luna3_blue_-_gb (1)

Upload: logics54

Post on 24-Feb-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 luna3_blue_-_gb (1)

    1/32

    HIGH PERFORMANCE GAS-FIRED WALL-MOUNTED BOILERSOPERATING AND INSTALLATION INSTRUCTIONS

    GB

  • 7/25/2019 luna3_blue_-_gb (1)

    2/32

    2C607504 - GBINSTRUCTIONS FOR USERS

    Dear Customer,

    We are confident your new boiler will meet all your requirements.

    All BAXIproducts have been designed to give you what you are looking for: good performance combined with simple

    and rational use.

    Please do not put away this booklet without reading it first as it contains some useful information which will help you tooperate your boiler correctly and efficiently.

    Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential source of

    danger.

    Baxi S.p.A. declares that these models of boiler bear the CE mark in compliance with the basic

    requirements of the following Directives:- Gas Directive 90/396/EEC

    - Efficiency Directive 92/42/EEC

    - Electromagnetic Compatibility Directive 2004/108/EEC

    - Low Voltage Directive 2006/95/EC

    1. Instructions prior to installation 3

    2. Instructions prior to commissioning 33. Commissioning the boiler 4

    4. Adjusting CHW and DHW temperatures 55. Filling the system 6

    6. Turning off the boiler 6

    7. Gas conversion 6

    8. Prolonged shutdown. Frost protection (central heating circuit) 6

    9. Troubleshooting 7

    10.Routine maintenance instructions 7

    11.General precautions 8

    12. Instructions prior to installation 8

    13.Boiler installation 9

    14. Installation of flue and air ducts 9

    15. Installation of flue and air ducts 1016.Connecting the mains supply 13

    17.Connecting the ambient thermostat 13

    18.Gas conversion methods 14

    19. Information on display 15

    20.Parameter settings 16

    21.Adjustment and safety devices 1822.Positioning the ignition and flame-sensor electrode 19

    23.Checking combustion parameters 19

    24.Output/pump head performance 20

    25.Connecting the external probe 2026.Connection to an external storage boiler and three-way valve motor 2227.Electrically connecting the climate controller 22

    28.Connecting a zone heating system 23

    29.Removing scale from the DHW circuit 24

    30.Dismounting the water-water heat exchanger 24

    31.Cleaning the cold water filter 24

    32.Annual service 2533.Circuit diagram 26

    34. Illustrated wiring diagram 28

    35.Technical specifications 32

    CONTENTS

    INSTRUCTIONS FOR USERS

    INSTRUCTIONS FOR FITTERS

    BAXI S.p.A.,a leading European manufacturer of hi-tech boilers and heating systems, has developed CSQ-

    certified quality management (ISO 9001), environmental (ISO 14001) and health and safety (OHSAS 18001)systems. This means that BAXI S.p .A. includes among its objectives the safeguarding of the environment, the

    reliability and quality of its products, and the health and safety of its employees.

    Through its organisation, the company is constantly committed to implementing and improving these aspects

    in favour of customer satisfaction.

  • 7/25/2019 luna3_blue_-_gb (1)

    3/32

    3C607504 - GBINSTRUCTIONS FOR USERS

    This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure. It must

    be connected to a central heating system and to a domestic hot water supply system according to its performance and

    power output.Before having the boiler installed by a qualified service engineer, make sure the following operations are performed:

    a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings

    on the packaging and the rating plate on the appliance.

    b) Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gasesfrom other appliances are expelled through the same flue duct, unless the latter has been specially designed to collect

    exhaust gas from more than one appliance, in compliance with current laws and regulations.c) Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual pro-

    ducts of combustion may detach from the walls during operation and obstruct the flow of fumes.

    d) To ensure correct operation and maintain the warranty, observe the following precautions:

    1. DHW circuit

    1.1.If the water is harder than 20 F (1 F = 10 mg calcium carbonate per litre of water), install a polyphosphate dis-penser or an equivalent treatment system, compliant with current regulations.

    1.2.Thoroughly flush the system after installation of the appliance and before use.

    1.3.The materials used for the products DHW circuit comply with Directive 98/83/EC.

    2. Heating circuit

    2.1.new system Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual

    thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, pla-

    stic and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning products

    are:

    SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliancewith the manufacturers instructions.

    2.2.existing system

    Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable

    proprietary products as described in section 2.1.

    To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such

    as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with themanufacturers instructions.

    Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.

    overheating and excessive noise of the heat exchanger).

    Failure to observe the above will render the guarantee null and void.

    1. INSTRUCTIONS PRIOR TO INSTALLATION

    Initial lighting of the boiler must be carried out by an authorised Service Engineer who must first ensure that:

    a) The rated data correspond to the supply (electricity, water and gas) data;

    b) The installation complies with current laws and regulations, an excerpt of which is given in the manual intended for thefitter.

    c) The appliance is correctly connected to the power supply and earthed.

    The names of the authorised Service Centres are indicated in the attached sheet. Failure to observe the above will render

    the guarantee null and void.

    Prior to commissioning, remove the protective plastic coating from the boiler. Do not use any tools or abrasive detergentsto do this as you may damage the painted surfaces.

    The appliance is not intended to be used by persons (including children) with reduced physical, sensory or mental

    capacities, or who lack experience or knowledge, unless, through the mediation of a person responsible for their

    safety, they have had the benefit of supervision or of instructions on the use of the appliance.

    2. INSTRUCTIONS PRIOR TO COMMISSIONING

  • 7/25/2019 luna3_blue_-_gb (1)

    4/32

    4C607504 - GBINSTRUCTIONS FOR USERS

    3. COMMISSIONING THE BOILERTo light the boiler correctly, proceed as follows:

    Power the boiler; Turn on the gas tap; Press button (approx. 2 seconds) to set the boiler operating mode as described in section 3.2.

    NOTE:if the SUMMER , mode is set, the boiler will only light during a DHW demand.

    To set the desired CHW and DHW temperatures, press the +/-buttons as described in section 4.

    WARNINGDuring initial ignition, the burner may not ignite (causing the boiler to shut down) until any air in the gas pipes is vented.In this case, repeat the ignition procedure until gas reaches the burner. Press the RESET button ( ) for at least 2 seconds.

    Figure 1

    KEY TO SYMBOLS ON DISPLAY

    Enable heating mode

    Flame present - figure 2

    (power level 0 25 %)

    Flame modulation level - figure 2

    (3 power levels)

    Enable DHW mode

    Generic fault

    No water

    (System pressure LOW)

    Numerical signal

    (Temperature, fault code, etc.)

    RESET

    ECO mode

    TASTEN

    DHW temperature settings (C)

    Heating temperature adjustment (C)

    RESET (boiler reset)

    ECO - COMFORT

    MODE button (see section 3.2)

    0609_

    2301

    If the optional climate controller is connected, always adjust the boiler using the climate controller. See the in-

    structions accompanying this accessory item.

    4 different boiler modulation levelsmay be shown during boiler

    operation, as indicated in figure 2:

    3.1 MEANING OF THE SYMBOL

    Figure 2 0603_

    1301

  • 7/25/2019 luna3_blue_-_gb (1)

    5/32

    5C607504 - GBINSTRUCTIONS FOR USERS

    4. ADJUSTING CHW AND DHW TEMPERATURES

    Adjust the heating flow temperature and the DHW temperature , by pressing the respective +/- buttons (figure 1).When the burner is lit, the control panel display shows the symbol .

    HEATING

    The system must be fitted with an ambient thermostat for controlling indoor temperature.

    While the boiler is operating in the heating mode, the display in figure 1 shows the flashing symbol and the heating flow

    temperature(C) .

    DHW

    While the boiler is operating in the DHW mode, the display in figure 1 shows the flashing symbol and the storage boiler water

    flow temperature (C).

    Press Pto set two different DHW temperature values, ECOand COMFORT. To modify the temperatures, proceed as follows

    ECO

    Press P, the display shows eco, set the required temperature by pressing +/-buttons.

    COMFORT

    Press P, the display shows just the temperature setting, and then +/-to set the required temperature setpoint.

    NOTE:if a storage boiler is connected, during boiler operation in DHW mode, the display shows the symbol( )and the sto-rage boiler flow temperature (C).

    3.2 DESCRIPTION OF BUTTONS (Summer - Winter - Heating only - Off)

    Press this button to set the following operating modes:

    SUMMER

    WINTER

    HEATING ONLY OFF

    In the SUMMERmode, the display shows . The boiler satisfies requests for DHW only while central heating is NOT

    enabled (ambient frost protection function active).

    In the WINTERmode, the display shows and . The boiler satisfies requests for both DHW and central heating

    (ambient frost protection function active).

    In the HEATING ONLYmode, the display shows . The boiler satisfies requests for central heating only (ambient frost

    protection function active).

    In the OFFmode, the display shows neither of the above two symbols . In this mode, only the ambient frost pro-

    tection function is active while requests for DHW and central heating are not satisfied.

    For more detailed technical information, please consult the SERVICE INSTRUCTIONS.

    3.3 ADDITIONAL INFORMATION

  • 7/25/2019 luna3_blue_-_gb (1)

    6/32

    6C607504 - GBINSTRUCTIONS FOR USERS

    IMPORTANT:Regularly check that the pressure displayed on the pressure gauge (Figure 3a) is 0.7 - 1.5 bar, withthe boiler cold. In case of overpressure, turn on the boiler drain tap. In case of insufficient temperature, turn on the boiler

    filling tap (figure 3a or 3b).

    Turn on the tap very slowly in order to vent the air. During this operation, the boiler must be OFF (press( ) figure 1).

    NOTE:The boiler is fitted with a hydraulic pressure gauge which prevents the boiler from working if there is no water.If pressure drops occur frequently, have the boiler checked by an authorised Service Engineer.

    5. FILLING THE SYSTEM

    Figure 3a

    To turn off the boiler, disconnect the electric power supply. With the gas boiler in the OFF mode (section 3.2), the electric

    circuits remain powered and the frost protection function is enabled (section 8).

    6. TURNING OFF THE BOILER

    7. GAS CONVERSION

    The boilers can operate both on natural gas and LPG.Any gas change must be effected by a Qualified Service Engineer.

    System filling tap

    System drain tap

    Pressure gauge

    Do not drain the whole system as filling up with water again causes unnecessary and harmful scale to build up inside the

    boiler and the heating elements. If the boiler is not used during winter and is therefore exposed to the danger of frost, addsome specific anti-freeze to the water in the system (e.g.: propylene glycol coupled with corrosion and scale inhibitors).

    The electronic boiler management system includes a frost protection function for the heating system which, when flow

    temperature falls below 5C, operates the burner until a flow temperature of 30C is reached.

    The frost protection function is enabled if:

    * the boiler is electrically powered;

    * the gas tap is open;

    * the system is at the correct pressure;

    * the boiler is not blocked.

    8. PROLONGED SHUTDOWN. FROST PROTECTION

    Figure 3a

    0603_

    1303/CG_

    1791

    180i AT - 240i - 240 Fi - 280 Fi 1.180i AT - 1.240Fi

    System filling tap

    0901_

    0802/CG_

    1791

  • 7/25/2019 luna3_blue_-_gb (1)

    7/32

    7C607504 - GBINSTRUCTIONS FOR USERS

    9. TROUBLESHOOTING

    To keep the boiler efficient and safe, have it checked by the authorised Service Centre at the end of every operating period.Careful servicing ensures economical operation of the system.

    Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily flammable cleaners (e.g.: petrol, alcohol, and

    so on). Always switch off the appliance before cleaning it (see section 6 Switching off the boiler).

    10. ROUTINE MAINTENANCE INSTRUCTIONS

    CODE

    DISPLAYEDTYPE OF FAULT ACTION

    E01 Ignition failure Press If this fault persists, call the Authorised Service Centre.

    E02 Safety thermostat tripped Press If this fault persists, call the Authorised Service Centre.E03 Fumes thermostat action Call an authorised Service centre.

    E04 Safety error due to frequent flame loss Call an authorised Service centre.

    E05 Flow sensor fault Call an authorised Service centre.

    E06 DHW sensor fault Call an authorised Service centre.

    E10 Hydraulic pressure switch blockCheck that the pressure in the system is correct; See section5. If this fault persists, call the Authorised Service Centre.

    E11Safety thermostat for low temperature system cuts in(if connected)

    Call an authorised Service centre.

    E25 No water safety trip Call an authorised Service centre.

    E31 No connection with the climate controller Call an authorised Service centre.

    E35 Parasite flame (flame error) Press If this fault persists, call the Authorised Service Centre.

    E51 Fumes pressure switch action during boiler operation Call an authorised Service centre.

    E52 Internal board error Call an authorised Service centre.

    E53 Fumes pressure switch action Call an authorised Service centre.

    E80 Internal climate controller error Call an authorised Service centre.

    E98 Internal board error Call an authorised Service centre.

    E99 Internal board error Call an authorised Service centre.

    Figure 4

    0605_1

    106

    Faults are shown on the display with an error code (e.g.: E01):The faults that can be reset by the user are indicated on the display with the symbol (figure 4).The faults that cannot be reset by the user are indicated on the display with the symbol (figure 4.1). To RESET the boiler,

    press and hold down for at least 2 seconds.

    Figure 4.1

    0605_1

    107

  • 7/25/2019 luna3_blue_-_gb (1)

    8/32

    8C607504 - GBINSTRUCTIONS FOR FITTERS

    This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure. It mustbe connected to a central heating system and to a domestic hot water supply system according to its performance andpower output. Do the following before connecting the boiler:a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings

    on the packaging and the rating plate on the appliance.

    b) Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gasesfrom other appliances are expelled through the same flue duct, unless the latter has been specially designed to collectexhaust gas from more than one appliance, in compliance with current laws and regulations.

    c) Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual pro-ducts of combustion may detach from the walls during operation and obstruct the flow of fumes.

    To ensure correct operation and maintain the warranty, observe the following precautions:

    1. DHW circuit1.1.If the water is harder than 20 F (1 F = 10 mg calcium carbonate per litre of water), install a polyphosphate dis-

    penser or an equivalent treatment system, compliant with current regulations.1.2.Thoroughly flush the system after installation of the appliance and before use.

    1.3.The materials used for the products DHW circuit comply with Directive 98/83/EC.

    2. Heating circuit

    2.1. new system Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual

    thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, pla-stic and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning productsare:

    SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliancewith the manufacturers instructions.

    2.2. existing system Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable

    proprietary products as described in section 2.1. To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such

    as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with themanufacturers instructions.

    Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.overheating and excessive noise of the heat exchanger).

    Failure to observe the above will render the guarantee null and void.

    WARNINGIf an instantaneous (mixed) boiler is connected to a system with solar panels, the maximum temperature of the domestichot water entering the boiler must not exceed:

    60Cwith flow limiting device 70Cwithout flow limiting device

    The following notes and instructions are addressed to fitters to allow them to carry out trouble-free installation. Instruc-tions for lighting and using the boiler are contained in the Instructions for Users section.Moreover, the fitter must be legally qualified to install heating appliances.Please, bear in mind the following.

    This boiler can be connected to any type of double- or single-pipe convector plate, radiator or thermoconvector. De-sign the system sections as usual, though, bearing in mind the available flow-head at the plate, as shown in section 24.

    Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential sourceof danger.

    Initial lighting of the boiler must be carried out by an authorised Service Engineer, as indicated on the attached sheet.Failure to observe the above will render the guarantee null and void.

    11. GENERAL PRECAUTIONS

    12. INSTRUCTIONS PRIOR TO INSTALLATION

  • 7/25/2019 luna3_blue_-_gb (1)

    9/32

    9C607504 - GBINSTRUCTIONS FOR FITTERS

    13. INSTALLING THE BOILERAfter deciding the exact location of the boiler, fix the template to the wall.

    Connect the system to the gas and water inlets present on the lower bar of the template. Fit two G3/4 taps (flow and

    return) on the central heating circuit; these taps make it possible to carry out important operations on the system without

    draining it completely. If you are either installing the boiler on an existing system or replacing one, as well as the above,fit a settling tank under the boiler on the system return line in order to collect any deposits and scale circulating in the

    system after flushing. After fixing the boiler to the template, connect the flue and air ducts, supplied as accessories, as

    described in the following sections.If natural draught boilers are installed, connect them to the flue with a metal pipe resistant to normal mechanical stress,

    heat, products of combustion and relative condensate.

    Figure 5

    = BOILER WIDTH 450 =

    BOILER CONNECTION POINT

    BOILERHEIGHT780

    14. DIMENSIONS OF BOILER

    Figure 6

    180 i AT - 240 i - 1.180 i AT 240 Fi - 280 Fi - 1.240 Fi

    : G 3/4 heating system flow/return

    : G 1/2 hot domestic water outlet/inlet

    : G 3/4 gas input to boiler

    0512_

    0504/CG1769

    0512_0505/CG1769

    0512_0503/CG1769

    : G 3/4 heating system flow/return

    : G 3/4 storage boiler flow - G 1/2 DHW inlet

    : G 3/4 gas inlet to boiler

    180 i AT - 240 i - 240 Fi - 280 Fi1.180 i AT - 1.240 Fi

    minimo

    0705_

    0609

    0606_26

    03

    A

    180i AT - 1.180i AT A= 110 mm240i A= 130 mm

  • 7/25/2019 luna3_blue_-_gb (1)

    10/32

    10C607504 - GBINSTRUCTIONS FOR FITTERS

    15. INSTALLATION OF FLUE AND AIR DUCTS

    model

    240 Fi - 280 Fi - 1.240 Fi

    The boiler is easy and flexible to install thanks to the extensiverange of available accessories, as described below.The boiler has been designed for connection to a vertical or hori-

    zontal coaxial flue-air duct. A splitting kit is also available if sepa-rate ducts are required.

    Only accessories supplied by the appliance manufacturermust be used for installation!

    WARNINGTo optimise operating safety, make sure the flue ducts are firmlyfixed to the wall with suitable brackets.

    COAXIAL FLUE - AIR DUCT (CONCENTRIC)

    This type of duct is used to discharge exhaust fumes and drawcombustion air both outside the building and if a LAS flue is fitted.The 90 coaxial bend allows the boiler to be connected to a flue-airduct in any direction as it can be rotated by 360. It can also beused as a supplementary curve combined with a coaxial duct or a45 curve.

    If fumes are discharged outside the building, the flue-air duct mustprotrude at least 18 mm from the wall to allow an aluminium wea-thering surround to be fitted and sealed to avoid water infiltrations.Make sure there is a minimum upward slope towards the outsideof 1 cm per metre of duct.

    A 90 curve reduces total duct length by 1 metre. A 45 curve reduces total duct length by 0.5 metre.

    Figure 7

    0503_

    0905/CG1638

    Figure 8

    15.1 HORIZONTAL FLUE INSTALLATION OPTIONS

    L max = 4 mL max = 4 m

    L max = 3 m L max = 3 m

    0512_

    2001

    0711_

    1901

    Connector

    Concentricconnector

  • 7/25/2019 luna3_blue_-_gb (1)

    11/32

    11C607504 - GBINSTRUCTIONS FOR FITTERS

    15.2 LAS FLUE DUCT INSTALLATION OPTIONS

    15.3 VERTICAL FLUE INSTALLATION OPTIONS

    This type of installation can be carried out on either a flat or a pitched roof by fitting a flue terminal and a special weathe-

    ring surround with sleeve (both available on request).

    0503_

    0908/CG1641

    L max = 4 m L max = 4 m L max = 2 m L max = 3 m

    L max = 4 m

    0512_

    2002

    For detailed installation instructions, consult the technical data provided with the accessories.

    SEPARATE FLUE AND AIR DUCTS

    This type of installation makes it possible to discharge exhaust fumes both outside the building and into single flue ducts.

    Comburent air can be drawn in at a different location from that of the flue terminal. The splitting kit comprises a flue duct

    adaptor (100/80) and an air duct adaptor. For the air duct adaptor, fit the screws and seals previously removed from the

    cap.

    The first 90 curve is not included when calculating the maximum available length.

    The 90 curve allows the boiler to be connected to a flue-air duct in any direction as it can be rotated by

    Figure 9

    0707_

    0803/CG_

    1795

    Flue duct adaptor

    Connector

    360. It can also be used as a supplementary cur-

    ve combined with a duct or a 45 curve.

    A 90 curve reduces total duct length by 0.5metre.

    A 45 curve reduces total duct length by

    0.25 metre.

  • 7/25/2019 luna3_blue_-_gb (1)

    12/32

    12C607504 - GBINSTRUCTIONS FOR FITTERS

    0503_

    2201/CG1643

    15.5 SEPARATE HORIZONTAL FLUE INSTALLATION OPTIONS

    IMPORTANT:Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length.In the event of installation of the condensate collection kit, the angle of the drain duct must be directed towards the boiler.

    (L1 + L2) max = 20 m

    NB:For the C52 type, do not fit the flue and air duct terminals on opposite walls of the building.

    The maximum length of the air duct is 10 metres. If the discharge duct is longer than 6 metres, install the condensatecollection kit, supplied as an accessory, near the boiler.

    L max = 10 m

    15.4 DIMENSIONS OF SEPARATE OUTLETS

    0504_

    1806/CG_

    1794

    0503_

    091

    1/CG1644

    L max = 10 m L max = 9 m

    15.6 SEPARATE VERTICAL FLUE INSTALLATION OPTIONS

    IMPORTANT:if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the ductpasses through building walls.

    For detailed installation instructions, consult the technical data provided with the accessories.

  • 7/25/2019 luna3_blue_-_gb (1)

    13/32

    13C607504 - GBINSTRUCTIONS FOR FITTERS

    16. CONNECTING THE MAINS SUPPLY

    This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current

    safety regulations.Connect the boiler to a 230V single-phase earthed power supply using the supplied three-pin cable, observing correct

    LIVE-NEUTRAL polarity.

    Use a two-pole switch with a contact separation of at least 3 mm. When replacing the power supply cable, fit a har-

    monised HAR H05 VV-F 3x0.75mm2 cable with a maximum diameter of 8 mm.

    Access to the power supply terminal block

    disconnect the boiler from the mains power supply using the two-pole switch;

    remove the two screws xing the control panel to the boiler;

    rotate the control panel; remove the cover and access the wiring area (gure 10).

    The 2A fast-blowing fuses are incorporated in the power supply terminal block (to check and/or replace the fuse, pull out

    the black fuse carrier).

    IMPORTANT:respect polarity L(LIVE) - N(NEUTRAL).

    (L) = Live(brown)

    (N) = Neutral(light blue)

    = Earth(yellow-green)

    (1) (2) = Contact for ambient thermostat

    Figure 10

    0512_

    0508/CG1770

    WARNINGIf the appliance is directly connected to an underfloor system, install a safety thermostat to prevent the latter from over-

    heating.

    17. CONNECTING THE AMBIENT THERMOSTAT

    access the power supply terminal block (gure 10);

    remove the jumper on terminals (1) and (2);

    thread the two-wire cable through the grommet and connect it to these two terminals.

  • 7/25/2019 luna3_blue_-_gb (1)

    14/32

    14C607504 - GBINSTRUCTIONS FOR FITTERS

    The Technical Assistance Service can convert this boiler to natural gas (G20) or liquid gas (G31).

    Carry out the following operations:

    A) Replace the burner injectors

    carefully pull the main burner off its seat; replace the main burner injectors making sure to fully tighten them to prevent gas leaks. Injector diameters are specied

    in table 1.

    18. GAS CONVERSION METHODS

    Figure 11

    Honeywell valve

    Mod. VK 4105 M

    0207_

    0406

    B) Change the modulator voltage

    set parameter F02according to the gas used, as described in

    section 20.

    C) Calibrate the pressure regulator

    connect the positive pressure test point of a differential pres-

    sure gauge (possibly water-operated) to the gas valve pres-

    sure test point (Pb) (Figure 11). Connect, for sealed chambermodels only, the negative pressure test point of the pressure

    gauge to a T fitting in order to join the boiler adjusting outlet,the gas valve adjusting outlet (Pc) and the pressure gauge .

    (The same measurement can be carried out by connecting the

    pressure gauge to the pressure test point (Pb) after removing

    the sealed chamber front panel); If you measure the pressure

    of burners in a different way you may obtain an altered result

    in that the low pressure created in the sealed chamber by thefan would not be taken into account.

    C1) Adjustment to nominal heat output

    turn on the gas tap;

    press (Figure 1) and switch the boiler to the winter mode

    (section 3.2); turn on a hot water tap to reach a minimum 10 l/min ow rate

    or ensure that maximum heating requirements are set; remove the modulator cover; adjust the brass screw (a) in Fig. 12 until the pressure values

    shown in table 1 are obtained; check that the boiler feeding dynamic pressure, as measured

    at the inlet gas valve pressure test point (Pa) (Figure 11) is cor-

    rect (37 mbarfor propane gas, 20 mbarfor natural gas).

    C2) Adjustment to reduced heat output

    disconnect the modulator power cable and unscrew the screw

    (b) in Fig. 12 until a pressure value corresponding to reduced

    heat output is achieved (see tab.1) connect the cable again;

    mount the modulator cover and seal.

    C3) Final checks

    mark on the data plate the type of gas and the calibration per-

    formed.

    Figure 12

    0605_

    1701

  • 7/25/2019 luna3_blue_-_gb (1)

    15/32

    15C607504 - GBINSTRUCTIONS FOR FITTERS

    TABLE OF BURNER PRESSURE AND INJECTORS

    240 i 240 Fi - 1.240 Fi 280 Fi

    Type of gas G20 G31 G20 G31 G20 G31

    Burner pressure (mbar*) 2,1 6,4 3,0 5,5 2,3 4,0REDUCED POWER

    Burner pressure (mbar*) 8,8 28,9 12,5 25,0 13,3 23,9RATED POWER

    Diameter of nozzles (mm) 0,87 0,5 0,82 0,52 0,82 0,55

    Number of nozzles 30 34* 1 mbar = 10,197 mm H

    2O

    Table 1

    180 i AT - 1.180 i AT

    Type of gas G20 G31

    Burner pressure (mbar*) 2,9 8,8

    REDUCED POWER

    Burner pressure (mbar*) 8,8 28,9

    RATED POWER

    Diameter of nozzles (mm) 0,87 0,5

    Number of nozzles 22

    * 1 mbar = 10,197 mm H2O

    Table 1

    TABLE OF BURNER PRESSURE AND INJECTORS

    240 Fi - 1.240 Fi 280 Fi

    consumption15 C - 1013 mbar G20 G31 G20 G31

    Rated power 2,78 m3/h 2,04 kg/h 3,18 m3/h 2,34 kg/h

    Reduced power 1,26 m3/h 0,92 kg/h 1,26 m3/h 0,92 kg/h

    p.c.i. 34,02 MJ/m3 46,30 MJ/kg 34,02 MJ/m3 46,30 MJ/kg

    Table 2

    240 i 180 i AT - 1.180 i AT

    consumption15 C - 1013 mbar G20 G31 G20 G31

    Rated power 2,78 m3/h 2,04 kg/h 2,05 m3/h 1,51 kg/h

    Reduced power 1,26 m3/h 0,92 kg/h 1,12 m3/h 0,82 kg/h

    p.c.i. 34,02 MJ/m3 46,30 MJ/kg 34,02 MJ/m3 46,30 MJ/kg

    Table 2

    19. INFORMATION ON DISPLAYTo light the boiler correctly, proceed as follows:

    Power the boiler. When the gas boiler is power supplied, for approximately the first 8 seconds, the display backlighting is on. Then, it

    displays the following information.

    1. all symbols lit;

    2. manufacturer information;

    3. manufacturer information;4. manufacturer information;

    5. boiler and gas type (e.g.) ). Die Bedeutung der angezeigten Zeichen ist folgende:

    = open chamber boiler = sealed chamber boiler;

    = Natural gas used = LPG gas used.

    6.Hydraulic system;

    7.Software version (two numbers x.x);

    Turn on the gas tap;

    Press button (approx. 2 seconds) to set the boiler operating mode as described in section 3.2.

  • 7/25/2019 luna3_blue_-_gb (1)

    16/32

    16C607504 - GBINSTRUCTIONS FOR FITTERS

    19.1 OPERATING INFORMATION

    To display some useful information during the boileroperation proceed as follows:

    Press ( ) for approx. 6 seconds. When the

    function is enabled, the display shows A00

    (A09) alternating with the respective value

    (e.g. figure 13);

    Press the +/-domestic hot water buttons to

    display the following instantaneous information:

    A00: domestic hot water temperature value (C);A01: outside temperature (C) (with external probe

    sensor connected);

    A02: modulation current value (100% = 230 mA ME-

    THANE - 100% = 310 mA LPG);

    A03: power range level value (%) - see parameter

    F13 (section 20);A04: temperature setpoint value (C);

    A05: central heating flow temperature value (C);Figure 13

    0706_

    1202

    5 seconds

    A06: DHW flow value (l/min x 10);A07: flame signal value (8-100%).

    A09: pressure signal value of the flue pressure switch (Pa)

    NOTE:display line A08 is not used

    This function is active for 3 minutes. To interrupt the INFO function, press .

    See section 9 for error codes and anomalies description.

    NOTE:the resetting operation is available only for 5 consecutive attempts, after which the gas boiler remains blocked.To carry out a new RESET attempt, proceed as follows:

    Press for approx. 2 seconds.

    press for about 2 seconds, the display shows OFF; reset the boiler operating mode as described in section3.2.

    19.2 FAULTS DISPLAY

    For more detailed technical information, please consult the SERVICE INSTRUCTIONS.

    19.3 ADDITIONAL INFORMATION

    20. PARAMETER SETTINGS

    To set the boiler parameters, press and -( ) together and hold down for at least 6 seconds. When the function isactivated, the display shows F01 alternated with the value of the parameter.

    Change parameters

    To scroll the parameters press+/-. Press +/-buttons to change the single parameter value.

    Press the Pbutton to save changes, the display shows MEM. Press the button .to leave the function without saving, the display

    shows ESC.

    0610_

    2504

  • 7/25/2019 luna3_blue_-_gb (1)

    17/32

    17C607504 - GBINSTRUCTIONS FOR FITTERS

    Description of parametersFactory settings

    180 i AT 1.180 i AT 240 i 240 Fi 1.240 Fi 280 Fi

    F01Types of gas boiler

    30-40 = sealed chamber - 20 = atmospheric20 30 40

    F02Gas used

    00= NATURAL - 01= LPG00 o 01

    F03

    Hydraulic system

    00= instantaneous appliance

    05= appliance with external storage boiler

    08= heating only appliance

    00 08 00 00 08 00

    F04Programmable relay 1 setting

    (02= zone system - See SERVICE Instructions)02

    F05

    Programmable relay 2 setting

    04: fault signalling contact

    05: Kitchen fan function (disabling, cooker extraction hood)

    13: cool function for external conditioning system

    (See SERVICE Instructions)

    04

    F06 External sensor programmable input setting (See SERVICE Instructions) 00

    F07F12 manufacturer information 00

    F13 Max. heating output (0-100%) 100F14 D.H.W. max. heating output (0-100%) 100

    F15 Min. heating output (0-100%) 00

    F16

    Maximum temperature setpoint setting (C)

    00= 85C - 01= 45C

    CAUTION: If the appliance is directly connected to an underfloor system, install

    a safety thermostat to prevent the latter from overheating

    00

    F17Pump overrun time

    (01-240 minutes)03

    F18Burner ignition delay in CH mode

    (00-10 minutes) - 00=10 seconds03

    F19 manufacturer information 07

    F20 manufacturer information --

    F21 Anti-legione llosis funct ion00= Disabled - 01= Enabled 00

    F22 manufacturer information 00

    F23 Maximum DHW setpoint 60

    F24 manufacturer information 35

    F25 No water safety device 00

    F26F29 Manufacturer information (read-only parameters) --

    F30 manufacturer information 10

    F31 manufacturer information 30

    F32F41 Diagnostics (See SERVICE Instructions) --

    Final

    parameter

    Calibration function activation

    (See SERVICE Instructions)0

    WARNING:do not modify the values of the Manufacturer information parameters.

  • 7/25/2019 luna3_blue_-_gb (1)

    18/32

    18C607504 - GBINSTRUCTIONS FOR FITTERS

    The boiler has been designed in full compliance with European reference standards and in particular is equipped with the

    following:

    Air pressure switch (models 240 Fi - 1.240 Fi - 280 Fi) This device only allows the burner to ignite if the exhaust flue duct is in perfect working order.

    In the event of one of the following faults:

    the ue terminal is obstructed; the venturi is obstructed;

    the fan is blocked;

    pressure switch is trippedThe boiler will stay on stand-by and the display shows error code E51 or E53 (see section 9).

    Fumes thermostat (model180 i AT - 1.180 i AT - 240 i)

    This device has a sensor positioned on the left section of the flue extraction hood and shuts off the gas flow to the

    burner if the flue duct is obstructed or in the event of draught failure.

    In these conditions the boiler shuts down and displays error code E03 (section 9). To relight the main burner immediately,see section 9.

    It is forbidden to disable this safety device.

    Safety thermostat

    This device has a sensor positioned on the left section of the flue extraction hood and shuts off the gas flow to the

    burner if the flue duct is obstructed or in the event of draught failure. Under such conditions the boiler is blocked and

    only after the fault has been eliminated can it be ignited again.

    In these conditions the boiler shuts down and displays error code E02 (section 9).

    It is forbidden to disable this safety device.

    Flame ionisation detector

    The flame sensing electrode, located on the right-hand side of the burner, guarantees safety of operation in case of gas

    failure or incomplete ignition of the burner.

    In these conditions, the boiler is blocked after 3 ignition attempts. To reset normal operating conditions, ...

    In these conditions the boiler shuts down and displays error code E01 (section 9).

    hydraulic pressure switch

    This device allows the main burner to be ignited only if system pressure is higher than 0.5 bars.

    In these conditions the boiler shuts down and displays error code E01 (section 9).

    Pump overrun for heating circuit

    The electronically-controlled pump post-circulation function lasts 3 minutes (F17 - section 20) and is enabled, in the

    heating mode, if the ambient thermostat causes the burner to go out.

    Pump overrun for DHW circuit

    The electronically-controlled pump post-circulation function lasts 30 seconds and is enabled, in the DHW mode, if theprobe causes the burner to go out.

    Frost protection device (heating and DHW systems)

    The electronic boiler management system includes a frost protection function for the heating system which, whenflow temperature falls below 5C, operates the burner until a flow temperature of 30C is reached.

    Water not circulating in primary circuit (pump probably blocked)

    If there is insufficient or no water circulating in the primary circuit, the boiler blocks and the error code E25 is shown on

    the display (section 9).

    Anti-block pump function

    If no heat demand is received for 24 consecutive hours, the pump will automatically start and operate for 10 seconds.

    This function is operative when the boiler is powered.

    Three-way valve anti-blockage function

    If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle. This

    function is operative when the boiler is powered.

    Hydraulic safety valve (heating circuit)

    This device is set to 3 bar and is used for the heating circuit.

    21. ADJUSTMENT AND SAFETY DEVICES

  • 7/25/2019 luna3_blue_-_gb (1)

    19/32

    19C607504 - GBINSTRUCTIONS FOR FITTERS

    22. POSITIONING THE IGNITION AND FLAME-SENSOR ELECTRODE

    Figure 16

    To measure combustion performance and the toxicity of the products of combustion, the boiler is fitted with two dedica-

    ted test points.

    One connection point is connected to the flue gas discharge circuit, and allows monitoring of the quality of the combusti-

    on products and the combustion efficiency.

    The other is connected to the combustion air intake circuit, allowing checking of any recycling of the combustion productsin case of coaxial pipelines.

    The following parameters can be measured at the connection point on the flue gas circuit:

    temperature of the combustion products;

    oxygen (O2) or carbon dioxide (CO

    2) concentration;

    carbon monoxide (CO) concentration.The temperature of the comburent air must be measured on the test point located on the air intake flue by inserting the

    measurement sensor by about 3 cm.

    For natural draught boiler models, a hole must be made in the flue gas discharge pipe at a distance from the boiler equal

    to twice the inside diameter of the pipe itself.

    The following parameters can be measured through this hole: temperature of the combustion products;

    oxygen (O2) or carbon dioxide (CO

    2) concentration;

    carbon monoxide (CO) concentration.

    The combustion air temperature must be measured close to the point where the air enters the boiler.

    The hole, which must be made by the person in charge of operating the system when it is commissioned, must be sealed

    in a way which ensures that the combustion product discharge pipe is airtight during normal operation.

    23. CHECKING COMBUSTION PARAMETERS

    0012180600

    180 i AT - 1.180 i AT - 240 i

    0206_

    0708

    240 Fi - 1.240 Fi - 280 Fi

    Connect the safety valve to a drain trap. Do not use it to drain the heating circuit.

    Anti-legionellosis function (model 1.180 i AT - 1.240 Fi with storage boiler)

    The anti-legionellosis function is NOT enabled.

    To enable this function, set parameter F21=01 (as described in section 20). When the function is enabled, the electronic

    management of the boiler, at weekly intervals, heats the water contained in the storage boiler to over 60C (the function

    only works if the water has never exceeded 60C in the previous 7 days).

    NOTE:domestic hot water is guaranteed even if the NTC sensor develops a fault.

    In this case, temperature is controlled by the flow sensor.

  • 7/25/2019 luna3_blue_-_gb (1)

    20/32

    20C607504 - GBINSTRUCTIONS FOR FITTERS

    This is a high static head pump fit for installation on any type of single or double-pipe heating systems. The air vent valve

    incorporated in the pump allows quick venting of the heating system.

    Graph1

    24. OUTPUT/PUMP HEAD PERFORMANCE

    FLOW l/h

    HEADmH

    2O

    0705_2101 Graph2

    FLOW l/h

    HEADmH

    2O

    280 Fi

    0705_2102

    240 Fi - 1.240 Fi

    Graph3

    FLOW l/h

    H

    EADmH

    2O

    0705_2103

    180 i AT - 1.180 i AT - 240 i

    25. CONNECTING THE EXTERNAL PROBE

    The boiler is prearranged for connection of an external probe (supplied as accessory). For the connection, refer to figuresbelow and the instructions supplied with the probe.

  • 7/25/2019 luna3_blue_-_gb (1)

    21/32

    21C607504 - GBINSTRUCTIONS FOR FITTERS

    With the external probe connected, buttons +/- adjusting the heating circuit temperature ( ) (figure 1) regulate the coeffici-

    ent of heat dispersion Kt (190). Charts below show the correspondence between the set value and the relative curves.

    Intermediate curves can also be selected.

    IMPORTANT:the maximum value of the flow temperature TMdepends on the F16 parameter setting (see section20). The maximum flow temperature may be 85 or 45C.

    0603_

    0305

    0603_

    0306

    kt curves

    Graph3 Graph4

    TM - flow temperature

    Te - external temperature

    Figure 17.2

    0605_

    1604models 1.180 i AT - 1.240 Fi

    Figure 17

    0610_1301 / CG_1855

    CN 5

    models 180 i AT - 1.180 i AT - 240 i models 240 Fi - 1.240 Fi - 280 Fi

    Figure 17.1

    0705_2801 / CG_1941

    CN 5

  • 7/25/2019 luna3_blue_-_gb (1)

    22/32

    22C607504 - GBINSTRUCTIONS FOR FITTERS

    (SUPPLIED AS ACCESSORY)

    The climate controller is not a

    standard boiler component as

    it is supplied as an accessory.

    Open the electronic board andconnect the cable (supplied to-

    gether with the two-pin terminal

    board) to connector CN7 on the

    boiler electronic board. Connect

    the terminals of the climate con-

    troller to the two-pin terminalboard (figure 19).

    27. ELECTRICAL CONNECTION OF THE CLIMATE CONTROLLER

    Figure 19

    NOTE:for models 1.180 i AT and 1.240 Fi, connect the climate controller as described in section 28.1 (figure 20).

    0610_

    1302/CG_

    1856

    CN 7

    Figure 18

    model 1.180 i AT - 1.240 Fi

    CONNECTING THE STORAGE BOILER PROBE

    The boiler is prearranged for connection of an external storage boiler. Hydraulically connect the storage boiler as shown infigure. 18. Connect the NTCDHW priority probe to terminals 5-6 in the terminal block M2. The sensitive element of the NTC

    probe must be inserted in the holder provided on the storage boiler. Adjust DHW temperature (35...65 C) by pressing +/-.

    26. CONNECTING AN EXTERNAL STORAGE BOILER

    0702_

    1602

    Key

    UB storage boilerUR heating unit

    M three-way valve motor (accessory)

    M2 connection terminal block

    SB DHW priority storage boiler probeMR heating flow

    MB storage boiler flow

    RR heating/storage boiler return

    MOTOR

    NOTE:Make sure parameter F03 = 05 (section 20).

  • 7/25/2019 luna3_blue_-_gb (1)

    23/32

    23C607504 - GBINSTRUCTIONS FOR FITTERS

    The relay board is not a standard boiler component as it is supplied as an accessory. Connect terminals 1-2-3 (common -

    normally closed - normally open) of connector CN1on the relay board, to the respective terminals 10-9-8 of boiler terminal

    block M2(figure20).

    28. CONNECTING A ZONE HEATING SYSTEM

    28.1 CONNECTING THE RELAY BOARD

    Figure 20

    Connect the contact relative to heating requests in zones that are not controlled by the climate controller in parallel toterminals 1-2 TA on terminal block M1.

    Remove the jumper.

    The zone controlled by the climate controller is managed by the zone 1 solenoid, as illustrated in figure 21.

    28.2 CONNECTING THE ZONES

    Figure 21

    CLIMATE CONTROLLER

    0706_

    1203/CG_

    1840

    CLIMATE CONTROLLER

    BOILER BOARD

    RELAY BOARD ACCESSORY

    RELAY 2

    RELAY 1

    ZONE 1

    ZONE 1

    REMOTE CONTROLZONE 2

    (AMBIENT THERMOSTAT)

    ZONE 3

    (AMBIENT THERMOSTAT)

    ZONE N

    (AMBIENT THERMOSTAT)

    SOLENOID

    ZONE 1

    0709_

    2403/CG_

    1825

  • 7/25/2019 luna3_blue_-_gb (1)

    24/32

    24C607504 - GBINSTRUCTIONS FOR FITTERS

    (Not contemplated in model 1.180 i AT - 1.240 Fi)

    The DHW circuit can be cleaned without removing the water-water heat exchanger if the assembly is fitted with the special tap (availa-

    ble on request) located on the DHW outlet.

    To clean, proceed as follows:

    Turn off the DHW inlet tap

    Drain the DHW system by turning on a hot water tap Turn off the DHW outlet tap

    Unscrew the two stopcocks

    Remove the lters

    If the special tap is not supplied, dismount the water-water heat exchanger, as described in the next section, and clean it separately.

    Remove the scale from the seat and relative NTC sensor fitted on the DHW circuit.

    To clean the exchanger and/or DHW circuit, use Cillit FFW-AL or Benckiser HF-AL.

    29. REMOVING SCALE FROM THE DHW CIRCUIT

    (Not contemplated in model 1.180 i AT - 1.240 Fi)

    The stainless steel plate-type water-water heat exchanger is easily disassembled with a screwdriver by operating as described below:

    drain the system, just the boiler if possible, through the drain tap;

    drain the DHW system;

    remove the two screws at the front securing the water-water heat exchanger and pull it out (gure 22).

    30. DISMOUNTING THE WATER-WATER HEAT EXCHANGER

    (Not contemplated in model 1.180 i AT - 1.240 Fi)

    The boiler is fitted with a cold water filter located on the hydraulic assembly. To clean, proceed as follows: Drain the domestic hot water system.

    Unscrew the nut on the ow sensor assembly (gure 22).

    Pull out the ow sensor and its lter.

    Remove any impurities.

    IMPORTANT:when replacing and/or cleaning the O-rings on the hydraulic assembly, only use Molykote 111 as a lubricant, notoil or grease.

    31. CLEANING THE COLD WATER FILTER

    0606_

    2703

    /CG_

    1839

    Figure 22water-water heat exchanger retaining screws

    fixing nut flow sensor

  • 7/25/2019 luna3_blue_-_gb (1)

    25/32

    25C607504 - GBINSTRUCTIONS FOR FITTERS

    To optimise boiler efficiency, carry out the following annual controls:

    check the appearance and air-tightness of the gaskets of the gas and combustion circuits;

    check the state and correct position of the ignition and ame-sensing electrodes; check the state of the burner and make sure it is rmly xed;

    check for any impurities inside the combustion chamber.

    Use a vacuum cleaner to do this;

    check the gas valve is correctly calibrated;

    check the pressure of the heating system; check the pressure of the expansion vessel;

    check the fan works correctly;

    make sure the ue and air ducts are unobstructed;

    check for any impurities inside the siphon;

    check the magnesium anode, where present, for boilers tted with storage boilers.

    WARNINGSBefore commencing any maintenance operations, make sure the boiler is disconnected from the power supply.

    Afterwards, move the knobs and/or operating parameters of the boiler to their original positions.

    32. ANNUAL SERVICE

  • 7/25/2019 luna3_blue_-_gb (1)

    26/32

    26C607504 - GBINSTRUCTIONS FOR FITTERS

    Figure 23

    33. CIRCUIT DIAGRAM

    240 Fi - 280 Fi - 1.240 Fi

    Key:

    1 DHW priority sensor

    2 hydraulic pressure switch

    3 DHW NTC probe

    4 three-way valve

    5 non-return valve

    6 3-way valve motor7 gas valve

    8 expansion vessel

    9 flame detection electrode

    10 NTC heating probe

    11 safety thermostat

    12 water-fumes exchanger

    13 fumes conveyor

    14 fan

    15 concentric connector

    16 air pressure switch

    17 negative pressure point

    18 ignition electrode

    19 burner

    20 pressure gauge

    21 water-water plate exchanger

    22 pump with air separator

    23 boiler filling tap

    24 boiler drain tap25 safety valve

    26 flow sensor with filter and water flow limiting device

    Heating DHW Gas DHW Heating

    flow outlet inlet return

    Heating Storage Gas DHW Heating

    flow boiler inlet return

    flow

    0705_

    1804/CG_1926

    240 Fi - 280 Fi 1.240 Fi

    Key:

    1 automatic by-pass

    2 hydraulic pressure switch

    3 three-way valve

    4 pressure gauge

    5 3-way valve motor

    6 gas valve7 expansion vessel

    8 flame detection electrode

    9 NTC heating probe

    10 safety thermostat

    11 water-fumes exchanger

    12 fumes conveyor

    13 fan

    14 concentric connector

    15 air pressure switch

    16 negative pressure point

    17 ignition electrode

    18 burner

    19 automatic vent valve

    20 pump with air separator

    21 non-return valve

    22 boiler drain tap

    23 safety valve

    CG_

    1925/0902_0

    301

  • 7/25/2019 luna3_blue_-_gb (1)

    27/32

    27C607504 - GBINSTRUCTIONS FOR FITTERS

    Figure 24

    180 i AT - 240 i - 1.180 i AT

    Key:

    1 DHW priority sensor2 hydraulic pressure switch3 DHW NTC probe4 three-way valve

    5 non-return valve6 3-way valve motor7 gas valve8 expansion vessel9 ignition electrode10 NTC heating probe11 safety thermostat12 water-fumes exchanger13 fumes hood14 fumes thermostat15 flame detection electrode16 burner17 pressure gauge18 water-water plate exchanger19 pump with air separator20 boiler filling tap21 boiler drain tap22 safety valve23 flow sensor with filter and water flow limiting device

    Heating DHW Gas DHW Heating

    flow outlet inlet return

    Heating Storage Gas DHW Heating

    flow boiler inlet return

    flow

    180 i AT - 240 i 1.180 i AT

    Key:

    1 automatic by-pass

    2 hydraulic pressure switch

    3 three-way valve

    4 pressure gauge

    5 3-way valve motor6 gas valve

    7 expansion vessel

    8 ignition electrode

    9 NTC heating probe

    10 safety thermostat

    11 water-fumes exchanger

    12 fumes hood

    13 fumes thermostat

    14 flame detection electrode

    15 burner

    16 automatic vent valve

    17 pump with air separator

    18 non-return valve

    19 boiler drain tap

    20 safety valve

    0705_

    1806/CG_

    1923

    CG_

    1924/0901_

    2902

  • 7/25/2019 luna3_blue_-_gb (1)

    28/32

    28C607504 - GBINSTRUCTIONS FOR FITTERS

    34. ILLUSTRATED WIRING DIAGRAM

    240 Fi - 280 Fi

    0711_

    1801/CG_1930

    DHWP

    RIORITY

    SENSOR

    DHWN

    TCPROBE

    HYDRAULICPRE

    SSURE

    SWITCH

    NTCHEATING

    PROBE

    SAFETY

    THERMOSTAT

    DETECTION

    ELECTRODE

    GASVALVE

    IGNITION

    ELECTRODE

    FAN

    THE

    RMOSTAT

    PUMP

    MAIN

    SPOWER

    SUPPLY

    AIRPRESSU

    RE

    SWITCH

    Cablecolours

    C

    =Lightblue

    M=

    Brown

    N

    =Black

    R

    =Red

    B

    =White

    G/V=Yellow/Green

    V

    =Green

  • 7/25/2019 luna3_blue_-_gb (1)

    29/32

    29C607504 - GBINSTRUCTIONS FOR FITTERS

    1.240 Fi

    0711_

    1802/CG_1929

    DHWP

    RIORITY

    SENSOR

    HYDRAUL

    IC

    PRESSUR

    E

    SWITCH

    NTCHEATING

    PROBE

    SAFETY

    THERMOSTAT

    DETECTION

    ELECTRODE

    GASVALVE

    IGNITION

    ELECTRODE

    FAN

    THERMOSTAT

    PUMP

    MAINSPOW

    ER

    SUPPLY

    AIRPRESSURE

    SWITCH

    Cablecolours

    C

    =Lightblue

    M=

    Brown

    N

    =Black

    R

    =Red

    B

    =White

    G/V=Yellow/Gr

    een

    V

    =Green

  • 7/25/2019 luna3_blue_-_gb (1)

    30/32

    30C607504 - GBINSTRUCTIONS FOR FITTERS

    180 i AT - 240 i

    0711_

    1906/CG_

    1928

    THREE-WAY

    VALVE

    FU

    MES

    TH

    ERMOSTAT

    THER

    MOSTAT

    PUMP

    MAINS

    POWER

    SUPPLY

    GASVALVE

    IGNITION

    ELECTRODE

    SAFETY

    THERMOSTAT

    DETECTIO

    N

    ELECTRODE

    NTCHEATING

    PROBE

    DHWP

    RIORITY

    SENSOR

    DHWN

    TCPROBE

    HYDRAULICPRESSURE

    SWITCH

    Cablecolours

    C

    =Lightblue

    M=

    Brown

    N

    =Black

    R

    =Red

    B

    =White

    G/V=Yellow/Gr

    een

    V

    =Green

  • 7/25/2019 luna3_blue_-_gb (1)

    31/32

    31C607504 - GBINSTRUCTIONS FOR FITTERS

    1.180 i AT

    0711_

    1907/CG_

    1927

    THERMOSTAT

    PUMP

    MAINSP

    OWER

    SUPPLYT

    HREE-WAY

    VALVE

    GASVALVE

    IGNITION

    ELECTRODE

    SAFETY

    THERMOSTAT

    DETECTION

    ELECTRODE

    FUME

    S

    THER

    MOSTAT

    NTCHEATING

    PROBE

    DHWP

    RIORITY

    SENSOR

    Cablecolours

    C

    =Lightblue

    M=

    Brown

    N

    =Black

    R

    =Red

    B

    =White

    G/V=Yellow/Gr

    een

    V

    =Green

  • 7/25/2019 luna3_blue_-_gb (1)

    32/32

    35.TECHNICAL SPECIFICATIONS

    Boiler model LUNA 3 BLUE 180 i AT 1.180 i AT 240 i 240 Fi 1.240 Fi 280 Fi

    Category II2H3P II2H3P II2H3P II2H3P II2H3P II2H3P

    Rated heat output kW 19,4 19,4 26,3 26,3 26,3 30,1

    Reduced heat output kW 10,6 10,6 11,9 11,9 11,9 11,9

    Rated heat power kW 17,5 17,5 24 24 24 28

    kcal/h 15.050 15.050 20.600 20.600 20.600 24.080

    Reduced heat power kW 9,3 9,3 10,4 10,7 10,7 10,7

    kcal/h 8.000 8.000 8.900 9.202 9.202 9.202

    Useful efficiency according to Directive 92/42/EEC

    Central heating system max. pressure bar 3 3 3 3 3 3

    Expansion vessel capacity l 8 8 8 8 8 10

    Expansion vessel pressure bar 0,5 0,5 0,5 0,5 0,5 0,5

    Max. pressure in DHW system bar 8 8 8 8

    Minimum dynamic pressure in DHW system bar 0,15 0,15 0,15 0,15

    Minimum DHW output l/min 2,0 2,0 2,0 2,0

    DHW output at T=25 C l/min 10 13,7 13,7 16

    DHW output at T=35 C l/min 7,1 9,8 9,8 11,4

    Specific output (*) l/min 8 10,5 10,5 12,5

    Type B11BS B11BS B11BS C12 - C32 - C42 - C52 - C82 - B22

    Temperature range in heating system C 3085 3085 3085 3085 3085 3085

    Temperature range in DHW system C 3560 3560 3560 3560

    Concentric flue duct diameter mm 60 60 60

    Concentric air duct diameter mm 100 100 100

    2-pipe flue duct diameter mm 80 80 80

    2-pipe air duct diameter mm 80 80 80

    Discharge pipe diameter B11BS

    mm 110 110 130

    Max. flue mass flow rate (G20) kg/s 0,015 0,015 0,021 0,018 0,018 0,016

    Min. flue mass flow rate (G20) kg/s 0,012 0,012 0,017 0,013 0,013 0,010

    Max. temperature of fumes C 116 116 120 135 135 140

    Min. temperature of fumes C 90 90 86 106 106 108

    NOx Class 5 5 5 5 5 5

    Gas used G20-G31 G20-G31 G20-G31 G20-G31 G20-G31 G20-G31

    Natural gas feeding pressure 2H (G20) mbar 20 20 20 20 20 20

    Propane gas supply pressure 3P (G31) mbar 50 50 50 50 50 50

    Power supply voltage V 230 230 230 230 230 230

    Power supply frequency Hz 50 50 50 50 50 50

    Power consumption W 110 110 110 135 135 165

    Net weight kg 31 29 33 41,5 39,5 42

    Dimensions Height mm 763 763 763 763 763 763

    width mm 450 450 450 450 450 450

    depth mm 345 345 345 345 345 345

    Protection-limit against humidity and water leakages (**) IP X5D IP X5D IP X5D IP X5D IP X5D IP X5D

    (*) according to EN 625

    (**) according to EN 60529

    As BAXI s.p.a.constantly strives to improve its products, it reserves the right to modify the information contained in this do-cument at any time and without prior notice. These Instructions are only meant to provide consumers with use information and

    under no circumstance should they be construed as a contract with a third party.

    BAXI S.p.A.36061 BASSANO DEL GRAPPA (VI) ITALIA

    Via Trozzetti, 20