Jürgen Schilder, Thorsten Reibel – ABB Customer Training Center Heidelberg
ABB STOTZ-KONTAKT GmbHWebinar ABB i-bus® KNX HVAC
© ABB9/18/2015 DESTO Jürgen Schilder | 2
HVAC Range Overview ABB i-bus® KNX Current situation
Fan CoilActuator
Fan CoilController
Room Master
AnalogueInput
RTCFan Coil
priOn
Air QualitySensor
ElectromotorValve Drive
RTRCommercial
RTCSolo
ElectrothermalValve Drive
Valve Drive Actuator
Electronic Switch Actuator
Fan CoilActuator
0-10 V
Blower Actuator
PresenceDetector
Universal Interface +Electronic Relay
RTCTriton
RoomController
Analogue Actuator
© ABB9/18/2015 DESTO Jürgen Schilder | 3
Valve Drive Actuatore.g. individual Room Temperature Control
MagnetReed
Contacte.g. Security
TerminalMT/U
Valve DriveActuator VAA/S
Thermoelectric Valve Drive
TSA/K
Room Thermostat
Switching between the operating modes in the
room thermostat,e.g. time switch, “good-
night”-switch sensor, presence detector, …
© ABB9/18/2015 DESTO Jürgen Schilder | 4
Electromotor Valve Drivee.g. individual Room Temperature Control
Room Thermostat
ElectromotorValve Drive
ST/K 1.1
MagnetReed
Contact
Switching between the operating modes in the
room thermostat,e.g. time switch, “good-
night”-switch sensor, presence detector, …
© ABB9/18/2015 DESTO Jürgen Schilder | 5
Blower Actuatore.g. Room with Radiators
Comfortable room climate in dependence on the Room temperature Humidity CO2 concentration
Air Quality Sensor LGS/A
Presence detector 6131
Switch sensor(manual fan speed)
Blower Actuator FCL/S
BlowerRTC 6138
ST/K 1.1
© ABB9/18/2015 DESTO Jürgen Schilder | 6
Fan Coil-Unit with drip tray, auxilliary heater, 3-speed fan, motor power operated heating and cooling valves
Switching between the operating modes in the room thermostate.g. time switch, presence detector
Fan Coil-Aktor FCA/S e.g. Office
Fan CoilActuator
MagnetReed
Contact
Presence Detector
Fan Coil-Unit
Room Thermostat
© ABB9/18/2015 DESTO Jürgen Schilder | 7
Fan Coil-Aktor FCA/Se.g. Hotel Room
Room Thermostat
Fan Coil-Unit with drip tray, auxilliary heater, 3-speed fan, motor power operated heating and cooling valves
Switching between the operating modes in the room thermostat,e.g. keycard reader, reception desk, …
FanCoil-Unit
Fan Coil Actuator
MagnetReed
Contact
© ABB9/18/2015 DESTO Jürgen Schilder | 8
Room Master RM/Se.g. Hotel Room
Fan Coil-Unit with drip tray, auxilliary heater, 3-speed fan, motor power operated heating and cooling valves
Switching between the operating modes in the room thermostat,e.g. keycard reader, reception desk, …
Fan Coil-Unit
Room ThermostatMagnet
ReedContact
RoomMaster
© ABB9/18/2015 DESTO Jürgen Schilder | 9
It measures the current room temperature (actual value) and sends a control value (0-1 or 0...100 %) to achieve the desired room temperature (target value)
Heating and CoolingRoom Thermostat
TritonSolo Fan Coil
Control Value1-Bit or
8-Bit (continuous)
Current Temperature
Window contact, drip tray, …
Operation ModeFrost/Night/Comfort
Setpoint
Busch priOn RTRCommercial
© ABB9/18/2015 DESTO Jürgen Schilder | 10
Air Quality Sensor LGS/A 1.1Features
To multiplex measurement to
the CO2-concentration
the air-humidity
the temperature
in a room
The detection is possible for
control a fan
control valves
control a outside air-dependent fans
position indicator for fan flaps
© ABB9/18/2015 DESTO Jürgen Schilder | 11
Air Quality Sensor LGS/A 1.1Comfortable room climate
People raise the CO2 concentration in the air when they breathe:
Normal room air has about 21% Oxygen (O2) and about
0.035 % Carbon Dioxide (CO2)
However, during exhalation the air only contains about 16 % O2 (reduction of about 24 %), but 4 % CO2 (a more than 100-fold increase!)
In addition to the CO2 concentration, the relationship between room temperature and humidity is also an important consideration in achieving a comfortable room climateComfortable room climate in dependence
on the room temperature and humidity
© ABB9/18/2015 DESTO Jürgen Schilder | 12
Air Quality Sensor LGS/A 1.1Application
(Multi-speed)
Fan
Motor drive
CO2concentrationTemperature
Air humidity
Air Quality SensorLGS/A with measurement
and monitoring ofCO2 concentration,
temperatureand humidity
Optional: manualsetting of fan speed,
e.g. US/U 4.2
Occupancy control,e.g. 6131
Timer control, logic control,e.g. ABZ/S, ABL/S,
FW/S
Control of fans andblowers, e.g. by FCL/S,
FCA/S, RM/S, RC/A
Control of motor operatedwindows, window slats or
roof hatches, e.g. by JRA/S
© ABB9/18/2015 DESTO Jürgen Schilder | 13
Room Thermostat with Actuators
FCA/S 1.1MFCA/S 1.2.2.1
ST/K US/Ux.2 + ER/U1.1 + TSA/K
ES/S + TSA/K or motor valve drive
RM/S x.1
For Fan Coil Units
VAA/S + TSA/K
RC/A x.2
FCL/S x.6.1.1
© ABB9/18/2015 DESTO Jürgen Schilder | 14
Heating and Cooling Control of Thermoelectric Valves Drives
Control Value from Room Thermostat
1-Bit or8-Bit (continuous)
Electronic Relay ER/U 1.1
Thermoelectric Valve DriveTSA/K
Valve DriveActuator VAA/S
Universal Interface US/U
Electronic Switch Actuator ES/S
FanCoilActuatorFCA/S
Blower ActuatorFCL/S
Room Master RM/S
© ABB9/18/2015 DESTO Jürgen Schilder | 15
Heating and Cooling 2-Step Control (1-Bit)
Room Thermostat
1
0
Setpointtemperature
CurrentTemperature
Valve Drive Actuator VAA/S
Electronic Switch Actuator ES/S
Transmitted control value
1-bit
Calculatedcontrol value
1-bit
© ABB9/18/2015 DESTO Jürgen Schilder | 16
Heating and Cooling Discontinuous PI Control (PWM control 1-bit)
Room Thermostat
Valve Drive Actuator VAA/S
Electronic Switch Actuator ES/S
Sensor: Convert
Control Valueto PWM
Transmitted control value
1-bit
Calculatedcontrol value
8-bit
© ABB9/18/2015 DESTO Jürgen Schilder | 17
Heating and Cooling Discontinuous PI Control (PWM control 8-bit)
Room Thermostat
Actuator:Convert
control Valueto PWM
Valve Drive Actuator VAA/S
Electronic Switch Actuator ES/STransmitted
control value8-bit
Calculatedcontrol value
8-bit
© ABB9/18/2015 DESTO Jürgen Schilder | 18
Heating and Cooling Control of Electromotor Valve Drives (3-point or KNX)
3-pointvalvedrive
Electronic Switch Actuator
ES/SControl Value
from Room Thermostat
8-Bit (continuous)
FanCoilActuatorFCA/S
Room Master RM/S
Electromotor Valve Drive ST/K
© ABB9/18/2015 DESTO Jürgen Schilder | 19
Heating and Cooling Continuous PI Control (8-Bit)
Transmitted control value
8-bit
Direct valve Positioning
Calculatedcontrol value
8-bit
Room Thermostat
© ABB9/18/2015 DESTO Jürgen Schilder | 20
Heating and Cooling Which control system ???
RadiatorPWM (cycle time 15 minutes) or 2-point control
Underfloor/Wall HeatingThis system reacts very slowly, therefore, a PWM control with a cycle time of 20 - 30 minutes is appropriate
Hot water Fan HeatersIn this case, the hot-water circuit is controlled. A continuous control is ideal. As a result, the temperature of the air stream remains relatively constant.
Electric convector HeatersPWM control and cycle time 15 minutes
Fan Cooling Continuous PI control, change for automatic transmission: 5%
© ABB9/18/2015 DESTO Jürgen Schilder | 21
Heating and Cooling Overview Valve Drives
Thermoelectric valve drive, ABB, Type TSA/K 2 step control, PWM
Voltage: 24 V AC/DC or 230 V AC VAA/S, ES/S, FCL/S, RM/S, FCA/S, RC/A, (SA/S)
Electromotor valve drive, 3-point Continous control
Voltage: 230 V AC ES/S, FCA/S 1.1M, RM/S
Electromotor valve drive, ABB, Type ST/K 1.1 Continous control
Voltage: via KNX direct KNX
© ABB9/18/2015 DESTO Jürgen Schilder | 22
Heating and CoolingOverview Valve Drives
Thermoelectric valve drive, e.g. Moehlenhoff analogue signal: 0...10 V (continous control)
Voltage: 24 V AC FCA/S 1.2.2.1
Electromotor valve drive, e.g. Heimeier, TYP EMO 1 analogue signal: 0...10 V (continous control)
Voltage: 24 V AC FCA/S 1.2.2.1
© ABB9/18/2015 DESTO Jürgen Schilder | 23
Thermoelectric Valve Drive TSA/K
Function The resistor-heated elastic element ① is heated and expands by applying the operating power
The integrated ram ② performs the adjustment travel
The adjustment travel (approx. 4 mm) is transformed to the valve lifter ③
The valve will be opened or closed.The function display ④ shows valve status
①
②
③
④
© ABB9/18/2015 DESTO Jürgen Schilder | 24
Heating and Cooling The perfect climate
Blower- and Fan Coil Actuators are basic devices in HVAC
No integrated controller to regulate the room temperature
Control values sent by external components like room thermostat or KNX push button
ABB i-bus KNX-Actuators
Electronic Switch Actuator ES/S x.1.2.1
Valve Drive Actuator VAA/S x.230.2.1
Blower Actuator FCL/S x.6.1.1
Fan Coil-Actuator FCA/S 1.1M and FCA/S 1.2.2.1
Room Controller RC/A with Switch Actuator Module SA/M 2.6.1
Room Master RM/S x.1
© ABB9/18/2015 DESTO Jürgen Schilder | 26
Electronic Switch Actuator ES/S x.1.2.1System Overview Room Temperature Control
ES/S x.1.2.1
24…230 V AC/DC
Radiators Cooling Ceilings Floor Heating
Room Thermostat
M
Fan Coil Units
Electromotorvalve drives
(3-point)
Thermoelectricvalve drives
© ABB9/18/2015 DESTO Jürgen Schilder | 27
Electronic Switch Actuator ES/S x.1.2.1Product and functional overview
Electronic Switch Actuator
ES/S 4.1.2.1 - 4 electronic outputs
ES/S 8.1.2.1 - 8 electronic outputs
Control thermoelectric valve drives (TSA/K 24.1 / 230.1)
Control electromotor valve drives (3-point)
Noiseless and wear-free switching of loads (e.g. lighting, up to 1 A) via SA/S application
M
© ABB9/18/2015 DESTO Jürgen Schilder | 28
Electronic Switch Actuator ES/S 4.1.2.1Combining Operating Modes
Installation Sample Output A:
Thermoelectric Valve Drive
Output B:Lighting
Output C/D:Electromotor Valve Drive
Each two outputs have one neutral conductor
© ABB9/18/2015 DESTO Jürgen Schilder | 29
Valve Drive Actuator VAA/S x.230.2.1Potential savings with individual room control
© ABB9/18/2015 DESTO Jürgen Schilder | 30
Valve Drive Actuator VAA/S x.230.2.1System overview
VAA/S x.230.2.1
24…230 V AC
Radiators Cooling Ceilings Floor Heating
Room Thermostat
Thermoelectricvalve drives
Fan Coil Units
© ABB9/18/2015 DESTO Jürgen Schilder | 31
Valve Drive Actuator VAA/S x.230.2.1Product and functional overview
Connection of thermoelectric valve drives (e.g. TSA/K)
6 or 12 semiconductor outputs
Manual operation for commissioning and diagnostic
Rated voltage: 24…230 V AC
Rated current: 160 mA per output
3 non-isolated outputs in one group (short circuit and overload protected)
Simplified commissioning: Copy and exchange
Universal head screw
The devices do not require an additional auxiliary power supply (only KNX)
© ABB9/18/2015 DESTO Jürgen Schilder | 32
Valve Drive Actuator VAA/S 12.230.2.1Connection schematics
(1) Label carrier
(2) Button/LED Programming (red)
(3) Bus connection terminal
(4) Button/LED Manual Operation (yellow)
(5) Button ON/OFF per output
(6) LED ON/OFF (yellow) per output
(7) Connection terminals for outputs A…L and power supply Un
(8) LED Overload/Short Circuit (red)
(9) Button Reset Overload/Short Circuit
© ABB9/18/2015 DESTO Jürgen Schilder | 33
Comparision Valve Drive - Electronic Switch Actuator VAA/S - ES/S
VAA/S ES/SNo. of channels 6/12 4/8
Thermoelectric valve drives
3-point valve drives -
Lamp load -
24 … 230 V AC/DC valve drives -
24 … 230 V AC valve drives
Peak current / Nominal current 750 /160 mA 8 A / 1 A
No. of thermoelectric valve drives per channel (230 V)
4* 26*
No. of thermoelectric valve drives per channel (24 V)
2* 4*
Price per channel ++ +
*valid for ABB TSA/K x.1
© ABB9/18/2015 DESTO Jürgen Schilder | 34
Fan Coil-Unit Overview
Heating circuit
Cold water generator Central-heating boiler
Fan Coil-Unit
Cooling circuit
Fan CoilActuatorFCA/S
Room Thermostat
6138
Valve Drives(e.g. TSA/K)
Heating Cooling
© ABB9/18/2015 DESTO Jürgen Schilder | 35
Fan Coil-Unit Control of a Fan Coil Unit with Fan Coil Actuator
Fan Electrical Heater Window Contact
Sensor forCondensation
Water
Fan ControlRecuperator
Chiller
HeatingValve
CoolingValve
© ABB9/18/2015 DESTO Jürgen Schilder | 36
Heating and CoolingPrinciple
HeatingMode
100%
Con
trol V
alue
%
0%
Deadzone:distance between heating
setpoint and cooling setpoint
Ventilatione.g. FanCoil-
Actuator
Speed 3
Speed 2
Speed 1
TemperatureSetpoint Heating
e.g. 21°CSetpoint Cooling
e.g. 24°C
CoolingMode
30%
10%
70%
100%
0%
Threshold value stage
© ABB9/18/2015 DESTO Jürgen Schilder | 38
Blower Actuator FCL/S x.6.1.1
A Blower Actuator FCL/S x.6.1.1 is used in ventilation applications
The FCL/S 1.6.1.1 1-fold actuator
Controls a single-phase fan with up to three fan speeds
Additional switching output
The FCL/S 2.6.1.1 2-fold actuator
Controls two independent fans with up to three fan speeds
Alternatively the second fan output can be used as three switch outputs
Two additional switching outputs
Outputs can be also used for valve drives (only open/close, no PWM)
© ABB9/18/2015 DESTO Jürgen Schilder | 39
Blower Actuator FCL/S x.6.1.1
Air Quality Sensor LGS/A
Blower Actuator FCL/S
Blower
Presence detector
Switch sensor(manual fan speed)
temperature, humidity,
CO2
Direct Operation Fan speed Byte
Fan speed Bit
Fan speed up/down
Automatic Control Control value
0 .. 100%
© ABB9/18/2015 DESTO Jürgen Schilder | 40
Blower Actuator FCL/S x.6.1.1
Connection schematic
FCL/S 1.6.1.1 Blower Actuator, 1-fold FCL/S 2.6.1.1 Blower Actuator, 2-fold
The second blower output can alternatively used as 3 Switch Actuator outputs
© ABB9/18/2015 DESTO Jürgen Schilder | 42
Fan Coil-Actuator FCA/S 1.1M
Two outputs Electronic (0.5 A) for control of 3-point valve drives or thermal heating and cooling valves
Multi-level fans with up to three fan speeds can be switched via floating contact
Two binary inputs, e.g. for monitoring of a window contact and the dew point are available
The additional contact (16 A) is used, for example, to control an electric heater
Manual operation via plastic foil keypad
© ABB9/18/2015 DESTO Jürgen Schilder | 44
Fan Coil-Actuator FCA/S 1.1M
Application Typ of Fan (Changeover Switch or Step Switch)
Start up Behaviour
Minimum Time in a Level
Threshold for Switching to another Level
Hysteresis
Limitation of Fan stage in Automatic Mode
Forced Operation of Fan stage in Automatic and Direct Mode
Status Messages (Fan stage, Valve, ...)
Monitoring of RTC with parametrisable Function
…
© ABB9/18/2015 DESTO Jürgen Schilder | 45
Fan Coil-Actuator FCA/S 1.1M
Application Direct Mode
1 Bit for up/down
1 Bit for direct Fan Speed
1 Byte for direct Fan Speed (Value 0,1,2,3)
Automatic Mode
Depending on Control Value from Room Thermostat
LimitationE.g. only Fan Stage 1 and 2
Control value fan speed0... 9 % 0 (fan off)10...39 % 140...69 % 270...100 % 3
© ABB9/18/2015 DESTO Jürgen Schilder | 46
Fan Coil-Actuator FCA/S 1.1M
Types of Fan control Control via changeover
switch
Control via step switch0123
Output
Off 0 0 0
Fan speed 1 1 0 0
Fan speed 2 0 1 0
Fan speed 3 0 0 1
Output
Off 0 0 0
Fan speed 1 1 0 0
Fan speed 2 1 1 0
Fan speed 3 1 1 1
© ABB9/18/2015 DESTO Jürgen Schilder | 47
Fan Coil Actuator FCA/S 1.2.2.1, 0…10 V
Fan
Filter
Relay 20 AX
Binary inputs
Valve Output 0…10 V
Manual operation
Tag Holder
© ABB9/18/2015 DESTO Jürgen Schilder | 49
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Room Thermostat
Fan Coil-Unit
Fan Coil Actuator
MagnetReed
Contact
Valve drive: Cooling HeatingFan
Electricalheater
© ABB9/18/2015 DESTO Jürgen Schilder | 50
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
© ABB9/18/2015 DESTO Jürgen Schilder | 51
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)
© ABB9/18/2015 DESTO Jürgen Schilder | 52
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)
© ABB9/18/2015 DESTO Jürgen Schilder | 53
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)
© ABB9/18/2015 DESTO Jürgen Schilder | 54
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)
© ABB9/18/2015 DESTO Jürgen Schilder | 55
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)
© ABB9/18/2015 DESTO Jürgen Schilder | 56
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation
Roo
m T
herm
osta
t 613
8
Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …
Fan
Coi
l-Act
uato
r FC
A/S
1.1M
Rocker 1Rocker 2Rocker 34-
fold
Rocker 4
Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)
Fan automatic/manual…
Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.
Control – Frost/heat protection
Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)
© ABB9/18/2015 DESTO Jürgen Schilder | 57
Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room
Simulation current
temperature
© ABBDESTO Jürgen Schilder | 9/18/2015 58
HVAC Documentation on www.abb.com/knx
Pdf: Heating, Air-Conditioning and Ventilation Control with EIB
Application Manual: Heating Ventilation Air-Conditioning Order Number 2CDC 500 067 M0201
E-Learning module: Room Climate Control
© ABB18.09.2015 DESTO Jürgen Schilder | 60