luna3_blue_-_gb (1)
TRANSCRIPT
-
7/25/2019 luna3_blue_-_gb (1)
1/32
HIGH PERFORMANCE GAS-FIRED WALL-MOUNTED BOILERSOPERATING AND INSTALLATION INSTRUCTIONS
GB
-
7/25/2019 luna3_blue_-_gb (1)
2/32
2C607504 - GBINSTRUCTIONS FOR USERS
Dear Customer,
We are confident your new boiler will meet all your requirements.
All BAXIproducts have been designed to give you what you are looking for: good performance combined with simple
and rational use.
Please do not put away this booklet without reading it first as it contains some useful information which will help you tooperate your boiler correctly and efficiently.
Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential source of
danger.
Baxi S.p.A. declares that these models of boiler bear the CE mark in compliance with the basic
requirements of the following Directives:- Gas Directive 90/396/EEC
- Efficiency Directive 92/42/EEC
- Electromagnetic Compatibility Directive 2004/108/EEC
- Low Voltage Directive 2006/95/EC
1. Instructions prior to installation 3
2. Instructions prior to commissioning 33. Commissioning the boiler 4
4. Adjusting CHW and DHW temperatures 55. Filling the system 6
6. Turning off the boiler 6
7. Gas conversion 6
8. Prolonged shutdown. Frost protection (central heating circuit) 6
9. Troubleshooting 7
10.Routine maintenance instructions 7
11.General precautions 8
12. Instructions prior to installation 8
13.Boiler installation 9
14. Installation of flue and air ducts 9
15. Installation of flue and air ducts 1016.Connecting the mains supply 13
17.Connecting the ambient thermostat 13
18.Gas conversion methods 14
19. Information on display 15
20.Parameter settings 16
21.Adjustment and safety devices 1822.Positioning the ignition and flame-sensor electrode 19
23.Checking combustion parameters 19
24.Output/pump head performance 20
25.Connecting the external probe 2026.Connection to an external storage boiler and three-way valve motor 2227.Electrically connecting the climate controller 22
28.Connecting a zone heating system 23
29.Removing scale from the DHW circuit 24
30.Dismounting the water-water heat exchanger 24
31.Cleaning the cold water filter 24
32.Annual service 2533.Circuit diagram 26
34. Illustrated wiring diagram 28
35.Technical specifications 32
CONTENTS
INSTRUCTIONS FOR USERS
INSTRUCTIONS FOR FITTERS
BAXI S.p.A.,a leading European manufacturer of hi-tech boilers and heating systems, has developed CSQ-
certified quality management (ISO 9001), environmental (ISO 14001) and health and safety (OHSAS 18001)systems. This means that BAXI S.p .A. includes among its objectives the safeguarding of the environment, the
reliability and quality of its products, and the health and safety of its employees.
Through its organisation, the company is constantly committed to implementing and improving these aspects
in favour of customer satisfaction.
-
7/25/2019 luna3_blue_-_gb (1)
3/32
3C607504 - GBINSTRUCTIONS FOR USERS
This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure. It must
be connected to a central heating system and to a domestic hot water supply system according to its performance and
power output.Before having the boiler installed by a qualified service engineer, make sure the following operations are performed:
a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings
on the packaging and the rating plate on the appliance.
b) Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gasesfrom other appliances are expelled through the same flue duct, unless the latter has been specially designed to collect
exhaust gas from more than one appliance, in compliance with current laws and regulations.c) Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual pro-
ducts of combustion may detach from the walls during operation and obstruct the flow of fumes.
d) To ensure correct operation and maintain the warranty, observe the following precautions:
1. DHW circuit
1.1.If the water is harder than 20 F (1 F = 10 mg calcium carbonate per litre of water), install a polyphosphate dis-penser or an equivalent treatment system, compliant with current regulations.
1.2.Thoroughly flush the system after installation of the appliance and before use.
1.3.The materials used for the products DHW circuit comply with Directive 98/83/EC.
2. Heating circuit
2.1.new system Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual
thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, pla-
stic and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning products
are:
SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliancewith the manufacturers instructions.
2.2.existing system
Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable
proprietary products as described in section 2.1.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such
as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with themanufacturers instructions.
Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.
overheating and excessive noise of the heat exchanger).
Failure to observe the above will render the guarantee null and void.
1. INSTRUCTIONS PRIOR TO INSTALLATION
Initial lighting of the boiler must be carried out by an authorised Service Engineer who must first ensure that:
a) The rated data correspond to the supply (electricity, water and gas) data;
b) The installation complies with current laws and regulations, an excerpt of which is given in the manual intended for thefitter.
c) The appliance is correctly connected to the power supply and earthed.
The names of the authorised Service Centres are indicated in the attached sheet. Failure to observe the above will render
the guarantee null and void.
Prior to commissioning, remove the protective plastic coating from the boiler. Do not use any tools or abrasive detergentsto do this as you may damage the painted surfaces.
The appliance is not intended to be used by persons (including children) with reduced physical, sensory or mental
capacities, or who lack experience or knowledge, unless, through the mediation of a person responsible for their
safety, they have had the benefit of supervision or of instructions on the use of the appliance.
2. INSTRUCTIONS PRIOR TO COMMISSIONING
-
7/25/2019 luna3_blue_-_gb (1)
4/32
4C607504 - GBINSTRUCTIONS FOR USERS
3. COMMISSIONING THE BOILERTo light the boiler correctly, proceed as follows:
Power the boiler; Turn on the gas tap; Press button (approx. 2 seconds) to set the boiler operating mode as described in section 3.2.
NOTE:if the SUMMER , mode is set, the boiler will only light during a DHW demand.
To set the desired CHW and DHW temperatures, press the +/-buttons as described in section 4.
WARNINGDuring initial ignition, the burner may not ignite (causing the boiler to shut down) until any air in the gas pipes is vented.In this case, repeat the ignition procedure until gas reaches the burner. Press the RESET button ( ) for at least 2 seconds.
Figure 1
KEY TO SYMBOLS ON DISPLAY
Enable heating mode
Flame present - figure 2
(power level 0 25 %)
Flame modulation level - figure 2
(3 power levels)
Enable DHW mode
Generic fault
No water
(System pressure LOW)
Numerical signal
(Temperature, fault code, etc.)
RESET
ECO mode
TASTEN
DHW temperature settings (C)
Heating temperature adjustment (C)
RESET (boiler reset)
ECO - COMFORT
MODE button (see section 3.2)
0609_
2301
If the optional climate controller is connected, always adjust the boiler using the climate controller. See the in-
structions accompanying this accessory item.
4 different boiler modulation levelsmay be shown during boiler
operation, as indicated in figure 2:
3.1 MEANING OF THE SYMBOL
Figure 2 0603_
1301
-
7/25/2019 luna3_blue_-_gb (1)
5/32
5C607504 - GBINSTRUCTIONS FOR USERS
4. ADJUSTING CHW AND DHW TEMPERATURES
Adjust the heating flow temperature and the DHW temperature , by pressing the respective +/- buttons (figure 1).When the burner is lit, the control panel display shows the symbol .
HEATING
The system must be fitted with an ambient thermostat for controlling indoor temperature.
While the boiler is operating in the heating mode, the display in figure 1 shows the flashing symbol and the heating flow
temperature(C) .
DHW
While the boiler is operating in the DHW mode, the display in figure 1 shows the flashing symbol and the storage boiler water
flow temperature (C).
Press Pto set two different DHW temperature values, ECOand COMFORT. To modify the temperatures, proceed as follows
ECO
Press P, the display shows eco, set the required temperature by pressing +/-buttons.
COMFORT
Press P, the display shows just the temperature setting, and then +/-to set the required temperature setpoint.
NOTE:if a storage boiler is connected, during boiler operation in DHW mode, the display shows the symbol( )and the sto-rage boiler flow temperature (C).
3.2 DESCRIPTION OF BUTTONS (Summer - Winter - Heating only - Off)
Press this button to set the following operating modes:
SUMMER
WINTER
HEATING ONLY OFF
In the SUMMERmode, the display shows . The boiler satisfies requests for DHW only while central heating is NOT
enabled (ambient frost protection function active).
In the WINTERmode, the display shows and . The boiler satisfies requests for both DHW and central heating
(ambient frost protection function active).
In the HEATING ONLYmode, the display shows . The boiler satisfies requests for central heating only (ambient frost
protection function active).
In the OFFmode, the display shows neither of the above two symbols . In this mode, only the ambient frost pro-
tection function is active while requests for DHW and central heating are not satisfied.
For more detailed technical information, please consult the SERVICE INSTRUCTIONS.
3.3 ADDITIONAL INFORMATION
-
7/25/2019 luna3_blue_-_gb (1)
6/32
6C607504 - GBINSTRUCTIONS FOR USERS
IMPORTANT:Regularly check that the pressure displayed on the pressure gauge (Figure 3a) is 0.7 - 1.5 bar, withthe boiler cold. In case of overpressure, turn on the boiler drain tap. In case of insufficient temperature, turn on the boiler
filling tap (figure 3a or 3b).
Turn on the tap very slowly in order to vent the air. During this operation, the boiler must be OFF (press( ) figure 1).
NOTE:The boiler is fitted with a hydraulic pressure gauge which prevents the boiler from working if there is no water.If pressure drops occur frequently, have the boiler checked by an authorised Service Engineer.
5. FILLING THE SYSTEM
Figure 3a
To turn off the boiler, disconnect the electric power supply. With the gas boiler in the OFF mode (section 3.2), the electric
circuits remain powered and the frost protection function is enabled (section 8).
6. TURNING OFF THE BOILER
7. GAS CONVERSION
The boilers can operate both on natural gas and LPG.Any gas change must be effected by a Qualified Service Engineer.
System filling tap
System drain tap
Pressure gauge
Do not drain the whole system as filling up with water again causes unnecessary and harmful scale to build up inside the
boiler and the heating elements. If the boiler is not used during winter and is therefore exposed to the danger of frost, addsome specific anti-freeze to the water in the system (e.g.: propylene glycol coupled with corrosion and scale inhibitors).
The electronic boiler management system includes a frost protection function for the heating system which, when flow
temperature falls below 5C, operates the burner until a flow temperature of 30C is reached.
The frost protection function is enabled if:
* the boiler is electrically powered;
* the gas tap is open;
* the system is at the correct pressure;
* the boiler is not blocked.
8. PROLONGED SHUTDOWN. FROST PROTECTION
Figure 3a
0603_
1303/CG_
1791
180i AT - 240i - 240 Fi - 280 Fi 1.180i AT - 1.240Fi
System filling tap
0901_
0802/CG_
1791
-
7/25/2019 luna3_blue_-_gb (1)
7/32
7C607504 - GBINSTRUCTIONS FOR USERS
9. TROUBLESHOOTING
To keep the boiler efficient and safe, have it checked by the authorised Service Centre at the end of every operating period.Careful servicing ensures economical operation of the system.
Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily flammable cleaners (e.g.: petrol, alcohol, and
so on). Always switch off the appliance before cleaning it (see section 6 Switching off the boiler).
10. ROUTINE MAINTENANCE INSTRUCTIONS
CODE
DISPLAYEDTYPE OF FAULT ACTION
E01 Ignition failure Press If this fault persists, call the Authorised Service Centre.
E02 Safety thermostat tripped Press If this fault persists, call the Authorised Service Centre.E03 Fumes thermostat action Call an authorised Service centre.
E04 Safety error due to frequent flame loss Call an authorised Service centre.
E05 Flow sensor fault Call an authorised Service centre.
E06 DHW sensor fault Call an authorised Service centre.
E10 Hydraulic pressure switch blockCheck that the pressure in the system is correct; See section5. If this fault persists, call the Authorised Service Centre.
E11Safety thermostat for low temperature system cuts in(if connected)
Call an authorised Service centre.
E25 No water safety trip Call an authorised Service centre.
E31 No connection with the climate controller Call an authorised Service centre.
E35 Parasite flame (flame error) Press If this fault persists, call the Authorised Service Centre.
E51 Fumes pressure switch action during boiler operation Call an authorised Service centre.
E52 Internal board error Call an authorised Service centre.
E53 Fumes pressure switch action Call an authorised Service centre.
E80 Internal climate controller error Call an authorised Service centre.
E98 Internal board error Call an authorised Service centre.
E99 Internal board error Call an authorised Service centre.
Figure 4
0605_1
106
Faults are shown on the display with an error code (e.g.: E01):The faults that can be reset by the user are indicated on the display with the symbol (figure 4).The faults that cannot be reset by the user are indicated on the display with the symbol (figure 4.1). To RESET the boiler,
press and hold down for at least 2 seconds.
Figure 4.1
0605_1
107
-
7/25/2019 luna3_blue_-_gb (1)
8/32
8C607504 - GBINSTRUCTIONS FOR FITTERS
This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure. It mustbe connected to a central heating system and to a domestic hot water supply system according to its performance andpower output. Do the following before connecting the boiler:a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings
on the packaging and the rating plate on the appliance.
b) Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gasesfrom other appliances are expelled through the same flue duct, unless the latter has been specially designed to collectexhaust gas from more than one appliance, in compliance with current laws and regulations.
c) Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual pro-ducts of combustion may detach from the walls during operation and obstruct the flow of fumes.
To ensure correct operation and maintain the warranty, observe the following precautions:
1. DHW circuit1.1.If the water is harder than 20 F (1 F = 10 mg calcium carbonate per litre of water), install a polyphosphate dis-
penser or an equivalent treatment system, compliant with current regulations.1.2.Thoroughly flush the system after installation of the appliance and before use.
1.3.The materials used for the products DHW circuit comply with Directive 98/83/EC.
2. Heating circuit
2.1. new system Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual
thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, pla-stic and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning productsare:
SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliancewith the manufacturers instructions.
2.2. existing system Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable
proprietary products as described in section 2.1. To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such
as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with themanufacturers instructions.
Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.overheating and excessive noise of the heat exchanger).
Failure to observe the above will render the guarantee null and void.
WARNINGIf an instantaneous (mixed) boiler is connected to a system with solar panels, the maximum temperature of the domestichot water entering the boiler must not exceed:
60Cwith flow limiting device 70Cwithout flow limiting device
The following notes and instructions are addressed to fitters to allow them to carry out trouble-free installation. Instruc-tions for lighting and using the boiler are contained in the Instructions for Users section.Moreover, the fitter must be legally qualified to install heating appliances.Please, bear in mind the following.
This boiler can be connected to any type of double- or single-pipe convector plate, radiator or thermoconvector. De-sign the system sections as usual, though, bearing in mind the available flow-head at the plate, as shown in section 24.
Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential sourceof danger.
Initial lighting of the boiler must be carried out by an authorised Service Engineer, as indicated on the attached sheet.Failure to observe the above will render the guarantee null and void.
11. GENERAL PRECAUTIONS
12. INSTRUCTIONS PRIOR TO INSTALLATION
-
7/25/2019 luna3_blue_-_gb (1)
9/32
9C607504 - GBINSTRUCTIONS FOR FITTERS
13. INSTALLING THE BOILERAfter deciding the exact location of the boiler, fix the template to the wall.
Connect the system to the gas and water inlets present on the lower bar of the template. Fit two G3/4 taps (flow and
return) on the central heating circuit; these taps make it possible to carry out important operations on the system without
draining it completely. If you are either installing the boiler on an existing system or replacing one, as well as the above,fit a settling tank under the boiler on the system return line in order to collect any deposits and scale circulating in the
system after flushing. After fixing the boiler to the template, connect the flue and air ducts, supplied as accessories, as
described in the following sections.If natural draught boilers are installed, connect them to the flue with a metal pipe resistant to normal mechanical stress,
heat, products of combustion and relative condensate.
Figure 5
= BOILER WIDTH 450 =
BOILER CONNECTION POINT
BOILERHEIGHT780
14. DIMENSIONS OF BOILER
Figure 6
180 i AT - 240 i - 1.180 i AT 240 Fi - 280 Fi - 1.240 Fi
: G 3/4 heating system flow/return
: G 1/2 hot domestic water outlet/inlet
: G 3/4 gas input to boiler
0512_
0504/CG1769
0512_0505/CG1769
0512_0503/CG1769
: G 3/4 heating system flow/return
: G 3/4 storage boiler flow - G 1/2 DHW inlet
: G 3/4 gas inlet to boiler
180 i AT - 240 i - 240 Fi - 280 Fi1.180 i AT - 1.240 Fi
minimo
0705_
0609
0606_26
03
A
180i AT - 1.180i AT A= 110 mm240i A= 130 mm
-
7/25/2019 luna3_blue_-_gb (1)
10/32
10C607504 - GBINSTRUCTIONS FOR FITTERS
15. INSTALLATION OF FLUE AND AIR DUCTS
model
240 Fi - 280 Fi - 1.240 Fi
The boiler is easy and flexible to install thanks to the extensiverange of available accessories, as described below.The boiler has been designed for connection to a vertical or hori-
zontal coaxial flue-air duct. A splitting kit is also available if sepa-rate ducts are required.
Only accessories supplied by the appliance manufacturermust be used for installation!
WARNINGTo optimise operating safety, make sure the flue ducts are firmlyfixed to the wall with suitable brackets.
COAXIAL FLUE - AIR DUCT (CONCENTRIC)
This type of duct is used to discharge exhaust fumes and drawcombustion air both outside the building and if a LAS flue is fitted.The 90 coaxial bend allows the boiler to be connected to a flue-airduct in any direction as it can be rotated by 360. It can also beused as a supplementary curve combined with a coaxial duct or a45 curve.
If fumes are discharged outside the building, the flue-air duct mustprotrude at least 18 mm from the wall to allow an aluminium wea-thering surround to be fitted and sealed to avoid water infiltrations.Make sure there is a minimum upward slope towards the outsideof 1 cm per metre of duct.
A 90 curve reduces total duct length by 1 metre. A 45 curve reduces total duct length by 0.5 metre.
Figure 7
0503_
0905/CG1638
Figure 8
15.1 HORIZONTAL FLUE INSTALLATION OPTIONS
L max = 4 mL max = 4 m
L max = 3 m L max = 3 m
0512_
2001
0711_
1901
Connector
Concentricconnector
-
7/25/2019 luna3_blue_-_gb (1)
11/32
11C607504 - GBINSTRUCTIONS FOR FITTERS
15.2 LAS FLUE DUCT INSTALLATION OPTIONS
15.3 VERTICAL FLUE INSTALLATION OPTIONS
This type of installation can be carried out on either a flat or a pitched roof by fitting a flue terminal and a special weathe-
ring surround with sleeve (both available on request).
0503_
0908/CG1641
L max = 4 m L max = 4 m L max = 2 m L max = 3 m
L max = 4 m
0512_
2002
For detailed installation instructions, consult the technical data provided with the accessories.
SEPARATE FLUE AND AIR DUCTS
This type of installation makes it possible to discharge exhaust fumes both outside the building and into single flue ducts.
Comburent air can be drawn in at a different location from that of the flue terminal. The splitting kit comprises a flue duct
adaptor (100/80) and an air duct adaptor. For the air duct adaptor, fit the screws and seals previously removed from the
cap.
The first 90 curve is not included when calculating the maximum available length.
The 90 curve allows the boiler to be connected to a flue-air duct in any direction as it can be rotated by
Figure 9
0707_
0803/CG_
1795
Flue duct adaptor
Connector
360. It can also be used as a supplementary cur-
ve combined with a duct or a 45 curve.
A 90 curve reduces total duct length by 0.5metre.
A 45 curve reduces total duct length by
0.25 metre.
-
7/25/2019 luna3_blue_-_gb (1)
12/32
12C607504 - GBINSTRUCTIONS FOR FITTERS
0503_
2201/CG1643
15.5 SEPARATE HORIZONTAL FLUE INSTALLATION OPTIONS
IMPORTANT:Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length.In the event of installation of the condensate collection kit, the angle of the drain duct must be directed towards the boiler.
(L1 + L2) max = 20 m
NB:For the C52 type, do not fit the flue and air duct terminals on opposite walls of the building.
The maximum length of the air duct is 10 metres. If the discharge duct is longer than 6 metres, install the condensatecollection kit, supplied as an accessory, near the boiler.
L max = 10 m
15.4 DIMENSIONS OF SEPARATE OUTLETS
0504_
1806/CG_
1794
0503_
091
1/CG1644
L max = 10 m L max = 9 m
15.6 SEPARATE VERTICAL FLUE INSTALLATION OPTIONS
IMPORTANT:if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the ductpasses through building walls.
For detailed installation instructions, consult the technical data provided with the accessories.
-
7/25/2019 luna3_blue_-_gb (1)
13/32
13C607504 - GBINSTRUCTIONS FOR FITTERS
16. CONNECTING THE MAINS SUPPLY
This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current
safety regulations.Connect the boiler to a 230V single-phase earthed power supply using the supplied three-pin cable, observing correct
LIVE-NEUTRAL polarity.
Use a two-pole switch with a contact separation of at least 3 mm. When replacing the power supply cable, fit a har-
monised HAR H05 VV-F 3x0.75mm2 cable with a maximum diameter of 8 mm.
Access to the power supply terminal block
disconnect the boiler from the mains power supply using the two-pole switch;
remove the two screws xing the control panel to the boiler;
rotate the control panel; remove the cover and access the wiring area (gure 10).
The 2A fast-blowing fuses are incorporated in the power supply terminal block (to check and/or replace the fuse, pull out
the black fuse carrier).
IMPORTANT:respect polarity L(LIVE) - N(NEUTRAL).
(L) = Live(brown)
(N) = Neutral(light blue)
= Earth(yellow-green)
(1) (2) = Contact for ambient thermostat
Figure 10
0512_
0508/CG1770
WARNINGIf the appliance is directly connected to an underfloor system, install a safety thermostat to prevent the latter from over-
heating.
17. CONNECTING THE AMBIENT THERMOSTAT
access the power supply terminal block (gure 10);
remove the jumper on terminals (1) and (2);
thread the two-wire cable through the grommet and connect it to these two terminals.
-
7/25/2019 luna3_blue_-_gb (1)
14/32
14C607504 - GBINSTRUCTIONS FOR FITTERS
The Technical Assistance Service can convert this boiler to natural gas (G20) or liquid gas (G31).
Carry out the following operations:
A) Replace the burner injectors
carefully pull the main burner off its seat; replace the main burner injectors making sure to fully tighten them to prevent gas leaks. Injector diameters are specied
in table 1.
18. GAS CONVERSION METHODS
Figure 11
Honeywell valve
Mod. VK 4105 M
0207_
0406
B) Change the modulator voltage
set parameter F02according to the gas used, as described in
section 20.
C) Calibrate the pressure regulator
connect the positive pressure test point of a differential pres-
sure gauge (possibly water-operated) to the gas valve pres-
sure test point (Pb) (Figure 11). Connect, for sealed chambermodels only, the negative pressure test point of the pressure
gauge to a T fitting in order to join the boiler adjusting outlet,the gas valve adjusting outlet (Pc) and the pressure gauge .
(The same measurement can be carried out by connecting the
pressure gauge to the pressure test point (Pb) after removing
the sealed chamber front panel); If you measure the pressure
of burners in a different way you may obtain an altered result
in that the low pressure created in the sealed chamber by thefan would not be taken into account.
C1) Adjustment to nominal heat output
turn on the gas tap;
press (Figure 1) and switch the boiler to the winter mode
(section 3.2); turn on a hot water tap to reach a minimum 10 l/min ow rate
or ensure that maximum heating requirements are set; remove the modulator cover; adjust the brass screw (a) in Fig. 12 until the pressure values
shown in table 1 are obtained; check that the boiler feeding dynamic pressure, as measured
at the inlet gas valve pressure test point (Pa) (Figure 11) is cor-
rect (37 mbarfor propane gas, 20 mbarfor natural gas).
C2) Adjustment to reduced heat output
disconnect the modulator power cable and unscrew the screw
(b) in Fig. 12 until a pressure value corresponding to reduced
heat output is achieved (see tab.1) connect the cable again;
mount the modulator cover and seal.
C3) Final checks
mark on the data plate the type of gas and the calibration per-
formed.
Figure 12
0605_
1701
-
7/25/2019 luna3_blue_-_gb (1)
15/32
15C607504 - GBINSTRUCTIONS FOR FITTERS
TABLE OF BURNER PRESSURE AND INJECTORS
240 i 240 Fi - 1.240 Fi 280 Fi
Type of gas G20 G31 G20 G31 G20 G31
Burner pressure (mbar*) 2,1 6,4 3,0 5,5 2,3 4,0REDUCED POWER
Burner pressure (mbar*) 8,8 28,9 12,5 25,0 13,3 23,9RATED POWER
Diameter of nozzles (mm) 0,87 0,5 0,82 0,52 0,82 0,55
Number of nozzles 30 34* 1 mbar = 10,197 mm H
2O
Table 1
180 i AT - 1.180 i AT
Type of gas G20 G31
Burner pressure (mbar*) 2,9 8,8
REDUCED POWER
Burner pressure (mbar*) 8,8 28,9
RATED POWER
Diameter of nozzles (mm) 0,87 0,5
Number of nozzles 22
* 1 mbar = 10,197 mm H2O
Table 1
TABLE OF BURNER PRESSURE AND INJECTORS
240 Fi - 1.240 Fi 280 Fi
consumption15 C - 1013 mbar G20 G31 G20 G31
Rated power 2,78 m3/h 2,04 kg/h 3,18 m3/h 2,34 kg/h
Reduced power 1,26 m3/h 0,92 kg/h 1,26 m3/h 0,92 kg/h
p.c.i. 34,02 MJ/m3 46,30 MJ/kg 34,02 MJ/m3 46,30 MJ/kg
Table 2
240 i 180 i AT - 1.180 i AT
consumption15 C - 1013 mbar G20 G31 G20 G31
Rated power 2,78 m3/h 2,04 kg/h 2,05 m3/h 1,51 kg/h
Reduced power 1,26 m3/h 0,92 kg/h 1,12 m3/h 0,82 kg/h
p.c.i. 34,02 MJ/m3 46,30 MJ/kg 34,02 MJ/m3 46,30 MJ/kg
Table 2
19. INFORMATION ON DISPLAYTo light the boiler correctly, proceed as follows:
Power the boiler. When the gas boiler is power supplied, for approximately the first 8 seconds, the display backlighting is on. Then, it
displays the following information.
1. all symbols lit;
2. manufacturer information;
3. manufacturer information;4. manufacturer information;
5. boiler and gas type (e.g.) ). Die Bedeutung der angezeigten Zeichen ist folgende:
= open chamber boiler = sealed chamber boiler;
= Natural gas used = LPG gas used.
6.Hydraulic system;
7.Software version (two numbers x.x);
Turn on the gas tap;
Press button (approx. 2 seconds) to set the boiler operating mode as described in section 3.2.
-
7/25/2019 luna3_blue_-_gb (1)
16/32
16C607504 - GBINSTRUCTIONS FOR FITTERS
19.1 OPERATING INFORMATION
To display some useful information during the boileroperation proceed as follows:
Press ( ) for approx. 6 seconds. When the
function is enabled, the display shows A00
(A09) alternating with the respective value
(e.g. figure 13);
Press the +/-domestic hot water buttons to
display the following instantaneous information:
A00: domestic hot water temperature value (C);A01: outside temperature (C) (with external probe
sensor connected);
A02: modulation current value (100% = 230 mA ME-
THANE - 100% = 310 mA LPG);
A03: power range level value (%) - see parameter
F13 (section 20);A04: temperature setpoint value (C);
A05: central heating flow temperature value (C);Figure 13
0706_
1202
5 seconds
A06: DHW flow value (l/min x 10);A07: flame signal value (8-100%).
A09: pressure signal value of the flue pressure switch (Pa)
NOTE:display line A08 is not used
This function is active for 3 minutes. To interrupt the INFO function, press .
See section 9 for error codes and anomalies description.
NOTE:the resetting operation is available only for 5 consecutive attempts, after which the gas boiler remains blocked.To carry out a new RESET attempt, proceed as follows:
Press for approx. 2 seconds.
press for about 2 seconds, the display shows OFF; reset the boiler operating mode as described in section3.2.
19.2 FAULTS DISPLAY
For more detailed technical information, please consult the SERVICE INSTRUCTIONS.
19.3 ADDITIONAL INFORMATION
20. PARAMETER SETTINGS
To set the boiler parameters, press and -( ) together and hold down for at least 6 seconds. When the function isactivated, the display shows F01 alternated with the value of the parameter.
Change parameters
To scroll the parameters press+/-. Press +/-buttons to change the single parameter value.
Press the Pbutton to save changes, the display shows MEM. Press the button .to leave the function without saving, the display
shows ESC.
0610_
2504
-
7/25/2019 luna3_blue_-_gb (1)
17/32
17C607504 - GBINSTRUCTIONS FOR FITTERS
Description of parametersFactory settings
180 i AT 1.180 i AT 240 i 240 Fi 1.240 Fi 280 Fi
F01Types of gas boiler
30-40 = sealed chamber - 20 = atmospheric20 30 40
F02Gas used
00= NATURAL - 01= LPG00 o 01
F03
Hydraulic system
00= instantaneous appliance
05= appliance with external storage boiler
08= heating only appliance
00 08 00 00 08 00
F04Programmable relay 1 setting
(02= zone system - See SERVICE Instructions)02
F05
Programmable relay 2 setting
04: fault signalling contact
05: Kitchen fan function (disabling, cooker extraction hood)
13: cool function for external conditioning system
(See SERVICE Instructions)
04
F06 External sensor programmable input setting (See SERVICE Instructions) 00
F07F12 manufacturer information 00
F13 Max. heating output (0-100%) 100F14 D.H.W. max. heating output (0-100%) 100
F15 Min. heating output (0-100%) 00
F16
Maximum temperature setpoint setting (C)
00= 85C - 01= 45C
CAUTION: If the appliance is directly connected to an underfloor system, install
a safety thermostat to prevent the latter from overheating
00
F17Pump overrun time
(01-240 minutes)03
F18Burner ignition delay in CH mode
(00-10 minutes) - 00=10 seconds03
F19 manufacturer information 07
F20 manufacturer information --
F21 Anti-legione llosis funct ion00= Disabled - 01= Enabled 00
F22 manufacturer information 00
F23 Maximum DHW setpoint 60
F24 manufacturer information 35
F25 No water safety device 00
F26F29 Manufacturer information (read-only parameters) --
F30 manufacturer information 10
F31 manufacturer information 30
F32F41 Diagnostics (See SERVICE Instructions) --
Final
parameter
Calibration function activation
(See SERVICE Instructions)0
WARNING:do not modify the values of the Manufacturer information parameters.
-
7/25/2019 luna3_blue_-_gb (1)
18/32
18C607504 - GBINSTRUCTIONS FOR FITTERS
The boiler has been designed in full compliance with European reference standards and in particular is equipped with the
following:
Air pressure switch (models 240 Fi - 1.240 Fi - 280 Fi) This device only allows the burner to ignite if the exhaust flue duct is in perfect working order.
In the event of one of the following faults:
the ue terminal is obstructed; the venturi is obstructed;
the fan is blocked;
pressure switch is trippedThe boiler will stay on stand-by and the display shows error code E51 or E53 (see section 9).
Fumes thermostat (model180 i AT - 1.180 i AT - 240 i)
This device has a sensor positioned on the left section of the flue extraction hood and shuts off the gas flow to the
burner if the flue duct is obstructed or in the event of draught failure.
In these conditions the boiler shuts down and displays error code E03 (section 9). To relight the main burner immediately,see section 9.
It is forbidden to disable this safety device.
Safety thermostat
This device has a sensor positioned on the left section of the flue extraction hood and shuts off the gas flow to the
burner if the flue duct is obstructed or in the event of draught failure. Under such conditions the boiler is blocked and
only after the fault has been eliminated can it be ignited again.
In these conditions the boiler shuts down and displays error code E02 (section 9).
It is forbidden to disable this safety device.
Flame ionisation detector
The flame sensing electrode, located on the right-hand side of the burner, guarantees safety of operation in case of gas
failure or incomplete ignition of the burner.
In these conditions, the boiler is blocked after 3 ignition attempts. To reset normal operating conditions, ...
In these conditions the boiler shuts down and displays error code E01 (section 9).
hydraulic pressure switch
This device allows the main burner to be ignited only if system pressure is higher than 0.5 bars.
In these conditions the boiler shuts down and displays error code E01 (section 9).
Pump overrun for heating circuit
The electronically-controlled pump post-circulation function lasts 3 minutes (F17 - section 20) and is enabled, in the
heating mode, if the ambient thermostat causes the burner to go out.
Pump overrun for DHW circuit
The electronically-controlled pump post-circulation function lasts 30 seconds and is enabled, in the DHW mode, if theprobe causes the burner to go out.
Frost protection device (heating and DHW systems)
The electronic boiler management system includes a frost protection function for the heating system which, whenflow temperature falls below 5C, operates the burner until a flow temperature of 30C is reached.
Water not circulating in primary circuit (pump probably blocked)
If there is insufficient or no water circulating in the primary circuit, the boiler blocks and the error code E25 is shown on
the display (section 9).
Anti-block pump function
If no heat demand is received for 24 consecutive hours, the pump will automatically start and operate for 10 seconds.
This function is operative when the boiler is powered.
Three-way valve anti-blockage function
If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle. This
function is operative when the boiler is powered.
Hydraulic safety valve (heating circuit)
This device is set to 3 bar and is used for the heating circuit.
21. ADJUSTMENT AND SAFETY DEVICES
-
7/25/2019 luna3_blue_-_gb (1)
19/32
19C607504 - GBINSTRUCTIONS FOR FITTERS
22. POSITIONING THE IGNITION AND FLAME-SENSOR ELECTRODE
Figure 16
To measure combustion performance and the toxicity of the products of combustion, the boiler is fitted with two dedica-
ted test points.
One connection point is connected to the flue gas discharge circuit, and allows monitoring of the quality of the combusti-
on products and the combustion efficiency.
The other is connected to the combustion air intake circuit, allowing checking of any recycling of the combustion productsin case of coaxial pipelines.
The following parameters can be measured at the connection point on the flue gas circuit:
temperature of the combustion products;
oxygen (O2) or carbon dioxide (CO
2) concentration;
carbon monoxide (CO) concentration.The temperature of the comburent air must be measured on the test point located on the air intake flue by inserting the
measurement sensor by about 3 cm.
For natural draught boiler models, a hole must be made in the flue gas discharge pipe at a distance from the boiler equal
to twice the inside diameter of the pipe itself.
The following parameters can be measured through this hole: temperature of the combustion products;
oxygen (O2) or carbon dioxide (CO
2) concentration;
carbon monoxide (CO) concentration.
The combustion air temperature must be measured close to the point where the air enters the boiler.
The hole, which must be made by the person in charge of operating the system when it is commissioned, must be sealed
in a way which ensures that the combustion product discharge pipe is airtight during normal operation.
23. CHECKING COMBUSTION PARAMETERS
0012180600
180 i AT - 1.180 i AT - 240 i
0206_
0708
240 Fi - 1.240 Fi - 280 Fi
Connect the safety valve to a drain trap. Do not use it to drain the heating circuit.
Anti-legionellosis function (model 1.180 i AT - 1.240 Fi with storage boiler)
The anti-legionellosis function is NOT enabled.
To enable this function, set parameter F21=01 (as described in section 20). When the function is enabled, the electronic
management of the boiler, at weekly intervals, heats the water contained in the storage boiler to over 60C (the function
only works if the water has never exceeded 60C in the previous 7 days).
NOTE:domestic hot water is guaranteed even if the NTC sensor develops a fault.
In this case, temperature is controlled by the flow sensor.
-
7/25/2019 luna3_blue_-_gb (1)
20/32
20C607504 - GBINSTRUCTIONS FOR FITTERS
This is a high static head pump fit for installation on any type of single or double-pipe heating systems. The air vent valve
incorporated in the pump allows quick venting of the heating system.
Graph1
24. OUTPUT/PUMP HEAD PERFORMANCE
FLOW l/h
HEADmH
2O
0705_2101 Graph2
FLOW l/h
HEADmH
2O
280 Fi
0705_2102
240 Fi - 1.240 Fi
Graph3
FLOW l/h
H
EADmH
2O
0705_2103
180 i AT - 1.180 i AT - 240 i
25. CONNECTING THE EXTERNAL PROBE
The boiler is prearranged for connection of an external probe (supplied as accessory). For the connection, refer to figuresbelow and the instructions supplied with the probe.
-
7/25/2019 luna3_blue_-_gb (1)
21/32
21C607504 - GBINSTRUCTIONS FOR FITTERS
With the external probe connected, buttons +/- adjusting the heating circuit temperature ( ) (figure 1) regulate the coeffici-
ent of heat dispersion Kt (190). Charts below show the correspondence between the set value and the relative curves.
Intermediate curves can also be selected.
IMPORTANT:the maximum value of the flow temperature TMdepends on the F16 parameter setting (see section20). The maximum flow temperature may be 85 or 45C.
0603_
0305
0603_
0306
kt curves
Graph3 Graph4
TM - flow temperature
Te - external temperature
Figure 17.2
0605_
1604models 1.180 i AT - 1.240 Fi
Figure 17
0610_1301 / CG_1855
CN 5
models 180 i AT - 1.180 i AT - 240 i models 240 Fi - 1.240 Fi - 280 Fi
Figure 17.1
0705_2801 / CG_1941
CN 5
-
7/25/2019 luna3_blue_-_gb (1)
22/32
22C607504 - GBINSTRUCTIONS FOR FITTERS
(SUPPLIED AS ACCESSORY)
The climate controller is not a
standard boiler component as
it is supplied as an accessory.
Open the electronic board andconnect the cable (supplied to-
gether with the two-pin terminal
board) to connector CN7 on the
boiler electronic board. Connect
the terminals of the climate con-
troller to the two-pin terminalboard (figure 19).
27. ELECTRICAL CONNECTION OF THE CLIMATE CONTROLLER
Figure 19
NOTE:for models 1.180 i AT and 1.240 Fi, connect the climate controller as described in section 28.1 (figure 20).
0610_
1302/CG_
1856
CN 7
Figure 18
model 1.180 i AT - 1.240 Fi
CONNECTING THE STORAGE BOILER PROBE
The boiler is prearranged for connection of an external storage boiler. Hydraulically connect the storage boiler as shown infigure. 18. Connect the NTCDHW priority probe to terminals 5-6 in the terminal block M2. The sensitive element of the NTC
probe must be inserted in the holder provided on the storage boiler. Adjust DHW temperature (35...65 C) by pressing +/-.
26. CONNECTING AN EXTERNAL STORAGE BOILER
0702_
1602
Key
UB storage boilerUR heating unit
M three-way valve motor (accessory)
M2 connection terminal block
SB DHW priority storage boiler probeMR heating flow
MB storage boiler flow
RR heating/storage boiler return
MOTOR
NOTE:Make sure parameter F03 = 05 (section 20).
-
7/25/2019 luna3_blue_-_gb (1)
23/32
23C607504 - GBINSTRUCTIONS FOR FITTERS
The relay board is not a standard boiler component as it is supplied as an accessory. Connect terminals 1-2-3 (common -
normally closed - normally open) of connector CN1on the relay board, to the respective terminals 10-9-8 of boiler terminal
block M2(figure20).
28. CONNECTING A ZONE HEATING SYSTEM
28.1 CONNECTING THE RELAY BOARD
Figure 20
Connect the contact relative to heating requests in zones that are not controlled by the climate controller in parallel toterminals 1-2 TA on terminal block M1.
Remove the jumper.
The zone controlled by the climate controller is managed by the zone 1 solenoid, as illustrated in figure 21.
28.2 CONNECTING THE ZONES
Figure 21
CLIMATE CONTROLLER
0706_
1203/CG_
1840
CLIMATE CONTROLLER
BOILER BOARD
RELAY BOARD ACCESSORY
RELAY 2
RELAY 1
ZONE 1
ZONE 1
REMOTE CONTROLZONE 2
(AMBIENT THERMOSTAT)
ZONE 3
(AMBIENT THERMOSTAT)
ZONE N
(AMBIENT THERMOSTAT)
SOLENOID
ZONE 1
0709_
2403/CG_
1825
-
7/25/2019 luna3_blue_-_gb (1)
24/32
24C607504 - GBINSTRUCTIONS FOR FITTERS
(Not contemplated in model 1.180 i AT - 1.240 Fi)
The DHW circuit can be cleaned without removing the water-water heat exchanger if the assembly is fitted with the special tap (availa-
ble on request) located on the DHW outlet.
To clean, proceed as follows:
Turn off the DHW inlet tap
Drain the DHW system by turning on a hot water tap Turn off the DHW outlet tap
Unscrew the two stopcocks
Remove the lters
If the special tap is not supplied, dismount the water-water heat exchanger, as described in the next section, and clean it separately.
Remove the scale from the seat and relative NTC sensor fitted on the DHW circuit.
To clean the exchanger and/or DHW circuit, use Cillit FFW-AL or Benckiser HF-AL.
29. REMOVING SCALE FROM THE DHW CIRCUIT
(Not contemplated in model 1.180 i AT - 1.240 Fi)
The stainless steel plate-type water-water heat exchanger is easily disassembled with a screwdriver by operating as described below:
drain the system, just the boiler if possible, through the drain tap;
drain the DHW system;
remove the two screws at the front securing the water-water heat exchanger and pull it out (gure 22).
30. DISMOUNTING THE WATER-WATER HEAT EXCHANGER
(Not contemplated in model 1.180 i AT - 1.240 Fi)
The boiler is fitted with a cold water filter located on the hydraulic assembly. To clean, proceed as follows: Drain the domestic hot water system.
Unscrew the nut on the ow sensor assembly (gure 22).
Pull out the ow sensor and its lter.
Remove any impurities.
IMPORTANT:when replacing and/or cleaning the O-rings on the hydraulic assembly, only use Molykote 111 as a lubricant, notoil or grease.
31. CLEANING THE COLD WATER FILTER
0606_
2703
/CG_
1839
Figure 22water-water heat exchanger retaining screws
fixing nut flow sensor
-
7/25/2019 luna3_blue_-_gb (1)
25/32
25C607504 - GBINSTRUCTIONS FOR FITTERS
To optimise boiler efficiency, carry out the following annual controls:
check the appearance and air-tightness of the gaskets of the gas and combustion circuits;
check the state and correct position of the ignition and ame-sensing electrodes; check the state of the burner and make sure it is rmly xed;
check for any impurities inside the combustion chamber.
Use a vacuum cleaner to do this;
check the gas valve is correctly calibrated;
check the pressure of the heating system; check the pressure of the expansion vessel;
check the fan works correctly;
make sure the ue and air ducts are unobstructed;
check for any impurities inside the siphon;
check the magnesium anode, where present, for boilers tted with storage boilers.
WARNINGSBefore commencing any maintenance operations, make sure the boiler is disconnected from the power supply.
Afterwards, move the knobs and/or operating parameters of the boiler to their original positions.
32. ANNUAL SERVICE
-
7/25/2019 luna3_blue_-_gb (1)
26/32
26C607504 - GBINSTRUCTIONS FOR FITTERS
Figure 23
33. CIRCUIT DIAGRAM
240 Fi - 280 Fi - 1.240 Fi
Key:
1 DHW priority sensor
2 hydraulic pressure switch
3 DHW NTC probe
4 three-way valve
5 non-return valve
6 3-way valve motor7 gas valve
8 expansion vessel
9 flame detection electrode
10 NTC heating probe
11 safety thermostat
12 water-fumes exchanger
13 fumes conveyor
14 fan
15 concentric connector
16 air pressure switch
17 negative pressure point
18 ignition electrode
19 burner
20 pressure gauge
21 water-water plate exchanger
22 pump with air separator
23 boiler filling tap
24 boiler drain tap25 safety valve
26 flow sensor with filter and water flow limiting device
Heating DHW Gas DHW Heating
flow outlet inlet return
Heating Storage Gas DHW Heating
flow boiler inlet return
flow
0705_
1804/CG_1926
240 Fi - 280 Fi 1.240 Fi
Key:
1 automatic by-pass
2 hydraulic pressure switch
3 three-way valve
4 pressure gauge
5 3-way valve motor
6 gas valve7 expansion vessel
8 flame detection electrode
9 NTC heating probe
10 safety thermostat
11 water-fumes exchanger
12 fumes conveyor
13 fan
14 concentric connector
15 air pressure switch
16 negative pressure point
17 ignition electrode
18 burner
19 automatic vent valve
20 pump with air separator
21 non-return valve
22 boiler drain tap
23 safety valve
CG_
1925/0902_0
301
-
7/25/2019 luna3_blue_-_gb (1)
27/32
27C607504 - GBINSTRUCTIONS FOR FITTERS
Figure 24
180 i AT - 240 i - 1.180 i AT
Key:
1 DHW priority sensor2 hydraulic pressure switch3 DHW NTC probe4 three-way valve
5 non-return valve6 3-way valve motor7 gas valve8 expansion vessel9 ignition electrode10 NTC heating probe11 safety thermostat12 water-fumes exchanger13 fumes hood14 fumes thermostat15 flame detection electrode16 burner17 pressure gauge18 water-water plate exchanger19 pump with air separator20 boiler filling tap21 boiler drain tap22 safety valve23 flow sensor with filter and water flow limiting device
Heating DHW Gas DHW Heating
flow outlet inlet return
Heating Storage Gas DHW Heating
flow boiler inlet return
flow
180 i AT - 240 i 1.180 i AT
Key:
1 automatic by-pass
2 hydraulic pressure switch
3 three-way valve
4 pressure gauge
5 3-way valve motor6 gas valve
7 expansion vessel
8 ignition electrode
9 NTC heating probe
10 safety thermostat
11 water-fumes exchanger
12 fumes hood
13 fumes thermostat
14 flame detection electrode
15 burner
16 automatic vent valve
17 pump with air separator
18 non-return valve
19 boiler drain tap
20 safety valve
0705_
1806/CG_
1923
CG_
1924/0901_
2902
-
7/25/2019 luna3_blue_-_gb (1)
28/32
28C607504 - GBINSTRUCTIONS FOR FITTERS
34. ILLUSTRATED WIRING DIAGRAM
240 Fi - 280 Fi
0711_
1801/CG_1930
DHWP
RIORITY
SENSOR
DHWN
TCPROBE
HYDRAULICPRE
SSURE
SWITCH
NTCHEATING
PROBE
SAFETY
THERMOSTAT
DETECTION
ELECTRODE
GASVALVE
IGNITION
ELECTRODE
FAN
THE
RMOSTAT
PUMP
MAIN
SPOWER
SUPPLY
AIRPRESSU
RE
SWITCH
Cablecolours
C
=Lightblue
M=
Brown
N
=Black
R
=Red
B
=White
G/V=Yellow/Green
V
=Green
-
7/25/2019 luna3_blue_-_gb (1)
29/32
29C607504 - GBINSTRUCTIONS FOR FITTERS
1.240 Fi
0711_
1802/CG_1929
DHWP
RIORITY
SENSOR
HYDRAUL
IC
PRESSUR
E
SWITCH
NTCHEATING
PROBE
SAFETY
THERMOSTAT
DETECTION
ELECTRODE
GASVALVE
IGNITION
ELECTRODE
FAN
THERMOSTAT
PUMP
MAINSPOW
ER
SUPPLY
AIRPRESSURE
SWITCH
Cablecolours
C
=Lightblue
M=
Brown
N
=Black
R
=Red
B
=White
G/V=Yellow/Gr
een
V
=Green
-
7/25/2019 luna3_blue_-_gb (1)
30/32
30C607504 - GBINSTRUCTIONS FOR FITTERS
180 i AT - 240 i
0711_
1906/CG_
1928
THREE-WAY
VALVE
FU
MES
TH
ERMOSTAT
THER
MOSTAT
PUMP
MAINS
POWER
SUPPLY
GASVALVE
IGNITION
ELECTRODE
SAFETY
THERMOSTAT
DETECTIO
N
ELECTRODE
NTCHEATING
PROBE
DHWP
RIORITY
SENSOR
DHWN
TCPROBE
HYDRAULICPRESSURE
SWITCH
Cablecolours
C
=Lightblue
M=
Brown
N
=Black
R
=Red
B
=White
G/V=Yellow/Gr
een
V
=Green
-
7/25/2019 luna3_blue_-_gb (1)
31/32
31C607504 - GBINSTRUCTIONS FOR FITTERS
1.180 i AT
0711_
1907/CG_
1927
THERMOSTAT
PUMP
MAINSP
OWER
SUPPLYT
HREE-WAY
VALVE
GASVALVE
IGNITION
ELECTRODE
SAFETY
THERMOSTAT
DETECTION
ELECTRODE
FUME
S
THER
MOSTAT
NTCHEATING
PROBE
DHWP
RIORITY
SENSOR
Cablecolours
C
=Lightblue
M=
Brown
N
=Black
R
=Red
B
=White
G/V=Yellow/Gr
een
V
=Green
-
7/25/2019 luna3_blue_-_gb (1)
32/32
35.TECHNICAL SPECIFICATIONS
Boiler model LUNA 3 BLUE 180 i AT 1.180 i AT 240 i 240 Fi 1.240 Fi 280 Fi
Category II2H3P II2H3P II2H3P II2H3P II2H3P II2H3P
Rated heat output kW 19,4 19,4 26,3 26,3 26,3 30,1
Reduced heat output kW 10,6 10,6 11,9 11,9 11,9 11,9
Rated heat power kW 17,5 17,5 24 24 24 28
kcal/h 15.050 15.050 20.600 20.600 20.600 24.080
Reduced heat power kW 9,3 9,3 10,4 10,7 10,7 10,7
kcal/h 8.000 8.000 8.900 9.202 9.202 9.202
Useful efficiency according to Directive 92/42/EEC
Central heating system max. pressure bar 3 3 3 3 3 3
Expansion vessel capacity l 8 8 8 8 8 10
Expansion vessel pressure bar 0,5 0,5 0,5 0,5 0,5 0,5
Max. pressure in DHW system bar 8 8 8 8
Minimum dynamic pressure in DHW system bar 0,15 0,15 0,15 0,15
Minimum DHW output l/min 2,0 2,0 2,0 2,0
DHW output at T=25 C l/min 10 13,7 13,7 16
DHW output at T=35 C l/min 7,1 9,8 9,8 11,4
Specific output (*) l/min 8 10,5 10,5 12,5
Type B11BS B11BS B11BS C12 - C32 - C42 - C52 - C82 - B22
Temperature range in heating system C 3085 3085 3085 3085 3085 3085
Temperature range in DHW system C 3560 3560 3560 3560
Concentric flue duct diameter mm 60 60 60
Concentric air duct diameter mm 100 100 100
2-pipe flue duct diameter mm 80 80 80
2-pipe air duct diameter mm 80 80 80
Discharge pipe diameter B11BS
mm 110 110 130
Max. flue mass flow rate (G20) kg/s 0,015 0,015 0,021 0,018 0,018 0,016
Min. flue mass flow rate (G20) kg/s 0,012 0,012 0,017 0,013 0,013 0,010
Max. temperature of fumes C 116 116 120 135 135 140
Min. temperature of fumes C 90 90 86 106 106 108
NOx Class 5 5 5 5 5 5
Gas used G20-G31 G20-G31 G20-G31 G20-G31 G20-G31 G20-G31
Natural gas feeding pressure 2H (G20) mbar 20 20 20 20 20 20
Propane gas supply pressure 3P (G31) mbar 50 50 50 50 50 50
Power supply voltage V 230 230 230 230 230 230
Power supply frequency Hz 50 50 50 50 50 50
Power consumption W 110 110 110 135 135 165
Net weight kg 31 29 33 41,5 39,5 42
Dimensions Height mm 763 763 763 763 763 763
width mm 450 450 450 450 450 450
depth mm 345 345 345 345 345 345
Protection-limit against humidity and water leakages (**) IP X5D IP X5D IP X5D IP X5D IP X5D IP X5D
(*) according to EN 625
(**) according to EN 60529
As BAXI s.p.a.constantly strives to improve its products, it reserves the right to modify the information contained in this do-cument at any time and without prior notice. These Instructions are only meant to provide consumers with use information and
under no circumstance should they be construed as a contract with a third party.
BAXI S.p.A.36061 BASSANO DEL GRAPPA (VI) ITALIA
Via Trozzetti, 20