HYPERTEC UNINTERRUPTIBLE POWER SUPPLY USER’S MANUAL SBUPS600VA SBUPS1000VA SBUPS1500VA

Upload: others

Post on 22-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

  • HYPERTEC UNINTERRUPTIBLE

    POWER SUPPLY

    USER’S MANUAL SBUPS600VA

    SBUPS1000VA SBUPS1500VA

  • Contents General Safety Instructions 2 Conditions of Use 2 Electrical Safety 3Safe Operating Practices 4Battery Information 6 Introduction 7

    Performance 7 Installation Instructions 9 Physical Appearance 10 Front Panel Operational Indicators 11Operation 12 Specification 13 Maintenance 14 Software Installation 15 Load configure reference 19Troubleshooting 20

    1

  • General safety instructions This manual contains important safety instructions that should be followed

    during the installation and maintenance of the UPS.

    Please read this manual thoroughly before attempting to install or operate

    this UPS.

    DO NOT under any circumstances attempt to remove the UPS cover.

    It may contain hazardous voltages internally that may cause electric

    shock. There are no user-serviceable parts inside. For service,

    please contact your nominated service agent.

    Conditions of Use This equipment is designed for domestic use only. The manufacturer

    neither recommends nor knowingly sells this product for use in critical life

    support applications.

    1. Intended for installation in a controlled environment.

    a. The controlled environment should be in accordance

    with the requirement of the specification

    b. Do not install or operate your UPS in or near water.

    c. Do not place UPS on an unstable cart, stand or table.

    d. Do not place UPS under direct sunlight or close to

    heat emitting sources.

    e. Do not place UPS power cord in any area where it may

    2

  • get damaged by heavy objects.

    2. Placing magnetic storage media on top of the UPS may result in data

    corruption.

    3. Your UPS provides conditioned power to connected equipment.

    Maximum load must not exceed that shown on the UPS rating label.

    If uncertain, contact Legend

    Electrical Safety DO NOT under any circumstances attempt to remove the UPS cover.

    It may contain hazardous voltages internally that may cause electric

    shock. There are no user-serviceable parts inside. For service,

    please contact your nominated service agent.

    1. The Hypertec UPS will provide a 220~240VAC 1φ(single-phase)rate

    power source. Please verify that this model matches your AC mains /

    load voltage requirements.

    2. The Hypertec UPS must be earthed at all times during operation.

    This can be achieved by only connecting the input power chord to a

    mains supply socket outlet with an integral earth terminal. A means of

    disconnecting the mains supply should be within 2 meters of the

    UPS.

    3. Output sockets on the UPS are electrically live if the UPS is switched

    3

  • ON, even if the UPS is not plugged in to mains supply. The On/Off

    button on the UPS does not electrically isolate the internal parts. To

    isolate the UPS, switch the UPS OFF first, then unplug it from the

    mains.

    4. To reduce the risk of fire, use fuses with the correct rating when

    replacing fuses.

    5. The UPS relies on your building wiring over-current protection, which

    must be rated between 10-16 amperes.

    6. When using the communication features on the UPS, ensure the

    cabling connected to the USB communication port are kept

    separated by at least 25 mm from the power cords to and from the

    UPS input and output.

    Safe Operating Practices This pluggable type A equipment has factory installed batteries, and hence

    may be operated by anyone that has read and understood this manual.

    During the installation of this equipment, it should be assured that the sum

    of the leakage currents of the UPS and the connected loads does not

    exceed 3.5mA.

    1. The mains socket outlet that supplies the UPS shall be installed near

    the UPS and shall be easily accessible.

    2. When replacing batteries, replace with the same type and number of

    batteries.

    3. Turn off and unplug your UPS before cleaning. Do not use liquid or

    4

  • aerosol cleaners. A dry cloth is recommended to remove dust from

    the surface of your UPS.

    4. Do not handle any metallic connector before the power has been

    disconnected.

    5. Turn off and unplug your UPS from the outlet and contact your

    nominated service agent if:

    o The power cord or plug damaged.

    o Liquid has been spilled on the UPS.

    o The fuse blows frequently.

    o The UPS does not operate even when user follows

    the operating instructions.

    5

  • Battery Information 1. CAUTION: Do not dispose of batteries in a fire, the battery may

    explode.

    2. CAUTION: Do not open or damage the battery or batteries, as

    released electrolyte is harmful to the skin and eyes.

    3. A battery can present a risk of electric shock and high short circuit

    current. The following precaution should be observed when working

    on batteries: Remove watches, rings or other metal objects. Use

    tools with insulated handles.

    4. NOTE. The batteries used in your Hypertec UPS are maintenance

    free. This means that you DO NOT need to check the battery fluid

    levels. Trying to do so may cause injury to yourself, or may cause a

    fault with the battery / UPS.

    5. The battery backup runtime is affected by the state of charge of the

    batteries, the age of the batteries and general condition of the

    batteries.

    6

  • Introduction The Hypertec UPS can instantly switch your computer to emergency

    battery backup power and allows you to work through mains power

    outages without data loss or downtime. It continuously conditions the

    power coming into your computer and provides a power source with

    virtually zero interruption.

    This UPS is specially designed for PC users and also suitable for

    computer peripherals or POS. A microcontroller is used as the main

    controller that renders the product an intelligent UPS, capable of

    self-protection and fault diagnosis. A built-in AVR function automatically

    adjusts itself to maintain a power supply of stable voltage when the utility

    power is of high or low voltage. High-performance surge suppression

    protects your computer from electrical noise and damaging power surges.

    Performance Your Hypertec UPS provides the following high performance features:

    • Uninterruptible Power

    Protects your data by supplying battery backup when power fails.

    • Microcontroller Control

    By means of innovative software control programs, the complicated

    hardware circuitry is inlaid in the powerful microcontroller. Apart from

    reduced size, it also lowers the rate of UPS failure.

    • LED Indicators

    7

  • Operational status is indicated by a series of 3 easy to read LED’s.

    • Audible Alarms

    Actively lets you know if the unit is in battery mode, if the battery is low, or

    if there is an over load condition.

    • High quality battery

    The selection of high quality sealed lead-acid maintenance free batteries

    maximises the life span of the battery for prolonged performance and

    enhanced economic benefits.

    • Automatic Detection

    When the UPS is turned ON, it immediately performs an inspection of the

    battery capacity.

    • Automatic Voltage Regulation

    Corrects over and under-voltages, without draining the battery. This

    preserves battery resources and ensures your UPS will provide the

    optimum runtime and optimum voltage source during a power blackout.

    • Surge Protection

    Protects hardware from damage due to unexpected power surges.

    • Automatic Charge

    The UPS charges its battery whenever it is connected to utility power. The

    UPS can be in either the ON or OFF mode.

    • Auto Restart (Cold Start)

    If the UPS has shutdown during a battery backup session due to

    discharged batteries, the UPS will automatically restart once mains power

    has been restored to supply mains power and recharge the batteries.

    8

  • Installation Instructions 1. Inspection

    Inspect the UPS upon receipt. The packaging is recyclable. Save it for

    reuse or dispose of it properly. Ensure the UPS is physically undamaged

    due to transit.

    2. Placement

    Install the UPS in a protected area with adequate airflow, and away from

    direct sunlight and excessive dust. Do not operate the UPS where the

    temperature and humidity is outside the specified limits in the

    Specifications Table.

    3. Connect to Mains Power

    Connect the AC input power cord to a socket outlet to power up the UPS.

    The battery in the UPS will lose some charge during shipping and storage.

    It will recharge completely after approximately 8 hours of normal operation.

    Do not expect full battery run time during this initial recharge period.

    4. Connect the loads

    Plug the loads into the output sockets on the rear of the UPS. Ensure the

    UPS is sized correctly so that the UPS is not run at full load constantly.

    Caution: NDO NOT connect a laser printer or plotter to the UPS with other

    computer equipment. A laser printer or plotter periodically draws

    significantly more power than when idle, and may overload the UPS.

    9

  • Physical Appearance Front Panel

    Rear Panel

    Item Description

    1 On/Off Power Switch

    2 LED 1 - GREEN - AC Normal Status LED

    3 LED 2 - YELLOW - Battery Charging LED

    4 LED 3 - RED – Battery State of charge LED

    5 AC Power socket outlets

    6 Phone/Fax line Surge Suppressor

    7 USB Communications Port

    8 Input AC Fuse

    9 Input Power Socket with Spare Fuse

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

  • Front Panel Operational Indicators Front Panel Indicator

    LED 1

    Green

    LED2

    Yellow

    LED 3

    Red

    Buzzer Status Operational

    Description

    OFF ON OFF OFF

    UPS OFF.

    Mains Normal.

    Batteries Charging.

    ON ON OFF 2 second Interval

    Beeping

    UPS ON.

    Mains Mode

    OFF OFF BLINK Beeping every 5

    seconds

    Mains not present.

    Battery Backup mode

    2 beeps per

    second i. Low battery Voltage

    4 beeps every 2

    seconds ii. Overload

    OFF OFF ON

    Continuous iii. Short-circuit

    OFF OFF OFF OFF Batteries Discharged.

    Sleep Mode.

    11

  • Operation • Switch On - With the UPS plugged in, press the power switch in to

    switch the UPS on. The UPS will perform a self-test each time it

    is switched on and the buzzer will beep 2 times.

    • Switch Off - By depressing the power switch. UPS will keep charging

    batteries.

    • Backup (Beeping 1 time every 5 seconds) - When in Backup mode,

    the battery illuminates and the UPS emits a beeping sound

    every four seconds. Press the power switch to stop the beeping.

    The alarm stops when the UPS returns to normal utility mode of

    operation

    • Low Battery (Beeping 2 times every 1 second) - In Backup mode,

    when the battery energy runs low, the UPS beeps rapidly until

    the UPS shuts down due to complete battery discharge.

    • Overload (Beeping 4 times every 2 seconds) - When the UPS is

    overloaded all three LED’s turn on and the buzzer beeps every

    1 second. Promptly disconnect non-essential load equipment

    from the UPS to eliminate the overload, otherwise, the UPS will

    shut off output power. The time for shut-down is determined by

    the size of the overload

    • NOTE: If the UPS is working in battery mode, DO NOT turn on

    any additional loads such as a computer or monitor or

    return any loads from sleep mode, otherwise, the UPS may

    operate its overload or short circuit protection.

    12

  • Specification Model SBUPS600VA SBUPS1000VA SBUPS1500VA

    Rated Output

    power 600VA / 360W 1000VA / 600W 1500VA / 750W

    Input Characteristics

    Rated Input Voltage 230/240V

    Input Voltage Range 175 – 285 V

    Rated Input Frequency 50 Hz ± 10%

    Output Characteristics

    Rated Output Voltage 230V ± 10%

    Output Frequency 50 Hz ± 10%

    Output Waveform Modified Square Wave

    Power Factor 0.6

    Change Over Time Typ. 0.4ms

    Max. 10ms

    Battery Information (at 25°C)

    Rating 1 x 12Vdc, 7Ah 2 x 12Vdc, 7Ah 2 x 12Vdc, 9Ah

    Type Sealed Lead Acid, Maintenance Free

    Service Life 2-3 years depending upon use

    Battery Recharge time

    for 90% capacity 8 hours

    Runtime in minutes at

    full load ≥ 3 mins

    13

  • General

    Audible Noise < 45dBA

    Net Mass 6 kg 10.9 kg 12.5 kg

    Dimensions(mm) 162×94×320 124×382×225

    Operating Temperature -10°C to +40°C

    Maximum Operating

    Relative Humidity 95% Relative

    Maintenance 1. With normal use, a UPS battery will last 2 to 3 years depending on the

    number of discharges and operating/ambient temperatures.

    2. Charge the UPS's battery every 3 months during extended storage.

    3. Disconnect the power during extended storage to avoid overcharge of

    the battery.

    4. Avoid overload or short circuit even though the UPS has build-in

    overload and short circuit protect function.

    14

  • Software Installation In order to utilise the UPS to its full potential, the monitoring software must

    first be installed. Please install the software according to the following

    steps. For information on how to operate the software, refer to the On-CD

    manual

    When the software

    CD is inserted, The

    Autorun screen will

    come up.

    Click Install.

    Click NEXT

    15

  • 3. Enter details as

    requested on this

    screen. Your

    product serial

    number will be on

    the CD envelope.

    Click NEXT

    4. Choose the

    installation

    directory.

    Click Next.

    16

  • 5. Select language.

    English is Default.

    Click NEXT.

    6. Software will

    Now Install.

    17

  • 7. Installation is

    now complete.

    Click FINISH

    8. The program is

    now running.

    For information on

    how to operate the

    software, refer to

    the On-CD manual.

    18

  • Load configuration reference

    UPS (VA) = PC power ATX (Watt) /0.6 + Monitor (VA)

    Monitor power ( reference )

    15”CRT 15”LCD 17”CRT 17”LCD 19”CRT 19”LCD

    80VA 40VA 130VA 60VA 180VA 80VA

    19

  • Troubleshooting Problem Possible Cause Action To Take

    i. Battery Discharged.

    Sleep Mode. Press the POWER button ONUPS not on &

    No LED’s on ii. PCB failure Contact Service Agent

    Power cord lose Re-plug the power cord

    Line voltage too high, too

    low or black out Normal condition

    UPS always at battery

    mode

    PCB failure Contact Service Agent

    i. Short Circuit. Remove the non-critical loadsBuzzer continuously

    sounding ii. UPS Faulty Contact Service Agent

    UPS does not provide

    expected run time. Low

    battery warning is

    sounded prematurely.

    Battery is weak due to

    wear or successive mains

    outages.

    Allow UPS to recharge battery

    for a minimum of 8 hours. If

    UPS sounds low battery

    warning prematurely, when

    retested, battery should be

    replaced.

    20