Heating foil ECOFILM FInstallation guide

ECOFILM F - OPTION

Suitable for laminate floating floors:width(mm) input (W/m2)

F 608 600 80 F (48V) 530 80

Suitable for wooden floors:F 606 600 60

Accessories for Ecofilm F installation

• Crimp connectors• Vulkanized tape MASTIC• Polyester insulation tape• Connection cables 1,5 mm2:

black and blue colour• Crimping tool

INSTALLATION

LAYOUT OF ECOFILM F INSTALLATION

• User should have to prepare simple laying plan of ECOFILM F for given room, which will show accurate position of heating foil laying and supply conductors before installation.

FIXTURE

El. connection cables

min. 50 mm

100 mm

1175 m

m

500 mm

EL.BOX

Heating foil preparation (cutting and insulation)

Prepare ECOFILM F in requested lengths according to layout. Heating foil Ecofilm F is possible to cut. Foil cutting must be provided along

the longitudinal axis.2 possible variants of longitudinal cutting axis:a/ 1st variant of longitudinal axis - each 320mm is wider cutting line (is enough

to insulate only uncovered edges of both copper tapes by means of polyester insulating tape – width 25 mm)

b/ 2nd variant of longitudinal axis - each 10mm is thin cutting line (is necessary to insulate whole uncovered shear edge by means of insulation tape of width 25 mm and then 35 mm wide insulation tape.

1 st variant 2 nd variant

Fixation and pressing of crimp connectors

Crimp connection is placed in the centre of copper tape and its oblique part

is subsequently closed by fingers pressure.Final perfect provision of crimp connection position will be provided bymeans of crimping tool. Crimp connectors must be carefully and perfectly fixed !

Crimp connector must be insulated by MASTIC strip.

Covering of crimp connectors

Important information for ECOFILM F installation planning:

Insulation against water penetration must be installed beneath the floor constructionWe recommend that you lay the thermal insulation beneath the heating film in two parallel layers with overlapping joints.Before floating wooden or laminated floor laying a PE film with thickness 0.2 mm must be laid on the heating film, with overlaps sufficient to prevent the wetness from leaking through.ECOFILM F is not suitable for rooms with high humidity (bathrooms, laundry rooms, etc.)

Installation Warning !!!

to lay upon itself in 2 and more layers and overlap each other

ECOFILM F is forbidden:

to laid over expansion joints.to lay beneath fixed room furnishings.

FIXTURE

to cut or damage black carbon heating element

ECOFILM F LAYINGSTEP 1

Check humidity of the laying surface, which must not exceed 2 % (roughly 60 % of relative humidity).

Clean the floor area and prime with a suitable proprietary primer. Surface must be suitably flat, with no juts, bumps, or depressions.

We recommend to use levelling layer 2-3mm thick (Mirelon) under heating foil ECOFILM F.

ECOFILM F LAYINGSTEP 2

After Mirelon laying you can install ECOFILM F (Never lay the strips of Ecofilm in such a way that their heating surfaces overlap).

ECOFILM F LAYING STEP 3

In the places where you expect to place connection points, and in the places where conductors lead towards the electricity box, you need to make a groove for sinking them into the laying surface.

Soldered connection points should face downwards and must be protected against mechanical stress.

ECOFILM F LAYING STEP 4

Check the resistance of electrical circuits with an ohmeter and insulation resistance if you have laid and connected all strips.

IMPORTANT NOTE: in case of el.conncetion in series current value of Ecofilm F must not exceed 10Amps !!!

                                                                        

ECOFILM F is necessary to overlay by PE foil (min. 0,2 mm thick) to prevent mechanical stress during laying of floating floor and to prevent surface moisture penetration as well.

The individual strips must overlap by at least 20 cm. Pull them up by about 3 cm along walls.

ECOFILM F LAYING STEP 5

If all ECOFILM F measurings are correct you can lay floating floor according to floating floor manufacturer´s instructions.If floating floor made up of individual segments, you must take special care to not damage the now-laid layers and the supply cables. Use a suitable subsurface.

FLOATING FLOOR LAYING STEP 6

A person with proper qualifications should connect the connection cables into an already-prepared electrical box.

No conductor should never pass below the heating film itself. Since the cable is 4.5 mm thick, you must sink it at least 4 mm into the laying surface (into a groove) and fix it in place.

ELECTRICAL CONNECTION STEP 6

Most suitable Floor constructions for ECOFILM F

installation

I. FLOATING FLOOR CONCRETE BASE

1. Concrete base2. MIRELON3. ECOFILM F heating foil (F606, F608)4. PE foil (min. 0,2 mm thickness)5. Laminate floating floor

II. FLOATING FLOORWOODEN CONSTRUCTION BASE

7. Load-bearing wooden construction6. Thermal insulation (ISOVER, ORSIL,etc.)5. Plastboard (fiberboard) desk – 22 mm thickness4. Mirelon (Polyurethane) layer3. ECOFILM F heating foil (F606, F608)2. PE foil (0,2 mm thickness)1. Floating floor

For floor heating are suitable following thermostats:

Fenix Therm 100

Eco M/z1

Microline OCD 1999 H

Eberle Instat 8

TEMPERATURE CONTROLS

THERMOSTAT WITH FLOOR PROBEElectrical connection with ECOFILM F

L – phase (el.supply)N – neutral (el.supply)L’ – phase (ECOFILM F)N’ – neutral (ECOFILM F)

NOTES: The total take-off (Amps) of

ECOFILM F must never exceed the maximum value of thermostat switched current !!!

ECOFILM FModern system of floor heating