—MICAFIL BUSHINGS, AUGUST 2018, LORENZO MARTINEL, HEAD OF SERVICE
Introducing MICAFIL BushingsMICAFIL High Voltage Dry BushingsIncrease safety and reliability by specifying your transformer bushings
—
Failure statistic of power transformer
Fig. 1 University of Stuttgard … http://www.mdpi.com/1996-1073/9/5/347/htm
Increase safety and reliability by specifying your transformer bushings
September 4, 2018 Slide 2
Statistics
—Specification of bushings
September 4, 2018 Slide 3
IEC 60137 - 2017 IEEE C57.19.00- 2004 and C57.19.01- 2000
Standards do not recommend any technologies
Most common standards for bushing transformers include test procedures, certain limits and properties
—
The utility/OEM should define the technology i.e. RIP / RIS / OIP
Specification of bushings
September 4, 2018 Slide 4
RIP (Resin Impregnated Paper) RIS (Resin Impregnated Synthetic) OIP (Oil Impregnated Paper)
The most common Standard i.e. IEC 60137 as well as IEEE C57.19.00 and C57.19.01 do not recommend orspecify any kind of technology of which the bushings should be made of. But CIGRE does.
—Increase safety and reliability by specifying your transformer bushings
September 4, 2018 Slide 5
Official papers published by CIGRE
The risk of fires being initiated by a failure of a RIP (Resin Impregnated Paper) or a RIS (Resin Impregnated Synthetic) bushing issignificantly less than … (page 3, §3.2)
—Increase safety and reliability by specifying your transformer bushings
September 4, 2018 Slide 6
Official papers published by CIGRE
Using RIP high voltage bushings is most cost effective method of reducing the risk of transformer fire…. (page 82, §6.8.1)
—Specification of bushings
September 4, 2018 Slide 7
Benefits of capacity – controlled electric field:
– homogeneous electric field in the insulation material
– lower maximum electrical stress on the insulation
– longer operational safety
– Standard available IEC 60137 and IEEE C57.19.00 and …01
– Measuring Tap / Voltage Tap on each bushing
Type of electrical field distribution
—
Due to safety aspects we recommend to specify composite insulation ….
Specification of bushings
September 4, 2018 Slide 8
Composite insulation HTV Composite insulation LSR Porcelain brown or gray
Airside insulation types
—
… which passed the relevant Type Tests for all voltage levels.
Specification of bushings
September 4, 2018 Slide 9
Composite insulation HTV (RIP) Composite insulation LSR (RIP/RIS) Porcelain brown or gray
Airside insulation types
To ensure highest quality of the compositematerial, following type tests should bespecified:
IEC 61462
- Tracking and erosion- flammability test- water diffusion test- …
Optional
IEC 61109 : 5000h multi stress test
KIPTS Koeberg pollution test or similar
To ensure highest quality of the compositematerial, following type tests should bespecified:
IEC 61462
- Tracking and erosion- flammability test- water diffusion test- …
Optional
IEC 61109 : 5000h multi stress test
KIPTS Koeberg pollution test or similar
—
RIP, Composite molded on fiberglass tube / RIS, composite is direct molded on condenser core
Specification of bushings
September 4, 2018 Slide 10
HTV on fiberglass tube LSR on fiberglass tube or direct mold Porcelain brown or gray
Airside insulation types and construction
—Specification of bushings
September 4, 2018 Slide 11
Routine test limits according: ABB Micafil bushings routine test limits
IEC 60137 – 2017 // IEEE C57.19.01 - 2000
- Dissipation factor (tand), Power Factor < 0.40%
- Partial Discharge < 2 pC at 2x Um/√3
Example: RTXF 420-1675/1000 KSI
- 2 x 420kV/√3 = 485kV
- Partial Discharge acceptable at 485kV < 2pC
IEC 60137 – 2017 // IEEE C57.19.01 - 2000
- Dissipation factor (tand), Power Factor < 0.7%
- Partial Discharge < 10 pC at Um
Example: RTXF 420-1675/1000 KSI
- Partial Discharge acceptable at 420kV < 10pC
Ensures a long lifetime for bushings and your equipment
Routine Test: limits of dissipation factor (tand) as well as partial discharge
—Specification of bushings
September 4, 2018 Slide 12
Voids causing partial discharge between al. layers Increase of capacitance due to short circuit of al layers
Typical sign of short circuit of aluminum layers is an increase of capacitance
Partial Discharge causes acceleration of aging
—Specification of bushings
September 4, 2018 Slide 13
The standard IEC 60137 refers to IEC 60815-2 and -3:
– Site severity determination (pollution on site)
• Light 16 mm/kV
• Medium 20 mm/kV
• Heavy 25 mm/kV
• Very heavy 31 mm/kV
MICAFIL bushings standard is 31mm/kV related to Um
MICAFIL bushings standard is 31mm/kV
Pollution level affects creepage distance and arcing distance
—Specification of bushings
September 4, 2018 Slide 14
Seismic specification according IEEE 693(moderate level, high level)
Shake table test to all bushings > 160kV
Calculation valid to all bushings < 160kV
Seismic specification according IEC TS 61463
Calculation valid for all bushings accelerationhas to be defined [m/s2]
Simulation on request
Simulation and report on request
Seismic requirements
—Specification of bushings
September 4, 2018 Slide 15
On which altitude will the transformer be installed:
All standard bushings are designed for an installation altitude of1000m / 3300ft.According IEC 60137 §5.2 as well as IEEE C57.19.00-2004 §4.2.1
Indicate the altitude in your specification, if you exceed 1000m or3300ft.
Installation altitude
—
Depending on the preference of the utility /OEM
Specification of bushings
September 4, 2018 Slide 16
Cable bolt for draw lead Removable solid rod conductor Fix conductor (non removable)
Type of conductors
Lower current range Medium currents current range High current range
—Specification of bushings
September 4, 2018 Slide 17
RIP bushings RIS bushings
– RIP bushings are very sensitive to humidity
– Paper absorbs humidity which has an impact to the quality ofthe condenser core (increase of tand)
– Precautions have to be taken
Specify the way of storage especially for spare bushings
Storage of bushings
- Less sensitive since Synthetic mash has been used
—
Specify the way of storage especially for spare bushings
Specification of bushings
September 4, 2018 Slide 18
Standard packing for < 6 months Long-term storage up to 2 years Long-term storage up to 2 years
Storage of bushings
—Specification of bushings
September 4, 2018 Slide 19
Specification for new transformer bushings Specification for replacement bushings
• Fleet Management will help to reduce cost and increaseavailability.
• Details were shown in this presentation
Take the opportunity for cost savings and increasing availability.
Taking Fleet Management into consideration
—Specification of bushings
September 4, 2018 Slide 20
Current transformer (CT) adjustments Specification for replacement bushings
• Fleet Management will help to reduce cost and increaseavailability.
• Adjustments with adapter flanges for CT adjustments
Take the opportunity for cost savings and increasing availability.
Taking Fleet Management into consideration
—Specification of bushings
September 4, 2018 Slide 21
Expected lifetime of the MICAFIL bushings as well as reference lists
—Your Contact Partners – Customer Service
September 4, 2018 Slide 22
MICAFIL Service Team 24 / 7
Your Service Team
We are pleased to inform you, that our Service Team will be available for you 24h a day and 7 days a week.
Please call +41 58 586 0770It will be a pleasure to support you for all technical requests or questions you have.
Lorenzo MartinelTeamleader [email protected]
Karl HechtService [email protected]
Zekeriya TanSenior Service [email protected]
Mario KoppService [email protected]
Gianluca BoccarelloService [email protected]