place picture here

Jürgen Schilder, Thorsten Reibel – ABB Customer Training Center Heidelberg

ABB STOTZ-KONTAKT GmbHWebinar ABB i-bus® KNX HVAC

© ABB9/18/2015 DESTO Jürgen Schilder | 2

HVAC Range Overview ABB i-bus® KNX Current situation

Fan CoilActuator

Fan CoilController

Room Master

AnalogueInput

RTCFan Coil

priOn

Air QualitySensor

ElectromotorValve Drive

RTRCommercial

RTCSolo

ElectrothermalValve Drive

Valve Drive Actuator

Electronic Switch Actuator

Fan CoilActuator

0-10 V

Blower Actuator

PresenceDetector

Universal Interface +Electronic Relay

RTCTriton

RoomController

Analogue Actuator

© ABB9/18/2015 DESTO Jürgen Schilder | 3

Valve Drive Actuatore.g. individual Room Temperature Control

MagnetReed

Contacte.g. Security

TerminalMT/U

Valve DriveActuator VAA/S

Thermoelectric Valve Drive

TSA/K

Room Thermostat

Switching between the operating modes in the

room thermostat,e.g. time switch, “good-

night”-switch sensor, presence detector, …

© ABB9/18/2015 DESTO Jürgen Schilder | 4

Electromotor Valve Drivee.g. individual Room Temperature Control

Room Thermostat

ElectromotorValve Drive

ST/K 1.1

MagnetReed

Contact

Switching between the operating modes in the

room thermostat,e.g. time switch, “good-

night”-switch sensor, presence detector, …

© ABB9/18/2015 DESTO Jürgen Schilder | 5

Blower Actuatore.g. Room with Radiators

Comfortable room climate in dependence on the Room temperature Humidity CO2 concentration

Air Quality Sensor LGS/A

Presence detector 6131

Switch sensor(manual fan speed)

Blower Actuator FCL/S

BlowerRTC 6138

ST/K 1.1

© ABB9/18/2015 DESTO Jürgen Schilder | 6

Fan Coil-Unit with drip tray, auxilliary heater, 3-speed fan, motor power operated heating and cooling valves

Switching between the operating modes in the room thermostate.g. time switch, presence detector

Fan Coil-Aktor FCA/S e.g. Office

Fan CoilActuator

MagnetReed

Contact

Presence Detector

Fan Coil-Unit

Room Thermostat

© ABB9/18/2015 DESTO Jürgen Schilder | 7

Fan Coil-Aktor FCA/Se.g. Hotel Room

Room Thermostat

Fan Coil-Unit with drip tray, auxilliary heater, 3-speed fan, motor power operated heating and cooling valves

Switching between the operating modes in the room thermostat,e.g. keycard reader, reception desk, …

FanCoil-Unit

Fan Coil Actuator

MagnetReed

Contact

© ABB9/18/2015 DESTO Jürgen Schilder | 8

Room Master RM/Se.g. Hotel Room

Fan Coil-Unit with drip tray, auxilliary heater, 3-speed fan, motor power operated heating and cooling valves

Switching between the operating modes in the room thermostat,e.g. keycard reader, reception desk, …

Fan Coil-Unit

Room ThermostatMagnet

ReedContact

RoomMaster

© ABB9/18/2015 DESTO Jürgen Schilder | 9

It measures the current room temperature (actual value) and sends a control value (0-1 or 0...100 %) to achieve the desired room temperature (target value)

Heating and CoolingRoom Thermostat

TritonSolo Fan Coil

Control Value1-Bit or

8-Bit (continuous)

Current Temperature

Window contact, drip tray, …

Operation ModeFrost/Night/Comfort

Setpoint

Busch priOn RTRCommercial

© ABB9/18/2015 DESTO Jürgen Schilder | 10

Air Quality Sensor LGS/A 1.1Features

To multiplex measurement to

the CO2-concentration

the air-humidity

the temperature

in a room

The detection is possible for

control a fan

control valves

control a outside air-dependent fans

position indicator for fan flaps

© ABB9/18/2015 DESTO Jürgen Schilder | 11

Air Quality Sensor LGS/A 1.1Comfortable room climate

People raise the CO2 concentration in the air when they breathe:

Normal room air has about 21% Oxygen (O2) and about

0.035 % Carbon Dioxide (CO2)

However, during exhalation the air only contains about 16 % O2 (reduction of about 24 %), but 4 % CO2 (a more than 100-fold increase!)

In addition to the CO2 concentration, the relationship between room temperature and humidity is also an important consideration in achieving a comfortable room climateComfortable room climate in dependence

on the room temperature and humidity

© ABB9/18/2015 DESTO Jürgen Schilder | 12

Air Quality Sensor LGS/A 1.1Application

(Multi-speed)

Fan

Motor drive

CO2concentrationTemperature

Air humidity

Air Quality SensorLGS/A with measurement

and monitoring ofCO2 concentration,

temperatureand humidity

Optional: manualsetting of fan speed,

e.g. US/U 4.2

Occupancy control,e.g. 6131

Timer control, logic control,e.g. ABZ/S, ABL/S,

FW/S

Control of fans andblowers, e.g. by FCL/S,

FCA/S, RM/S, RC/A

Control of motor operatedwindows, window slats or

roof hatches, e.g. by JRA/S

© ABB9/18/2015 DESTO Jürgen Schilder | 13

Room Thermostat with Actuators

FCA/S 1.1MFCA/S 1.2.2.1

ST/K US/Ux.2 + ER/U1.1 + TSA/K

ES/S + TSA/K or motor valve drive

RM/S x.1

For Fan Coil Units

VAA/S + TSA/K

RC/A x.2

FCL/S x.6.1.1

© ABB9/18/2015 DESTO Jürgen Schilder | 14

Heating and Cooling Control of Thermoelectric Valves Drives

Control Value from Room Thermostat

1-Bit or8-Bit (continuous)

Electronic Relay ER/U 1.1

Thermoelectric Valve DriveTSA/K

Valve DriveActuator VAA/S

Universal Interface US/U

Electronic Switch Actuator ES/S

FanCoilActuatorFCA/S

Blower ActuatorFCL/S

Room Master RM/S

© ABB9/18/2015 DESTO Jürgen Schilder | 15

Heating and Cooling 2-Step Control (1-Bit)

Room Thermostat

1

0

Setpointtemperature

CurrentTemperature

Valve Drive Actuator VAA/S

Electronic Switch Actuator ES/S

Transmitted control value

1-bit

Calculatedcontrol value

1-bit

© ABB9/18/2015 DESTO Jürgen Schilder | 16

Heating and Cooling Discontinuous PI Control (PWM control 1-bit)

Room Thermostat

Valve Drive Actuator VAA/S

Electronic Switch Actuator ES/S

Sensor: Convert

Control Valueto PWM

Transmitted control value

1-bit

Calculatedcontrol value

8-bit

© ABB9/18/2015 DESTO Jürgen Schilder | 17

Heating and Cooling Discontinuous PI Control (PWM control 8-bit)

Room Thermostat

Actuator:Convert

control Valueto PWM

Valve Drive Actuator VAA/S

Electronic Switch Actuator ES/STransmitted

control value8-bit

Calculatedcontrol value

8-bit

© ABB9/18/2015 DESTO Jürgen Schilder | 18

Heating and Cooling Control of Electromotor Valve Drives (3-point or KNX)

3-pointvalvedrive

Electronic Switch Actuator

ES/SControl Value

from Room Thermostat

8-Bit (continuous)

FanCoilActuatorFCA/S

Room Master RM/S

Electromotor Valve Drive ST/K

© ABB9/18/2015 DESTO Jürgen Schilder | 19

Heating and Cooling Continuous PI Control (8-Bit)

Transmitted control value

8-bit

Direct valve Positioning

Calculatedcontrol value

8-bit

Room Thermostat

© ABB9/18/2015 DESTO Jürgen Schilder | 20

Heating and Cooling Which control system ???

RadiatorPWM (cycle time 15 minutes) or 2-point control

Underfloor/Wall HeatingThis system reacts very slowly, therefore, a PWM control with a cycle time of 20 - 30 minutes is appropriate

Hot water Fan HeatersIn this case, the hot-water circuit is controlled. A continuous control is ideal. As a result, the temperature of the air stream remains relatively constant.

Electric convector HeatersPWM control and cycle time 15 minutes

Fan Cooling Continuous PI control, change for automatic transmission: 5%

© ABB9/18/2015 DESTO Jürgen Schilder | 21

Heating and Cooling Overview Valve Drives

Thermoelectric valve drive, ABB, Type TSA/K 2 step control, PWM

Voltage: 24 V AC/DC or 230 V AC VAA/S, ES/S, FCL/S, RM/S, FCA/S, RC/A, (SA/S)

Electromotor valve drive, 3-point Continous control

Voltage: 230 V AC ES/S, FCA/S 1.1M, RM/S

Electromotor valve drive, ABB, Type ST/K 1.1 Continous control

Voltage: via KNX direct KNX

© ABB9/18/2015 DESTO Jürgen Schilder | 22

Heating and CoolingOverview Valve Drives

Thermoelectric valve drive, e.g. Moehlenhoff analogue signal: 0...10 V (continous control)

Voltage: 24 V AC FCA/S 1.2.2.1

Electromotor valve drive, e.g. Heimeier, TYP EMO 1 analogue signal: 0...10 V (continous control)

Voltage: 24 V AC FCA/S 1.2.2.1

© ABB9/18/2015 DESTO Jürgen Schilder | 23

Thermoelectric Valve Drive TSA/K

Function The resistor-heated elastic element ① is heated and expands by applying the operating power

The integrated ram ② performs the adjustment travel

The adjustment travel (approx. 4 mm) is transformed to the valve lifter ③

The valve will be opened or closed.The function display ④ shows valve status

© ABB9/18/2015 DESTO Jürgen Schilder | 24

Heating and Cooling The perfect climate

Blower- and Fan Coil Actuators are basic devices in HVAC

No integrated controller to regulate the room temperature

Control values sent by external components like room thermostat or KNX push button

ABB i-bus KNX-Actuators

Electronic Switch Actuator ES/S x.1.2.1

Valve Drive Actuator VAA/S x.230.2.1

Blower Actuator FCL/S x.6.1.1

Fan Coil-Actuator FCA/S 1.1M and FCA/S 1.2.2.1

Room Controller RC/A with Switch Actuator Module SA/M 2.6.1

Room Master RM/S x.1

© ABB9/18/2015 DESTO Jürgen Schilder | 25

Electronic Switch Actuator ES/S x.1.2.1

© ABB9/18/2015 DESTO Jürgen Schilder | 26

Electronic Switch Actuator ES/S x.1.2.1System Overview Room Temperature Control

ES/S x.1.2.1

24…230 V AC/DC

Radiators Cooling Ceilings Floor Heating

Room Thermostat

M

Fan Coil Units

Electromotorvalve drives

(3-point)

Thermoelectricvalve drives

© ABB9/18/2015 DESTO Jürgen Schilder | 27

Electronic Switch Actuator ES/S x.1.2.1Product and functional overview

Electronic Switch Actuator

ES/S 4.1.2.1 - 4 electronic outputs

ES/S 8.1.2.1 - 8 electronic outputs

Control thermoelectric valve drives (TSA/K 24.1 / 230.1)

Control electromotor valve drives (3-point)

Noiseless and wear-free switching of loads (e.g. lighting, up to 1 A) via SA/S application

M

© ABB9/18/2015 DESTO Jürgen Schilder | 28

Electronic Switch Actuator ES/S 4.1.2.1Combining Operating Modes

Installation Sample Output A:

Thermoelectric Valve Drive

Output B:Lighting

Output C/D:Electromotor Valve Drive

Each two outputs have one neutral conductor

© ABB9/18/2015 DESTO Jürgen Schilder | 29

Valve Drive Actuator VAA/S x.230.2.1Potential savings with individual room control

© ABB9/18/2015 DESTO Jürgen Schilder | 30

Valve Drive Actuator VAA/S x.230.2.1System overview

VAA/S x.230.2.1

24…230 V AC

Radiators Cooling Ceilings Floor Heating

Room Thermostat

Thermoelectricvalve drives

Fan Coil Units

© ABB9/18/2015 DESTO Jürgen Schilder | 31

Valve Drive Actuator VAA/S x.230.2.1Product and functional overview

Connection of thermoelectric valve drives (e.g. TSA/K)

6 or 12 semiconductor outputs

Manual operation for commissioning and diagnostic

Rated voltage: 24…230 V AC

Rated current: 160 mA per output

3 non-isolated outputs in one group (short circuit and overload protected)

Simplified commissioning: Copy and exchange

Universal head screw

The devices do not require an additional auxiliary power supply (only KNX)

© ABB9/18/2015 DESTO Jürgen Schilder | 32

Valve Drive Actuator VAA/S 12.230.2.1Connection schematics

(1) Label carrier

(2) Button/LED Programming (red)

(3) Bus connection terminal

(4) Button/LED Manual Operation (yellow)

(5) Button ON/OFF per output

(6) LED ON/OFF (yellow) per output

(7) Connection terminals for outputs A…L and power supply Un

(8) LED Overload/Short Circuit (red)

(9) Button Reset Overload/Short Circuit

© ABB9/18/2015 DESTO Jürgen Schilder | 33

Comparision Valve Drive - Electronic Switch Actuator VAA/S - ES/S

VAA/S ES/SNo. of channels 6/12 4/8

Thermoelectric valve drives

3-point valve drives -

Lamp load -

24 … 230 V AC/DC valve drives -

24 … 230 V AC valve drives

Peak current / Nominal current 750 /160 mA 8 A / 1 A

No. of thermoelectric valve drives per channel (230 V)

4* 26*

No. of thermoelectric valve drives per channel (24 V)

2* 4*

Price per channel ++ +

*valid for ABB TSA/K x.1

© ABB9/18/2015 DESTO Jürgen Schilder | 34

Fan Coil-Unit Overview

Heating circuit

Cold water generator Central-heating boiler

Fan Coil-Unit

Cooling circuit

Fan CoilActuatorFCA/S

Room Thermostat

6138

Valve Drives(e.g. TSA/K)

Heating Cooling

© ABB9/18/2015 DESTO Jürgen Schilder | 35

Fan Coil-Unit Control of a Fan Coil Unit with Fan Coil Actuator

Fan Electrical Heater Window Contact

Sensor forCondensation

Water

Fan ControlRecuperator

Chiller

HeatingValve

CoolingValve

© ABB9/18/2015 DESTO Jürgen Schilder | 36

Heating and CoolingPrinciple

HeatingMode

100%

Con

trol V

alue

%

0%

Deadzone:distance between heating

setpoint and cooling setpoint

Ventilatione.g. FanCoil-

Actuator

Speed 3

Speed 2

Speed 1

TemperatureSetpoint Heating

e.g. 21°CSetpoint Cooling

e.g. 24°C

CoolingMode

30%

10%

70%

100%

0%

Threshold value stage

© ABB9/18/2015 DESTO Jürgen Schilder | 37

Blower Actuator FCL/S x.6.1.1

© ABB9/18/2015 DESTO Jürgen Schilder | 38

Blower Actuator FCL/S x.6.1.1

A Blower Actuator FCL/S x.6.1.1 is used in ventilation applications

The FCL/S 1.6.1.1 1-fold actuator

Controls a single-phase fan with up to three fan speeds

Additional switching output

The FCL/S 2.6.1.1 2-fold actuator

Controls two independent fans with up to three fan speeds

Alternatively the second fan output can be used as three switch outputs

Two additional switching outputs

Outputs can be also used for valve drives (only open/close, no PWM)

© ABB9/18/2015 DESTO Jürgen Schilder | 39

Blower Actuator FCL/S x.6.1.1

Air Quality Sensor LGS/A

Blower Actuator FCL/S

Blower

Presence detector

Switch sensor(manual fan speed)

temperature, humidity,

CO2

Direct Operation Fan speed Byte

Fan speed Bit

Fan speed up/down

Automatic Control Control value

0 .. 100%

© ABB9/18/2015 DESTO Jürgen Schilder | 40

Blower Actuator FCL/S x.6.1.1

Connection schematic

FCL/S 1.6.1.1 Blower Actuator, 1-fold FCL/S 2.6.1.1 Blower Actuator, 2-fold

The second blower output can alternatively used as 3 Switch Actuator outputs

© ABB9/18/2015 DESTO Jürgen Schilder | 41

Fan Coil-Actuator FCA/S 1.1M

© ABB9/18/2015 DESTO Jürgen Schilder | 42

Fan Coil-Actuator FCA/S 1.1M

Two outputs Electronic (0.5 A) for control of 3-point valve drives or thermal heating and cooling valves

Multi-level fans with up to three fan speeds can be switched via floating contact

Two binary inputs, e.g. for monitoring of a window contact and the dew point are available

The additional contact (16 A) is used, for example, to control an electric heater

Manual operation via plastic foil keypad

© ABB9/18/2015 DESTO Jürgen Schilder | 43

Fan Coil-Actuator FCA/S 1.1M

Connection diagram

KN

X

© ABB9/18/2015 DESTO Jürgen Schilder | 44

Fan Coil-Actuator FCA/S 1.1M

Application Typ of Fan (Changeover Switch or Step Switch)

Start up Behaviour

Minimum Time in a Level

Threshold for Switching to another Level

Hysteresis

Limitation of Fan stage in Automatic Mode

Forced Operation of Fan stage in Automatic and Direct Mode

Status Messages (Fan stage, Valve, ...)

Monitoring of RTC with parametrisable Function

© ABB9/18/2015 DESTO Jürgen Schilder | 45

Fan Coil-Actuator FCA/S 1.1M

Application Direct Mode

1 Bit for up/down

1 Bit for direct Fan Speed

1 Byte for direct Fan Speed (Value 0,1,2,3)

Automatic Mode

Depending on Control Value from Room Thermostat

LimitationE.g. only Fan Stage 1 and 2

Control value fan speed0... 9 % 0 (fan off)10...39 % 140...69 % 270...100 % 3

© ABB9/18/2015 DESTO Jürgen Schilder | 46

Fan Coil-Actuator FCA/S 1.1M

Types of Fan control Control via changeover

switch

Control via step switch0123

Output

Off 0 0 0

Fan speed 1 1 0 0

Fan speed 2 0 1 0

Fan speed 3 0 0 1

Output

Off 0 0 0

Fan speed 1 1 0 0

Fan speed 2 1 1 0

Fan speed 3 1 1 1

© ABB9/18/2015 DESTO Jürgen Schilder | 47

Fan Coil Actuator FCA/S 1.2.2.1, 0…10 V

Fan

Filter

Relay 20 AX

Binary inputs

Valve Output 0…10 V

Manual operation

Tag Holder

© ABB9/18/2015 DESTO Jürgen Schilder | 48

Fan Coil Actuator FCA/S 1.2.2.1, 0…10 V

© ABB9/18/2015 DESTO Jürgen Schilder | 49

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Room Thermostat

Fan Coil-Unit

Fan Coil Actuator

MagnetReed

Contact

Valve drive: Cooling HeatingFan

Electricalheater

© ABB9/18/2015 DESTO Jürgen Schilder | 50

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

© ABB9/18/2015 DESTO Jürgen Schilder | 51

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)

© ABB9/18/2015 DESTO Jürgen Schilder | 52

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)

© ABB9/18/2015 DESTO Jürgen Schilder | 53

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)

© ABB9/18/2015 DESTO Jürgen Schilder | 54

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)

© ABB9/18/2015 DESTO Jürgen Schilder | 55

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)

© ABB9/18/2015 DESTO Jürgen Schilder | 56

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Control value HeatingControl value CoolingFan manual – Fan stage manualStatus FanCoil operation

Roo

m T

herm

osta

t 613

8

Control input – value HeatingControl input – value CoolingFan – Fan speed switchFan – Status fan speedFan – Automatic On/OffFan – Status automaticFan – Limitation 1Fan – Limitation 2Fan – Limitation …Input A – SwitchInput B – SwitchValve Heating – Forced operationValve Cooling – Forced operationOutput – Switch …

Fan

Coi

l-Act

uato

r FC

A/S

1.1M

Rocker 1Rocker 2Rocker 34-

fold

Rocker 4

Switch sensor 4-fold:Rocker 1: Absence operation (limitation 2)

Fan automatic/manual…

Control – Current setpoint coolingControl – Current setpoint heatingControl – Value add. heat. stageTemperature sensor – current temp.

Control – Frost/heat protection

Fan Automatic OperationFan Direct OperationWindow ContactSleeping Mode (limitation 1)Absence Operation (limitation 2)

© ABB9/18/2015 DESTO Jürgen Schilder | 57

Exercise Fan Coil-Actuator and Room Thermostate.g. Hotel Room

Simulation current

temperature

© ABBDESTO Jürgen Schilder | 9/18/2015 58

HVAC Documentation on www.abb.com/knx

Pdf: Heating, Air-Conditioning and Ventilation Control with EIB

Application Manual: Heating Ventilation Air-Conditioning Order Number 2CDC 500 067 M0201

E-Learning module: Room Climate Control

© ABBDESTO Jürgen Schilder | 9/18/2015 59

E-Learning moduleRoom Climate Control

© ABB18.09.2015 DESTO Jürgen Schilder | 60

Thank you very much for being present at today's webinar