terminations.

    The shield should operate at or near groundpotential at all times. Frequent grounding ofshields reduces the possibility of opensections on nonmetallic covered cable.Multiple grounding of shields is desirable inorder to improve the reliability and safety ofthe circuit. All grounding connections shouldbe made to the shield in such a way as toprovide a permanent low resistance bond.

    Using a mechanical clamp (such as aconstant tension spring or a hose clamp) isusually adequate to secure the connection.In some instances, it may be preferable to

    solder the connection. The area of contactshould be ample to prevent the current fromheating the connection and melting thesolder. For additional security, a mechanicaldevice, such as a clamp, may be used tofasten the ends of the connection together.

    This combination will ensure a permanentlow resistance, which will maintain contacteven if the solder melts.

    The wire or strap used to connect the cableshield ground connection to the permanentground must be of adequate size to carrythe fault current. Shielding which does nothave adequate ground connection due todiscontinuity of the shield or to impropertermination may be more dangerous thannon-shielded non-metallic cable andhazardous to life.

    Shield Materials

    Two distinct types of materials are employedin constructing cable shields:

    Nonmetallic shields - consist of either aconducting tape or a layer of conductingcompound. The tape may be conductingcompound, fibrous tape faced or filled withconducting compound, or conducting fibroustape.

    Metallic shield - should be nonmagneticand may consist of tape, braid, concentricserving of wires, or a sheath.

  • 7/22/2019 General Calculations Rev 4

    8/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 8 of 20

    Cable GeometryConfiguration

    Induced SheathVoltage Formulae

    (V to Neutral per ft)

    Metallic Shield LossFormulae for SolidlyGrounded Shields

    Where:

    Single Phase

    A A

    S

    Phase A:IXM

    Phase A:

    I2 RS

    XM( )

    2

    RS( )

    2X

    M( )2

    +

    Total Loss:

    2I2

    RS

    XM( )

    2

    RS( )

    2X

    M( )2

    +

    Equilateral

    A B

    S

    C

    S

    Phase A, B & C:IXM

    Phase A, B & C:

    I2

    RS

    XM( )

    2

    RS( )

    2X

    M( )2

    +

    Total Loss:

    3I2

    RS

    XM( )

    2

    RS( )

    2X

    M( )2

    +

    P =RS / Y

    Q =RS / Z

    Rectangular

    A B

    S

    C

    S

    Phase A & C:

    I 3 Y2

    XM

    A

    2

    2

    +

    2

    Phase B:IXM

    Phase A & C:

    I2

    RS

    P

    23Q

    2+( )2 3 P Q( ) 4+4 P

    21+( ) Q2 1+( )

    Phase B:

    I2

    RS

    I

    Q2

    1+

    Total Loss:

    3I2

    RS

    P

    2Q

    2+ 2+

    2 P2

    1+( ) Q2 1+( )

    Y =xM +A/2

    Z =xM - A/6

    Formulae continued on Next Page.

  • 7/22/2019 General Calculations Rev 4

    9/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 9 of 20

    Cable GeometryConfiguration

    Induced SheathVoltage Formulae

    (V to Neutral per ft)

    Loss Formulae forSolidly GroundedMetallic Sheaths

    Where:

    Flat

    A B

    S

    C

    S

    Phase A & C:

    I 3 Y2

    XM

    A( )2

    +

    2

    Phase B:IXM

    Y =xM +A

    Z =xM - A/3

    2-Circu it, No PhaseRotation

    A B

    S

    C

    S

    A B C

    Phase A & C:

    I 3 Y2

    XM

    B

    2

    2

    +

    2

    Phase B:I X

    M

    A

    2+

    Y =xM +A +B/2

    Z =xM +A/3 - B/6

    2-Circuit, PhaseRotation

    A B

    S

    C

    S

    ABC

    Phase A & C:

    I 3 Y2

    XM

    B

    2

    2

    +

    2

    Phase B:I X

    M

    A

    2+

    Phase A & C:

    I2

    RS

    P

    23Q

    2+( )2 3 P Q( ) 4+4 P

    21+( ) Q2 1+( )

    Phase B:

    I2

    RS

    I

    Q2

    1+

    Total Loss:

    3I2

    RS

    P2 Q2+ 2+

    2 P2

    1+( ) Q2 1+( )

    Y =xM +A - B/2

    Z =xM +A/3 - B/6

    xM = 2f (0.1404 log10(S/rm))/ft

    A = 2f (0.1404 log10(2))/ft

    B = 2f (0.1404 log10(5))/ft

    RS = /(8rmt) /ft

    RS = Metallic Shield Resistance (/ft)

    t = Metallic Tape Thickness (inches)

    f = Frequency (Hz)

    S = Center to Center Spacing of Cables (inches)

    rm = Metallic Shield Mean Radius (inches)

    I = Conductor Current (amperes)

    = Metallic Shield Resistivity at 50C (cmil/ft)

    Values (cmil/ft)Overlapped Copper Tape 30

    Overlapped Brass Tape 70

    Overlapped Monet Tape 2500

    Overlapped Ambrac Tape 350

    Lead Sheath 150

    Aluminum Sheath 20

    Aluminum Interlocked Armor 28

    Galvanized Steel Interlocked Armor 70

    Galvanized Steel Armor Wire 102

    Aluminum (5052 Alloy) 30

  • 7/22/2019 General Calculations Rev 4

    10/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 10 of 20

    Splices and Terminations

    The insulation shields must be removed

    completely at splices and terminations,otherwise excessive leakage current andflashover will result. Auxiliary nonmetallicconducting shields may adhere to theinsulation, so that the use of a 100 gritaluminum oxide cloth (or similar material)may be required to assure removal of theconducting material from the insulationsurface (See pages 28 - 30 for generalizeddiscussion of cable preparation for splicingand terminating).

    Short-Circuit Currents for

    Insulated Cable Conductors

    Steady increases in kVA capacity of powerdistribution systems have resulted inpossible short circuit currents of suchmagnitude that the resulting high conductortemperature may seriously damage theconductor insulation. As a guide inpreventing such serious damage, maximumallowable short circuit temperatures thatdamage the insulation to a slight extent only,

    have been established for the variousinsulations as follows (based on ICEA P-32-382):

    Thermoplastic Compound 150C

    Rubber and Varnished Cloth 200C

    Impregnated Paper 200C

    Thermoset Compound 250C

    The charts on the following pages show thecurrents, which, after flowing for the timesindicated, will produce these maximumtemperatures for the given conductor sizes.

    These charts are for copper or aluminumconductors operating at 90C or 105C withthermoset insulations. For other, lesscommon charts, reference ICEA P-32-382.

    The system short circuit capacity, theconductor cross-sectional area and thecircuit breaker opening time should be suchthat these maximum allowable short circuitcurrents are not exceeded.

  • 7/22/2019 General Calculations Rev 4

    11/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 11 of 20

    I

    0.1

    0.2

    0.5

    1

    2

    5

    10

    20

    50

    100

    1cycle

    -0.0167

    seconds

    2cycle

    s-0.0333seconds

    4cycle

    s-0.0667seco

    nds

    8cycle

    s-0.1333seconds

    16cycle

    s-0.2667seconds

    30cycles

    -0.5000

    seconds

    60cycle

    s-1.0000seconds

    100cycle

    s-1.6667seconds

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    ShortCircuitCurrent(thousandsofa

    mperes)

    Conductor-Aluminum

    ThermosetInsulations

    Ratedfor90C

    Ma

    ximumContinuousOperation

    CurvesBasedonFormula:

    2A2

    t=0.0125log

    (T2+228.1)

    +228.1)

    (T1

    Where:

    I=ShortCircuit,Amperes

    A=ConductorArea,CircularMils

    t=TimeofShortCircuit,Seconds

    T T1 2=MaximumOperatingTemperature(90C)

    =MaximumShortCircuitTemperature(250C)

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

  • 7/22/2019 General Calculations Rev 4

    12/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 12 of 20

    I

    1cycle

    -0.0167

    seconds

    2cycle

    s-0.0333seconds

    4cycles-

    0.0667seconds

    8cycle

    s-0.1333

    seconds

    16cycle

    s-0.2667seconds

    30cycles

    -0.5000

    seconds

    60cycles-

    1.0000seconds

    100cycle

    s-1.6667seconds

    ShortCircuitCurrent(thousandsofam

    peres)

    Conductor-Copper

    ThermosetInsulations

    Ratedfor90C

    MaximumContinuousOperation

    CurvesBasedonFormula:

    2A2

    t=0.0297log

    (T2+234.5)

    +234.5)

    (T1

    Where:

    I=ShortCircuit,Amperes

    A=ConductorArea,CircularMils

    t=TimeofShortCircuit,Seconds

    T T1 2=MaximumOperatingTemperature(90C)

    =MaximumShortCircuitTemperature(250C)

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    0.1

    0.2

    0.5

    1

    2

    5

    10

    20

    50

    100

  • 7/22/2019 General Calculations Rev 4

    13/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 13 of 20

    I

    1cycle

    -0.0167

    seconds

    2cycle

    s-0.0333seconds

    4cycle

    s-0.0667seco

    nds

    8cycle

    s-0.1333seconds

    16cycles

    -0.2667

    seconds

    30cycle

    s-0.5000seconds

    60cycle

    s-1.0000seconds

    100c

    ycles

    -1.6667

    seconds

    ShortCircuitCurrent(thousandsofamperes)

    Conductor-Aluminum

    ThermosetInsulations

    Ratedfor105C

    MaximumContinuousOperation

    CurvesBasedonFormula:

    2A2

    t=0.0125log

    (T2+228.1)

    +228.1)

    (T1

    Where:

    I=ShortCircuit,Amperes

    A=ConductorArea,CircularMils

    t=TimeofShortCircuit,Seconds

    T T1 2=MaximumOperatingTemperature(105C)

    =MaximumShortCircuitTemperature(250C)

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    0.1

    0.2

    0.5

    1

    2

    5

    10

    20

    50

    100

  • 7/22/2019 General Calculations Rev 4

    14/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 14 of 20

    I

    1cycle

    -0.0167

    seconds

    2cycle

    s-0.0333seconds

    4cycles

    -0.0667seconds

    8cycle

    s-0.1333se

    conds

    16cycles-

    0.2667seconds

    30cycles-

    0.5000seconds

    60cycle

    s-1.0000seconds

    100cycle

    s-1.6667seconds

    Conductor-Copper

    ThermosetInsulations

    Ratedfor105C

    MaximumContinuousOperation

    CurvesBasedonFormula:

    2A2

    t=0.0297log

    (T2+234.5)

    +234.5)

    (T1

    Where:

    I=ShortCircuit,Amperes

    A=ConductorArea,CircularMils

    t=TimeofShortCircuit,Seconds

    T T1 2=MaximumOperatingTemperature(105C)

    =MaximumShortCircuitTemperature(250C)

    ShortCircuitCurrent(thousandsofamperes)

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    10AWG

    8AWG

    6AWG

    4AWG

    2AWG

    1AWG

    1/0AWG

    2/0AWG

    3/0AWG

    4/0AWG

    250kcm

    350kcm

    500kcm

    750kcm

    1000kcm

    0.1

    0.2

    0.5

    1

    2

    5

    10

    20

    50

    100

  • 7/22/2019 General Calculations Rev 4

    15/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 15 of 20

    Shield Short Circuit CurrentFormula

    The following simplified formula may beused to calculate allowable sheath currents(based on ICEA P-45-482):

    1. The maximum time that a given short-circuit current can flow in a given shieldor sheath, or

    2. The maximum short-circuit current thatcan flow in a given shield or sheath for agiven time, or

    3. The effective cross-sectional area of ashield or sheath needed to withstand a

    given short-circuit current for a giventime.

    IMA

    N=

    60

    Where:

    I = Short circuit current, amperesA = Shield Area in cmilsN = Number of cyclesM = See Tables on next page

    The final temperature the shield or sheathcan reach without damaging the adjacentmaterials limits allowable shield or sheathcurrents. This limiting temperature is definedin ICEA P-45-482 as the variable T2.Various values of T2 are listed below. For

    greater detail in regards to the calculationplease refer to ICEA P-45-482.

    Values of T2, Maximum Allowable Shield or Sheath TransientTemperature

    Cable Material inContact with Shield or

    Sheath

    T2

    (C)

    Crosslinked (thermoset)ThermoplasticImpregnated PaperVarnished Cloth

    350*200200200

    * For lead (Pb) sheaths this temperature is limited to 200C.

    NOTE: The material in contact with the shield or sheath shall limit the temperature of theshield or sheath. For example, a cable having a cross linked semi-conducting shield underthe metallic shield and a crosslinked jacket over the metallic shield would have a

    maximum allowable temperature of 350C. With a thermoplastic jacket, it wou ld be 200C.

  • 7/22/2019 General Calculations Rev 4

    16/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 16 of 20

    Values of M Based on Shield Temperature (T2) Above

    Values of M(90C)

    Values of M(105C)

    T2Max

    (C)Rated

    Voltage(kV) Cu Al Pb Cu Al Pb

    200350

    200350

    200350

    200350

    200350

    55

    1515

    2525

    3535

    4646

    0.0630.089

    0.0630.089

    0.0630.089

    0.0650.090

    0.0650.090

    0.0420.059

    0.0420.059

    0.0420.059

    0.0430.060

    0.0430.060

    0.012----

    0.012----

    0.012----

    0.012----

    0.012----

    0.0580.085

    0.0580.085

    0.0600.086

    0.0600.086

    0.0600.086

    0.0390.056

    0.0390.056

    0.0400.057

    0.0400.057

    0.0400.057

    0.011

    ----

    0.011

    ----

    0.01

    1----

    0.011

    ----

    0.011

    ----

  • 7/22/2019 General Calculations Rev 4

    17/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 17 of 20

    To calculate the circular mil area of a shield design, use the followingformulas:

    Type of Shield or SheathFormulas For

    Calculating A(See notes 1 & 2)

    1. Wires applied either helically, as a braid or serving; orlongitudinally with corrugations. ndS

    2

    2. Helically applied tape not overlapped. 127. nwb

    3. Helically applied flat tape, overlapped (See note 3).)

    (

    4100

    2 100bd

    Lm

    4. Corrugated tape, longitudinally applied. ( )[ ]127 50. + + d B bis

    5. Tubular Sheath. 4bdm

    NOTE 1:Where:

    A = Effect ive cross-sect ional area, shield or sheathB = Tape overlap, mils (usually 375)b = Thickness of tape, mils

    d is = Diameter over semiconducting insulation shield, milsdm = Mean diameter of shield or sheath, milsds = Diameter of wires, milsw = Width of tape, milsn = Number of serving or braid wires, or tapesL = Overlap of tape, percent

    NOTE 2:The effective area of composite shields is the sum of the effective areas of thecomponents. For example, the effective area of a composite shield consisting of ahelically applied tape and a wire serving would be the sum of the areas calculated fromFormula 2 (or 3) and Formula 1.

    NOTE 3:The effective area of thin, helically applied overlapped tapes depends, also, upon thedegree of electrical contact resistance of the overlaps. Formula 3 may be used to calculatethe effective cross-sectional area of the shield for new cable. An increase in contactresistance may occur after cable installation, during service exposed to moisture andheat. Under these conditions the contact resistance may approach infi nity, where Formula2 could apply.

  • 7/22/2019 General Calculations Rev 4

    18/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 18 of 20

    OTHER CALCULATIONS

    Charging Current

    The charging current I of a singleconductor insulated power cable can beobtained from the following formula:

    ECfI = 2

    Where:

    I = microamperes per 1000 ft.f = Frequency, HzC = Capacitance, picofarads per ftE = Voltage, phase-to-ground, kV

    Capacitance of Cables

    The capacitance of a one conductorshielded cable is given by the followingformula:

    CSIC

    D

    d

    =7 354. ( )

    log

    Where:

    C = Capacitance, picofarads per ftSIC = Dielectric constant of the

    insulation materialD = Diameter over insulationd = Diameter under insulation

    Typical Values of SIC

    Polyvinyl Chloride......................... 3.5 - 8.0EPR Insulation.............................. 2.5 - 4.0

    Polyethylene................................. 3.0 - 6.0Crosslinked Polyethylene............. 2.1 - 2.3Impregnated Paper ....................... 3.3 - 3.7

    Dielectric Loss of CableInsulation

    The dielectric loss of a single conductorcable can be calculated by the followingformula:

    WE SIC

    Dd

    d =

    0 00276 2. ( ) tan

    log

    Where:

    Wd = Dielectric loss, watts per ft.E = Phase-to-neutral voltage, kVSIC = Dielectric constant of the

    insulation material

    tan = dissipation factor

    Maximum Voltage Stress AcrossInsulation

    =

    cs

    ics

    g

    D

    DD

    EV

    ln

    2

    Where:

    V = Maximum voltage stress, kVEg = Phase-to-neutral voltage, kVDCS = Diameter over conductor shieldDi = Diameter over insulation

    Dissipation Factors for InsulationMaterials (tan )

    Impregnated Paper..0.002 - 0.0025EPR Insulation. 0.002 - 0.0800Crosslinked Polyethylene..0.0001 - 0.0003

  • 7/22/2019 General Calculations Rev 4

    19/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 4

    06/21/2006Page 19 of 20

    Support Grip Length or

    Maximum Riser Length for GivenSupport Grip

    The following formula may be used todetermine either:

    1) Minimum support grip lengths fora given riser section length, or

    2) Maximum riser section length fora given support grip workinglength.

    ( )CW

    GLDSL = 8.1

    Where:

    SL = Riser Section Length, in feetD = Diameter over cable jacket, in.GL = Working length of grip, in.WC= Cable weight, pounds per ft

    Prysmian recommends that a recognizedmanufacturer supply the correct grip(s) onan individual application basis, utilizing theformula shown above. Prysmian doessuggest using grips, which will provide

    balanced support for the cable (i.e. aDouble Eye grip vs. a Single Eye type).

    NOTE: Grips are not suitable for allvertical riser installation and the aboveis offered as a general guide only. If

    you have any questions of thesuitability of a grip and/or cableconstruction for a vertical application,please consult the cable manufacturer.

    Inductive Reactance to Neutral

    The following is a nomogram used todetermine the inductive reactance of solidor stranded (concentric) conductors at 60Hz. It accommodates various spacing ofthe conductors and other unique

    parameters as indicated within thenomogram itself.

    Special consideration should be given tocables when installed in magnetic ducts.Installing a single cable in a magnetic ductresults in HIGH reactance and a de-ratedampacity. If magnetic ducts must be used,it is recommended that all three cables beplaced in a single duct. While resulting inslightly higher reactances than threecables in a non-magnetic duct, it is optimalrelative to the alternative of a single cable

    in a magnetic duct.

  • 7/22/2019 General Calculations Rev 4

    20/20

    700 Industrial DriveLexington, South Carolina 29072Phone: 1.800.845.8507Fax: 1.803.951.1142www.na.prysmian.com/energy

    General CalculationsRevision 2

    01/18/2005Page 20 of 20

    Nomogram for Determining Conductor Reactance at 60 Hz(Series Inductive Reactance to Neutral)