www.nampower.com.na "Our deepest fear is not that we are inadequate. Our deepest fear is that we are powerful beyond measure…” Nelson Mandela. South African Statesman , 1993 Nobel Prize for Peace, b.1918 Implementation of 220 kV In-Service Insulator Performance Test Tower in Namibia Authors: Dr WL Vosloo F Engelbrecht N Heger Dr JP Holtzhausen

Upload: hadiep

Post on 14-Apr-2018

231 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

www.nampower.com.na

"Our deepest fear is not that we are inadequate. Our deepest fear is that we are powerful beyond measure…”Nelson Mandela. South African Statesman , 1993 Nobel Prize for Peace, b.1918

Implementation of 220 kVIn-Service Insulator Performance

Test Tower in Namibia

Authors:

Dr WL VoslooF Engelbrecht

N HegerDr JP Holtzhausen

Page 2: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Beulah Sepo LimboNampower: Assistant EngineerMasters: Electrical Engineering

University of Stellenbosch

Page 3: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Introduction

Walmund 220 kV Test Tower

Swakopmund

Walvis Bay

Page 4: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Insulator Performance Test Tower

Page 5: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Design of the Test Insulators for Phase A,B,&C

A1: Manufacturer A, SR, 20mm/kV,S/P=1.6, no corona ring.A2:Manufacturer B, EPDM, 25mm/kV,S/P=0.9, with corona ring.A3:Manufacturer A, SR, 25mm/kV,S/P=1.1,no corona ring.B1:Manufacturer C,SR,25mm/kV,S/P=1.3,no corona ring.B2:Manufacturer C,SR,25mm/kV,S/P=1.3,with corona ring.B3: Manufacturer C,SR,25mm/kV,S/P=1.3,with corona ring.C1:Manufacturer B,SR,25mm/kV,S/P=0.9,with corona ring.C2:Manufacturer B,SR,25mm/kV,S/P=0.9,with corona ring.C3:Reference,Glass,fog type, cap and pin,25mm/kV,form factor=10.3,no corona ring.

Page 6: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Substation with the Insulator Test Tower

Page 7: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Insulator Test Tower

Page 8: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Insulator Test Tower for One Phase

Page 9: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Insulator Test Tower

Commissioned on the 31st March 2006.Recommissioned on the 9th June 2006.

Page 10: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Objectives of the Walmund Insulator Test Tower

1. Compare A1 with A3 to determine the effect that different Specific Creepage Distance and S/P ratio has on the Insulator.

2. Compare A2(EPDM) with C2(SR) to find out the effect that different materials have on the performance of the Insulators.

3. Compare A3 with B1 and B3 with C1 to find out how SR Insulators from different manufacturers behave.

4. Compare B2 with B3 and C1 with C2 to determine the effect that horizontal and vertical orientation has on the Insulators.

5. Compare B1 with B3 to see the effect that corona rings have on the performance of the Insulator.

6. C3 is a referenced horizontal, glass cap and pin disk string.

Page 11: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Substation

Experienced Pollution FlashoversInsulators were greased with siliconeInsulators were coated with RTV SR.CT’s have Scd = 18 mm/kV.For diameters above 500mm, the effective Scd is given as 14.4 mm/kv.

Page 12: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Substation

Page 13: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Substation

Page 14: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Walmund Substation

Page 15: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Pollution Monitoring

Directional Dust Deposit Gauges (DDDG)

Insulator Surface Conductivity Monitor (ISCoM)

Page 16: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Climate Monitoring

Accumulated RainfallRelative HumidityTemperatureWind Speed and DirectionUVB Solar Radiation

Page 17: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Data captured at Walmund Insulator Test Tower

Pollution Data Climate DataLeakage Current Data

Page 18: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Pollution Data

Page 19: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

ISCoM Surface Conductivity

Max = 1.9 SAvg = 1.5 Sµ

µ

Page 20: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Climate Data

Page 21: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Average Relative Humidity vs Time of Day plot

Page 22: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

The Average Maximum Absolute Leakage I peak

Page 23: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Maximum Leakage Current on the Glass Disk(C3)

Page 24: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Maximum Leakage Current for EPDM (A2)

Page 25: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Maximum Absolute Leakage Current Peak for A2 &C2

Page 26: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Accumulative Resulting Charge on Insulators A2 & C2

Page 27: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Accumulative Resulting Charge for Insulators B2 & B3

Page 28: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Conclusions

A 220 kV Insulator Performance Test Tower has being implemented.The First series of data shows promising results.The effect of Material Choice and Insulator Orientation is well demonstrated.The data obtained correlates with the Results obtained from Clansdale Insulator Performance Test Tower in Natal.

Page 29: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith

Recommendations

Data should continuously be captured for at least 10 years so that the effect of Material Ageing can be investigated.The data should be entered into the the Insulator Selection Tool Program every 2 years.This is to aid Namibia with Insulator Selection for the Power Network.

Page 30: Implementation of 220 kV In-Service Insulator … Substation Experienced ... A 220 kV Insulator Performance Test Tower has being implemented. ... PowerPoint Presentation Author: judith